Two footnotes of the table explain the grouping. Types G, D, LP and CN are considered to have comparable fire hazard, and so are the safeguarded Types GS, DS, LPS and CNS.<ref name="Bouchard-8-33" /> In storage occupancies, J. Moore (2008) adds that lift trucks used where flammable or combustible liquids are stored must be specifically listed for such areas.<ref name="Moore-20-162" /> In grain facilities, the internal combustion engines of industrial trucks are among the miscellaneous ignition sources of dust explosions.<ref name="MS-9-97">Maness and Sargent (2008), p. 9-97.</ref>
Two footnotes of the table explain the grouping. Types G, D, LP and CN are considered to have comparable fire hazard, and so are the safeguarded Types GS, DS, LPS and CNS.<ref name="Bouchard-8-33" /> In storage occupancies, J. Moore (2008) adds that lift trucks used where flammable or combustible liquids are stored must be specifically listed for such areas.<ref name="Moore-20-162" /> In grain facilities, the internal combustion engines of industrial trucks are among the miscellaneous ignition sources of dust explosions.<ref name="MS-9-97">Maness and Sargent (2008), p. 9-97.</ref>
[[File:fse-powered-industrial-truck-v1.svg|thumb|upright=1.5|alt=Matrix of truck type designations against hazardous location classes with recommended, conditional and not recommended cells|Recommended powered industrial truck types by location in US practice around 2008 (FM Global table).]]


== Fire hazards ==
== Fire hazards ==
For trucks with combustion engines, the main fire source is a fuel leak ignited by the hot engine, the hot muffler, the ignition system, other electrical equipment or other sparks. Hydraulic oil can also ignite. The danger is somewhat lower for diesel fuel and hydraulic oil because of their higher flashpoints.<ref name="Bouchard-8-32" /> Many fires involving trucks with liquid fuels result from spillage during refuelling.<ref name="Bouchard-8-35" /> J. Moore (2008) names refuelling, maintenance and storage of trucks when not in use as the general hazards of lift trucks in storage buildings.<ref name="Moore-20-162" />
For trucks with combustion engines, the main fire source is a fuel leak ignited by the hot engine, the hot muffler, the ignition system, other electrical equipment or other sparks. Hydraulic oil can also ignite. The danger is somewhat lower for diesel fuel and hydraulic oil because of their higher flashpoints.<ref name="Bouchard-8-32" /> Many fires involving trucks with liquid fuels result from spillage during refuelling.<ref name="Bouchard-8-35" /> J. Moore (2008) names refuelling, maintenance and storage of trucks when not in use as the general hazards of lift trucks in storage buildings.<ref name="Moore-20-162" />
[[File:fse-powered-industrial-truck-v2.svg|thumb|upright=1.5|alt=Side view of an LP-gas forklift with callouts for fuel leaks, hot engine and muffler, hydraulic oil and vapour flowing into a floor pit|Fire sources on an engine-powered lift truck and the tendency of LP-gas vapour to collect in low spots.]]


[[Liquefied petroleum gas]] brings a special hazard: its vapours are difficult to disperse and tend to collect in low spots and pits. LP-gas and CN-gas trucks must also be kept away from high temperatures near ovens, furnaces and similar heat sources. Design safeguards reduce these hazards, but they cannot remove them, so the areas of use must be strictly controlled.<ref name="Bouchard-8-32" /> LP-gas fuel containers must not be overfilled, and leaks should be found with soap solution, never with a match or open flame.<ref name="Bouchard-8-35" />
[[Liquefied petroleum gas]] brings a special hazard: its vapours are difficult to disperse and tend to collect in low spots and pits. LP-gas and CN-gas trucks must also be kept away from high temperatures near ovens, furnaces and similar heat sources. Design safeguards reduce these hazards, but they cannot remove them, so the areas of use must be strictly controlled.<ref name="Bouchard-8-32" /> LP-gas fuel containers must not be overfilled, and leaks should be found with soap solution, never with a match or open flame.<ref name="Bouchard-8-35" />
Line 71: Line 73:


The same drum holds about 6,700 MJ of energy (0.208 m³ × 740 kg/m³ × 43.7 MJ/kg). ''Introduction to Fire Safety Engineering'' gives about 1,925 MJ for a complete forklift truck, close to the 1,884 MJ of a three-seat sofa.<ref name="VR-4.4">Van Rossum (2027), §4.4.</ref> The drum therefore holds about three and a half times the energy content of a forklift truck, and the example shows that a [[Spill fire]] can release it within a few minutes.
The same drum holds about 6,700 MJ of energy (0.208 m³ × 740 kg/m³ × 43.7 MJ/kg). ''Introduction to Fire Safety Engineering'' gives about 1,925 MJ for a complete forklift truck, close to the 1,884 MJ of a three-seat sofa.<ref name="VR-4.4">Van Rossum (2027), §4.4.</ref> The drum therefore holds about three and a half times the energy content of a forklift truck, and the example shows that a [[Spill fire]] can release it within a few minutes.
[[File:fse-powered-industrial-truck-v4.svg|thumb|upright=1.5|alt=Bar chart of energy content: forklift 1,925 MJ, sofa 1,884 MJ, 208 L gasoline drum about 6,700 MJ, car 6,000 to 12,000 MJ|Energy content of a forklift truck compared with a sofa, a car and one 208 L drum of gasoline.]]


== Prevention in US practice ==
== Prevention in US practice ==
Line 80: Line 83:


Refuelling and battery charging should be done by trained, designated personnel in well-ventilated areas away from manufacturing and service areas, outdoors where practicable, with smoking prohibited.<ref name="Bouchard-8-35" /> J. Moore (2008) recommends refuelling outside or in a segregated area of the warehouse, because fuel leakage during refuelling has caused many fires.<ref name="Moore-20-162" /> Liquid fuel for the trucks is stored under NFPA 30, and fuel tanks are placed so that spills cannot flow under or around the storage.<ref name="Moore-20-176">J. Moore (2008), p. 20-176.</ref> Battery-charging areas need means to flush and neutralise spilled electrolyte, barriers against truck damage, ventilation to disperse the gases from charging batteries, and fire protection. Open flames, smoking, sparks and arcs are kept out of them.<ref name="Bouchard-8-35" />
Refuelling and battery charging should be done by trained, designated personnel in well-ventilated areas away from manufacturing and service areas, outdoors where practicable, with smoking prohibited.<ref name="Bouchard-8-35" /> J. Moore (2008) recommends refuelling outside or in a segregated area of the warehouse, because fuel leakage during refuelling has caused many fires.<ref name="Moore-20-162" /> Liquid fuel for the trucks is stored under NFPA 30, and fuel tanks are placed so that spills cannot flow under or around the storage.<ref name="Moore-20-176">J. Moore (2008), p. 20-176.</ref> Battery-charging areas need means to flush and neutralise spilled electrolyte, barriers against truck damage, ventilation to disperse the gases from charging batteries, and fire protection. Open flames, smoking, sparks and arcs are kept out of them.<ref name="Bouchard-8-35" />
[[File:fse-powered-industrial-truck-v3.svg|thumb|upright=1.5|alt=Plan of a battery-charging area with chargers behind barriers, ventilation, electrolyte flushing point and no-ignition-source sign|Features of a battery-charging area for electric industrial trucks.]]


For LP-gas trucks, a calibrated scale is recommended to check the full weight of a container. Removable containers are mounted securely and fitted with a quick-closing coupling, with the pressure relief device in contact with the vapour space.<ref name="Bouchard-8-35" /> Many filling hazards can be avoided by an exchange programme in which a supplier delivers full containers and takes empty ones away for filling off site.<ref name="Bouchard-8-35" /> Where a user fills LP-gas containers for industrial trucks on site, the user is usually also the owner and is responsible for requalifying the containers.<ref name="LR-7-40">Lemoff and Rivkin (2008), p. 7-40.</ref> Composite fibreglass cylinders approved by the US Department of Transportation are available in the sizes used on propane-powered forklift trucks.<ref name="LR-7-36">Lemoff and Rivkin (2008), p. 7-36.</ref>
For LP-gas trucks, a calibrated scale is recommended to check the full weight of a container. Removable containers are mounted securely and fitted with a quick-closing coupling, with the pressure relief device in contact with the vapour space.<ref name="Bouchard-8-35" /> Many filling hazards can be avoided by an exchange programme in which a supplier delivers full containers and takes empty ones away for filling off site.<ref name="Bouchard-8-35" /> Where a user fills LP-gas containers for industrial trucks on site, the user is usually also the owner and is responsible for requalifying the containers.<ref name="LR-7-40">Lemoff and Rivkin (2008), p. 7-40.</ref> Composite fibreglass cylinders approved by the US Department of Transportation are available in the sizes used on propane-powered forklift trucks.<ref name="LR-7-36">Lemoff and Rivkin (2008), p. 7-36.</ref>

Latest revision as of 09:12, 9 November 2026

A powered industrial truck is a self-propelled vehicle used to lift and move materials in factories and warehouses, such as a forklift truck (lift truck) or an automatic guided vehicle (AGV). Industrial trucks, which include lift trucks and AGVs, are among the most common types of materials-handling equipment. They are driven by electric motors or by diesel, gasoline, liquefied petroleum gas (LP-gas) or compressed natural gas (CN-gas) engines.[1] In storage occupancies they are usually electric or propane powered and are an integral part of most storage occupancies.[2]

For fire safety, a powered industrial truck is both an Ignition source and a cause of damage to fire protection. Fuel leaks can be ignited by the hot engine, the muffler or the electrical system, and battery charging releases hydrogen.[3][4] Careless operation can damage sprinkler piping and fire doors or spill flammable liquids.[5] The Fire Protection Handbook (2008) reports many multimillion-dollar losses caused by the improper use or application of lift trucks.[2] In the United States, NFPA 505 assigns trucks to type designations according to their power source and built-in safeguards, and limits each type to suitable locations.[1][3] The rules summarised here are US practice as described in the 2008 handbook.

Types and type designations

Lift trucks come in many special designs for different loads; the fork and the squeeze or clamp types are the most common.[1] In a warehouse, most of the work of moving materials through the building is done by employees using lift trucks, although some warehouses are fully automated with storage and retrieval systems.[6] NFPA 505, Fire Safety Standard for Powered Industrial Trucks, as described by Bouchard (2008), lists 18 type designations of powered industrial trucks and tractors. The letter of the designation gives the power type: CN for compressed natural gas, D for diesel, E for electric, G for gasoline and LP for liquefied petroleum gas.

Dual-fuel trucks also exist.[1] A further letter indicates the level of safeguards, as determined by testing at a recognised laboratory. A Type ES truck, for example, is a battery-powered unit that meets the minimum requirements for Type E and has additional safeguards against hazardous sparks and high surface temperatures.[3]

The test standards behind these designations are UL 558 for trucks with internal combustion engines and UL 583 for battery-powered trucks. The level of safeguarding determines whether a truck is acceptable in a particular location.[3] A uniform marking system, described in NFPA 505, uses markers on the trucks and signs at the entrances to hazardous areas. The signs read "Only trucks marked ... permitted in this area", so that staff can recognise at a glance which vehicles are approved.[3][5]

Certain trucks of Type G, LP or G/LP can be converted to another of those designations with kits approved by a recognised testing laboratory under UL 558. The converted truck receives a new plate next to the original nameplate. Responsibility for accepting a converted truck rests entirely with the authority having jurisdiction, because returning each truck to the laboratory is impractical.[7]

Areas of use

The choice of truck follows the Hazardous area classification of the location in NFPA 70, the National Electrical Code. Bouchard (2008) reproduces a table from FM Global that recommends truck types for each class and division. Fires or explosions can result if trucks of less than the minimum type operate in hazardous locations.[3] The table can be summarised as follows.

Recommended truck types by location (US, FM Global table in Bouchard, 2008)[3][7]
Location Typical occupancies Recommended types
Ordinary fire hazard Grocery warehouse, paper manufacturing, bakery, machine-tool occupancies E, G, D, LP, CN, G-LP, G-CN
Class I, Division 1 (flammable gas or vapour present in normal operation) Few areas where trucks would be used EX (Group D only); fuel-powered trucks not recommended
Class I, Division 2 (flammable liquids or gases in closed systems) Paint mixing and spraying, drum storage of flammable liquids, solvent recovery EE; EX and DY in Group D (Groups A–C subject to local authority); gasoline, D, DS, LP and CN not recommended
Class II, Division 1 (combustible dust clouds in normal operation) Grain and starch processing, wood-flour processing EX (Groups F and G, special investigation), DY; gasoline, D, DS, LP and CN not recommended
Class II, Division 2 (dust deposits, closed containers) Grain, starch or wood flour in bags, feed mills with enclosed equipment EE, EX, DY; ES, GS, DS, LPS, CNS subject to special investigation
Class III, Division 1 (ignitable fibres processed) Cotton opening and carding, cotton gins, woodworking sanding areas EE, EX, DY; gasoline, D, DS, LP and CN not recommended
Class III, Division 2 (ignitable fibres stored) Storage of textile and cordage fibres EE, ES, EX preferred; E (special investigation), GS, DS, DY, LPS, CNS

Two footnotes of the table explain the grouping. Types G, D, LP and CN are considered to have comparable fire hazard, and so are the safeguarded Types GS, DS, LPS and CNS.[7] In storage occupancies, J. Moore (2008) adds that lift trucks used where flammable or combustible liquids are stored must be specifically listed for such areas.[2] In grain facilities, the internal combustion engines of industrial trucks are among the miscellaneous ignition sources of dust explosions.[8]

Matrix of truck type designations against hazardous location classes with recommended, conditional and not recommended cells
Recommended powered industrial truck types by location in US practice around 2008 (FM Global table).

Fire hazards

For trucks with combustion engines, the main fire source is a fuel leak ignited by the hot engine, the hot muffler, the ignition system, other electrical equipment or other sparks. Hydraulic oil can also ignite. The danger is somewhat lower for diesel fuel and hydraulic oil because of their higher flashpoints.[3] Many fires involving trucks with liquid fuels result from spillage during refuelling.[4] J. Moore (2008) names refuelling, maintenance and storage of trucks when not in use as the general hazards of lift trucks in storage buildings.[2]

Side view of an LP-gas forklift with callouts for fuel leaks, hot engine and muffler, hydraulic oil and vapour flowing into a floor pit
Fire sources on an engine-powered lift truck and the tendency of LP-gas vapour to collect in low spots.

Liquefied petroleum gas brings a special hazard: its vapours are difficult to disperse and tend to collect in low spots and pits. LP-gas and CN-gas trucks must also be kept away from high temperatures near ovens, furnaces and similar heat sources. Design safeguards reduce these hazards, but they cannot remove them, so the areas of use must be strictly controlled.[3] LP-gas fuel containers must not be overfilled, and leaks should be found with soap solution, never with a match or open flame.[4]

A US nuclear guidance document examines a release from a propane-powered forklift with a maximum fuel capacity of 10 gal (38 L). Assuming a vapour release of 48 lb (21.8 kg), it calculates about 1,011,000 kJ of energy and a TNT equivalent of 225 kg (496 lb).[9]

Battery-powered trucks have their own fire causes: electrical short circuits, hot resistors, arcing and fused contacts, lint accumulation and exploding batteries. The lead and nickel-iron batteries in common use contain acid or alkali. During charging they generate hydrogen and oxygen, which can explode when mixed in certain concentrations.[4]

The third group of hazards comes from the way trucks are driven. Bouchard (2008) lists collisions with sprinkler piping, fire doors and other fire protection equipment, excessively high stacking, and careless handling of loads such as containers of flammable liquids. These can contribute directly to fires and make fire fighting more difficult.[5] The use of lift trucks indoors must be planned and supervised to avoid damaging sprinklers and sprinkler piping.[10] Strobe lights mounted at 2.0 to 2.4 m along racked aisles suffer frequent mechanical damage from forklift trucks and stock.[11] In process risk assessment, Barry (2002) lists forklifts, with hot exhaust, exhaust sparks and batteries or electrical systems, among linear ignition sources in materials handling.[12] He also describes forklift damage to fire doors or fire barriers as a problem that can recur constantly.[13]

Worked example: a ruptured fuel drum

The SFPE Handbook gives a worked example of a warehouse accident with a flammable liquid, the kind of load whose careless handling Bouchard (2008) warns about. A 208 L (55 gal) drum of gasoline ruptures during a warehouse accident, the fuel spreads freely across the floor, and faulty equipment ignites it.[14] The spill area follows from the spilled volume, the burning area is taken as 1.55 times that area, and the heat release rate follows from the burning area:

As=0.36V,A=1.55As,Q˙=m˙″AΔhc

Symbol Description Unit
V Volume of fuel spilled L
As Area of the unconfined spill (0.36 m² per litre) m²
A Maximum burning area of the spill m²
m˙″ Mass burning rate per unit area of the spill kg/(m²·s)
Δhc Heat of combustion of the fuel MJ/kg
Q˙ Heat release rate MW

The relations assume an instantaneous release that spreads freely on a flat floor. For a spill, the burning rate is taken as one-fifth of the pool value of 0.055 kg/(m²·s) for gasoline.[14] With 208 L, the spill covers 0.36 × 208 = 75 m² and the burning area is 1.55 × 75 = 116 m², a circle about 12.2 m across. The Heat release rate is 0.011 × 116 × 43.7 = 56 MW. Burning at that rate, the fuel would last about 121 s, although the source notes that the real fire lasts longer because flame needs time to spread across the spill.[14] In the second part of the example, flame crosses the 6.1 m radius at 2.0 m/s, so the whole spill is involved after about 3 s.[14]

The same drum holds about 6,700 MJ of energy (0.208 m³ × 740 kg/m³ × 43.7 MJ/kg). Introduction to Fire Safety Engineering gives about 1,925 MJ for a complete forklift truck, close to the 1,884 MJ of a three-seat sofa.[15] The drum therefore holds about three and a half times the energy content of a forklift truck, and the example shows that a Spill fire can release it within a few minutes.

Bar chart of energy content: forklift 1,925 MJ, sofa 1,884 MJ, 208 L gasoline drum about 6,700 MJ, car 6,000 to 12,000 MJ
Energy content of a forklift truck compared with a sofa, a car and one 208 L drum of gasoline.

Prevention in US practice

Training and layout are the first measures. A thorough instruction course for operators reduces the risk of accidents, as do clear passageways and clear warnings of overhead and exposed piping. Bouchard (2008) names ANSI B56.1 and the US OSHA rule 29 CFR 1910.178 as good sources of operating rules.[5] Aisles between storage need to be wide enough for the trucks: sprinkler design for storage assumes aisles of at least 2.4 m (8 ft), the width typically needed to manoeuvre a lift truck.[16]

Maintenance should be scheduled by engine or motor hours, and OSHA standards require each truck to be inspected before every day or shift of operation. Faulty fuel connections and accumulated grease, lint and dirt are the main things to look for.[5] Trucks should never be repaired in Class I, II or III hazardous locations.[4]

Battery trucks are repaired only with the battery disconnected, and replacement parts must give the same degree of fire safety as the original ones. Water mufflers are kept at least 75 percent full, and a truck that emits sparks or flames from its exhaust, or overheats, is taken out of service until the cause is removed.[4] Repairs that need Hot work should follow a formal permit programme and preferably take place outside the building. Trucks are cleaned with non-combustible agents, never with solvents with a flashpoint below 38 °C (100 °F).[4]

Refuelling and battery charging should be done by trained, designated personnel in well-ventilated areas away from manufacturing and service areas, outdoors where practicable, with smoking prohibited.[4] J. Moore (2008) recommends refuelling outside or in a segregated area of the warehouse, because fuel leakage during refuelling has caused many fires.[2] Liquid fuel for the trucks is stored under NFPA 30, and fuel tanks are placed so that spills cannot flow under or around the storage.[17] Battery-charging areas need means to flush and neutralise spilled electrolyte, barriers against truck damage, ventilation to disperse the gases from charging batteries, and fire protection. Open flames, smoking, sparks and arcs are kept out of them.[4]

Plan of a battery-charging area with chargers behind barriers, ventilation, electrolyte flushing point and no-ignition-source sign
Features of a battery-charging area for electric industrial trucks.

For LP-gas trucks, a calibrated scale is recommended to check the full weight of a container. Removable containers are mounted securely and fitted with a quick-closing coupling, with the pressure relief device in contact with the vapour space.[4] Many filling hazards can be avoided by an exchange programme in which a supplier delivers full containers and takes empty ones away for filling off site.[4] Where a user fills LP-gas containers for industrial trucks on site, the user is usually also the owner and is responsible for requalifying the containers.[18] Composite fibreglass cylinders approved by the US Department of Transportation are available in the sizes used on propane-powered forklift trucks.[19]

LP-gas vehicles include industrial trucks, and LP-gas has the longest history of the alternative vehicle fuels.[20] Vehicles take propane in liquid form, using transfer equipment of the kind long used at bulk plants to fill delivery trucks and containers. Rivkin (2008b) notes that this equipment has been used extensively to fuel forklift trucks at manufacturing and storage occupancies.[21]

Trucks in storage layouts

The trucks shape the layout of storage. In solid piling without pallets, lift trucks stack goods with side clamps or prongs, and spaces are left between cartons for the prongs.[22] Pallets contain open horizontal spaces for the forks. In multiple-row drive-in Rack storage, forklift trucks drive into the rack to place and remove loads in its depth.[23] These horizontal spaces make the Storage arrangement functional, but they increase the fire hazard. They let air pass easily to a fire and can shield burning goods from the water of overhead sprinklers.[23]

Lift-truck operation is also linked to large losses. J. Moore (2008) reports many multimillion-dollar losses from improper use or application of lift trucks, and notes that misuse can turn a truck into an ignition source.[2] Once started, a Warehouse fire in a storage area can develop and spread rapidly.[2] Areas used to service and maintain trucks should be designated, marked and separated from the storage.[17]

Trucks also interact with the means of escape. Although the occupant load of a storage building is generally light, J. Moore (2008) treats emergency egress as a concern.[2] Lathrop (2008a) gives the use of a gasoline-powered forklift in a corridor designated as an exit passageway as an example that would violate the principles of exit design.[24]

The handbook material has limits. It describes US standards and practice around 2007–2008, and the type designations and Table 8.3.1 recommendations may have changed in later editions of NFPA 505. The table comes from one insurer, FM Global, and several of its entries are marked as subject to special investigation.[7] The sources give no fire test data, heat release rates or loss statistics for the trucks themselves, beyond the energy content of about 1,925 MJ and one LP-gas release calculation.[15][9]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Bouchard (2008), p. 8-31.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 J. Moore (2008), p. 20-162.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Bouchard (2008), p. 8-32.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 Bouchard (2008), p. 8-35.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Bouchard (2008), p. 8-34.
  6. ↑ J. Moore (2008), p. 20-158.
  7. ↑ 7.0 7.1 7.2 7.3 Bouchard (2008), p. 8-33.
  8. ↑ Maness and Sargent (2008), p. 9-97.
  9. ↑ 9.0 9.1 Iqbal and Salley (2004), p. 15-18.
  10. ↑ Hague (2008a), p. 16-217.
  11. ↑ Schifiliti (2008), p. 14-35.
  12. ↑ Barry (2002), p. 5-194.
  13. ↑ Barry (2002), p. 5-202.
  14. ↑ 14.0 14.1 14.2 14.3 Gottuk and White (2002), p. 2-314.
  15. ↑ 15.0 15.1 Van Rossum (2027), §4.4.
  16. ↑ Golinveaux (2008), p. 16-78.
  17. ↑ 17.0 17.1 J. Moore (2008), p. 20-176.
  18. ↑ Lemoff and Rivkin (2008), p. 7-40.
  19. ↑ Lemoff and Rivkin (2008), p. 7-36.
  20. ↑ Rivkin (2008b), p. 21-72.
  21. ↑ Rivkin (2008b), p. 21-66.
  22. ↑ Golinveaux (2008), p. 16-74.
  23. ↑ 23.0 23.1 Golinveaux (2008), p. 16-75.
  24. ↑ Lathrop (2008a), p. 4-86.

References

  • Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-176–5-213). National Fire Protection Association; Society of Fire Protection Engineers.
  • Bouchard, J. K. (2008). Materials-Handling equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-31–8-41). National Fire Protection Association.
  • Golinveaux, J. E. (2008). Sprinkler systems for storage facilities. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-71–16-89). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hague, D. R. (2008a). Care and maintenance of water-based extinguishing systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-205–16-222). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008a). Concepts of egress design. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 4-69–4-91). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Maness, J. E., & Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-85–9-103). National Fire Protection Association.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Schifiliti, R. P. (2008). Notification appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-29–14-37). National Fire Protection Association.