Under the US [[Flammable and combustible liquid classification|classification of flammable and combustible liquids]] in NFPA 30, liquids with a flash point of 37.8 °C (100 °F) or more are combustible. They are Class II up to 60 °C, Class IIIA from 60 to 93 °C and Class IIIB above.<ref name="Slye-6-198" /> Data compiled in NUREG-1805 give a flash point above 38 °C for domestic No. 2 fuel oil, 40 to 50 °C for diesel fuel and above 54 °C for No. 5 fuel oil.<ref name="Benedetti-B-19">Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.</ref> Older closed-cup data compiled by Kanury give 82 to 166 °C for North American diesel fuels, which shows how much the values vary.<ref name="Kanury-2-191" /> | Under the US [[Flammable and combustible liquid classification|classification of flammable and combustible liquids]] in NFPA 30, liquids with a flash point of 37.8 °C (100 °F) or more are combustible. They are Class II up to 60 °C, Class IIIA from 60 to 93 °C and Class IIIB above.<ref name="Slye-6-198" /> Data compiled in NUREG-1805 give a flash point above 38 °C for domestic No. 2 fuel oil, 40 to 50 °C for diesel fuel and above 54 °C for No. 5 fuel oil.<ref name="Benedetti-B-19">Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.</ref> Older closed-cup data compiled by Kanury give 82 to 166 °C for North American diesel fuels, which shows how much the values vary.<ref name="Kanury-2-191" /> | ||
[[File:fse-fuel-oil-system-v4.svg|thumb|upright=1.5|alt=Bar chart of minimum flash points of fuel oil grades No. 1 to No. 6 with NFPA 30 Class II, IIIA and IIIB boundaries|Minimum flash points of fuel oil grades in ASTM D396 compared with the NFPA 30 classes of combustible liquids. Based on Gore Willse (2008a), p. 10-13; Slye (2008), p. 6-198.]] | |||
A high flash point does not make the oil safe in every form. Slye (2008) explains that the hazard comes from the vapours, which form in ignitable amounts once the liquid is heated to its flash point.<ref name="Slye-6-197">Slye (2008), p. 6-197.</ref> NUREG-1805 adds that a high-flash-point liquid in the form of a spray, froth or foam ignites at once on contact with a small flame. The few droplets touched are heated above their flash point, and the fire then spreads through the spray.<ref name="IqbalSalley-B-19" /> Heavy fuel oil does not produce flammable vapours unless it is heated, but once burning, the heat of the fire keeps it burning.<ref name="Frank-17-37">Frank (2008), p. 17-37.</ref> The gross [[Heat of combustion|heat of combustion]] is about 46.1 MJ/kg for No. 1 fuel oil and 42.5 MJ/kg for No. 6.<ref name="Babrauskas-6-280">Babrauskas (2008a), p. 6-280.</ref> | A high flash point does not make the oil safe in every form. Slye (2008) explains that the hazard comes from the vapours, which form in ignitable amounts once the liquid is heated to its flash point.<ref name="Slye-6-197">Slye (2008), p. 6-197.</ref> NUREG-1805 adds that a high-flash-point liquid in the form of a spray, froth or foam ignites at once on contact with a small flame. The few droplets touched are heated above their flash point, and the fire then spreads through the spray.<ref name="IqbalSalley-B-19" /> Heavy fuel oil does not produce flammable vapours unless it is heated, but once burning, the heat of the fire keeps it burning.<ref name="Frank-17-37">Frank (2008), p. 17-37.</ref> The gross [[Heat of combustion|heat of combustion]] is about 46.1 MJ/kg for No. 1 fuel oil and 42.5 MJ/kg for No. 6.<ref name="Babrauskas-6-280">Babrauskas (2008a), p. 6-280.</ref> | ||
| Line 31: | Line 32: | ||
A handbook diagram for an industrial burner supply shows a tank with fill pipe, vent and gauge well, a suction line, a duplex filter and duplicate pumps with integral relief valves. A return line takes surplus oil back to the tank, and heavy oil also needs a tank suction heater.<ref name="GoreWillse-10-14" /> Engines and emergency generators are often fed through a day tank. This is a small tank near the generator that a transfer pump keeps full from a main tank at or below grade.<ref name="GrillJohnson-xxxi">Grill and Johnson (2005a), p. xxxi.</ref> A centralised oil distribution system supplies several buildings, manufactured homes or recreational vehicles from a central tank.<ref name="GoreWillse-10-16" /> | A handbook diagram for an industrial burner supply shows a tank with fill pipe, vent and gauge well, a suction line, a duplex filter and duplicate pumps with integral relief valves. A return line takes surplus oil back to the tank, and heavy oil also needs a tank suction heater.<ref name="GoreWillse-10-14" /> Engines and emergency generators are often fed through a day tank. This is a small tank near the generator that a transfer pump keeps full from a main tank at or below grade.<ref name="GrillJohnson-xxxi">Grill and Johnson (2005a), p. xxxi.</ref> A centralised oil distribution system supplies several buildings, manufactured homes or recreational vehicles from a central tank.<ref name="GoreWillse-10-16" /> | ||
[[File:fse-fuel-oil-system-v1.svg|thumb|upright=1.5|alt=Schematic of a building fuel oil system with outside fill and vent, storage tank, filter, pumps, relief valve, return line, burner and remote shutoff|Example industrial burner supply and some of the US rules summarised in the 2008 Fire Protection Handbook. Based on Gore Willse (2008a), pp. 10-14–10-16 and 10-19.]] | |||
Fuel oil is also the auxiliary fuel of many plants. Most incinerators fire natural gas or distillate oil, and many coal-fired power stations use oil for ignition.<ref name="Doucet-11-9">Doucet and Gilyeat (2008), p. 11-9.</ref><ref name="Sheridan-9-184">Sheridan (2008), p. 9-184.</ref> In power stations, fuel oil is often heated before it is pumped to the burner tips. Pipe failure and human error can cause fires in the pumping and heating equipment, and NFPA 850 calls for automatic suppression and a 2 hour fire barrier around it.<ref name="Sheridan-9-184" /> | Fuel oil is also the auxiliary fuel of many plants. Most incinerators fire natural gas or distillate oil, and many coal-fired power stations use oil for ignition.<ref name="Doucet-11-9">Doucet and Gilyeat (2008), p. 11-9.</ref><ref name="Sheridan-9-184">Sheridan (2008), p. 9-184.</ref> In power stations, fuel oil is often heated before it is pumped to the burner tips. Pipe failure and human error can cause fires in the pumping and heating equipment, and NFPA 850 calls for automatic suppression and a 2 hour fire barrier around it.<ref name="Sheridan-9-184" /> | ||
| Line 49: | Line 51: | ||
Further interlocks cover specific failures. Burners that need heated oil have a low oil temperature switch, and burners that depend on a fan or compressor shut off the fuel if the air supply stops.<ref name="GoreWillse-10-19" /> Where atomising steam or air can fail while oil still flows, an interlock must stop the oil at once. Pressure interlocks act when the fuel pressure is too low or too high.<ref name="GoreWillse-10-19" /> Burners that cannot restart safely on their own must require a manual restart after any safety shutdown, and a remote shutoff near the entrance to the burner room is good practice. Safety shutoff valves should close when de-energised and should not be easy to block open.<ref name="GoreWillse-10-19" /> | Further interlocks cover specific failures. Burners that need heated oil have a low oil temperature switch, and burners that depend on a fan or compressor shut off the fuel if the air supply stops.<ref name="GoreWillse-10-19" /> Where atomising steam or air can fail while oil still flows, an interlock must stop the oil at once. Pressure interlocks act when the fuel pressure is too low or too high.<ref name="GoreWillse-10-19" /> Burners that cannot restart safely on their own must require a manual restart after any safety shutdown, and a remote shutoff near the entrance to the burner room is good practice. Safety shutoff valves should close when de-energised and should not be easy to block open.<ref name="GoreWillse-10-19" /> | ||
[[File:fse-fuel-oil-system-v2.svg|thumb|upright=1.5|alt=Line diagram of an industrial oil burner supply with manual valves, strainer, preheater, safety shutoff valves and pressure, temperature and air switches|Typical safety valves and interlocks on the supply to an industrial oil burner. Based on Gore Willse (2008a), pp. 10-19–10-20.]] | |||
Large boilers need more. Burner shutoff valves should be close to the burner, so that little oil can drain into the furnace after a trip, and oil must not leak into an idle burner.<ref name="Mattern-10-96">Mattern et al. (2008), p. 10-96.</ref> Oil must reach the burners at the right temperature and pressure for atomisation, but oil that is too hot can vapour-bind the pumps and interrupt the supply. Fill and recirculation lines should discharge below the liquid level, which limits evaporation and static charging of free-falling oil.<ref name="Mattern-10-96" /> Mattern et al. (2008) describe the classic [[Boiler furnace explosion|boiler furnace explosion]]. Leaking fuel evaporates in an idle furnace and ignites explosively when the first burner is lit, or an operator fails to purge between unsuccessful light-off attempts.<ref name="Mattern-10-101" /> | Large boilers need more. Burner shutoff valves should be close to the burner, so that little oil can drain into the furnace after a trip, and oil must not leak into an idle burner.<ref name="Mattern-10-96">Mattern et al. (2008), p. 10-96.</ref> Oil must reach the burners at the right temperature and pressure for atomisation, but oil that is too hot can vapour-bind the pumps and interrupt the supply. Fill and recirculation lines should discharge below the liquid level, which limits evaporation and static charging of free-falling oil.<ref name="Mattern-10-96" /> Mattern et al. (2008) describe the classic [[Boiler furnace explosion|boiler furnace explosion]]. Leaking fuel evaporates in an idle furnace and ignites explosively when the first burner is lit, or an operator fails to purge between unsuccessful light-off attempts.<ref name="Mattern-10-101" /> | ||
| Line 93: | Line 96: | ||
As a worked example, take a confined pool of heavy fuel oil 2.0 m in diameter, with an area of 3.14 m². The correlation gives 39,700 × 0.035 × (1 − e<sup>−1.7 × 2.0</sup>) = 1340 kW/m², or about 4.2 MW for the pool. The simpler confined value gives 1390 × 3.14 = 4.4 MW.<ref name="Babrauskas-3-26" /><ref name="Budnick-3-149" /> This is close to twice the 2.5 MW of an average living-room sofa fire.<ref name="VR-4.5">Van Rossum (2027), §4.5.</ref> | As a worked example, take a confined pool of heavy fuel oil 2.0 m in diameter, with an area of 3.14 m². The correlation gives 39,700 × 0.035 × (1 − e<sup>−1.7 × 2.0</sup>) = 1340 kW/m², or about 4.2 MW for the pool. The simpler confined value gives 1390 × 3.14 = 4.4 MW.<ref name="Babrauskas-3-26" /><ref name="Budnick-3-149" /> This is close to twice the 2.5 MW of an average living-room sofa fire.<ref name="VR-4.5">Van Rossum (2027), §4.5.</ref> | ||
[[File:fse-fuel-oil-system-v3.svg|thumb|upright=1.5|alt=Line chart of heat release rate against pool diameter for heavy fuel oil, confined and unconfined, with the 2 m example and a 2.5 MW sofa reference line|Heat release rate of heavy fuel oil pool fires against pool diameter, for open burning. Based on Babrauskas (2002b), pp. 3-25–3-26; Budnick et al. (2008), p. 3-149; Van Rossum (2027), §4.5.]] | |||
If the 1040 L (275 gal) contents of a common tank size fed the pool, the energy content would be 1.04 × 940 × 39.7 ≈ 38,800 MJ. That is about 2,000 kg of spruce equivalent at 19 MJ/kg. If all the oil burned at a steady 4.2 MW, it would last about 9,200 s, or 2.6 hours.<ref name="VR-4.4" /><ref name="MBIE-25" /> The same oil spread as an unconfined spill at 2.8 mm would cover about 370 m² and burn at an estimated 280 kW/m². Its total heat release rate would depend on how much of that area burned at once.<ref name="Budnick-3-149" /> | If the 1040 L (275 gal) contents of a common tank size fed the pool, the energy content would be 1.04 × 940 × 39.7 ≈ 38,800 MJ. That is about 2,000 kg of spruce equivalent at 19 MJ/kg. If all the oil burned at a steady 4.2 MW, it would last about 9,200 s, or 2.6 hours.<ref name="VR-4.4" /><ref name="MBIE-25" /> The same oil spread as an unconfined spill at 2.8 mm would cover about 370 m² and burn at an estimated 280 kW/m². Its total heat release rate would depend on how much of that area burned at once.<ref name="Budnick-3-149" /> | ||
Revision as of 13:08, 12 November 2026
A fuel oil system is the combination of storage tanks, fill and vent pipes, pumps, piping, controls and burners that stores liquid fuel oil and delivers it to boilers, furnaces, space heaters, engines or generators.[1][2] Fuel oils are blends of hydrocarbons, ranging from light distillates such as No. 1 and No. 2 fuel oil, kerosene and diesel oil to heavy residual oils such as No. 6.[3] Under NFPA 30 as summarised in the 2008 handbook, fuel oil with a flash point of at least 37.8 °C (100 °F) is classed as a combustible liquid.[4] The handbook’s reprint of ASTM D396 gives minimum values of 38 °C or the applicable legal minimum for No. 1 and No. 2 oil.[5] Once a leak or spray brings oil into contact with an ignition source, it can burn as a pool or spray fire.[6][7]
The second main hazard lies inside the appliance. Unburned oil that collects in a combustion chamber after a flame failure can explode when it is lit.[8] In the United States, NFPA 31, Standard for the Installation of Oil-Burning Equipment, covers tanks, piping and burners, and NFPA 30 covers larger outside tanks.[9][10] The 20th edition of the NFPA Fire Protection Handbook (2008) summarises these rules as limits on tank size and location, enclosures for larger tanks and safety controls. Under these controls a burner shuts off its fuel whenever ignition, flame, air or atomisation fails.[11][12]
Fuel oils and their properties
Fuel oil, like other petroleum products, consists of varying hydrocarbon compounds, and even one grade varies with the crude oil and the refining process.[3] No. 1 and No. 2 fuel oil, kerosene, range oil, furnace oil and diesel oil are classed as distillates, and No. 4, No. 5 and No. 6 oil and Bunker C as residuals. Oil burners are tested and listed for specific grades, and only those grades should be used.[3][13] The grades are specified in ASTM D396 and in a Canadian government specification, and the handbook reprints the main ASTM requirements (Table 1).[13]
| Grade | Description | Minimum flash point |
|---|---|---|
| No. 1 | Distillate for vaporising pot-type burners | 38 °C (100 °F) or legal |
| No. 2 | Distillate for general-purpose domestic heating | 38 °C (100 °F) or legal |
| No. 4 | Preheating not usually required for handling or burning | 55 °C (130 °F) or legal |
| No. 5 (light and heavy) | Preheating may be required for burning and, in cold climates, for handling | 55 °C (130 °F) or legal |
| No. 6 | Preheating required for burning and handling | 65 °C (150 °F) |
The flash point of a liquid is the temperature at which the vapour and air just above its surface can carry a brief flash of flame from a small pilot. At the slightly higher fire point the flame is self-sustaining.[14] The measured value depends on the apparatus. Kerosene, for example, gives 52.8 °C in the Abel tester and 60.0 °C in the Cleveland tester.[15]
Under the US classification of flammable and combustible liquids in NFPA 30, liquids with a flash point of 37.8 °C (100 °F) or more are combustible. They are Class II up to 60 °C, Class IIIA from 60 to 93 °C and Class IIIB above.[4] Data compiled in NUREG-1805 give a flash point above 38 °C for domestic No. 2 fuel oil, 40 to 50 °C for diesel fuel and above 54 °C for No. 5 fuel oil.[16] Older closed-cup data compiled by Kanury give 82 to 166 °C for North American diesel fuels, which shows how much the values vary.[15]
A high flash point does not make the oil safe in every form. Slye (2008) explains that the hazard comes from the vapours, which form in ignitable amounts once the liquid is heated to its flash point.[17] NUREG-1805 adds that a high-flash-point liquid in the form of a spray, froth or foam ignites at once on contact with a small flame. The few droplets touched are heated above their flash point, and the fire then spreads through the spray.[6] Heavy fuel oil does not produce flammable vapours unless it is heated, but once burning, the heat of the fire keeps it burning.[18] The gross heat of combustion is about 46.1 MJ/kg for No. 1 fuel oil and 42.5 MJ/kg for No. 6.[19]
System components
Oil is prepared for combustion either by evaporating it or by atomising it. Air is supplied by natural or mechanical draft, and ignition is electric, by a gas or oil pilot, or manual.[13] Burners of up to about 25 L/h (6.5 gal/h) count as residential types and are intended for oil not heavier than No. 2. Most of them are pressure-atomising gun burners, in which a motor-driven pump delivers oil to the nozzle at 690 to 2070 kPa (100 to 300 psi).[13][1] Sleeve and pot burners, common in older stoves and heaters, evaporate the oil with the heat of the fire. Large boilers and industrial furnaces use mechanical, rotary-cup, steam or air atomising burners, often with No. 4, 5 or 6 oil.[1][9]
A handbook diagram for an industrial burner supply shows a tank with fill pipe, vent and gauge well, a suction line, a duplex filter and duplicate pumps with integral relief valves. A return line takes surplus oil back to the tank, and heavy oil also needs a tank suction heater.[1] Engines and emergency generators are often fed through a day tank. This is a small tank near the generator that a transfer pump keeps full from a main tank at or below grade.[20] A centralised oil distribution system supplies several buildings, manufactured homes or recreational vehicles from a central tank.[10]
Fuel oil is also the auxiliary fuel of many plants. Most incinerators fire natural gas or distillate oil, and many coal-fired power stations use oil for ignition.[21][22] In power stations, fuel oil is often heated before it is pumped to the burner tips. Pipe failure and human error can cause fires in the pumping and heating equipment, and NFPA 850 calls for automatic suppression and a 2 hour fire barrier around it.[22]
Storage tanks
Gore Willse (2008a) summarises the NFPA 31 tank rules as follows. Unenclosed tanks may hold no more than 2500 L (660 gal) per burner or burner group and 5000 L (1320 gal) in total. Each tank must be at least 1.5 m (5 ft) from any fire or flame and must not obstruct access to utility service metering, switch panels or shutoff valves.[9] Larger tanks inside buildings need an enclosure with a fire resistance rating of at least 3 hours. Its walls must be sealed to the floor, and its openings need sills at least 150 mm (6 in.) high and self-closing fire doors.[9]
Inside buildings, tanks of up to 227 L (60 gal) are allowed on any floor, and individual tanks of up to 2500 L (660 gal) on the lowest floor. On a higher floor the same size is allowed only where no space lies below and spilled oil cannot spread into the structure.[9] A recent NFPA 31 change allowed up to five 1040 L (275 gal) tanks to be cross-connected with a single fill and vent if the piping is pre-engineered.[9] Ordile (2008), in another chapter of the same handbook, summarises NFPA 31 differently. Individual tanks of up to 5000 L (1320 gal) are allowed there, 2500 L on higher floors, and up to 5200 L (1375 gal) in total for an engineered system outside a 3 hour room.[23]
Small supply tanks of up to 38 L (10 gal) for a single appliance must stand at least 0.6 m (2 ft) from any heat source. At full firing rate the oil in them may not rise more than about 14 K (25 °F) above room temperature.[10] An underground storage tank must be of a type recognised by NFPA 31 and installed according to NFPA 30. Both documents address foundations, property lines, vehicle traffic and flotation in floods.[10] Fill and vent pipes of underground and indoor tanks must end outside the building, and vents of tanks up to 2500 L must be at least 1¼ in. nominal pipe size. Gauges on indoor tanks may not release oil or vapour inside, and test wells are not allowed there.[10]
New York City set its own rules. The Port Authority policy was to follow the New York City building code where applicable. For the WTC 7 installations of 1987–1999, that code required oil with a flash point of at least 37.8 °C (100 °F).[24] Tanks had to stand at least 2.1 m (7 ft) from exposed flame unless protected. On the lowest floor, tanks of up to 2080 L (550 gal) could stand unenclosed, larger ones needed a 2 hour enclosure and those of 4160 L (1100 gal) or more a 3 hour enclosure.[25] Above the lowest floor, one tank of no more than 1040 L (275 gal) was allowed per storey. It needed a curb or pan holding twice its capacity and a float switch that stopped the transfer pump and sounded an alarm.[26]
Internal corrosion of tanks can be a major problem. Water that condenses in steel tanks attacks the steel, and the resulting leaks are mainly an environmental problem. A fire can follow, however, when a burner stands in a basement pit into which a leaking tank drains.[9] In small tanks, sloping the tank and connecting the supply line at its low end keeps water from collecting. In large boiler installations, suction lines should draw from above the water that settles below the oil, and sludge can plug strainers and burner tips.[9][27]
Controls and burner safeguards
Gore Willse (2008a) warns that an uncontrolled flow of unburned fuel into an appliance can form a combustible mixture that explodes if ignited.[8] Every burner therefore needs a primary safety control that shuts off the fuel on ignition or flame failure within a prescribed time. Commercial and industrial controls may purge the appliance with air before fuel flows and must prove the ignition flame before admitting main burner fuel.[11] Pot and sleeve burners use a constant-level valve or barometric feed instead, so that oil stays below any overflow point.[11][12]
Further interlocks cover specific failures. Burners that need heated oil have a low oil temperature switch, and burners that depend on a fan or compressor shut off the fuel if the air supply stops.[12] Where atomising steam or air can fail while oil still flows, an interlock must stop the oil at once. Pressure interlocks act when the fuel pressure is too low or too high.[12] Burners that cannot restart safely on their own must require a manual restart after any safety shutdown, and a remote shutoff near the entrance to the burner room is good practice. Safety shutoff valves should close when de-energised and should not be easy to block open.[12]
Large boilers need more. Burner shutoff valves should be close to the burner, so that little oil can drain into the furnace after a trip, and oil must not leak into an idle burner.[28] Oil must reach the burners at the right temperature and pressure for atomisation, but oil that is too hot can vapour-bind the pumps and interrupt the supply. Fill and recirculation lines should discharge below the liquid level, which limits evaporation and static charging of free-falling oil.[28] Mattern et al. (2008) describe the classic boiler furnace explosion. Leaking fuel evaporates in an idle furnace and ignites explosively when the first burner is lit, or an operator fails to purge between unsuccessful light-off attempts.[27]
Fuel quality matters as well. Oils from different sources can react when stored together, and shipments of different viscosity can change the fuel input without a matching change in airflow.[27] Water separated from water-containing fuels can be pumped to the burner instead of oil. Very volatile oils require explosionproof motors and switches, and light oils of low conductivity can build up static electricity.[27][29] NFPA 31 also prevents the contamination of oil stove and kerosene heater supplies with other fuels, which can cause explosions or flare-ups.[10]
Fire hazards and experience
The handbook names several hazards of heat-producing appliances. They operate above the ignition temperature of many common materials, and combustion appliances can accumulate combustible mixtures, discharge unburned fuel or expose fuel to ignition sources.[30] Explosions from unburned fuel or overpressure in a boiler can rupture fuel lines and add a fire to the explosion damage.[12][31] All oil-fired appliances must be connected to a chimney, except direct-fired heaters, listed kerosene stoves and portable kerosene heaters.[32] Portable kerosene heaters add the risk of misfuelling with gasoline and of refuelling while hot.[33]
Fuel oil fires belong to the wider group of heating equipment fires. In US one- and two-family dwellings in 1999 to 2002, heating equipment caused about 48,900 reported fires a year, 17 % of the total, with 300 civilian deaths.[34] Of these, about 2,500 a year were confined fuel burner or boiler fires, which caused no deaths. These numbers cover all fuels; the source does not separate oil from gas.[34]
The emergency power systems of World Trade Center Building 7 show the scale of a large building installation. Two independent systems held an estimated 163 m³ (43,000 gal) of No. 2 fuel oil, mostly in tanks below the loading dock. Duplex pump sets fed 1040 L (275 gal) day tanks and pressurised loops for generators of up to 1750 kW on several floors.[20][35] The systems had anti-siphon, foot, fusible-link and solenoid valves, level switches, rupture basins and leak detectors to stop unwanted discharge.[35] After the building collapsed in 2001, NIST examined hypothetical fuel oil fires from ruptured lines and concluded that they did not contribute to the collapse.[36]
Pool fire and energy calculations
A spill from a tank or a broken line can form a pool fire. Its heat release rate is the heat release rate per unit area multiplied by the area of the pool.[7] Babrauskas (2002b) gives a correlation for the radiative regime, valid for pools larger than about 0.2 m across. Smaller pools are rarely dangerous.[37] The burning time follows from the energy content of the fuel, which is volume times density times heat of combustion:[7][38]
| Symbol | Description | Unit |
|---|---|---|
| Heat release rate of the pool fire | kW | |
| Heat of combustion of the fuel | kJ/kg | |
| Mass burning rate per unit area of a large pool | kg/(m²·s) | |
| Empirical constant for the fuel | 1/m | |
| Pool diameter | m | |
| Pool area | m² | |
| Energy content of the fuel | kJ | |
| Density of the fuel | kg/m³ | |
| Volume of the fuel | m³ | |
| Burning time | s |
For heavy fuel oil, Babrauskas (2002b) gives a density of 940 to 1000 kg/m³, a heat of combustion of 39.7 MJ/kg, a burning rate of 0.035 kg/(m²·s) and kβ = 1.7 1/m.[39] The New Zealand commentary on Verification Method C/VM2 (2013) uses the same heat of combustion and 940 kg/m³ when it compares the total energy of stored fuels.[40] Budnick et al. (2008) give 1390 kW/m² for a confined pool of heavy fuel oil and 280 kW/m² for an unconfined spill. The corresponding values for diesel are 1950 and 390 kW/m².[7] An unconfined spill spreads thinly, to about 2.8 mm or less on concrete, and burns at about one fifth of the confined rate per unit area.[7]
As a worked example, take a confined pool of heavy fuel oil 2.0 m in diameter, with an area of 3.14 m². The correlation gives 39,700 × 0.035 × (1 − e−1.7 × 2.0) = 1340 kW/m², or about 4.2 MW for the pool. The simpler confined value gives 1390 × 3.14 = 4.4 MW.[39][7] This is close to twice the 2.5 MW of an average living-room sofa fire.[41]
If the 1040 L (275 gal) contents of a common tank size fed the pool, the energy content would be 1.04 × 940 × 39.7 ≈ 38,800 MJ. That is about 2,000 kg of spruce equivalent at 19 MJ/kg. If all the oil burned at a steady 4.2 MW, it would last about 9,200 s, or 2.6 hours.[38][40] The same oil spread as an unconfined spill at 2.8 mm would cover about 370 m² and burn at an estimated 280 kW/m². Its total heat release rate would depend on how much of that area burned at once.[7]
The example assumes open burning in a large, well-ventilated space. In a small room, radiation from the hot room raises the burning rate, while the air entering through the openings limits the size of the fire.[39][7] Spilled heavy oil must also first be heated before it gives off enough vapour to ignite.[18] A spray from a pressurised line behaves differently from a pool and ignites far more easily.[6]
Engines, generators and fire suppression
Diesel fuel and gasoline are the most common liquid fuels for a stationary combustion engine. Gasoline has a flash point of −43 °C (−45 °F), so NFPA 37 limits it in buildings to an engine-mounted tank of no more than 95 L (25 gal). Larger indoor fuel supplies are therefore normally diesel.[42] Biggins (2008) recommends alarms, float-controlled valves, gauges and spill containment for engine fuel tanks. Pump-filled tanks should have an overflow line, a high-level alarm and an automatic high-level shutoff. Fuel lines, vents and overflow lines should be kept away from the engine air intake.[42]
Water can control fires in high-flash-point oils. A coarse water spray cools the surface, and on viscous oils such as No. 6 it forms an emulsion, a froth that retards the release of vapour.[43][18] A solid stream should be avoided because it causes violent frothing, and frothing can spread burning oil over the side of a deep container.[43]
The requirements above are US practice as summarised in the 2008 handbook, which does not name the NFPA 31 edition. Its two chapters summarise the tank limits differently, and neither names the edition used.[9][23] Rules in other countries, and in later editions, may differ.
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 Gore Willse (2008a), p. 10-14.
- ↑ Grill and Johnson (2005a), p. iii.
- ↑ 3.0 3.1 3.2 Gore Willse (2008a), p. 10-11.
- ↑ 4.0 4.1 Slye (2008), p. 6-198.
- ↑ Gore Willse (2008a), p. 10-13.
- ↑ 6.0 6.1 6.2 Iqbal and Salley (2004), p. B-19.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 Budnick et al. (2008), p. 3-149.
- ↑ 8.0 8.1 Gore Willse (2008a), p. 10-17.
- ↑ 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 Gore Willse (2008a), p. 10-15.
- ↑ 10.0 10.1 10.2 10.3 10.4 10.5 Gore Willse (2008a), p. 10-16.
- ↑ 11.0 11.1 11.2 Gore Willse (2008a), p. 10-18.
- ↑ 12.0 12.1 12.2 12.3 12.4 12.5 Gore Willse (2008a), p. 10-19.
- ↑ 13.0 13.1 13.2 13.3 Gore Willse (2008a), p. 10-12.
- ↑ Kanury (2002b), p. 2-190.
- ↑ 15.0 15.1 Kanury (2002b), p. 2-191.
- ↑ Benedetti (1997), as cited in Iqbal and Salley (2004), p. B-19.
- ↑ Slye (2008), p. 6-197.
- ↑ 18.0 18.1 18.2 Frank (2008), p. 17-37.
- ↑ Babrauskas (2008a), p. 6-280.
- ↑ 20.0 20.1 Grill and Johnson (2005a), p. xxxi.
- ↑ Doucet and Gilyeat (2008), p. 11-9.
- ↑ 22.0 22.1 Sheridan (2008), p. 9-184.
- ↑ 23.0 23.1 Ordile (2008), p. 7-25.
- ↑ Grill and Johnson (2005a), p. 3.
- ↑ Grill and Johnson (2005a), p. 4.
- ↑ Grill and Johnson (2005a), p. 5.
- ↑ 27.0 27.1 27.2 27.3 Mattern et al. (2008), p. 10-101.
- ↑ 28.0 28.1 Mattern et al. (2008), p. 10-96.
- ↑ Ordile (2008), p. 7-29.
- ↑ Gore Willse (2008a), p. 10-9.
- ↑ Gore Willse (2008a), p. 10-20.
- ↑ Gore Willse (2008a), p. 10-39.
- ↑ Gore Willse (2008a), p. 10-25.
- ↑ 34.0 34.1 Lathrop (2008b), p. 20-57.
- ↑ 35.0 35.1 Grill and Johnson (2005a), p. xxxii.
- ↑ McAllister et al. (2008), p. 355.
- ↑ Babrauskas (2002b), p. 3-25.
- ↑ 38.0 38.1 Van Rossum (2027), §4.4.
- ↑ 39.0 39.1 39.2 Babrauskas (2002b), p. 3-26.
- ↑ 40.0 40.1 Ministry of Business, Innovation and Employment (2013), p. 25.
- ↑ Van Rossum (2027), §4.5.
- ↑ 42.0 42.1 Biggins (2008), p. 8-107.
- ↑ 43.0 43.1 Frank (2008), p. 17-34.
References
- Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
- Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
- Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
- Budnick, E. K., Hunt, S. P., & Wright, M. T. (2008). Closed form enclosure fire calculations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-145–3-166). National Fire Protection Association.
- Doucet, L. G., & Gilyeat, S. S. (2008). Waste handling and control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-3–11-25). National Fire Protection Association.
- Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
- Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
- Grill, R. A., & Johnson, D. A. (2005a). Documentation of the fuel system for emergency power in World Trade Center 7 (NIST NCSTAR 1-1J). National Institute of Standards and Technology.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
- Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
- Mattern, L. J., Catania, E., & Ehrlich, S. (2008). Boiler furnaces. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-91–10-104). National Fire Protection Association.
- McAllister, T. P., Gann, R. G., Averill, J. D., Gross, J. L., Grosshandler, W. L., Lawson, J. R., McGrattan, K. B., Pitts, W. M., Prasad, K. R., Sadek, F. H., & Nelson, H. E. (2008). Structural fire response and probable collapse sequence of World Trade Center Building 7 (NIST NCSTAR 1-9, Vols. 1–2). National Institute of Standards and Technology.
- Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
- Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
- Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.