New FSE wiki article: Cooking fire (written by Claude Opus 5.5) |
FSE wiki: Fact-check: source scope for US estimates, Class K restaurant example and Hagerstown outcome (written by Claude Opus 5.5) |
||
| Line 11: | Line 11: | ||
== Scale of the problem == | == Scale of the problem == | ||
In US [[fire statistics]] for all structure fires in 1999–2002, cooking equipment caused 126,800 fires a year (25 percent) and 280 civilian deaths (9 percent).<ref name="HallCote-3-14" /> It also caused 4,570 injuries (26 percent) and 665 million dollars of direct damage (8 percent). Homes accounted for about 83 percent of these fires.<ref name="Ahrens-3-74" /> | In US [[fire statistics]] for all structure fires in 1999–2002, cooking equipment caused 126,800 fires a year (25 percent) and 280 civilian deaths (9 percent).<ref name="HallCote-3-14" /> It also caused 4,570 injuries (26 percent) and 665 million dollars of direct damage (8 percent). The source's national estimates exclude the events of 11 September 2001.<ref name="HallCote-3-14" /> Homes accounted for about 83 percent of these fires.<ref name="Ahrens-3-74" /> | ||
In US homes, cooking equipment caused 105,400 fires a year (28 percent), 270 deaths (9 percent), 4,230 injuries (28 percent) and 519 million dollars of damage (10 percent).<ref name="Ahrens-3-74" /> That is 0.3 deaths per 100 fires, against about 0.79 for all home fires, and an average loss of 4,900 dollars, against about 14,400 dollars.<ref name="Ahrens-3-75">Ahrens et al. (2008), p. 3-75.</ref> Confined cooking fires averaged only 300 dollars of loss each. By comparison, a [[candle fire]] or a smoking-material fire in a US home averaged 21,500 and 18,300 dollars of loss, but each group accounted for no more than 7 percent of home fires.<ref name="Ahrens-3-74" /> Fires that began in the kitchen or cooking area caused 26 percent of home fires, 16 percent of the deaths and 30 percent of the injuries.<ref name="Madrzykowski-16-92">Madrzykowski and Fleming (2008), p. 16-92.</ref> | In US homes, cooking equipment caused 105,400 fires a year (28 percent), 270 deaths (9 percent), 4,230 injuries (28 percent) and 519 million dollars of damage (10 percent).<ref name="Ahrens-3-74" /> That is 0.3 deaths per 100 fires, against about 0.79 for all home fires, and an average loss of 4,900 dollars, against about 14,400 dollars.<ref name="Ahrens-3-75">Ahrens et al. (2008), p. 3-75.</ref> Confined cooking fires averaged only 300 dollars of loss each. By comparison, a [[candle fire]] or a smoking-material fire in a US home averaged 21,500 and 18,300 dollars of loss, but each group accounted for no more than 7 percent of home fires.<ref name="Ahrens-3-74" /> Fires that began in the kitchen or cooking area caused 26 percent of home fires, 16 percent of the deaths and 30 percent of the injuries.<ref name="Madrzykowski-16-92">Madrzykowski and Fleming (2008), p. 16-92.</ref> | ||
| Line 24: | Line 24: | ||
The handbook gives simple reasons for the high frequency of cooking fires in commercial kitchens. The cooking itself provides an ignition source, grease and residue build up a fuel load, the air supply is designed to be effective, and keeping the hazard low requires constant inspection and maintenance.<ref name="Demers-10-77" /> Most cooking fires stay small for equally simple reasons: an awake, unimpaired adult is usually nearby, the first fuel is small, and nothing blocks a quick response. Home cooking fires show the same pattern of high frequency and low average severity. | The handbook gives simple reasons for the high frequency of cooking fires in commercial kitchens. The cooking itself provides an ignition source, grease and residue build up a fuel load, the air supply is designed to be effective, and keeping the hazard low requires constant inspection and maintenance.<ref name="Demers-10-77" /> Most cooking fires stay small for equally simple reasons: an awake, unimpaired adult is usually nearby, the first fuel is small, and nothing blocks a quick response. Home cooking fires show the same pattern of high frequency and low average severity. | ||
In homes, unattended cooking is the principal cause.<ref name="Lathrop-20-58" /> Other causes are combustibles such as rags, pot holders or bags placed too close to the heat, stove tops and ovens that are not cleaned, and overhanging curtains, drapes or clothing. A local study in Hagerstown, Maryland, found that most fires involved stovetop cooking, with no reason to treat gas and electric stoves differently.<ref name="HallWeller-5-124">Hall and Weller (2008), p. 5-124.</ref> The typical behaviour was leaving a pan of grease on the stove after being distracted by children, the television, the telephone or neighbours. Some people simply assumed there was time to do something else while it heated. | In homes, unattended cooking is the principal cause.<ref name="Lathrop-20-58" /> Other causes are combustibles such as rags, pot holders or bags placed too close to the heat, stove tops and ovens that are not cleaned, and overhanging curtains, drapes or clothing. A local study in Hagerstown, Maryland, found that most fires involved stovetop cooking, with no reason to treat gas and electric stoves differently.<ref name="HallWeller-5-124">Hall and Weller (2008), p. 5-124.</ref> The typical behaviour was leaving a pan of grease on the stove after being distracted by children, the television, the telephone or neighbours. Some people simply assumed there was time to do something else while it heated.<ref name="HallWeller-5-124" /> | ||
Cooking oils and fats are the most dangerous fuel on the stove. In frying they are heated to their [[flash point]]s, and when overheated or spilled on a hot stovetop they can reach their [[autoignition temperature]] and ignite without a flame.<ref name="Mattern-11-31" /> The autoignition temperature of most vegetable oils is about 363 °C (685 °F), higher than that of animal fats.<ref name="Lake-17-25">Lake (2008), p. 17-25.</ref> For lard oil, the SFPE Handbook lists a flash point of 240 °C and an autoignition temperature of 273 °C.<ref name="Kanury-2-191">Kanury (2002b), p. 2-191.</ref> Some cooking oils autoignite below their boiling point, so a burning pot of oil can become superheated above its autoignition temperature.<ref name="Wysocki-17-13">Wysocki (2008), p. 17-13.</ref> | Cooking oils and fats are the most dangerous fuel on the stove. In frying they are heated to their [[flash point]]s, and when overheated or spilled on a hot stovetop they can reach their [[autoignition temperature]] and ignite without a flame.<ref name="Mattern-11-31" /> The autoignition temperature of most vegetable oils is about 363 °C (685 °F), higher than that of animal fats.<ref name="Lake-17-25">Lake (2008), p. 17-25.</ref> For lard oil, the SFPE Handbook lists a flash point of 240 °C and an autoignition temperature of 273 °C.<ref name="Kanury-2-191">Kanury (2002b), p. 2-191.</ref> Some cooking oils autoignite below their boiling point, so a burning pot of oil can become superheated above its autoignition temperature.<ref name="Wysocki-17-13">Wysocki (2008), p. 17-13.</ref> | ||
| Line 43: | Line 43: | ||
A short example shows the temperatures involved. Take a vegetable oil with an autoignition temperature of about 363 °C. After the fire its ignition temperature falls to about 363 − 28 = 335 °C, so the whole volume of oil must be cooled below about 335 °C.<ref name="Lake-17-25" /> Greasy surfaces must also cool at least 28 °C (50 °F) below their own autoignition temperature after a suppression system discharges, or they will reignite.<ref name="Demers-10-86">Demers (2008b), p. 10-86.</ref> Deep fryers are critical, because late detection can leave them so hot that the agent breaks down before the surfaces have cooled. | A short example shows the temperatures involved. Take a vegetable oil with an autoignition temperature of about 363 °C. After the fire its ignition temperature falls to about 363 − 28 = 335 °C, so the whole volume of oil must be cooled below about 335 °C.<ref name="Lake-17-25" /> Greasy surfaces must also cool at least 28 °C (50 °F) below their own autoignition temperature after a suppression system discharges, or they will reignite.<ref name="Demers-10-86">Demers (2008b), p. 10-86.</ref> Deep fryers are critical, because late detection can leave them so hot that the agent breaks down before the surfaces have cooled. | ||
Portable equipment follows the same logic. | Portable equipment follows the same logic. For a restaurant kitchen, Conroy (2008) identifies cooking oils and fats as the hazard requiring a Class-K-rated [[fire extinguisher]].<ref name="Conroy-17-72">Conroy (2008), p. 17-72.</ref> Class K extinguishers contain water additives intended for fires in commercial fryers, whereas plain water extinguishers used on liquid fuel fires can make the fire flare up and spread.<ref name="Conroy-17-75">Conroy (2008), pp. 17-75–17-76.</ref> For fixed carbon dioxide systems on oils that can superheat, the handbook gives a minimum local application time of 3 minutes so that the mass of oil can cool.<ref name="Wysocki-17-13" /> | ||
== Protection in homes and commercial kitchens == | == Protection in homes and commercial kitchens == | ||
| Line 55: | Line 55: | ||
== Prevention and education == | == Prevention and education == | ||
Cooking fires contribute far more to fire incidents and injuries than to deaths, and prevention programmes are chosen with that in mind.<ref name="Hall-5-105">Hall (2008), p. 5-105.</ref> Hagerstown, Maryland, a city of about 37,000 people, chose cooking after reviewing a decade of local fire data. Cooking, and unattended cooking in particular, caused a large or leading share of local fires.<ref name="HallWeller-5-123">Hall and Weller (2008), pp. 5-123–5-124.</ref> The goals were a 30 percent cut in cooking fires and smoke alarms in 90 percent of homes within 10 years. The programme combined school education, door-to-door visits to about 4,000 homes a year, tours of burned homes and a media campaign. | Cooking fires contribute far more to fire incidents and injuries than to deaths, and prevention programmes are chosen with that in mind.<ref name="Hall-5-105">Hall (2008), p. 5-105.</ref> Hagerstown, Maryland, a city of about 37,000 people, chose cooking after reviewing a decade of local fire data. Cooking, and unattended cooking in particular, caused a large or leading share of local fires.<ref name="HallWeller-5-123">Hall and Weller (2008), pp. 5-123–5-124.</ref> The goals were a 30 percent cut in cooking fires and smoke alarms in 90 percent of homes within 10 years. The programme combined school education, door-to-door visits to about 4,000 homes a year, tours of burned homes and a media campaign.<ref name="HallWeller-5-123" /> | ||
The programme | The programme reported smoke alarms in nearly 99 percent of homes it reached. Its contact rate was about 40 percent, so the rate in uncontacted homes was uncertain. Cooking fires declined by one-third over a decade, a larger reduction than the national data showed over more than two decades.<ref name="HallWeller-5-132">Hall and Weller (2008), p. 5-132.</ref> Knowledge that cooking was the leading fire cause grew by up to 50 percent in some neighbourhoods, for example from 16 to 24 percent of residents.<ref name="HallWeller-5-128">Hall and Weller (2008), p. 5-128.</ref> Local data also showed which unsafe fire-fighting methods residents used and how they were injured, which helped to choose the messages.<ref name="HallWeller-5-124" /> | ||
Messages must also fit the households they address. Where it is a cultural norm to cook in deep skillets filled with grease, the risk of kitchen fires and burns increases.<ref name="Kirtley-5-17">Kirtley (2008b), p. 5-17.</ref> Fire departments serving immigrant communities have had to teach the use of multi-burner stoves and ovens to people who previously cooked on open fires, and to discourage hibachis and barbecue grills indoors.<ref name="Gamache-5-73">Gamache (2008), p. 5-73.</ref> In assembly buildings, large propane cylinders such as those of outdoor gas grills must never be used indoors.<ref name="Miller-20-91">Miller and Roether (2008), p. 20-91.</ref> | Messages must also fit the households they address. Where it is a cultural norm to cook in deep skillets filled with grease, the risk of kitchen fires and burns increases.<ref name="Kirtley-5-17">Kirtley (2008b), p. 5-17.</ref> Fire departments serving immigrant communities have had to teach the use of multi-burner stoves and ovens to people who previously cooked on open fires, and to discourage hibachis and barbecue grills indoors.<ref name="Gamache-5-73">Gamache (2008), p. 5-73.</ref> In assembly buildings, large propane cylinders such as those of outdoor gas grills must never be used indoors.<ref name="Miller-20-91">Miller and Roether (2008), p. 20-91.</ref> | ||
Revision as of 00:01, 8 November 2026
A cooking fire is a fire that starts in or from equipment used to prepare food, such as a range, oven, fryer or griddle, usually when cooking oil, fat or food overheats.[1][2] In US fire statistics the term covers fires in which cooking equipment supplied the heat of ignition, including small "confined" fires that stay within a pan or an oven.[3] In US data for 1999–2002, cooking equipment was the leading cause of reported structure fires and fire injuries, while unattended cooking was the main behaviour behind these fires.[4] In US homes during that period, cooking equipment was involved in 28 percent of reported fires and 28 percent of fire injuries, but in only 9 percent of the deaths.[5]
Frying heats oils and fats close to their flash points, and they can reach their autoignition temperature when they are overheated or spilled on a hot stovetop.[2] Water, milk or flour make such a fire worse, while a lid or an extinguishing agent that turns the oil into a soapy foam puts it out.[6][7][8] In commercial kitchens, grease that builds up in hoods and ducts can carry a fire into the ventilation system, so these kitchens rely on fixed suppression systems and regular cleaning.[9]
Definition and classification
In the US National Fire Incident Reporting System (NFIRS), a "cooking equipment fire" combines two groups: fires in which identified cooking equipment was involved in ignition, and confined cooking fires.[3] The category is defined by the equipment that supplied the ignition source, not by the room. In 1999–2002, 34 percent of reported US home fires began in the kitchen, but 28 percent involved cooking equipment.[10] The equipment category locates the problem more precisely, because a kitchen contains many hazards but most homes have only a few types of cooking equipment.
Confined fires are a feature of NFIRS version 5.0. Fire departments may file an abbreviated report for small fires confined to cooking vessels, chimneys, incinerators or similar containers.[11] The change answered the complaint of fire fighters who had to fill in the same information repeatedly for many minor fires. A confined structure fire is a small fire generally confined to a noncombustible container, with no flame damage beyond it, and incident type 113 is "cooking fire, confined to container".[12]
Other NFIRS data elements describe the same fires from different angles, which is why the fire cause of a cooking fire can be stated in several ways. A range or cooking surface was involved in 14 percent of US home fires and an oven in 3 percent, and cooking materials, including food, were the first item ignited in 16 percent.[1] The NFPA notes that more often than not the equipment was used improperly, and that unattended cooking is a far more frequent cause than defective equipment. Fires in cooking appliances that involve cooking media, such as vegetable or animal oils and fats, form their own fire class, Class K, in NFPA 10.[13]
Scale of the problem
In US fire statistics for all structure fires in 1999–2002, cooking equipment caused 126,800 fires a year (25 percent) and 280 civilian deaths (9 percent).[3] It also caused 4,570 injuries (26 percent) and 665 million dollars of direct damage (8 percent). The source's national estimates exclude the events of 11 September 2001.[3] Homes accounted for about 83 percent of these fires.[5]
In US homes, cooking equipment caused 105,400 fires a year (28 percent), 270 deaths (9 percent), 4,230 injuries (28 percent) and 519 million dollars of damage (10 percent).[5] That is 0.3 deaths per 100 fires, against about 0.79 for all home fires, and an average loss of 4,900 dollars, against about 14,400 dollars.[14] Confined cooking fires averaged only 300 dollars of loss each. By comparison, a candle fire or a smoking-material fire in a US home averaged 21,500 and 18,300 dollars of loss, but each group accounted for no more than 7 percent of home fires.[5] Fires that began in the kitchen or cooking area caused 26 percent of home fires, 16 percent of the deaths and 30 percent of the injuries.[15]
In US one- and two-family dwellings, cooking equipment caused 63,400 fires a year (23 percent), 220 deaths (9 percent) and 2,570 injuries (24 percent).[16] It ranked fifth as a cause of deaths there but first in fires and injuries, and it also accounts for most unreported fires.[17] In apartments the share is even larger: cooking caused 46 percent of apartment fires, against 23 percent in one- and two-family dwellings.[18]
Outside homes, cooking equipment caused 19,100 US nonhome structure fires a year (14 percent) but only 10 deaths.[19] In eating and drinking establishments it caused 4,500 fires a year (45 percent) and 51 percent of the injuries.[20] In hotels and motels it was the leading cause of fires, with 1,060 a year (23 percent), and in educational buildings it came second, with 930 fires a year (13 percent).[21][22] The handbook concludes that in every property type cooking fires account for a much larger share of fires and injuries than of losses or deaths.[9]
Reported fires are only part of the picture. Past studies have estimated that unreported fires are 10 to 20 times as numerous as reported fires, and most of them are small cooking fires.[23] Among the four leading causes of US home fire deaths, cooking had the least favourable trend.[24]
How cooking fires start and grow
The handbook gives simple reasons for the high frequency of cooking fires in commercial kitchens. The cooking itself provides an ignition source, grease and residue build up a fuel load, the air supply is designed to be effective, and keeping the hazard low requires constant inspection and maintenance.[9] Most cooking fires stay small for equally simple reasons: an awake, unimpaired adult is usually nearby, the first fuel is small, and nothing blocks a quick response. Home cooking fires show the same pattern of high frequency and low average severity.
In homes, unattended cooking is the principal cause.[17] Other causes are combustibles such as rags, pot holders or bags placed too close to the heat, stove tops and ovens that are not cleaned, and overhanging curtains, drapes or clothing. A local study in Hagerstown, Maryland, found that most fires involved stovetop cooking, with no reason to treat gas and electric stoves differently.[25] The typical behaviour was leaving a pan of grease on the stove after being distracted by children, the television, the telephone or neighbours. Some people simply assumed there was time to do something else while it heated.[25]
Cooking oils and fats are the most dangerous fuel on the stove. In frying they are heated to their flash points, and when overheated or spilled on a hot stovetop they can reach their autoignition temperature and ignite without a flame.[2] The autoignition temperature of most vegetable oils is about 363 °C (685 °F), higher than that of animal fats.[26] For lard oil, the SFPE Handbook lists a flash point of 240 °C and an autoignition temperature of 273 °C.[27] Some cooking oils autoignite below their boiling point, so a burning pot of oil can become superheated above its autoignition temperature.[28]
Hot cookware and burners can also ignite nearby materials directly. In tests summarised by the US Nuclear Regulatory Commission, contact with hot metal ignited paper at 250 °C, cloth at 300 °C and wood at 350 °C within 30 seconds, without a pilot flame.[29] Rags, pot holders and bags placed too close to the heat are accordingly among the listed causes of home cooking fires.[17]
Commercial kitchens add further mechanisms. Failed thermostats and high-limit controls cause fires every year when fryers overheat the oil until it autoignites, and pots of oil left unattended on manually controlled equipment do the same.[30] Hot flue gases from gas appliances can overheat grease in the hood if the exhaust fan is not interlocked with the appliance. Exhaust flows sized for normal cooking can contain a small fire, but a long grease fire eventually overwhelms the hood and escapes. Sparks or small fires in overheated oil can ignite the grease that condenses in hoods and ducts, whereas stovetop fires without such deposits can often be put out readily.[2] Early spread into the commercial kitchen exhaust system is therefore one of the factors in severe commercial cooking fires.[9]
Extinguishing cooking oil fires
Burning cooking oil should not be attacked with water. Cooking oil fires form Class K, for which water is not an appropriate agent.[31] Untrained kitchen workers have made fires worse by using water, milk or other liquids, and flour or cornstarch thrown on the fire has caused major flare-ups and injuries, unlike baking soda.[6] The simplest home message is to slide a lid on a grease fire, which can be put into practice without delay.[8] A lid works on the fire triangle: a fire needs fuel, oxygen and heat, and when the oxygen supply falls it stops spreading and goes out.[32]
Chemical agents put out oil fires mainly by saponification. Alkaline agents react with the fatty acids in the cooking medium and convert them into a soap-like foam that smothers the fire.[33] For this reason an alkaline dry chemical, such as sodium bicarbonate, is preferred on hot cooking oil. Monoammonium phosphate, the common "ABC" powder, is not recommended there, because it does not form such a foam layer.[34]
Changes in cooking practice have made this harder. Commercial kitchens moved from animal fats to vegetable oils, which contain fewer fatty acids and so form a weaker foam blanket.[26] After ignition, the oil also changes composition, and its ignition temperature becomes about 28 °C lower than that of the fresh oil. Energy-efficient fryers keep the oil hot for longer, so the whole volume of oil must be cooled below its autoignition temperature to prevent reflash. As a result, no dry chemical system has been able to meet the newer listing criteria for hoods, ducts and fryers.[35]
Wet chemical agents were developed for this hazard. They are alkaline solutions of potassium salts, such as potassium carbonate, acetate or citrate, in water.[7] When sprayed on burning grease, they saponify it at once and form a foam blanket that both smothers and cools the fire, and they are tested so that they do not splash burning grease. In the 2008 handbook, they are the only agents listed for fires in commercial cooking equipment such as deep-fat fryers, griddles, range tops and broilers. Some systems follow the agent with water to cool the surrounding surfaces further.[26]
A short example shows the temperatures involved. Take a vegetable oil with an autoignition temperature of about 363 °C. After the fire its ignition temperature falls to about 363 − 28 = 335 °C, so the whole volume of oil must be cooled below about 335 °C.[26] Greasy surfaces must also cool at least 28 °C (50 °F) below their own autoignition temperature after a suppression system discharges, or they will reignite.[36] Deep fryers are critical, because late detection can leave them so hot that the agent breaks down before the surfaces have cooled.
Portable equipment follows the same logic. For a restaurant kitchen, Conroy (2008) identifies cooking oils and fats as the hazard requiring a Class-K-rated fire extinguisher.[37] Class K extinguishers contain water additives intended for fires in commercial fryers, whereas plain water extinguishers used on liquid fuel fires can make the fire flare up and spread.[38] For fixed carbon dioxide systems on oils that can superheat, the handbook gives a minimum local application time of 3 minutes so that the mass of oil can cool.[28]
Protection in homes and commercial kitchens
Smoke alarms in homes have to be placed with cooking in mind. Some smoke alarms are unsuitable in kitchens because cooking vapours cause false alarms.[39] NFPA 72 (2007 edition), as summarised in the handbook, requires a smoke alarm within 6.1 m (20 ft) of a cooking appliance to be photoelectric or to have a temporary silencing feature. Alarms should never be disconnected because of nuisance alarms; moving the alarm farther from the cooking source or replacing it with a less sensitive type usually solves the problem.[40]
Sprinklers also see much of their work in kitchens. In a US project that collected 448 residential sprinkler activations from 167 fire departments, kitchens accounted for 40 percent of the incidents, and about 83 percent of the activations involved a single sprinkler.[41] Sprinklers that protect commercial cooking equipment and its ventilation must have a high or extra-high temperature rating, according to the NFPA 13 text quoted by the US Nuclear Regulatory Commission.[42]
In commercial kitchens, the fixed suppression system is the primary means of fire control and portable extinguishers are secondary.[6] The cooking hazards of traditional kitchens are handled by automatic extinguishing systems and vapour removal as set out in NFPA 96, as summarised in the 2008 handbook.[20] In US eating and drinking establishments, only 43 percent of the reported automatic extinguishing systems were sprinklers, and another 43 percent were dry chemical systems for stovetops or ducts.[43] The restaurant kitchens of the World Trade Center, for example, had dry chemical systems released by a thermal link above the appliance or in the duct. Their large kitchen ducts also had steam smothering systems.[44]
Maintenance is part of the protection. Grease filters should be cleaned at least once a day, and running the exhaust without its filters puts far more grease into the hood and duct.[45] Grease ducts need a clearance of 457 mm (18 in.) to combustible construction unless they are protected in accordance with NFPA 96.[46] Performance-based codes also treat cooking as a fire load factor. In New Zealand, Verification Method C/VM2 (second edition, 2025) assigns 400 MJ/m² to eating places without cooking facilities and 800 MJ/m² to restaurants and eating places.[47]
Prevention and education
Cooking fires contribute far more to fire incidents and injuries than to deaths, and prevention programmes are chosen with that in mind.[48] Hagerstown, Maryland, a city of about 37,000 people, chose cooking after reviewing a decade of local fire data. Cooking, and unattended cooking in particular, caused a large or leading share of local fires.[49] The goals were a 30 percent cut in cooking fires and smoke alarms in 90 percent of homes within 10 years. The programme combined school education, door-to-door visits to about 4,000 homes a year, tours of burned homes and a media campaign.[49]
The programme reported smoke alarms in nearly 99 percent of homes it reached. Its contact rate was about 40 percent, so the rate in uncontacted homes was uncertain. Cooking fires declined by one-third over a decade, a larger reduction than the national data showed over more than two decades.[50] Knowledge that cooking was the leading fire cause grew by up to 50 percent in some neighbourhoods, for example from 16 to 24 percent of residents.[51] Local data also showed which unsafe fire-fighting methods residents used and how they were injured, which helped to choose the messages.[25]
Messages must also fit the households they address. Where it is a cultural norm to cook in deep skillets filled with grease, the risk of kitchen fires and burns increases.[52] Fire departments serving immigrant communities have had to teach the use of multi-burner stoves and ovens to people who previously cooked on open fires, and to discourage hibachis and barbecue grills indoors.[53] In assembly buildings, large propane cylinders such as those of outdoor gas grills must never be used indoors.[54]
Limits of the data and common misconceptions
Changes in reporting distort trends in cooking fires. Confined cooking fires reported to NFIRS rose from 804 in 1999 to 56,453 in 2003, or from 0.9 to 20.4 percent of structure fires, largely because more fire departments adopted NFIRS 5.0.[55] These incidents generally lack causal data, so analysts must infer that they involved cooking equipment and food. The statistics here are US data for 1999–2002 from a 2008 handbook, and the many unreported fires are not included at all.[23]
In homes, behaviour matters more than equipment faults. In the NFPA data, the equipment was more often than not used improperly, and unattended cooking was a far more frequent cause than defective equipment.[1] Equipment design still matters in commercial kitchens, where failed thermostats and missing interlocks cause fires every year.[30]
A low death rate does not make cooking fires a minor problem. They caused 28 percent of US home fire injuries, and burning oil that is handled wrongly can cause severe injuries.[5][6] Water is also the wrong agent on burning oil. On cooking oil, water, milk and flour make the fire worse, while a lid or an alkaline agent that forms a foam blanket smothers it.[31][33]
See also
- Wet chemical extinguishing system
- Heating equipment fire
- Smoking-material fire
- National Fire Incident Reporting System
- Fire loss
Notes
- ↑ 1.0 1.1 1.2 Ahrens et al. (2008), pp. 3-72–3-73.
- ↑ 2.0 2.1 2.2 2.3 Mattern (2008b), pp. 11-31–11-32.
- ↑ 3.0 3.1 3.2 3.3 Hall and Cote (2008), p. 3-14.
- ↑ Hall and Cote (2008), p. 3-15.
- ↑ 5.0 5.1 5.2 5.3 5.4 Ahrens et al. (2008), p. 3-74.
- ↑ 6.0 6.1 6.2 6.3 Demers (2008b), p. 10-85.
- ↑ 7.0 7.1 Lake (2008), p. 17-24.
- ↑ 8.0 8.1 Hall and Weller (2008), p. 5-131.
- ↑ 9.0 9.1 9.2 9.3 Demers (2008b), p. 10-77.
- ↑ Ahrens et al. (2008), p. 3-70.
- ↑ Ahrens and Stewart (2008), pp. 3-49–3-50.
- ↑ Ahrens et al. (2008), pp. 3-66–3-67.
- ↑ Iqbal and Salley (2004), p. B-13.
- ↑ Ahrens et al. (2008), p. 3-75.
- ↑ Madrzykowski and Fleming (2008), p. 16-92.
- ↑ Lathrop (2008b), p. 20-57.
- ↑ 17.0 17.1 17.2 Lathrop (2008b), p. 20-58.
- ↑ Bush (2008), p. 20-38.
- ↑ Hall and Cote (2008), p. 3-16.
- ↑ 20.0 20.1 Miller and Roether (2008), p. 20-90.
- ↑ Berkol et al. (2008), p. 20-27.
- ↑ Szachnowicz (2008), p. 20-116.
- ↑ 23.0 23.1 Schwartzman (2008), p. 5-88.
- ↑ Hall (2008), p. 5-108.
- ↑ 25.0 25.1 25.2 Hall and Weller (2008), p. 5-124.
- ↑ 26.0 26.1 26.2 26.3 Lake (2008), p. 17-25.
- ↑ Kanury (2002b), p. 2-191.
- ↑ 28.0 28.1 Wysocki (2008), p. 17-13.
- ↑ Iqbal and Salley (2004), p. 2-22.
- ↑ 30.0 30.1 Demers (2008b), p. 10-83.
- ↑ 31.0 31.1 Frank (2008), p. 17-36.
- ↑ Van Rossum (2027), §4.2.
- ↑ 33.0 33.1 Lake (2008), p. 17-19.
- ↑ Yu and Newman (2008), p. 2-90.
- ↑ Lake (2008), p. 17-20.
- ↑ Demers (2008b), p. 10-86.
- ↑ Conroy (2008), p. 17-72.
- ↑ Conroy (2008), pp. 17-75–17-76.
- ↑ Gottuk (2008), p. 14-85.
- ↑ Gottuk (2008), p. 14-86.
- ↑ Madrzykowski and Fleming (2008), p. 16-105.
- ↑ Iqbal and Salley (2004), p. 10-8.
- ↑ Hall and Cote (2008), p. 3-19.
- ↑ Evans et al. (2005), pp. 15–16.
- ↑ Demers (2008b), p. 10-84.
- ↑ Demers (2008b), p. 10-79.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 22.
- ↑ Hall (2008), p. 5-105.
- ↑ 49.0 49.1 Hall and Weller (2008), pp. 5-123–5-124.
- ↑ Hall and Weller (2008), p. 5-132.
- ↑ Hall and Weller (2008), p. 5-128.
- ↑ Kirtley (2008b), p. 5-17.
- ↑ Gamache (2008), p. 5-73.
- ↑ Miller and Roether (2008), p. 20-91.
- ↑ Ahrens et al. (2008), pp. 3-76–3-77.
References
- Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
- Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
- Berkol, A., Briese, B., & Comeau, E. (2008). Hotels and university housing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-23–20-36). National Fire Protection Association.
- Bush, K. (2008). Apartment buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-37–20-47). National Fire Protection Association.
- Conroy, M. T. (2008). Fire extinguisher use and maintenance. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-71–17-92). National Fire Protection Association.
- Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
- Evans, D. D., Peacock, R. D., Kuligowski, E. D., Dols, W. S., & Grosshandler, W. L. (2005). Active fire protection systems (NIST NCSTAR 1-4). National Institute of Standards and Technology.
- Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
- Gamache, S. (2008). Reaching high-risk groups. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-63–5-85). National Fire Protection Association.
- Gottuk, D. T. (2008). Household fire-warning equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-79–14-87). National Fire Protection Association.
- Hall, J. R., Jr. (2008). Using data for public education planning and decision making. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-103–5-118). National Fire Protection Association.
- Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
- Hall, J. R., Jr., & Weller, M. W. (2008). Evaluation techniques for fire and life safety education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-119–5-137). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
- Kirtley, E. (2008b). Principles and techniques of fire and life safety education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-3–5-20). National Fire Protection Association.
- Lake, J. D. (2008). Chemical extinguishing agents and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-17–17-29). National Fire Protection Association.
- Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
- Madrzykowski, D., & Fleming, R. P. (2008). Residential sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-91–16-107). National Fire Protection Association.
- Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
- Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
- Schwartzman, P. (2008). Juvenile firesetting. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-87–5-102). National Fire Protection Association.
- Szachnowicz, A. L. (2008). Educational occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-115–20-122). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.
- Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.