Skip to content
From Fire Safety Academy Wiki
Jan (talk | contribs)
New FSE wiki article: NFPA 704 (written by Claude Opus 5.5)
 
Jan (talk | contribs)
NFPA wiki: fact-check corrections (written by Claude Opus 5.5)
Line 1: Line 1:
'''NFPA 704''' is a standard of the [[NFPA]] (National Fire Protection Association) that sets out a marking system for showing the hazards of materials to emergency responders. The marking is a diamond-shaped sign, often called the '''NFPA diamond'''.<ref name="CJW-13-122">C. J. Wright (2008a), pp. 13-122–13-123.</ref> Its full title in the 2008 edition of the ''Fire Protection Handbook'' is ''Standard System for the Identification of the Hazards of Materials for Emergency Response''.<ref name="CJW-13-122" /> The diamond is divided into four coloured quadrants: blue for health, red for flammability, yellow for reactivity or instability, and a bottom quadrant for special hazards such as oxidisers and water-reactive materials.<ref name="CJW-13-123">C. J. Wright (2008a), p. 13-123.</ref>
'''NFPA 704''' is a standard of the [[NFPA]] (National Fire Protection Association) that sets out a marking system for showing the hazards of materials to emergency responders. The marking is a diamond-shaped sign, often called the '''NFPA diamond'''.<ref name="CJW-13-122">C. J. Wright (2008a), pp. 13-122–13-123.</ref><ref name="Davenport-7-43" /> Its full title in the 2008 edition of the ''Fire Protection Handbook'' is ''Standard System for the Identification of the Hazards of Materials for Emergency Response''.<ref name="CJW-13-122" /> The diamond is divided into four coloured quadrants: blue for health, red for flammability, yellow for reactivity or instability, and a bottom quadrant for special hazards such as oxidisers and water-reactive materials.<ref name="CJW-13-123">C. J. Wright (2008a), p. 13-123.</ref>


Each of the three numbered quadrants carries a number from 0 to 4 that gives the relative degree of hazard, from 0 (low) to 4 (high).<ref name="CJW-13-123" /> The markings are used within facilities such as chemical stores, laboratories and hospitals; they are not used on transport vehicles, which carry transport placards instead.<ref name="CJW-13-122" /><ref name="Davenport-7-44">Davenport (2008), p. 7-44.</ref> The ratings describe the hazards of a material under emergency conditions, and fire fighters trained in the system are, in the words of one handbook chapter, "instantly apprised" of the hazards they face.<ref name="Allen-6-194">Allen (2008), p. 6-194.</ref> The descriptions in this article follow the 2008 ''Fire Protection Handbook'', which reproduces material from the 2001 and 2007 editions of the standard.<ref name="CJW-13-123" />
Each of the three numbered quadrants carries a number from 0 to 4 that gives the relative degree of hazard, from 0 (low) to 4 (high).<ref name="CJW-13-123" /> The markings are used within facilities, for example in chemical storage areas, laboratories and hospitals; they may be found on nonbulk packages but are not used on transport vehicles, which carry transport placards instead.<ref name="CJW-13-122" /><ref name="Davenport-7-44">Davenport (2008), p. 7-44.</ref><ref name="Allen-6-194" /><ref name="CJW-13-124" /> The system is intended for emergency response; the health criteria, for example, describe what a material can do to people under emergency conditions.<ref name="CJW-13-123" /> Fire fighters trained in the system are, in the words of one handbook chapter, "instantly apprised" of the hazards they face.<ref name="Allen-6-194">Allen (2008), p. 6-194.</ref> The descriptions in this article follow the 2008 ''Fire Protection Handbook'', which reproduces material from the 2001 and 2007 editions of the standard.<ref name="CJW-13-123" />


== Purpose and scope ==
== Purpose and scope ==
Line 13: Line 13:
The symbol is a square standing on one corner, divided into four smaller diamonds. The blue quadrant on the left gives the health hazard, the red quadrant at the top the flammability hazard and the yellow quadrant on the right the reactivity hazard.<ref name="CJW-13-123" /> The bottom quadrant carries special information, such as "OX" for an [[Oxidiser|oxidiser]] or "W" for a [[Water-reactive material|water-reactive material]].<ref name="CJW-13-123" /> The sample marking printed in the handbook is taken from the 2007 edition of NFPA 704. It shows a health rating of 2, a flammability rating of 4 and an instability rating of 3, with a W crossed by a horizontal bar below.<ref name="CJW-13-123" />
The symbol is a square standing on one corner, divided into four smaller diamonds. The blue quadrant on the left gives the health hazard, the red quadrant at the top the flammability hazard and the yellow quadrant on the right the reactivity hazard.<ref name="CJW-13-123" /> The bottom quadrant carries special information, such as "OX" for an [[Oxidiser|oxidiser]] or "W" for a [[Water-reactive material|water-reactive material]].<ref name="CJW-13-123" /> The sample marking printed in the handbook is taken from the 2007 edition of NFPA 704. It shows a health rating of 2, a flammability rating of 4 and an instability rating of 3, with a W crossed by a horizontal bar below.<ref name="CJW-13-123" />


The numbers give a relative degree of hazard. A 4 means the most severe hazard in that category and a 0 the least severe; the degrees are defined by descriptions, not by measured quantities, so a 4 is not "twice" a 2.<ref name="CJW-13-123" /> Each quadrant is rated on its own, so one material can be harmless in one category and extreme in another. Chlorine, for example, carries a health rating of 4 and flammability and instability ratings of 0, together with the OX symbol.<ref name="Lemoff-6-180">Lemoff (2008), p. 6-180.</ref>
The numbers give a relative degree of hazard. A 4 means the most severe hazard in that category and a 0 the least severe; the degrees are defined by descriptions, not by measured quantities.<ref name="CJW-13-123" /> Each quadrant is rated on its own, so one material can be harmless in one category and extreme in another. Chlorine, for example, carries a health rating of 4 and flammability and instability ratings of 0, together with the OX symbol.<ref name="Lemoff-6-180">Lemoff (2008), p. 6-180.</ref>


The handbook uses two words for the yellow quadrant. The text of C. J. Wright (2008a) calls it the reactivity hazard, while the table reproduced from the 2001 edition of the standard heads the column "Instability Hazard".<ref name="CJW-13-123" /> Allen (2008) writes "self-reactivity (instability)", and Scarbrough (2008b) speaks of five degrees of health, flammability and reactivity hazards.<ref name="Allen-6-194" /><ref name="Scarbrough-9-33">Scarbrough (2008b), p. 9-33.</ref> The criteria in the 2001 table describe the stability of "materials that in themselves" detonate, decompose or change violently, while reaction with water is shown by the W symbol in the bottom quadrant.<ref name="CJW-13-123" />
The handbook uses two words for the yellow quadrant. The text of C. J. Wright (2008a) calls it the reactivity hazard, while the table reproduced from the 2001 edition of the standard heads the column "Instability Hazard".<ref name="CJW-13-123" /> Allen (2008) writes "self-reactivity (instability)", and Scarbrough (2008b) speaks of five degrees of health, flammability and reactivity hazards.<ref name="Allen-6-194" /><ref name="Scarbrough-9-33">Scarbrough (2008b), p. 9-33.</ref> The criteria in the 2001 table describe the stability of "materials that in themselves" detonate, decompose or change violently, while reaction with water is shown by the W symbol in the bottom quadrant.<ref name="CJW-13-123" />
Line 74: Line 74:
For pesticide storage, Whitford (2008) recommends hazard warning signs using the NFPA 704 system on all structures and fixed tanks that house or store hazardous materials, coordinated with the fire jurisdiction that serves the site.<ref name="Whitford-6-242">Whitford (2008), p. 6-242.</ref> Operators may also post the W signal from NFPA 704 to warn responders not to use water, but only after consulting the local authorities and the insurers.<ref name="Whitford-6-242" /> The same chapter advises that nonflammable materials with a health rating of 3 or 4 be isolated from other materials in storage.<ref name="Whitford-6-239">Whitford (2008), p. 6-239.</ref>
For pesticide storage, Whitford (2008) recommends hazard warning signs using the NFPA 704 system on all structures and fixed tanks that house or store hazardous materials, coordinated with the fire jurisdiction that serves the site.<ref name="Whitford-6-242">Whitford (2008), p. 6-242.</ref> Operators may also post the W signal from NFPA 704 to warn responders not to use water, but only after consulting the local authorities and the insurers.<ref name="Whitford-6-242" /> The same chapter advises that nonflammable materials with a health rating of 3 or 4 be isolated from other materials in storage.<ref name="Whitford-6-239">Whitford (2008), p. 6-239.</ref>


In laboratories, the 2008 handbook describes NFPA 45 as requiring a second means of access from the laboratory unit to a means of egress in six situations. Two of them concern a compressed gas cylinder larger than a lecture bottle, or a cryogenic container, holding a gas that is flammable or has a health rating of 3 or 4.<ref name="Anderson-9-158">Anderson (2008a), p. 9-158.</ref> Lecture-bottle cylinders containing pyrophoric gases, gases with a health rating of 3 or 4, or gases rated 2 without physiological warning properties need continuously mechanically ventilated enclosures.<ref name="Anderson-9-165">Anderson (2008a), p. 9-165.</ref> In health care, Allen (2008) reports that NFPA 99 requires the symbols in laboratories and calls it prudent to apply them also in general stores, pharmacies, operating rooms and gas and flammable liquid storage rooms.<ref name="Allen-6-194" />
In laboratories, the 2008 handbook describes NFPA 45 as requiring a second means of access from the laboratory unit to a means of egress in six situations. Two of them concern a compressed gas cylinder larger than a lecture bottle, or a cryogenic container, holding a gas that is flammable or has a health rating of 3 or 4.<ref name="Anderson-9-158">Anderson (2008a), p. 9-158.</ref> As described in the 2008 handbook, some lecture-bottle cylinders are required to be kept in special continuously mechanically ventilated enclosures. This applies to cylinders containing pyrophoric gases, gases with a health rating of 3 or 4, or gases rated 2 without physiological warning properties.<ref name="Anderson-9-165">Anderson (2008a), p. 9-165.</ref> In health care, Allen (2008) reports that NFPA 99 requires the symbols in laboratories and calls it prudent to apply them also in general stores, pharmacies, operating rooms and gas and flammable liquid storage rooms.<ref name="Allen-6-194" />


Other chapters use the markings for planning. In chemical plants, NFPA 704 symbols posted where chemicals are present give guidance on the inherent hazards and on planning fire-fighting operations.<ref name="Schwab-8-22">Schwab (2008a), p. 8-22.</ref> Schwab (2008a) also names NFPA 704 as a reference on chemical stability and shock sensitivity.<ref name="Schwab-8-24">Schwab (2008a), p. 8-24.</ref> For spray finishing, Scarbrough (2008b) advises that the hazards of materials be identified with the system as soon as they arrive in the facility, and that personnel be trained on them.<ref name="Scarbrough-9-33" />
Other chapters use the markings for planning. In chemical plants, NFPA 704 symbols posted where chemicals are present give guidance on the inherent hazards and on planning fire-fighting operations.<ref name="Schwab-8-22">Schwab (2008a), p. 8-22.</ref> Schwab (2008a) also names NFPA 704 as a reference on chemical stability and shock sensitivity.<ref name="Schwab-8-24">Schwab (2008a), p. 8-24.</ref> For spray finishing, Scarbrough (2008b) advises that the hazards of materials be identified with the system as soon as they arrive in the facility, and that personnel be trained on them.<ref name="Scarbrough-9-33" />


== Use in emergency response ==
== Use in emergency response ==
In [[Hazardous materials response]], recognising that hazardous materials are present is the first task of the size-up. C. J. Wright (2008a) lists facility and transport markings among the clues responders look for, with NFPA 704 as the marking used within facilities.<ref name="CJW-13-122" /> The hazardous material data sheet that the chapter offers for recording information at an incident has fields for the NFPA 704 health, flammability and reactivity ratings and for other special hazards.<ref name="CJW-13-129">C. J. Wright (2008a), p. 13-129.</ref>
In [[Hazardous materials response]], recognising that hazardous materials are present is the first task of the size-up.<ref name="CJW-13-121">C. J. Wright (2008a), p. 13-121.</ref> C. J. Wright (2008a) lists facility and transport markings among the clues responders look for, with NFPA 704 as the marking used within facilities.<ref name="CJW-13-122" /> The hazardous material data sheet that the chapter offers for recording information at an incident has fields for the NFPA 704 health, flammability and reactivity ratings and for other special hazards.<ref name="CJW-13-129">C. J. Wright (2008a), p. 13-129.</ref>


Not every reference guide gives the rating. A cross-reference of common printed guides lists the NFPA 704 marking for three of them. These are the ''Emergency Action Guides'' of the Association of American Railroads, the NFPA guide and the US Coast Guard CHRIS manual series.<ref name="CJW-13-131">C. J. Wright (2008a), pp. 13-130–13-131.</ref> The same table does not mark it for the ''Emergency Response Guidebook'', the NIOSH ''Pocket Guide to Chemical Hazards'' or material safety data sheets.<ref name="CJW-13-131" />
Not every reference guide gives the rating. A cross-reference of common printed guides lists the NFPA 704 marking for three of them. These are the ''Emergency Action Guides'' of the Association of American Railroads, the NFPA guide and the US Coast Guard CHRIS manual series.<ref name="CJW-13-131">C. J. Wright (2008a), pp. 13-130–13-131.</ref> The same table does not mark it for the ''Emergency Response Guidebook'', the NIOSH ''Pocket Guide to Chemical Hazards'' or material safety data sheets.<ref name="CJW-13-131" />
Line 95: Line 95:
The marking shows hazard, not quantity. The criteria in the 2001 table describe the properties of a material and say nothing about the amount present.<ref name="CJW-13-123" /> Responders therefore need other information, such as planning documents and container sizes, to judge the size of an incident; the FDNY plan, for example, grades container size in a separate row.<ref name="CJW-13-122" /><ref name="LV-A" />
The marking shows hazard, not quantity. The criteria in the 2001 table describe the properties of a material and say nothing about the amount present.<ref name="CJW-13-123" /> Responders therefore need other information, such as planning documents and container sizes, to judge the size of an incident; the FDNY plan, for example, grades container size in a separate row.<ref name="CJW-13-122" /><ref name="LV-A" />


The health number refers to the material under emergency conditions, not to the smoke of a fire. Davenport (2008) warns that products of combustion may present very different hazards, more or less severe than those of the uncombusted chemical.<ref name="Davenport-7-44" /><ref name="Davenport-7-45">Davenport (2008), p. 7-45.</ref> The [[Fire toxicity|fire toxicity]] of the effluent therefore has to be judged separately from the blue quadrant.
The health criteria describe the material itself under emergency conditions.<ref name="CJW-13-123" /> Davenport (2008) warns that products of combustion may present very different hazards, more or less severe than those of the uncombusted chemical.<ref name="Davenport-7-44" /><ref name="Davenport-7-45">Davenport (2008), p. 7-45.</ref> The handbook does not link this warning to the NFPA 704 rating, but it means that the [[Fire toxicity|fire toxicity]] of the effluent cannot be read from the blue quadrant.


A composite area sign can hide detail. As the worked example shows, the "most severe" rule produces a combination that may belong to no single material in the room. The signs are also only as good as the information behind them. Whitford (2008) asks that their use be coordinated with the fire jurisdiction that serves the site, and Allen (2008) notes that the survey needed to post them can reveal hazardous materials no longer in use.<ref name="Whitford-6-242" /><ref name="Allen-6-194" />
A composite area sign can hide detail. As the worked example shows, the "most severe" rule produces a combination that may belong to no single material in the room. The signs are also only as good as the information behind them. Whitford (2008) asks that their use be coordinated with the fire jurisdiction that serves the site, and Allen (2008) notes that the survey needed to post them can reveal hazardous materials no longer in use.<ref name="Whitford-6-242" /><ref name="Allen-6-194" />

Revision as of 22:34, 7 November 2026

NFPA 704 is a standard of the NFPA (National Fire Protection Association) that sets out a marking system for showing the hazards of materials to emergency responders. The marking is a diamond-shaped sign, often called the NFPA diamond.[1][2] Its full title in the 2008 edition of the Fire Protection Handbook is Standard System for the Identification of the Hazards of Materials for Emergency Response.[1] The diamond is divided into four coloured quadrants: blue for health, red for flammability, yellow for reactivity or instability, and a bottom quadrant for special hazards such as oxidisers and water-reactive materials.[3]

Each of the three numbered quadrants carries a number from 0 to 4 that gives the relative degree of hazard, from 0 (low) to 4 (high).[3] The markings are used within facilities, for example in chemical storage areas, laboratories and hospitals; they may be found on nonbulk packages but are not used on transport vehicles, which carry transport placards instead.[1][4][5][6] The system is intended for emergency response; the health criteria, for example, describe what a material can do to people under emergency conditions.[3] Fire fighters trained in the system are, in the words of one handbook chapter, "instantly apprised" of the hazards they face.[5] The descriptions in this article follow the 2008 Fire Protection Handbook, which reproduces material from the 2001 and 2007 editions of the standard.[3]

Purpose and scope

The 2008 handbook describes NFPA 704 markings as diamond-shaped symbols used within facilities to alert people to the type and degree of hazard of the materials present.[1] Benedetti (2008) names hazardous material identification systems, such as transport placarding and NFPA 704, as the principal means by which the impact of large flammable gas fires in populated areas is minimised.[7] The system is therefore an information tool for the people who must act during an emergency.

The main users are fire fighters and other responders. Allen (2008) notes that fire-fighting personnel are trained to recognise the relative hazard potential shown by the "704 diamond", so that they are "instantly apprised" of the hazards they face.[5] The same author lists a second benefit: employees learn about the hazards of the materials they handle every day. The survey needed to post the signs may also reveal hazardous materials no longer in use, which can then be removed.[5]

The title of the standard has changed over time. The SFPE handbook chapter on fire risk indexing cites it under the older title Identification of the Fire Hazards of Materials. Its text names the 1990 edition and its reference list the 1996 edition.[8][9] The 2008 Fire Protection Handbook uses the longer title that refers to emergency response.[1]

The diamond and its quadrants

The symbol is a square standing on one corner, divided into four smaller diamonds. The blue quadrant on the left gives the health hazard, the red quadrant at the top the flammability hazard and the yellow quadrant on the right the reactivity hazard.[3] The bottom quadrant carries special information, such as "OX" for an oxidiser or "W" for a water-reactive material.[3] The sample marking printed in the handbook is taken from the 2007 edition of NFPA 704. It shows a health rating of 2, a flammability rating of 4 and an instability rating of 3, with a W crossed by a horizontal bar below.[3]

The numbers give a relative degree of hazard. A 4 means the most severe hazard in that category and a 0 the least severe; the degrees are defined by descriptions, not by measured quantities.[3] Each quadrant is rated on its own, so one material can be harmless in one category and extreme in another. Chlorine, for example, carries a health rating of 4 and flammability and instability ratings of 0, together with the OX symbol.[10]

The handbook uses two words for the yellow quadrant. The text of C. J. Wright (2008a) calls it the reactivity hazard, while the table reproduced from the 2001 edition of the standard heads the column "Instability Hazard".[3] Allen (2008) writes "self-reactivity (instability)", and Scarbrough (2008b) speaks of five degrees of health, flammability and reactivity hazards.[5][11] The criteria in the 2001 table describe the stability of "materials that in themselves" detonate, decompose or change violently, while reaction with water is shown by the W symbol in the bottom quadrant.[3]

Degrees of hazard

The meaning of each number is defined in words, not by measured values. The table below gives the criteria as printed in the 2008 handbook from the 2001 edition of NFPA 704.[3] For health, the criteria describe what the material can do to a person under emergency conditions. For flammability, they describe how easily the material ignites. For instability, they describe how readily it detonates or decomposes violently.

Degrees of hazard in the NFPA 704 marking system (2001 edition, as reproduced in the 2008 handbook)[3]
Number Health hazard Flammability hazard Instability hazard
4 Under emergency conditions, can be lethal Rapidly or completely vaporises at atmospheric pressure and normal ambient temperature, or is readily dispersed in air, and burns readily Readily capable of detonation, explosive decomposition or explosive reaction at normal temperatures and pressures, including materials sensitive to localised thermal or mechanical shock
3 Under emergency conditions, can cause serious or permanent injury Liquids and solids that can be ignited under almost all atmosphere and temperature conditions Capable of detonation, explosive decomposition or explosive reaction, but needs a strong initiating source or heating under confinement
2 Under emergency conditions, can cause temporary incapacitation or residual injury Must be moderately heated or exposed to relatively high ambient temperatures before ignition can occur Undergoes violent chemical change at elevated temperatures and pressures
1 Under emergency conditions, can cause severe irritation Must be preheated before ignition can occur Normally stable, but can become unstable at elevated temperatures and pressures
0 Under emergency conditions, no hazard beyond that of ordinary combustible materials Will not burn, including any material that does not burn in air when exposed to 816 °C (1500 °F) for 5 minutes Normally stable even under fire conditions

The flammability criteria follow the ease of forming an ignitable atmosphere. A degree 3 material produces hazardous atmospheres with air under almost all ambient temperatures, or is readily ignited under almost all conditions even if it is unaffected by temperature.[3] A degree 2 material would not form hazardous atmospheres under normal conditions, but might release enough vapour to do so at high ambient temperatures or under moderate heating.[3] A degree 1 material needs considerable preheating under all ambient conditions before it can ignite and burn.[3] The only numerical criterion in the table is the 816 °C, 5-minute exposure that separates degree 0 from the combustible materials.[3]

Ratings of common gases

The gases chapter of the 2008 handbook prints an NFPA 704 diamond next to each gas it describes, together with the four-digit UN identification number used in transport.[12] These diamonds show how the system separates different kinds of hazard. They also show that one substance can carry two markings when it is handled in two forms.

NFPA 704 ratings of selected gases as printed in Lemoff (2008)
Gas and form UN number Health Flammability Instability Special Page
Acetylene 1001 0 4 3 – 6-177
Anhydrous ammonia 1005 3 1 0 – 6-178
Chlorine 1017 4 0 0 OX 6-180
Ethylene, cryogenic liquid 1038 3 4 2 – 6-180
Ethylene, compressed gas 1962 1 4 2 – 6-180
Hydrogen, cryogenic liquid 1066 3 4 0 – 6-181
Hydrogen, compressed gas 1049 1 4 0 – 6-181
Liquefied petroleum gas 1075 0 4 0 – 6-183
Oxygen, cryogenic liquid 1073 3 0 0 OX 6-185
Oxygen, compressed gas 1072 1 0 0 OX 6-185

Acetylene stands out because of its instability rating of 3. Lemoff (2008) explains that acetylene in the liquid or solid state, or as a gas at moderate or high pressure, can decompose rapidly. Heat can start the decomposition, and in liquid or solid acetylene so can mechanical impact.[12] Chlorine is rated 0 for flammability yet carries the OX symbol, because it is a strong oxidiser that can react with many organic materials, in some cases explosively.[10] For ethylene, hydrogen and oxygen, the cryogenic liquid carries a health rating of 3 while the compressed gas carries 1, with the other quadrants unchanged.[10][13][14] The marking therefore belongs to a material in a stated form, not to the chemical name alone.

Use in codes and practice

For US facilities, the 2008 handbook recommends NFPA 704 markings in several occupancies and reports code requirements that refer to the ratings. For chemical storage, Davenport (2008) states that all storage areas should display signs identifying the materials stored and handled there, and that the NFPA 704 system should be used.[4] Where materials with different ratings are stored in the same area, the area should be marked with the most severe health, flammability and reactivity hazard present.[4] Ratings for many materials can be found in NFPA 49 and NFPA 325, which are collected in the NFPA Fire Protection Guide to Hazardous Materials.[4][2]

A worked example shows how this rule builds an area sign. Consider a gas store holding compressed hydrogen (1-4-0), compressed ethylene (1-4-2) and anhydrous ammonia (3-1-0), using the ratings printed by Lemoff (2008).[15][10][13] The highest health number is 3 from ammonia, the highest flammability number is 4 from hydrogen and ethylene, and the highest instability number is 2 from ethylene. The area sign therefore reads health 3, flammability 4 and instability 2, although no single gas in the room has that combination. The sign warns of the worst case in each category but no longer tells a responder which material causes which hazard.

For pesticide storage, Whitford (2008) recommends hazard warning signs using the NFPA 704 system on all structures and fixed tanks that house or store hazardous materials, coordinated with the fire jurisdiction that serves the site.[16] Operators may also post the W signal from NFPA 704 to warn responders not to use water, but only after consulting the local authorities and the insurers.[16] The same chapter advises that nonflammable materials with a health rating of 3 or 4 be isolated from other materials in storage.[17]

In laboratories, the 2008 handbook describes NFPA 45 as requiring a second means of access from the laboratory unit to a means of egress in six situations. Two of them concern a compressed gas cylinder larger than a lecture bottle, or a cryogenic container, holding a gas that is flammable or has a health rating of 3 or 4.[18] As described in the 2008 handbook, some lecture-bottle cylinders are required to be kept in special continuously mechanically ventilated enclosures. This applies to cylinders containing pyrophoric gases, gases with a health rating of 3 or 4, or gases rated 2 without physiological warning properties.[19] In health care, Allen (2008) reports that NFPA 99 requires the symbols in laboratories and calls it prudent to apply them also in general stores, pharmacies, operating rooms and gas and flammable liquid storage rooms.[5]

Other chapters use the markings for planning. In chemical plants, NFPA 704 symbols posted where chemicals are present give guidance on the inherent hazards and on planning fire-fighting operations.[20] Schwab (2008a) also names NFPA 704 as a reference on chemical stability and shock sensitivity.[21] For spray finishing, Scarbrough (2008b) advises that the hazards of materials be identified with the system as soon as they arrive in the facility, and that personnel be trained on them.[11]

Use in emergency response

In Hazardous materials response, recognising that hazardous materials are present is the first task of the size-up.[22] C. J. Wright (2008a) lists facility and transport markings among the clues responders look for, with NFPA 704 as the marking used within facilities.[1] The hazardous material data sheet that the chapter offers for recording information at an incident has fields for the NFPA 704 health, flammability and reactivity ratings and for other special hazards.[23]

Not every reference guide gives the rating. A cross-reference of common printed guides lists the NFPA 704 marking for three of them. These are the Emergency Action Guides of the Association of American Railroads, the NFPA guide and the US Coast Guard CHRIS manual series.[24] The same table does not mark it for the Emergency Response Guidebook, the NIOSH Pocket Guide to Chemical Hazards or material safety data sheets.[24]

Fire departments have also used the ratings to scale their response, as in a 1994 hazardous materials plan of the Fire Department of the City of New York (FDNY). The plan, dated 30 September 1994, is reproduced in the National Institute of Standards and Technology (NIST) report on the World Trade Center emergency response and has a row headed "NFPA #704".[25] In that row, ratings of 0 or 1 in all categories correspond to level one and a 2 in any category to level two. A 3 or 4 in any category, including special hazards, corresponds to level three.[25] Other rows of the same plan grade the product by its transport placard of the US Department of Transportation (DOT), the container size and integrity, the leak severity and the fire and explosion potential.[25] Under that row, all three gases of the worked example above would fall in level three, because each has at least one rating of 3 or 4.

Relation to other hazard systems

NFPA 704 is not a transport marking. In US transport, Hazardous materials placarding is required on some bulk packages, such as cargo tanks, portable tanks and tank cars, and placards measure 273 mm by 273 mm (10.8 in. by 10.8 in.).[6] Placards convey hazard class and division, colour, symbol and either the class wording or the four-digit identification number.[6] The 704 diamond, by contrast, gives graded numbers for three kinds of hazard but no class number or substance identification.[3]

Other numbering systems use similar digits with different meanings. For refrigerants, the ANSI/ASHRAE 34 classification method uses flammability ratings of 1, 2 and 3. A rating of 1 there means no fire hazard and 3 means highly flammable, with a separate letter for toxicity.[26] A refrigerant number must therefore not be read as an NFPA 704 number.

The ratings also feed into risk indexing. The Dow Fire and Explosion Index, described by Watts (2002), uses a material factor for each process unit. That factor is determined from the flammability and reactivity of the material as given in NFPA 704, NFPA 49 and NFPA 325.[8] The material factor ranges from 1 to 40 and is described as an arbitrary ordinal ranking. The Fire and Explosion Index is the product of the material factor and a process unit hazards factor that ranges from 1 to 8.[8]

Limits and common misconceptions

The marking shows hazard, not quantity. The criteria in the 2001 table describe the properties of a material and say nothing about the amount present.[3] Responders therefore need other information, such as planning documents and container sizes, to judge the size of an incident; the FDNY plan, for example, grades container size in a separate row.[1][25]

The health criteria describe the material itself under emergency conditions.[3] Davenport (2008) warns that products of combustion may present very different hazards, more or less severe than those of the uncombusted chemical.[4][27] The handbook does not link this warning to the NFPA 704 rating, but it means that the fire toxicity of the effluent cannot be read from the blue quadrant.

A composite area sign can hide detail. As the worked example shows, the "most severe" rule produces a combination that may belong to no single material in the room. The signs are also only as good as the information behind them. Whitford (2008) asks that their use be coordinated with the fire jurisdiction that serves the site, and Allen (2008) notes that the survey needed to post them can reveal hazardous materials no longer in use.[16][5]

Finally, the handbook presents NFPA 704 as US practice. The editions it reproduces are those of 2001 and 2007, and the requirements it reports from NFPA 45 and NFPA 99 are described as they stood around 2007–2008.[3][18][5] The handbook gives no criteria from later editions of the standard.

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 C. J. Wright (2008a), pp. 13-122–13-123.
  2. ↑ 2.0 2.1 Davenport (2008), p. 7-43.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 C. J. Wright (2008a), p. 13-123.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 Davenport (2008), p. 7-44.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Allen (2008), p. 6-194.
  6. ↑ 6.0 6.1 6.2 C. J. Wright (2008a), p. 13-124.
  7. ↑ Benedetti (2008), p. 6-6.
  8. ↑ 8.0 8.1 8.2 Watts (2002), p. 5-129.
  9. ↑ Watts (2002), p. 5-141.
  10. ↑ 10.0 10.1 10.2 10.3 Lemoff (2008), p. 6-180.
  11. ↑ 11.0 11.1 Scarbrough (2008b), p. 9-33.
  12. ↑ 12.0 12.1 Lemoff (2008), p. 6-177.
  13. ↑ 13.0 13.1 Lemoff (2008), p. 6-181.
  14. ↑ Lemoff (2008), p. 6-185.
  15. ↑ Lemoff (2008), p. 6-178.
  16. ↑ 16.0 16.1 16.2 Whitford (2008), p. 6-242.
  17. ↑ Whitford (2008), p. 6-239.
  18. ↑ 18.0 18.1 Anderson (2008a), p. 9-158.
  19. ↑ Anderson (2008a), p. 9-165.
  20. ↑ Schwab (2008a), p. 8-22.
  21. ↑ Schwab (2008a), p. 8-24.
  22. ↑ C. J. Wright (2008a), p. 13-121.
  23. ↑ C. J. Wright (2008a), p. 13-129.
  24. ↑ 24.0 24.1 C. J. Wright (2008a), pp. 13-130–13-131.
  25. ↑ 25.0 25.1 25.2 25.3 Lawson and Vettori (2005), Appendix A.
  26. ↑ Febo (2008), p. 8-121.
  27. ↑ Davenport (2008), p. 7-45.

References

  • Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
  • Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
  • Febo, H. L., Jr. (2008). Refrigeration systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-117–8-125). National Fire Protection Association.
  • Lawson, J. R., & Vettori, R. L. (2005). The emergency response operations (NIST NCSTAR 1-8). National Institute of Standards and Technology.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Schwab, R. F. (2008a). Chemical processing equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-17–8-29). National Fire Protection Association.
  • Watts, J. M., Jr. (2002). Fire risk indexing. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-125–5-142). National Fire Protection Association; Society of Fire Protection Engineers.
  • Whitford, F. (2008). Pesticides in the workplace. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-233–6-245). National Fire Protection Association.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.