Exposure time limits for inert gas agents, with the corresponding residual oxygen concentration | Exposure time limits for inert gas agents, with the corresponding residual oxygen concentration. | ||
Original vector illustration for [[Gaseous extinguishing system]], level 2 Intermediate. | Original vector illustration for [[Gaseous extinguishing system]], level 2 Intermediate. | ||
* Alt text: Step chart of allowed exposure time against inert gas concentration: 5 min up to 43 %, 3 min from 43 to 52 %, 30 s above 52 %. | * Alt text: Step chart of allowed exposure time against inert gas concentration: 5 min up to 43 %, 3 min from 43 to 52 %, 30 s above 52 %. | ||
== Licensing == | == Licensing == | ||
New drawing by Fire Safety Academy. © Fire Safety Academy. | New drawing by Fire Safety Academy. © Fire Safety Academy. | ||
Revision as of 09:07, 13 November 2026
Summary
Exposure time limits for inert gas agents, with the corresponding residual oxygen concentration.
Original vector illustration for Gaseous extinguishing system, level 2 Intermediate.
- Alt text: Step chart of allowed exposure time against inert gas concentration: 5 min up to 43 %, 3 min from 43 to 52 %, 30 s above 52 %.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 18:41, 23 November 2026 | 1,000 × 660 (5 KB) | Mark (talk | contribs) | Correct factcheck 23 Nov 2026, points 8: primary-source corrections, edition context and consistent figures | |