The '''methenamine pill test''' is a small-scale fire test that checks whether a carpet or rug lets a flame spread from a small [[ignition source]] across its surface. A square carpet specimen lies flat on the floor of a small box under a metal plate with a circular hole. A methenamine tablet is lit at the centre of the hole and burns with a candle-like flame for about 100 s.<ref name="HB-18-33">Hirschler (2008b), p. 18-33.</ref> The specimen fails if the flame or char advances to within 25.4 mm (1 in.) of the edge of the hole, and at least seven of eight specimens must pass.<ref name="HB-18-33" /><ref name="SC-6-96">Stull and Chines (2008), p. 6-96.</ref> | The '''methenamine pill test''' is a small-scale fire test that checks whether a carpet or rug lets a flame spread from a small [[ignition source]] across its surface. A square carpet specimen lies flat on the floor of a small box under a metal plate with a circular hole. A methenamine tablet is lit at the centre of the hole and burns with a candle-like flame for about 100 s.<ref name="HB-18-33">Hirschler (2008b), p. 18-33.</ref> The specimen fails if the flame or char advances to within 25.4 mm (1 in.) of the edge of the hole, and at least seven of eight specimens must pass.<ref name="HB-18-33" /><ref name="SC-6-96">Stull and Chines (2008), p. 6-96.</ref> | ||
The test was developed at the National Bureau of Standards (NBS, now the National Institute of Standards and Technology, NIST) to keep highly flammable carpet off the market. The United States federal government adopted it in 1970 as DOC FF-1-70 for carpets and DOC FF-2-70 for small carpets and rugs, and ASTM adopted it as ASTM D2859.<ref name="HB-18-33" /> | The test was developed at the National Bureau of Standards (NBS, now the National Institute of Standards and Technology, NIST) to keep highly flammable carpet off the market. The United States federal government adopted it in 1970 as DOC FF-1-70 for carpets and DOC FF-2-70 for small carpets and rugs, and ASTM adopted it as ASTM D2859.<ref name="HB-18-33" /> Hirschler (2008b) dates the US test requirement to April 1971; Stull and Chines (2008) note that small carpets and rugs that fail may still be sold with a permanent warning label.<ref name="HB-18-33" /><ref name="SC-6-96">Stull and Chines (2008), p. 6-96.</ref> The test was intended to limit the risk of carpet being the first item to ignite in a room. It does not show how a carpet behaves in a corridor exposed to a large fire, which is the task of the [[flooring radiant panel test]].<ref name="HB-18-33" /><ref name="HB-18-35">Hirschler (2008b), p. 18-35.</ref> | ||
== Purpose and history == | == Purpose and history == | ||
| Line 32: | Line 32: | ||
== Regulation and use == | == Regulation and use == | ||
In the United States, the pill test is the baseline for | In the United States, the pill test is described by the 2008 handbook as the federal baseline for carpet sales, subject to the small-carpet warning-label exception. Hirschler (2008b) explains that floor coverings in open building spaces and in rooms generally merit no further regulation, provided they resist [[flame spread]] at least as well as a material meeting FF-1-70 or ASTM D2859.<ref name="HB-18-35" /> Floor coverings in exits and corridors are regulated in addition by the flooring radiant panel test, under NFPA 101, ''Life Safety Code'' (2006 edition), as described by Hirschler (2008b).<ref name="HB-18-35" /> For health care occupancies, O'Connor (2008) states that where automatic sprinklers are provided, interior floor finishes need not be regulated beyond the federal flammability standard.<ref name="OC-20-145">O'Connor (2008), p. 20-145.</ref> | ||
The test also appears in standards for other products. The Canvas Products Association International (CPAI) specification for flame-resistant camping tent materials | The test also appears in standards for other products. The Canvas Products Association International (CPAI) specification for flame-resistant camping tent materials cited in the 2008 handbook prescribes the methenamine tablet carpet test for tent floors, with the Part 1630 criteria.<ref name="SC-6-98">Stull and Chines (2008), p. 6-98.</ref> ASTM D4372, a specification for flame-resistant tentage materials, likewise measures the flame resistance of flooring with a methenamine pill as the ignition source.<ref name="SC-6-98" /> | ||
Local codes adopted the test alongside other methods. In New York City, Local Law 16 of 1984 added a reference standard for the flammability of carpets, RS 5-20. It cited a pill test (printed as "Methane Pill Test, DOC FF1-1970"), ASTM E 648-1978 and ASTM E 662-1979.<ref name="RG-23">Razza and Grill (2005a), p. 23.</ref> Under the amended code, all carpets and underlays had to pass the pill test to RS 5-20. Carpets in corridors also needed a critical radiant flux of at least 5 kW/m² (0.5 W/cm²), and in other general areas at least 4 kW/m² (0.4 W/cm²).<ref name="GJ-107">Grill and Johnson (2005b), p. 107.</ref> Carpet was not allowed in required exits, except wool carpet in lobbies, exit passageways and convenient stairs.<ref name="GJ-107" /> | Local codes adopted the test alongside other methods. In New York City, Local Law 16 of 1984 added a reference standard for the flammability of carpets, RS 5-20. It cited a pill test (printed as "Methane Pill Test, DOC FF1-1970"), ASTM E 648-1978 and ASTM E 662-1979.<ref name="RG-23">Razza and Grill (2005a), p. 23.</ref> Under the amended code, all carpets and underlays had to pass the pill test to RS 5-20. Carpets in corridors also needed a critical radiant flux of at least 5 kW/m² (0.5 W/cm²), and in other general areas at least 4 kW/m² (0.4 W/cm²).<ref name="GJ-107">Grill and Johnson (2005b), p. 107.</ref> Carpet was not allowed in required exits, except wool carpet in lobbies, exit passageways and convenient stairs.<ref name="GJ-107" /> | ||
Revision as of 23:59, 7 November 2026
The methenamine pill test is a small-scale fire test that checks whether a carpet or rug lets a flame spread from a small ignition source across its surface. A square carpet specimen lies flat on the floor of a small box under a metal plate with a circular hole. A methenamine tablet is lit at the centre of the hole and burns with a candle-like flame for about 100 s.[1] The specimen fails if the flame or char advances to within 25.4 mm (1 in.) of the edge of the hole, and at least seven of eight specimens must pass.[1][2]
The test was developed at the National Bureau of Standards (NBS, now the National Institute of Standards and Technology, NIST) to keep highly flammable carpet off the market. The United States federal government adopted it in 1970 as DOC FF-1-70 for carpets and DOC FF-2-70 for small carpets and rugs, and ASTM adopted it as ASTM D2859.[1] Hirschler (2008b) dates the US test requirement to April 1971; Stull and Chines (2008) note that small carpets and rugs that fail may still be sold with a permanent warning label.[1][2] The test was intended to limit the risk of carpet being the first item to ignite in a room. It does not show how a carpet behaves in a corridor exposed to a large fire, which is the task of the flooring radiant panel test.[1][3]
Purpose and history
Until 1960 there was very little fire experience to suggest that carpets were a significant factor in fires, and building codes customarily exempted floor coverings.[4] Official attention turned to soft floor coverings after a series of small fires in the Washington, D.C., area in 1960 and 1961.[1] Stull and Chines describe a 1970 fire in a California dwelling that was first seen as a fire a few feet across on carpet in front of the fireplace. The occupant applied water with a garden hose, but the fire spread rapidly over the carpet and within ten minutes involved the whole room, including furniture and wood panelling.[4] Because of such experiences, carpet flammability came to be regulated at federal, state and municipal levels.[4]
NIST, then NBS, developed the pill test as a means of preventing the use of highly flammable carpet floor coverings.[1] In the handbook's references, the two federal standards appear as 16 CFR Part 1630, Standard for the Surface Flammability of Carpets and Rugs (FF 1-70). The rule for small carpets and rugs is 16 CFR Part 1631 (FF 2-70). Both are issued by the U.S. Consumer Product Safety Commission (CPSC).[5][6]
The two parts sit among the Flammable Fabrics Act regulations of the Code of Federal Regulations.[7] The same act, passed in 1953 and amended in 1967, underlies the CPSC standard for clothing textiles.[8][4] When the carpet requirement was introduced, it eliminated only a small percentage of the carpets on the market, usually those of low quality.[2]
The test is one of a family of simple textile fire tests. The handbook compares it with the clothing test 16 CFR Part 1610, in which a 16 mm butane flame touches a fabric at 45° for 1 s and the rate of flame spread is measured.[9] For carpets and rugs, both 16 CFR Part 1630 and ASTM D2859 use a horizontal specimen, a methenamine pill on the fabric face, a variable exposure time and a measurement of char distance.[9] Stull and Chines treat these methods in their chapter on fibres and textile flammability.[4] The handbook's table of equivalent fire test standards places ASTM D2859 in the floor coverings group, next to NFPA 253 and ASTM E648.[10] Iqbal and Salley (2004) list both 16 CFR 1630.4 and ASTM D2859 among the empirical standard small-scale flammability tests.[11]
Apparatus and procedure
Eight square sections of carpet, each 229 mm (9 in.) on a side, are cut from the product.[1] They are conditioned to drive off excess moisture and then brought to room temperature in a desiccator before testing.[1] Each specimen in turn is placed on the bottom of an enclosed cube of 0.3 m (1 ft), open at the top. A square metal plate of 229 mm (9 in.) with a circular cutout of 203 mm (8 in.) holds it flat.[1] Stull and Chines describe the plate as a flat steel plate with a hole of that diameter in its centre.[2]
A methenamine tablet is placed at the centre of the circle and lit.[1] The pill produces a candle-like flame for about 100 s.[1] If the carpet ignites, flame may advance outward from the pill. The specimen fails if the flame advances to within 25.4 mm (1 in.) of the metal ring of the hold-down plate.[1] Stull and Chines phrase the pass condition in terms of char: the charred portion must not extend to within 25 mm of the edge of the hole at any point.[2] The measured quantity is thus a char distance on a horizontal specimen, and the exposure time is not fixed but depends on how long the pill and the carpet burn.[9]
The criterion is a count of specimens. At least seven of the eight specimens must pass for the carpet to meet the established criteria.[1] Under the federal rules, separate parts apply to different sizes. For carpets and rugs other than small ones, seven of eight specimens must pass if carpets of the tested material are to be sold.[2] Small carpets and rugs that fail may still be sold if they carry a permanent label stating that they failed the test and should not be used near an ignition source.[2]
The methenamine pill as an ignition source
Methenamine, also called hexamethylenetetramine, has the formula C6H12N4 and a molecular weight of 140.19.[12] The handbook's table of heats of combustion gives it a gross heat of combustion of 29.97 MJ/kg and a net value of 28.08 MJ/kg. The SFPE Handbook gives the same values.[12][13] Methenamine sublimes: like carbon dioxide, it passes directly from solid to gas at normal temperature and pressure.[14] Beyler and Hirschler note that this substance is of interest in fire science because its pills are the ignition source in ASTM D2859, used in mandatory national regulations.[14]
A flame needs fuel, oxygen and enough heat. A combustible substance mixed with oxygen cannot ignite unless sufficient heat is added, and the amount depends on the substance.[15] The pill supplies that heat as a small flame. Babrauskas, in his comparison of ignition sources used in furniture fire experiments, lists a methenamine pill of 0.15 g with a typical heat output of 45 W and about 90 s of significant flaming.[16] In the same table a cigarette of 1.1 g gives about 5 W for 1,200 s, and a wooden match laid on a solid surface gives about 80 W for 20 to 30 s.[16] The data in that table come from Krasny, Parker and Babrauskas (2001), as cited in Babrauskas (2008b).[16]
Babrauskas adds that the maximum heat fluxes of these sources, except the methenamine pill, lie between 18 and 42 kW/m². A typical "incidental" ignition source produces a flame heat flux of about 35 kW/m².[16] What changes as a source becomes stronger is not so much the flux as the area over which it acts, and small heated areas need higher fluxes to reach their ignition temperature than large ones.[16] The pill is thus a small source, with a power between that of a cigarette and a wooden match.[16] How fast a surface heats under such a source depends on its thermal inertia. Materials with a low thermal inertia, such as light insulation, show a rapid rise in surface temperature that can contribute to rapid ignition.[17]
Worked example: energy and pass zone
The heat released by one pill can be estimated from its mass and its heat of combustion. With the net heat of combustion of 28.08 MJ/kg, a pill of 0.15 g releases about 0.15 × 10−3 kg × 28.08 × 106 J/kg ≈ 4,200 J, or 4.2 kJ.[12][16] Spread over the 90 s of significant flaming, this is an average of about 47 W, close to the tabulated 45 W. Over the 100 s given by Hirschler, it is about 42 W.[16][1] The two sources thus describe a consistent source of roughly 40 to 50 W.
The geometry of the plate sets how far the flame may travel. The hole has a diameter of 203 mm (8 in.), so its edge lies 101.6 mm from the centre. A specimen fails once flame or char reaches 25.4 mm from that edge, which leaves a limiting radius of 76.2 mm, or a circle of 152 mm diameter around the pill.[1][2] That circle has an area of about 182 cm², just over half of the 324 cm² of carpet exposed in the hole. In words, a passing carpet must stop the flame within about 76 mm of the pill in every direction on at least seven of eight specimens.
Regulation and use
In the United States, the pill test is described by the 2008 handbook as the federal baseline for carpet sales, subject to the small-carpet warning-label exception. Hirschler (2008b) explains that floor coverings in open building spaces and in rooms generally merit no further regulation, provided they resist flame spread at least as well as a material meeting FF-1-70 or ASTM D2859.[3] Floor coverings in exits and corridors are regulated in addition by the flooring radiant panel test, under NFPA 101, Life Safety Code (2006 edition), as described by Hirschler (2008b).[3] For health care occupancies, O'Connor (2008) states that where automatic sprinklers are provided, interior floor finishes need not be regulated beyond the federal flammability standard.[18]
The test also appears in standards for other products. The Canvas Products Association International (CPAI) specification for flame-resistant camping tent materials cited in the 2008 handbook prescribes the methenamine tablet carpet test for tent floors, with the Part 1630 criteria.[19] ASTM D4372, a specification for flame-resistant tentage materials, likewise measures the flame resistance of flooring with a methenamine pill as the ignition source.[19]
Local codes adopted the test alongside other methods. In New York City, Local Law 16 of 1984 added a reference standard for the flammability of carpets, RS 5-20. It cited a pill test (printed as "Methane Pill Test, DOC FF1-1970"), ASTM E 648-1978 and ASTM E 662-1979.[20] Under the amended code, all carpets and underlays had to pass the pill test to RS 5-20. Carpets in corridors also needed a critical radiant flux of at least 5 kW/m² (0.5 W/cm²), and in other general areas at least 4 kW/m² (0.4 W/cm²).[21] Carpet was not allowed in required exits, except wool carpet in lobbies, exit passageways and convenient stairs.[21]
What the test shows and its limits
Although the pill test is small, its results have large implications for floor covering performance. It has been shown to give adequate "first to ignite" protection for carpet located in rooms.[1] Experiments at NIST found that carpets and floor coverings were unlikely to become involved in a fire, or to spread flame, until a room fire approached or exceeded flashover. The exception was a fire that started at floor level.[1] Little additional safety is therefore gained by regulating floor coverings within rooms beyond the pill test, and these findings helped to shape the code restrictions for floor coverings.[1] Babrauskas likewise notes that carpets in the room of fire origin are not likely to contribute significantly to fire growth.[22]
Passing the pill test does not mean that a carpet resists flame spread under strong radiant heating. A precision study of the flooring radiant panel test found carpets with critical radiant fluxes well under 2 kW/m².[1] The minimum critical radiant flux of a product that still passes the pill test has been found to be 0.4 kW/m².[23] This value is well below the 2.2 kW/m² of the lowest NFPA 101 floor finish class.[3] The two tests answer different questions, ignition by a small source in a room and flame spread under radiation in a corridor, which is why codes use both.[24][3]
Other limits follow from the method. The test uses one small source on a flat, horizontal specimen. The ignition hazard of a carpet, however, depends on many construction factors: fibre type, pile density and height, backing, padding, adhesive, single or double backing, and dye.[4] Traditional floor finishes such as wood or resilient flooring will not ignite unless exposed to well over 1 kW/m², but some carpet-like and loose-fill materials may ignite at lower fluxes.[1]
Fire statistics give the scale of the problem. In the United States in 1999–2003, a textile floor covering, rug, carpet or mat was the item first ignited in an average of about 4,900 nonconfined structure fires a year. These fires caused about 80 civilian deaths and 240 injuries a year.[25] Stull and Chines note that the fatal carpet and rug fires that persist occur mainly in the home, a much less regulated environment.[4]
See also
- Interior finish
- Steiner tunnel test
- Children's sleepwear flammability
- Mattress flammability
- Reaction to fire
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 Hirschler (2008b), p. 18-33.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Stull and Chines (2008), p. 6-96.
- ↑ 3.0 3.1 3.2 3.3 3.4 Hirschler (2008b), p. 18-35.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Stull and Chines (2008), p. 6-89.
- ↑ Stull and Chines (2008), p. 6-101.
- ↑ Hirschler (2008b), p. 18-41.
- ↑ Beyler and Hirschler (2002), p. 1-130.
- ↑ Stull and Chines (2008), p. 6-86.
- ↑ 9.0 9.1 9.2 Stull and Chines (2008), p. 6-90.
- ↑ Hirschler (2008a), p. 6-38.
- ↑ Iqbal and Salley (2004), p. C-17.
- ↑ 12.0 12.1 12.2 Babrauskas (2008a), p. 6-271.
- ↑ DiNenno et al. (2002), p. A-38.
- ↑ 14.0 14.1 Beyler and Hirschler (2002), p. 1-114.
- ↑ Van Rossum (2027), §4.2.
- ↑ 16.0 16.1 16.2 16.3 16.4 16.5 16.6 16.7 Babrauskas (2008b), p. 6-118.
- ↑ Van Rossum (2027), §5.2.
- ↑ O'Connor (2008), p. 20-145.
- ↑ 19.0 19.1 Stull and Chines (2008), p. 6-98.
- ↑ Razza and Grill (2005a), p. 23.
- ↑ 21.0 21.1 Grill and Johnson (2005b), p. 107.
- ↑ Babrauskas (2002b), p. 3-11.
- ↑ Hirschler (2008b), p. 18-34.
- ↑ Hirschler (2008b), p. 18-39.
- ↑ Stull and Chines (2008), p. 6-78.
References
- Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
- Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
- Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
- Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
- DiNenno, P. J., Drysdale, D., Beyler, C. L., Walton, W. D., Custer, R. L. P., Hall, J. R., Jr., & Watts, J. M., Jr. (Eds.). (2002). SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association; Society of Fire Protection Engineers.
- Grill, R. A., & Johnson, D. A. (2005b). Fire protection and life safety provisions applied to the design and construction of WTC 1, 2, and 7 and post-construction provisions applied after occupancy (NIST NCSTAR 1-1D). National Institute of Standards and Technology.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
- Razza, J. C., & Grill, R. A. (2005a). Amendments to the fire protection and life safety provisions of the New York City Building Code by local laws adopted while World Trade Center 1, 2, and 7 were in use (NIST NCSTAR 1-1G). National Institute of Standards and Technology.
- Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.