== Lamp surface temperatures ==
== Lamp surface temperatures ==
The handbook gives bare-bulb and base temperatures for standard incandescent lamps, taken from the fifth edition of the ''IES Handbook'' and measured in open sockets at 25 °C ambient with the lamp burning base up.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-155">Milatovich (2008), pp. 8-155–8-156.</ref> In most luminaires the lamp works in a warmer ambient and so runs hotter than these values. Any position other than vertical and base up raises the bulb temperature further.<ref name="Milatovich-8-154" />
The handbook gives bare-bulb and base temperatures for standard incandescent lamps, taken from the fifth edition of the ''IES Handbook'' and measured in open sockets at 25 °C ambient with the lamp burning base up.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-155">Milatovich (2008), pp. 8-155–8-156.</ref> In most luminaires the lamp works in a warmer ambient and so runs hotter than these values. Other burning positions may raise the bulb temperature further.<ref name="Milatovich-8-154" />


{| class="wikitable"
{| class="wikitable"
Line 36: Line 36:
Discharge lamps differ. A fluorescent tube runs at an average of 38–43 °C over most of its length, because this is needed for efficient light production. Small areas above the cathodes at each end reach 49–121 °C, depending on the type.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-157" /> High-intensity discharge (HID) lamps, such as mercury vapour lamps, usually run much hotter than incandescent or fluorescent lamps, exceeding 288 °C in some sizes.<ref name="Milatovich-8-157" />
Discharge lamps differ. A fluorescent tube runs at an average of 38–43 °C over most of its length, because this is needed for efficient light production. Small areas above the cathodes at each end reach 49–121 °C, depending on the type.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-157" /> High-intensity discharge (HID) lamps, such as mercury vapour lamps, usually run much hotter than incandescent or fluorescent lamps, exceeding 288 °C in some sizes.<ref name="Milatovich-8-157" />


Some lamp types are known for high temperatures. Spotlights can easily reach the ignition temperature of paper or textiles.<ref name="McDaniel-20-184" /> Halogen torchiere lamps became a concern in U.S. residence halls because of their high bulb temperature. Manufacturers later changed designs to keep combustibles from touching the bulb, yet a number of universities still discourage them, also because of their high power demand.<ref name="Berkol-20-33">Berkol et al. (2008), p. 20-33.</ref>
Some lamp types are known for high temperatures. Spotlights can easily reach the ignition temperature of paper or textiles.<ref name="McDaniel-20-184" /> The 2008 handbook reports that halogen torchiere lamps had become a concern in U.S. residence halls because of their high bulb temperature. Manufacturers had changed designs to keep combustibles from touching the bulb, yet some universities still discouraged their use at that time, also because of their high power demand.<ref name="Berkol-20-33">Berkol et al. (2008), p. 20-33.</ref>


== Heat transfer and worked example ==
== Heat transfer and worked example ==
Line 64: Line 64:


== Ballasts, fittings and installation ==
== Ballasts, fittings and installation ==
Fluorescent lamps often need a high voltage to start, which requires transformers, reactors, capacitors and switches whose heat must be safeguarded.<ref name="Milatovich-8-154" /> The handbook calls for extreme care when fluorescent luminaires with ballasts are mounted on low-density cellulose fibreboard, defined as bonded plant material with a density of 320 kg/m³ or less. Unless the luminaire is listed for such mounting, it should be spaced at least 38 mm (1½ in.) from the surface, because the fibreboard can ignite at relatively low temperatures.<ref name="Milatovich-8-157" /> Indoor fluorescent luminaires now carry integral thermal ballast protection against overheating from failed capacitors, lamps or shorted windings.<ref name="Milatovich-8-157" /> A failing ballast can still be a source of ignition and at least produces large quantities of acrid smoke.<ref name="McDaniel-20-184" />
Fluorescent lamps often need a high voltage to start, which requires transformers, reactors, capacitors and switches whose heat must be safeguarded.<ref name="Milatovich-8-154" /> The handbook calls for extreme care when fluorescent luminaires with ballasts are mounted on low-density cellulose fibreboard, defined as bonded plant material with a density of 320 kg/m³ or less. Unless the luminaire is listed for such mounting, it should be spaced at least 38 mm (1½ in.) from the surface, because the fibreboard can ignite at relatively low temperatures.<ref name="Milatovich-8-157" /> The 2008 handbook describes indoor fluorescent luminaires as having integral thermal ballast protection against overheating from failed capacitors, lamps or shorted windings.<ref name="Milatovich-8-157" /> A failing ballast can still be a source of ignition and may produce significant quantities of acrid smoke.<ref name="McDaniel-20-184" />


Fittings in ceilings bring further risks. Recessed luminaires contain a thermal protector that opens the circuit temporarily when the fitting exceeds a set temperature.<ref name="Milatovich-8-146">Milatovich (2008), p. 8-146.</ref> In fire-rated membrane ceilings, light fittings must be of suitable design and spacing and often need shielding against heat transmission. Because the fire test is based on specific fittings and spacing, indiscriminate substitution can cause premature failure.<ref name="GoreWillse-19-21">Gore Willse (2008b), p. 19-21.</ref>
Fittings in ceilings bring further risks. Recessed luminaires contain a thermal protector that opens the circuit temporarily when the fitting exceeds a set temperature.<ref name="Milatovich-8-146">Milatovich (2008), p. 8-146.</ref> In fire-rated membrane ceilings, light fittings must be of suitable design and spacing and often need shielding against heat transmission. Because the fire test is based on specific fittings and spacing, indiscriminate substitution can cause premature failure.<ref name="GoreWillse-19-21">Gore Willse (2008b), p. 19-21.</ref>
Line 72: Line 72:
Spacing rules set a [[clearance to combustibles]] for some fittings. Under the 2005 NEC, as summarised in the handbook, electric signs must keep at least 50 mm (2 in.) between wood or other combustibles and an incandescent or HID lamp or lampholder. Signs must also not expose adjacent combustibles to more than 90 °C.<ref name="Milatovich-8-162" /> In storage occupancies, sufficient clearance must be kept between stored goods and any lighting fixtures, with the NEC consulted for minimum distances.<ref name="JMoore-20-161">J. Moore (2008), p. 20-161.</ref>
Spacing rules set a [[clearance to combustibles]] for some fittings. Under the 2005 NEC, as summarised in the handbook, electric signs must keep at least 50 mm (2 in.) between wood or other combustibles and an incandescent or HID lamp or lampholder. Signs must also not expose adjacent combustibles to more than 90 °C.<ref name="Milatovich-8-162" /> In storage occupancies, sufficient clearance must be kept between stored goods and any lighting fixtures, with the NEC consulted for minimum distances.<ref name="JMoore-20-161">J. Moore (2008), p. 20-161.</ref>


Other rules address particular settings. In clothes closets, open, partially enclosed or pendant incandescent fittings are not permitted.<ref name="Milatovich-8-154" /> Plastic diffusers are often acceptable if they deform and drop out of the fitting at a temperature well below their ignition point.<ref name="Benedetti-6-229">Benedetti and Colonna (2008), p. 6-229.</ref> U.S. recreational vehicle standards, from the 1993 edition of NFPA 501C onwards, required listed low-voltage lighting fixtures to reduce heat build-up at their mounting surfaces.<ref name="Hopkins-21-99">Hopkins (2008), p. 21-99.</ref>
Other rules address particular settings. In clothes closets, open, partially enclosed or pendant incandescent fittings are not permitted under the 2005 NEC.<ref name="Milatovich-8-154" /> Plastic diffusers are often acceptable if they deform and drop out of the fitting at a temperature well below their ignition point.<ref name="Benedetti-6-229">Benedetti and Colonna (2008), p. 6-229.</ref> Among U.S. recreational-vehicle standard changes beginning with the 1993 edition of NFPA 501C, the handbook lists a requirement for listed low-voltage lighting fixtures to reduce heat build-up at mounting surfaces.<ref name="Hopkins-21-99">Hopkins (2008), p. 21-99.</ref>


== Hazardous locations ==
== Hazardous locations ==
In atmospheres with flammable vapours, combustible dusts or ignitable fibres, lamps must be in luminaires approved for the location.<ref name="Milatovich-8-154" /> Dust clouds have been ignited by the hot filaments of lightbulbs.<ref name="Schwab-6-144">Schwab (2008c), p. 6-144.</ref> In U.S. Class I, Division 1 locations, luminaires must be of the explosionproof or purged type, marked with the maximum lamp wattage and either guarded or located beyond the area of potential damage.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-169">Milatovich (2008), p. 8-169.</ref> [[Explosionproof equipment]] is defined in the NEC as apparatus whose case withstands an internal explosion, prevents ignition of the surrounding gas and runs cool enough not to ignite it.<ref name="Milatovich-8-164">Milatovich (2008), p. 8-164.</ref>
In atmospheres with flammable vapours, combustible dusts or ignitable fibres, lamps must be in luminaires approved for the location.<ref name="Milatovich-8-154" /> Dust clouds have been ignited by the hot filaments of lightbulbs.<ref name="Schwab-6-144">Schwab (2008c), p. 6-144.</ref> In U.S. Class I, Division 1 locations, luminaires must be of the explosionproof or purged type, marked with the maximum lamp wattage and either guarded or located beyond the area of potential damage.<ref name="Milatovich-8-154" /><ref name="Milatovich-8-169">Milatovich (2008), p. 8-169.</ref> [[Explosionproof equipment]] is defined in the NEC as apparatus whose case withstands an internal explosion, prevents ignition of the surrounding gas and runs cool enough not to ignite it.<ref name="Milatovich-8-164">Milatovich (2008), p. 8-164.</ref>


In Class I, Division 2 locations, lamps that run above the ignition temperature of the gas need explosionproof or purged enclosures. Fittings from which sparks or hot metal of a broken lamp could fall onto local concentrations of vapour also need suitable enclosures.<ref name="Milatovich-8-170" /> Where a larger lamp could make the luminaire surface exceed 80 % of the gas's ignition temperature in degrees Celsius, the luminaire must be tested for its marked temperature range:<ref name="Milatovich-8-154" />
In Class I, Division 2 locations, lamps that run above the ignition temperature of the gas need explosionproof or purged enclosures. Fittings from which sparks or hot metal of a broken lamp could fall onto local concentrations of vapour also need suitable enclosures.<ref name="Milatovich-8-170" /> A larger lamp may raise the luminaire's normal-operation surface temperature. If it could exceed 80 % of the gas or vapour's ignition temperature in degrees Celsius, the 2005 NEC requires a luminaire type tested for its marked temperature operating range:<ref name="Milatovich-8-154" />


<math display="block">T_\text{s} \leq 0.8 \, T_\text{AIT}</math>
<math display="block">T_\text{s,potential} > 0.8 \, T_\text{AIT} \quad\Rightarrow\quad \text{marked-range test required}</math>


Here <math>T_\text{s}</math> is the luminaire surface temperature and <math>T_\text{AIT}</math> the autoignition temperature of the gas or vapour, both in °C. The handbook lists autoignition temperatures of 280–471 °C for gasoline, 225 °C for hexane and 160 °C for diethyl ether.<ref name="Milatovich-8-165">Milatovich (2008), p. 8-165.</ref> The 80 % limits are therefore about 224 °C, 180 °C and 128 °C.
Here <math>T_\text{s,potential}</math> is the possible luminaire surface temperature after fitting a larger lamp and <math>T_\text{AIT}</math> is the gas or vapour's autoignition temperature, both in °C. The handbook lists autoignition temperatures of 280–471 °C for gasoline, 225 °C for hexane and 160 °C for diethyl ether.<ref name="Milatovich-8-165">Milatovich (2008), p. 8-165.</ref> The corresponding 80 % test triggers are about 224 °C, 180 °C and 128 °C, using the lower gasoline value. These thresholds trigger testing; they are not general maximum permissible surface temperatures.


Bare-lamp temperatures are not luminaire surface temperatures, but they show the margins involved. A bare 100 W A-19 lamp at 25 °C ambient reaches 149 °C base up and 230–247 °C in other positions. It would therefore exceed the diethyl ether limit in every position and the gasoline limit in every position except base up.<ref name="Milatovich-8-154" /> Listed equipment carries a temperature identification number, from T1 for a maximum of 450 °C down to T6 for 85 °C, which must not exceed the ignition temperature of the gas.<ref name="Milatovich-8-168" /><ref name="Milatovich-8-169" />
Bare-lamp temperatures are not luminaire surface temperatures, but they show the scale of these test triggers. A bare 100 W A-19 lamp at 25 °C ambient reaches 149 °C base up and 230–247 °C in other positions.<ref name="Milatovich-8-154" /> Those bulb values are above the diethyl ether trigger in every position and above the gasoline trigger except base up, but they do not establish whether the luminaire itself requires the marked-range test. Listed equipment carries a temperature identification number, from T1 for a maximum of 450 °C down to T6 for 85 °C, which must not exceed the ignition temperature of the gas.<ref name="Milatovich-8-168" /><ref name="Milatovich-8-169" />


Dust and fibre locations follow the same logic. In Class II, Division 1 locations, luminaires must have dust-ignitionproof enclosures, and surface temperatures under actual operating conditions must not exceed the ignition temperature of the dust.<ref name="Milatovich-8-170" /> Some coal dusts have minimum ignition temperatures of 170–180 °C.<ref name="Milatovich-8-169" /> In Class II, Division 2 locations, fixed lamps need enclosures that limit dust deposits and keep in sparks, burning material and hot metal. In Class III locations, where ignitable fibres are handled, lamps must be dust-tight and surfaces may not exceed 165 °C for equipment that cannot be overloaded.<ref name="Milatovich-8-171">Milatovich (2008), p. 8-171.</ref> Spray finishing areas apply a similar principle: fittings above a classified area should be totally enclosed or guarded so that hot particles cannot drop into it.<ref name="Scarbrough-9-34">Scarbrough (2008b), p. 9-34.</ref>
Dust and fibre locations follow the same logic. In Class II, Division 1 locations, luminaires must have dust-ignitionproof enclosures, and surface temperatures under actual operating conditions must not exceed the ignition temperature of the dust.<ref name="Milatovich-8-170" /> Some coal dusts have minimum ignition temperatures of 170–180 °C.<ref name="Milatovich-8-169" /> In Class II, Division 2 locations, fixed lamps need enclosures that limit dust deposits and keep in sparks, burning material and hot metal. In Class III locations, where ignitable fibres are handled, lamps must be dust-tight and surfaces may not exceed 165 °C for equipment that cannot be overloaded.<ref name="Milatovich-8-171">Milatovich (2008), p. 8-171.</ref> Spray finishing areas apply a similar principle: fittings above a classified area should be totally enclosed or guarded so that hot particles cannot drop into it.<ref name="Scarbrough-9-34">Scarbrough (2008b), p. 9-34.</ref>

Revision as of 00:44, 8 November 2026

Luminaire fire hazards are the ways in which lighting equipment, meaning lamps, lampholders, ballasts and the fittings that contain them, can start a fire.[1] The Fire Protection Handbook (2008), which follows the 2005 National Electrical Code (NEC), treats luminaire and lighting fixture as equivalent terms.[2] The main hazard is heat: incandescent lamps can ignite combustible material that touches, surrounds or lies on them, while ballasts can overheat and broken lamps can drop sparks or hot metal.[2][3][4] In the United States in 1994–1998, fires that began at fixtures, lampholders, ballasts or signs averaged 8,900 a year and those at lamps 3,900, about a quarter of the total at electrical distribution equipment.[1] With the lamp in an approved lampholder and the fixture properly guarded, the heating hazard is negligible, and the handbook traces nearly all fires with electrically powered equipment to avoidable human error.[2][5] U.S. electrical rules respond with spacing requirements, temperature limits, thermal protection and special enclosures for hazardous locations.[3][6]

Definition and mechanisms

A luminaire becomes an ignition source when it raises a nearby material to its ignition temperature. Introduction to Fire Safety Engineering defines the ignition temperature as the lowest temperature of a substance at which ignition takes place, and notes that the heat needed depends on the fuel.[7] The handbook's electrical chapter adds that it is the minimum temperature needed to cause self-sustained combustion, independent of the heating element.[8]

Four mechanisms appear in the sources. The first is direct heating of combustibles in contact with or close to a hot lamp, such as a lamp shade, clothing draped over a lamp or paper near an exposed bulb.[1][9] The second is overheating of auxiliary equipment, above all fluorescent ballasts mounted against low-density fibreboard.[3] The third is the release of sparks, burning material or hot metal from a broken or failing lamp, which matters most in flammable atmospheres.[4] The fourth is an ordinary electrical fault in the fitting or its wiring, one of the routes of electrical ignition that the Fire Protection Handbook groups under arcing and overheating.[10]

Ignition does not require the bulb itself to reach the ignition temperature of the material. The handbook chapter on libraries and museums warns that incandescent bulbs near or in contact with combustibles may ignite them even if the bulb surface is below the ignition temperature of the material. Steady heating below that temperature can generate enough heat to ignite the material, given enough time. Cellulosic materials such as wood, paper and textiles store heat and may ignite after prolonged contact with hot objects well below their usual ignition temperature.[11] Rosales and Stoltzfus use a halogen lamp igniting a curtain as their example of ignition by external heating.[12]

Lamp surface temperatures

The handbook gives bare-bulb and base temperatures for standard incandescent lamps, taken from the fifth edition of the IES Handbook and measured in open sockets at 25 °C ambient with the lamp burning base up.[2][13] In most luminaires the lamp works in a warmer ambient and so runs hotter than these values. Other burning positions may raise the bulb temperature further.[2]

Maximum bare-bulb temperature of selected general service lamps, base up, 25 °C ambient[13]
Lamp Maximum bulb temperature (°C) Base temperature (°C)
25 W A-19 inside frosted 43 42
40 W A-19 inside frosted and white 127 105
40 W S-11 clear 299 199
60 W A-19 inside frosted and white 124 93
100 W A-19 inside frosted and white 149 98
200 W A-23 inside frosted, white or clear 174 107
500 W PS-35 clear or inside frosted 213 79
1500 W PS-52 clear or inside frosted 265 129

Wattage alone does not set the temperature. The small 40 W S-11 bulb reaches 299 °C, hotter than the much larger 1500 W PS-52 lamp at 265 °C.[13] Orientation also matters. For a 100 W A-19 lamp, the hottest spot rises from about 149 °C base up to 230 °C base down and about 247 °C when tilted. For a 500 W PS-35 lamp it rises from about 212 °C base up to about 309 °C base down.[2] Older Christmas tree lamps of U.S. manufacture reach about 127 °C at the hottest spot for blue and green colours.[2]

Discharge lamps differ. A fluorescent tube runs at an average of 38–43 °C over most of its length, because this is needed for efficient light production. Small areas above the cathodes at each end reach 49–121 °C, depending on the type.[2][3] High-intensity discharge (HID) lamps, such as mercury vapour lamps, usually run much hotter than incandescent or fluorescent lamps, exceeding 288 °C in some sizes.[3]

Some lamp types are known for high temperatures. Spotlights can easily reach the ignition temperature of paper or textiles.[11] The 2008 handbook reports that halogen torchiere lamps had become a concern in U.S. residence halls because of their high bulb temperature. Manufacturers had changed designs to keep combustibles from touching the bulb, yet some universities still discouraged their use at that time, also because of their high power demand.[14]

Heat transfer and worked example

A hot bulb loses heat by convection and by thermal radiation. Introduction to Fire Safety Engineering notes that radiation becomes the dominant mode at high temperatures, from about 400 °C, while convection dominates at lower temperatures.[15] The radiation that a hot surface emits to cooler surroundings follows from the Stefan–Boltzmann law:[15]

E=εσ(Th4−Tk4)

Symbol Description Unit
E Net radiant heat flux emitted by the hot surface W/m²
ε Emissivity of the surface (1 for a black body) –
σ Stefan–Boltzmann constant, 5.67 × 10−8 W/(m²·K⁴)
Th Absolute temperature of the hot surface K
Tk Absolute temperature of the cold surroundings K

A target some distance away receives only a fraction of this flux, given by the view factor.[15] Whether radiation alone can ignite a material is judged with the critical heat flux for ignition: at or below this flux the time to ignition is effectively infinite.[16] Table 3.9.5 of the handbook gives critical heat fluxes of 9–15 kW/m² for PMMA, 16 kW/m² for plywood, 10–17 kW/m² for hardboard and 10–23 kW/m² for carpet.[17]

Worked example. Take the hottest spot of a 500 W PS-35 lamp burning base down, 309 °C, in a 25 °C room.[2] As an upper bound, treat the glass as a black body with ε = 1. The net emitted flux is then 5.67 × 10−8 × (582.154 − 298.154) ≈ 6.1 kW/m², at the bulb surface itself. This is below the lowest critical heat flux in the table, 9 kW/m² for PMMA, and the flux falls further with distance. A black body would need a surface temperature of about 366 °C to emit 9 kW/m².

The lamp surface temperature, however, lies within the ignition temperature ranges given for PMMA (278–378 °C), hardboard (298–400 °C) and carpet (300–465 °C).[17] The calculation is consistent with the handbook's emphasis on lamps in contact with, surrounded by or laid on combustible material, where conduction and trapped heat act directly.[2] It does not cover concentrated beams such as spotlights, which the handbook singles out as able to reach the ignition temperature of paper or textiles.[11]

Ballasts, fittings and installation

Fluorescent lamps often need a high voltage to start, which requires transformers, reactors, capacitors and switches whose heat must be safeguarded.[2] The handbook calls for extreme care when fluorescent luminaires with ballasts are mounted on low-density cellulose fibreboard, defined as bonded plant material with a density of 320 kg/m³ or less. Unless the luminaire is listed for such mounting, it should be spaced at least 38 mm (1½ in.) from the surface, because the fibreboard can ignite at relatively low temperatures.[3] The 2008 handbook describes indoor fluorescent luminaires as having integral thermal ballast protection against overheating from failed capacitors, lamps or shorted windings.[3] A failing ballast can still be a source of ignition and may produce significant quantities of acrid smoke.[11]

Fittings in ceilings bring further risks. Recessed luminaires contain a thermal protector that opens the circuit temporarily when the fitting exceeds a set temperature.[18] In fire-rated membrane ceilings, light fittings must be of suitable design and spacing and often need shielding against heat transmission. Because the fire test is based on specific fittings and spacing, indiscriminate substitution can cause premature failure.[19]

Building codes also regulate fittings in fire-rated ceilings. The New York City Building Code, in both its 1968 and 2003 versions as compared by NIST, let fire-rated ceilings be pierced for outlet boxes and recessed lighting fixtures only within limits. Their aggregate area could not exceed 103 cm² per 8.4 m² (16 in.² per 90 ft²), and they had to be of steel at least 0.56 mm (0.022 in.) thick, sealed tightly at the ceiling.[20] In lightweight truss floors, a ceiling light fitting can start a fire in the truss void that spreads unnoticed.[21]

Spacing rules set a clearance to combustibles for some fittings. Under the 2005 NEC, as summarised in the handbook, electric signs must keep at least 50 mm (2 in.) between wood or other combustibles and an incandescent or HID lamp or lampholder. Signs must also not expose adjacent combustibles to more than 90 °C.[6] In storage occupancies, sufficient clearance must be kept between stored goods and any lighting fixtures, with the NEC consulted for minimum distances.[22]

Other rules address particular settings. In clothes closets, open, partially enclosed or pendant incandescent fittings are not permitted under the 2005 NEC.[2] Plastic diffusers are often acceptable if they deform and drop out of the fitting at a temperature well below their ignition point.[23] Among U.S. recreational-vehicle standard changes beginning with the 1993 edition of NFPA 501C, the handbook lists a requirement for listed low-voltage lighting fixtures to reduce heat build-up at mounting surfaces.[24]

Hazardous locations

In atmospheres with flammable vapours, combustible dusts or ignitable fibres, lamps must be in luminaires approved for the location.[2] Dust clouds have been ignited by the hot filaments of lightbulbs.[25] In U.S. Class I, Division 1 locations, luminaires must be of the explosionproof or purged type, marked with the maximum lamp wattage and either guarded or located beyond the area of potential damage.[2][26] Explosionproof equipment is defined in the NEC as apparatus whose case withstands an internal explosion, prevents ignition of the surrounding gas and runs cool enough not to ignite it.[27]

In Class I, Division 2 locations, lamps that run above the ignition temperature of the gas need explosionproof or purged enclosures. Fittings from which sparks or hot metal of a broken lamp could fall onto local concentrations of vapour also need suitable enclosures.[4] A larger lamp may raise the luminaire's normal-operation surface temperature. If it could exceed 80 % of the gas or vapour's ignition temperature in degrees Celsius, the 2005 NEC requires a luminaire type tested for its marked temperature operating range:[2]

Ts,potential>0.8TAIT⇒marked-range test required

Here Ts,potential is the possible luminaire surface temperature after fitting a larger lamp and TAIT is the gas or vapour's autoignition temperature, both in °C. The handbook lists autoignition temperatures of 280–471 °C for gasoline, 225 °C for hexane and 160 °C for diethyl ether.[28] The corresponding 80 % test triggers are about 224 °C, 180 °C and 128 °C, using the lower gasoline value. These thresholds trigger testing; they are not general maximum permissible surface temperatures.

Bare-lamp temperatures are not luminaire surface temperatures, but they show the scale of these test triggers. A bare 100 W A-19 lamp at 25 °C ambient reaches 149 °C base up and 230–247 °C in other positions.[2] Those bulb values are above the diethyl ether trigger in every position and above the gasoline trigger except base up, but they do not establish whether the luminaire itself requires the marked-range test. Listed equipment carries a temperature identification number, from T1 for a maximum of 450 °C down to T6 for 85 °C, which must not exceed the ignition temperature of the gas.[8][26]

Dust and fibre locations follow the same logic. In Class II, Division 1 locations, luminaires must have dust-ignitionproof enclosures, and surface temperatures under actual operating conditions must not exceed the ignition temperature of the dust.[4] Some coal dusts have minimum ignition temperatures of 170–180 °C.[26] In Class II, Division 2 locations, fixed lamps need enclosures that limit dust deposits and keep in sparks, burning material and hot metal. In Class III locations, where ignitable fibres are handled, lamps must be dust-tight and surfaces may not exceed 165 °C for equipment that cannot be overloaded.[29] Spray finishing areas apply a similar principle: fittings above a classified area should be totally enclosed or guarded so that hot particles cannot drop into it.[30]

Fire experience

U.S. fire statistics in the handbook show both the share of lighting and the role of non-electrical causes. In 1994–1998, fires coded as electrical failure averaged 81,670 a year, of which 4,890 involved light fixtures, lampholders, ballasts or signs and 740 involved lamps or lightbulbs.[1] When all causes are counted, fires that began at fixtures, lampholders, ballasts or signs rise to 8,900 a year and those at lamps to 3,900. The handbook explains that such totals include scenarios that are not electrical failures, such as equipment with hot surfaces installed or used too close to combustibles.[5] In U.S. facilities that care for the sick, light fixtures, lampholders, ballasts or signs were involved in about 100 of 2,600 fires a year in 1994–1998, or 3.9 %.[31]

Typical scenarios recur across occupancies. A lightbulb of higher wattage than the fixture's rating can overheat and ignite a lamp shade, and the handbook gives clothes draped over a lamp as an example of carelessness.[1] In records storage, paper in narrow aisles can be ignited by a faulty fluorescent ballast or an exposed incandescent bulb.[9] Portable handlamps add mechanical risks: a worn cord or a broken lamp can cause a fire, so handlamps need an insulating handle and a substantial guard.[3] The heat involved is small compared with a fire. NUREG-1805 lists a typical light bulb at 60 W, between a burning cigarette at 5 W and a candle at 80 W.[32]

Limits of the data

The temperature data in the handbook come from the fifth edition of the IES Handbook and were measured on bare lamps in open sockets at 25 °C. The handbook asks readers to keep in mind that lamps in fittings run hotter.[2] The sources in this article do not give comparable data for compact fluorescent or light-emitting diode lamps. All code rules quoted are U.S. rules from the 2005 NEC and related NFPA standards as summarised in the 20th edition of the Fire Protection Handbook (2008). The black-body calculation above gives an upper bound for emitted radiation and does not model conduction into a material in contact with the bulb.

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Milatovich (2008), p. 8-136.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 Milatovich (2008), p. 8-154.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Milatovich (2008), p. 8-157.
  4. ↑ 4.0 4.1 4.2 4.3 Milatovich (2008), p. 8-170.
  5. ↑ 5.0 5.1 Milatovich (2008), p. 8-135.
  6. ↑ 6.0 6.1 Milatovich (2008), p. 8-162.
  7. ↑ Van Rossum (2027), §4.2.
  8. ↑ 8.0 8.1 Milatovich (2008), p. 8-168.
  9. ↑ 9.0 9.1 Beals (2008), p. 9-106.
  10. ↑ Milatovich (2008), p. 8-134.
  11. ↑ 11.0 11.1 11.2 11.3 McDaniel (2008), pp. 20-184–20-185.
  12. ↑ Rosales and Stoltzfus (2008), p. 9-227.
  13. ↑ 13.0 13.1 13.2 Milatovich (2008), pp. 8-155–8-156.
  14. ↑ Berkol et al. (2008), p. 20-33.
  15. ↑ 15.0 15.1 15.2 Van Rossum (2027), §5.4.
  16. ↑ Madrzykowski and Stroup (2008), p. 2-34.
  17. ↑ 17.0 17.1 Budnick et al. (2008), p. 3-159.
  18. ↑ Milatovich (2008), p. 8-146.
  19. ↑ Gore Willse (2008b), p. 19-21.
  20. ↑ Razza and Grill (2005c), pp. 21–22.
  21. ↑ Corbett (2008), p. 12-132.
  22. ↑ J. Moore (2008), p. 20-161.
  23. ↑ Benedetti and Colonna (2008), p. 6-229.
  24. ↑ Hopkins (2008), p. 21-99.
  25. ↑ Schwab (2008c), p. 6-144.
  26. ↑ 26.0 26.1 26.2 Milatovich (2008), p. 8-169.
  27. ↑ Milatovich (2008), p. 8-164.
  28. ↑ Milatovich (2008), p. 8-165.
  29. ↑ Milatovich (2008), p. 8-171.
  30. ↑ Scarbrough (2008b), p. 9-34.
  31. ↑ O'Connor (2008), p. 20-141.
  32. ↑ Karlsson and Quintiere (1999), as cited in Iqbal and Salley (2004), p. 3-2.

References

  • Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-105–9-117). National Fire Protection Association.
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Berkol, A., Briese, B., & Comeau, E. (2008). Hotels and university housing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-23–20-36). National Fire Protection Association.
  • Budnick, E. K., Hunt, S. P., & Wright, M. T. (2008). Closed form enclosure fire calculations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-145–3-166). National Fire Protection Association.
  • Corbett, G. P. (2008). Effect of building construction and fire protection systems on fire fighter safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-127–12-141). National Fire Protection Association.
  • Gore Willse, P. J. (2008b). Types of building construction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-3–19-27). National Fire Protection Association.
  • Hopkins, B. A. (2008). Recreational vehicles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-91–21-100). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
  • Razza, J. C., & Grill, R. A. (2005c). Comparison of the 1968 and current (2003) New York City Building Code provisions (NIST NCSTAR 1-1F). National Institute of Standards and Technology.
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-141–6-152). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.