Skip to content
From Fire Safety Academy Wiki
Mark (talk | contribs)
m Remove source references from image captions
Peter (talk | contribs)
Wiki review: single-page locators "pp." -> "p." (8 footnotes) (Claude Opus 5.5)
 
Line 7: Line 7:


== Characteristics and practical interpretation ==
== Characteristics and practical interpretation ==
The protein hydrolysate supplies polymers that help give the bubble structure strength and water-retaining characteristics. The handbook describes stabilising salts as part of the formulation. The useful result is a foam with particular spreading and persistence characteristics, not simply a solution containing a natural ingredient. Concentrate formulation and generation equipment determine the product applied to the fire.<ref name="F-fcc18f638f">Cote et al. (2008), chapter 17.4, pp. 17-47.</ref>
The protein hydrolysate supplies polymers that help give the bubble structure strength and water-retaining characteristics. The handbook describes stabilising salts as part of the formulation. The useful result is a foam with particular spreading and persistence characteristics, not simply a solution containing a natural ingredient. Concentrate formulation and generation equipment determine the product applied to the fire.<ref name="F-fcc18f638f">Cote et al. (2008), chapter 17.4, p. 17-47.</ref>


Ordinary protein foam, fluoroprotein foam and film-forming fluoroprotein foam are different formulations. The SFPE chapter explains that added fluorinated surfactants can change fuel shedding and spreading, while film formation requires a suitable formulation. These names therefore cannot be used as synonyms. The selected product's evidence identifies which characteristics are actually supported.<ref name="P-e29e7624aa" />
Ordinary protein foam, fluoroprotein foam and film-forming fluoroprotein foam are different formulations. The SFPE chapter explains that added fluorinated surfactants can change fuel shedding and spreading, while film formation requires a suitable formulation. These names therefore cannot be used as synonyms. The selected product's evidence identifies which characteristics are actually supported.<ref name="P-e29e7624aa" />
Line 23: Line 23:
Heat, drainage and contact with fuel can reduce the useful foam layer. Mechanical disturbance, including an unsuitable water stream, can also disrupt coverage. The Fire Protection Handbook therefore connects successful application with both supply and losses. A large volume discharged nearby is not necessarily equivalent to a maintained blanket on the burning surface, especially where wind or fire-driven air movement diverts the agent.<ref name="F-a275fc79a7">Cote et al. (2008), chapter 17.4, pp. 17-46, 17-49.</ref>
Heat, drainage and contact with fuel can reduce the useful foam layer. Mechanical disturbance, including an unsuitable water stream, can also disrupt coverage. The Fire Protection Handbook therefore connects successful application with both supply and losses. A large volume discharged nearby is not necessarily equivalent to a maintained blanket on the burning surface, especially where wind or fire-driven air movement diverts the agent.<ref name="F-a275fc79a7">Cote et al. (2008), chapter 17.4, pp. 17-46, 17-49.</ref>


The fire geometry limits the mechanism. A stable blanket is particularly relevant to a pool with a reasonably defined surface. Falling or pressurised fuel can create a continuing three-dimensional flame that is not controlled by covering a horizontal surface alone. The SFPE chapter describes combined-agent arrangements for such hazards, while the handbook stresses the need to match application method and fuel conditions.<ref name="P-1eb9986b02">Scheffey (2002), pp. 4-88.</ref><ref name="F-41e79dad0b">Cote et al. (2008), chapter 17.4, pp. 17-46.</ref>
The fire geometry limits the mechanism. A stable blanket is particularly relevant to a pool with a reasonably defined surface. Falling or pressurised fuel can create a continuing three-dimensional flame that is not controlled by covering a horizontal surface alone. The SFPE chapter describes combined-agent arrangements for such hazards, while the handbook stresses the need to match application method and fuel conditions.<ref name="P-1eb9986b02">Scheffey (2002), p. 4-88.</ref><ref name="F-41e79dad0b">Cote et al. (2008), chapter 17.4, p. 17-46.</ref>


== Expansion, drainage and stability ==
== Expansion, drainage and stability ==
Expansion describes how much finished foam is produced from a given volume of solution. It is distinct from the proportion of concentrate in that solution. A solution can be correctly proportioned but poorly aerated, or well expanded while containing an unsuitable concentrate percentage. The handbook treats proportioning, foam generation and distribution as separate operations because each affects the final result.<ref name="F-04fed1f27d">Cote et al. (2008), chapter 17.4, pp. 17-49–17-50.</ref><ref name="P-cb791d46af" />
Expansion describes how much finished foam is produced from a given volume of solution. It is distinct from the proportion of concentrate in that solution. A solution can be correctly proportioned but poorly aerated, or well expanded while containing an unsuitable concentrate percentage. The handbook treats proportioning, foam generation and distribution as separate operations because each affects the final result.<ref name="F-04fed1f27d">Cote et al. (2008), chapter 17.4, pp. 17-49–17-50.</ref><ref name="P-cb791d46af" />


Drainage describes liquid leaving the bubble structure over time. As liquid drains, the properties of the remaining foam change, affecting spreading and persistence. The handbook identifies the time for a specified fraction to drain as one measure used in foam evaluation. That measurement concerns a physical characteristic under test conditions, rather than a direct universal measure of extinguishing ability.<ref name="F-2ef4d8b6a4">Cote et al. (2008), chapter 17.4, pp. 17-68.</ref>
Drainage describes liquid leaving the bubble structure over time. As liquid drains, the properties of the remaining foam change, affecting spreading and persistence. The handbook identifies the time for a specified fraction to drain as one measure used in foam evaluation. That measurement concerns a physical characteristic under test conditions, rather than a direct universal measure of extinguishing ability.<ref name="F-2ef4d8b6a4">Cote et al. (2008), chapter 17.4, p. 17-68.</ref>


More expansion is not automatically better. The SFPE discussion of early film-forming foam development describes a compromise between spreading, drainage and bubble stability. A stiff foam can resist flowing around obstructions, while a very wet foam can lose liquid rapidly. The appropriate characteristics depend on whether the task is surface coverage, retention, penetration into a solid fuel or filling a volume.<ref name="P-5377d100d3">Scheffey (2002), pp. 4-89–4-90.</ref><ref name="F-11110dd3cd">Cote et al. (2008), chapter 17.4, pp. 17-48.</ref>
More expansion is not automatically better. The SFPE discussion of early film-forming foam development describes a compromise between spreading, drainage and bubble stability. A stiff foam can resist flowing around obstructions, while a very wet foam can lose liquid rapidly. The appropriate characteristics depend on whether the task is surface coverage, retention, penetration into a solid fuel or filling a volume.<ref name="P-5377d100d3">Scheffey (2002), pp. 4-89–4-90.</ref><ref name="F-11110dd3cd">Cote et al. (2008), chapter 17.4, p. 17-48.</ref>


The generating conditions therefore belong with any reported foam property. Concentrate identity, water quality, pressure, discharge device and air source can all affect the produced foam. High-expansion systems are particularly sensitive to the conditions of the air used for generation. The handbook describes reduced production and stability where hot, contaminated fire gases enter the generator, illustrating why a nominal expansion value is not sufficient by itself.<ref name="F-2e24d1a4ce">Cote et al. (2008), chapter 17.4, pp. 17-48–17-50, 17-67.</ref>
The generating conditions therefore belong with any reported foam property. Concentrate identity, water quality, pressure, discharge device and air source can all affect the produced foam. High-expansion systems are particularly sensitive to the conditions of the air used for generation. The handbook describes reduced production and stability where hot, contaminated fire gases enter the generator, illustrating why a nominal expansion value is not sufficient by itself.<ref name="F-2e24d1a4ce">Cote et al. (2008), chapter 17.4, pp. 17-48–17-50, 17-67.</ref>
Line 48: Line 48:
For liquid surfaces, gentle application can reduce disruption and mixing of foam with fuel. Fixed tank outlets and discharge devices are designed around that requirement and the tank geometry. A monitor operating from outside the hazard must additionally overcome wind, fire updrafts and limitations in positioning. The amount leaving the device can consequently exceed the amount that reaches and remains on the intended surface.<ref name="F-f3c2d5f4e8">Cote et al. (2008), chapter 17.4, pp. 17-49, 17-60–17-61.</ref>
For liquid surfaces, gentle application can reduce disruption and mixing of foam with fuel. Fixed tank outlets and discharge devices are designed around that requirement and the tank geometry. A monitor operating from outside the hazard must additionally overcome wind, fire updrafts and limitations in positioning. The amount leaving the device can consequently exceed the amount that reaches and remains on the intended surface.<ref name="F-f3c2d5f4e8">Cote et al. (2008), chapter 17.4, pp. 17-49, 17-60–17-61.</ref>


Application rate describes solution delivered per unit area per unit time. It is not the same as the volume of expanded foam occupying that area. A successful application has to overcome foam destruction and leave a protective layer. The handbook relates the required rate to fuel, foam and application method, and presents test-based guidance rather than a single rate applicable to every liquid fire.<ref name="F-c9a598a0c9">Cote et al. (2008), chapter 17.4, pp. 17-49.</ref>
Application rate describes solution delivered per unit area per unit time. It is not the same as the volume of expanded foam occupying that area. A successful application has to overcome foam destruction and leave a protective layer. The handbook relates the required rate to fuel, foam and application method, and presents test-based guidance rather than a single rate applicable to every liquid fire.<ref name="F-c9a598a0c9">Cote et al. (2008), chapter 17.4, p. 17-49.</ref>


High-expansion filling introduces a different delivery problem. The system has to build and retain sufficient foam volume while allowing displaced air to leave. Openings, foam collapse, obstruction and the effects of other water discharges can influence the rate of accumulation. The handbook consequently connects generation capacity with enclosure geometry and the time available to cover the hazard, instead of using expansion ratio alone as the design criterion.<ref name="F-aae3546b7e">Cote et al. (2008), chapter 17.4, pp. 17-67.</ref>
High-expansion filling introduces a different delivery problem. The system has to build and retain sufficient foam volume while allowing displaced air to leave. Openings, foam collapse, obstruction and the effects of other water discharges can influence the rate of accumulation. The handbook consequently connects generation capacity with enclosure geometry and the time available to cover the hazard, instead of using expansion ratio alone as the design criterion.<ref name="F-aae3546b7e">Cote et al. (2008), chapter 17.4, p. 17-67.</ref>


== Fuel compatibility and environmental conditions ==
== Fuel compatibility and environmental conditions ==
The fuel's interaction with the aqueous phase is a principal selection issue. Ordinary foam can break down rapidly on water-miscible polar solvents. Alcohol-resistant formulations provide protection appropriate to specified fuels, with some formulations forming a polymeric layer between fuel and foam. The SFPE and NFPA handbooks both distinguish this function from ordinary film formation on a hydrocarbon surface.<ref name="P-795ef6a1bf">Scheffey (2002), pp. 4-89.</ref><ref name="F-b8bcea31cb">Cote et al. (2008), chapter 17.4, pp. 17-47–17-49.</ref>
The fuel's interaction with the aqueous phase is a principal selection issue. Ordinary foam can break down rapidly on water-miscible polar solvents. Alcohol-resistant formulations provide protection appropriate to specified fuels, with some formulations forming a polymeric layer between fuel and foam. The SFPE and NFPA handbooks both distinguish this function from ordinary film formation on a hydrocarbon surface.<ref name="P-795ef6a1bf">Scheffey (2002), p. 4-89.</ref><ref name="F-b8bcea31cb">Cote et al. (2008), chapter 17.4, pp. 17-47–17-49.</ref>


Fuel temperature and geometry also influence performance. Hot liquid can destroy foam or cause disruptive boiling of its water content, while a continuing fuel release can prevent a stable blanket from developing. Compatibility therefore means more than assigning a general liquid-fire label. The agent, fuel, temperature, application method and tested protection arrangement define the conditions supporting an extinguishing claim.<ref name="F-62ad716b6d">Cote et al. (2008), chapter 17.4, pp. 17-46–17-49.</ref>
Fuel temperature and geometry also influence performance. Hot liquid can destroy foam or cause disruptive boiling of its water content, while a continuing fuel release can prevent a stable blanket from developing. Compatibility therefore means more than assigning a general liquid-fire label. The agent, fuel, temperature, application method and tested protection arrangement define the conditions supporting an extinguishing claim.<ref name="F-62ad716b6d">Cote et al. (2008), chapter 17.4, pp. 17-46–17-49.</ref>

Latest revision as of 01:35, 16 November 2026

Protein foam is a firefighting foam produced from an aqueous concentrate containing hydrolysed protein material and associated stabilising ingredients. The SFPE Handbook describes the concentrate being proportioned with water and aerated to create a bubble blanket. Ordinary protein foam does not form the separate aqueous film associated with film-forming agents.[1]

Distinguish ordinary protein and modified foam families.
Distinguish ordinary protein and modified foam families.

The Fire Protection Handbook relates the protein-based structure to foam stability, heat resistance and resistance to renewed burning. These characteristics differ from the spreading behaviour of aqueous film-forming foam. Foam expansion ratio alone cannot describe the distinction because the chemistry and drainage behaviour also matter.[2][3]

A foam proportioner and suitable discharge device must match the formulation. Alcohol-resistant foam is selected for additional fuel-compatibility demands, while a floating-roof tank presents its own application geometry. Neither property follows automatically from the generic description protein foam.[4]

Characteristics and practical interpretation

The protein hydrolysate supplies polymers that help give the bubble structure strength and water-retaining characteristics. The handbook describes stabilising salts as part of the formulation. The useful result is a foam with particular spreading and persistence characteristics, not simply a solution containing a natural ingredient. Concentrate formulation and generation equipment determine the product applied to the fire.[5]

Ordinary protein foam, fluoroprotein foam and film-forming fluoroprotein foam are different formulations. The SFPE chapter explains that added fluorinated surfactants can change fuel shedding and spreading, while film formation requires a suitable formulation. These names therefore cannot be used as synonyms. The selected product's evidence identifies which characteristics are actually supported.[1]

Fuel contamination and application method remain relevant. The handbook contrasts the resistance to fuel pickup of ordinary protein foam with other formulations. A system that plunges foam into fuel creates different demands from gentle surface application. The appropriate comparison consequently includes the discharge route and fuel, rather than relying only on a general description of heat resistance.[6]

Storage and proportioning also affect continuing performance. Concentrate can deteriorate or become contaminated, and the delivered percentage needs to match the intended system. The handbook treats concentrate surveillance separately from equipment testing. A stored product name therefore does not establish that a functioning system will still produce the originally assessed foam characteristics.[7]

Foam formation and extinguishing action

The SFPE Handbook describes firefighting foam as air-filled bubbles formed from an aqueous solution. Concentrate is first mixed with water in the specified proportion. Air is then incorporated to create the bubble structure. Concentrate, solution and finished foam consequently refer to different stages, with different volumes. Keeping those stages separate is necessary when interpreting equipment capacities or an application-rate calculation.[1]

Explain the mechanism supporting protein foam.
Explain the mechanism supporting protein foam.

A foam blanket can suppress the release of combustible vapour from a liquid surface while its water content contributes cooling. The blanket must reach and cover the relevant surface, and sufficient foam must remain despite losses. Film-forming agents add a further mechanism through solution spreading across suitable hydrocarbon fuels. The SFPE discussion distinguishes that film from the bubble blanket and from the behaviour of ordinary protein foam.[1]

Heat, drainage and contact with fuel can reduce the useful foam layer. Mechanical disturbance, including an unsuitable water stream, can also disrupt coverage. The Fire Protection Handbook therefore connects successful application with both supply and losses. A large volume discharged nearby is not necessarily equivalent to a maintained blanket on the burning surface, especially where wind or fire-driven air movement diverts the agent.[8]

The fire geometry limits the mechanism. A stable blanket is particularly relevant to a pool with a reasonably defined surface. Falling or pressurised fuel can create a continuing three-dimensional flame that is not controlled by covering a horizontal surface alone. The SFPE chapter describes combined-agent arrangements for such hazards, while the handbook stresses the need to match application method and fuel conditions.[9][10]

Expansion, drainage and stability

Expansion describes how much finished foam is produced from a given volume of solution. It is distinct from the proportion of concentrate in that solution. A solution can be correctly proportioned but poorly aerated, or well expanded while containing an unsuitable concentrate percentage. The handbook treats proportioning, foam generation and distribution as separate operations because each affects the final result.[11][3]

Drainage describes liquid leaving the bubble structure over time. As liquid drains, the properties of the remaining foam change, affecting spreading and persistence. The handbook identifies the time for a specified fraction to drain as one measure used in foam evaluation. That measurement concerns a physical characteristic under test conditions, rather than a direct universal measure of extinguishing ability.[12]

More expansion is not automatically better. The SFPE discussion of early film-forming foam development describes a compromise between spreading, drainage and bubble stability. A stiff foam can resist flowing around obstructions, while a very wet foam can lose liquid rapidly. The appropriate characteristics depend on whether the task is surface coverage, retention, penetration into a solid fuel or filling a volume.[13][14]

The generating conditions therefore belong with any reported foam property. Concentrate identity, water quality, pressure, discharge device and air source can all affect the produced foam. High-expansion systems are particularly sensitive to the conditions of the air used for generation. The handbook describes reduced production and stability where hot, contaminated fire gases enter the generator, illustrating why a nominal expansion value is not sufficient by itself.[15]

Proportioning and operating range

Proportioning establishes the concentrate fraction in the water-based solution. The handbook distinguishes systems that draw concentrate using a low-pressure region from systems that inject it using a pump or pressure head. Both must deliver the intended ratio under the relevant operating conditions. The proportioner is consequently matched to the concentrate, water supply and downstream discharge equipment.[16]

A venturi eductor uses the flowing water's pressure energy to create a region into which concentrate is drawn. Its performance depends on inlet conditions and the resistance downstream. Hose length, elevation and the discharge device can therefore affect the resulting mixture. The handbook's discussion of in-line eductors makes this dependence explicit, rather than treating the metering setting alone as evidence of correct proportioning.[17]

Balanced-pressure and bladder arrangements establish the concentrate supply differently. Their useful operating range still has limits, particularly at low water flows. The handbook identifies the possibility of under-proportioning before a bladder arrangement reaches its approved flow range. Higher concentrate viscosity can increase losses in the concentrate piping and affect that limit. These issues are especially relevant when only a small number of closed sprinklers initially operate.[18]

The mixture also affects available operating time. Too little concentrate can produce unsuitable foam, while excessive concentrate consumes the stored supply more rapidly. Verification therefore measures the delivered concentration under representative conditions, rather than relying only on the quantity originally placed in the tank. The handbook treats concentration testing as evidence about the proportioning system and distinguishes it from expansion and drainage measurements.[19]

Application method and useful delivery

Foam can be delivered through hand-held devices, monitors, fixed outlets and sprinkler arrangements. These methods differ in reach, aeration, distribution and dependence on operator positioning. The handbook therefore treats the discharge equipment as part of the tested system. Substituting a different nozzle can change foam quality and coverage even when the solution concentration remains the same.[20]

For liquid surfaces, gentle application can reduce disruption and mixing of foam with fuel. Fixed tank outlets and discharge devices are designed around that requirement and the tank geometry. A monitor operating from outside the hazard must additionally overcome wind, fire updrafts and limitations in positioning. The amount leaving the device can consequently exceed the amount that reaches and remains on the intended surface.[21]

Application rate describes solution delivered per unit area per unit time. It is not the same as the volume of expanded foam occupying that area. A successful application has to overcome foam destruction and leave a protective layer. The handbook relates the required rate to fuel, foam and application method, and presents test-based guidance rather than a single rate applicable to every liquid fire.[22]

High-expansion filling introduces a different delivery problem. The system has to build and retain sufficient foam volume while allowing displaced air to leave. Openings, foam collapse, obstruction and the effects of other water discharges can influence the rate of accumulation. The handbook consequently connects generation capacity with enclosure geometry and the time available to cover the hazard, instead of using expansion ratio alone as the design criterion.[23]

Fuel compatibility and environmental conditions

The fuel's interaction with the aqueous phase is a principal selection issue. Ordinary foam can break down rapidly on water-miscible polar solvents. Alcohol-resistant formulations provide protection appropriate to specified fuels, with some formulations forming a polymeric layer between fuel and foam. The SFPE and NFPA handbooks both distinguish this function from ordinary film formation on a hydrocarbon surface.[24][25]

Fuel temperature and geometry also influence performance. Hot liquid can destroy foam or cause disruptive boiling of its water content, while a continuing fuel release can prevent a stable blanket from developing. Compatibility therefore means more than assigning a general liquid-fire label. The agent, fuel, temperature, application method and tested protection arrangement define the conditions supporting an extinguishing claim.[26]

Water and air quality affect the generated product. Contaminated water can change foam properties, and smoke-laden or hot air can reduce high-expansion foam production. Equipment location must consequently be considered relative to the fire environment. The handbook identifies these effects as practical limitations on foam generation and distribution, alongside the influence of weather where foam is used outdoors.[27]

Discharged solution can also carry fuel and other contaminants beyond the protected area. Environmental assessment therefore includes containment, drainage and the characteristics of the particular formulation. The handbook discusses toxicity, persistence, treatment and oxygen demand as different concerns. Its historical statements about named products or regulatory status do not establish the current acceptability of a formulation or an uncontrolled release.[28]

Performance evidence and continuing condition

Foam performance has a strong experimental basis. The SFPE chapter explains that physical properties and small-scale measurements do not always correlate directly with extinguishment in a particular fire test. A test result therefore needs its fuel, scale, equipment and application conditions. A generic claim of good expansion or rapid spreading cannot replace evidence for the intended protection arrangement.[3]

Distinguish complementary evidence needed to assess protein foam.
Distinguish complementary evidence needed to assess protein foam.

The handbook distinguishes measurements of concentration, expansion, drainage and discharge pattern. These observations address different parts of foam production and application. Concentration examines proportioning; expansion examines incorporation of air; drainage examines changes in the bubble structure. The complete assessment relates these properties to the tested agent and equipment combination rather than selecting one favourable measurement as proof of all-round performance.[12]

Stored concentrate can change through contamination, extreme temperatures or separation. Pumps, valves and small openings can also deteriorate or become obstructed. The handbook consequently treats concentrate surveillance and equipment inspection as separate continuing tasks. Testing arrangements can sometimes assess components without distributing foam over the hazard, but the recorded scope needs to identify which functions were actually demonstrated.[12]

Changes to the protected use can invalidate a previously suitable system. A different fuel, altered storage height or revised discharge route can change the conditions supporting the original test evidence. The IFEG lifecycle framework connects alterations with review of the fire engineering assessment. This makes maintaining the design basis part of continuing protection, alongside maintaining the physical condition of tanks, proportioners and outlets.[29][30]

Protection objectives and limits of performance

Suppression describes an intended change in a fire, but the required outcome needs further definition. Control can limit growth or reduce the rate of heat release without extinguishing every burning item. Extinguishment removes the continuing combustion under the conditions considered. Prevention of renewed burning may require cooling, continued agent retention or removal of an ignition source. These outcomes impose different demands on the protection arrangement.[31][32]

Agent selection follows the fuel and the objective. Water can cool a solid surface, foam can maintain a barrier over a liquid, and a gaseous agent can change the atmosphere surrounding a fire. None of these descriptions establishes universal effectiveness. The protected material, fire geometry, ventilation and available delivery arrangement determine whether the relevant mechanism can operate where it is needed.[33][34]

The assessment also distinguishes successful operation from unsuccessful or delayed operation. An explicit example appears in Australia's Fire Safety Verification Method Standard, 2022 edition. Its structural-stability scenario considers failures of suppression, delayed fire brigade intervention and combinations of failures. That requirement belongs to the Australian method and its stated scenario. It illustrates why the mere presence of equipment is insufficient evidence of the building's performance.[35]

The protection claim consequently includes its conditions of use. These include the hazard, the quantity and distribution of agent, the expected activation sequence and the time for which protection is maintained. Changes to storage, ventilation or operating procedures can alter those conditions. The International Fire Engineering Guidelines connect continued building use and alterations with review of the original engineering assumptions.[29]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Scheffey (2002), pp. 4-88–4-89.
  2. ↑ Cote et al. (2008), chapter 17.4, pp. 17-47–17-48.
  3. ↑ 3.0 3.1 3.2 Scheffey (2002), pp. 4-88–4-90.
  4. ↑ Cote et al. (2008), chapter 17.4, pp. 17-47, 17-50–17-52, 17-61.
  5. ↑ Cote et al. (2008), chapter 17.4, p. 17-47.
  6. ↑ Cote et al. (2008), chapter 17.4, pp. 17-47, 17-49–17-51.
  7. ↑ Cote et al. (2008), chapter 17.4, pp. 17-50–17-52, 17-68.
  8. ↑ Cote et al. (2008), chapter 17.4, pp. 17-46, 17-49.
  9. ↑ Scheffey (2002), p. 4-88.
  10. ↑ Cote et al. (2008), chapter 17.4, p. 17-46.
  11. ↑ Cote et al. (2008), chapter 17.4, pp. 17-49–17-50.
  12. ↑ 12.0 12.1 12.2 Cote et al. (2008), chapter 17.4, p. 17-68.
  13. ↑ Scheffey (2002), pp. 4-89–4-90.
  14. ↑ Cote et al. (2008), chapter 17.4, p. 17-48.
  15. ↑ Cote et al. (2008), chapter 17.4, pp. 17-48–17-50, 17-67.
  16. ↑ Cote et al. (2008), chapter 17.4, pp. 17-50–17-52.
  17. ↑ Cote et al. (2008), chapter 17.4, pp. 17-50–17-51.
  18. ↑ Cote et al. (2008), chapter 17.4, pp. 17-51–17-52.
  19. ↑ Cote et al. (2008), chapter 17.4, pp. 17-50, 17-68.
  20. ↑ Cote et al. (2008), chapter 17.4, pp. 17-59–17-61, 17-64.
  21. ↑ Cote et al. (2008), chapter 17.4, pp. 17-49, 17-60–17-61.
  22. ↑ Cote et al. (2008), chapter 17.4, p. 17-49.
  23. ↑ Cote et al. (2008), chapter 17.4, p. 17-67.
  24. ↑ Scheffey (2002), p. 4-89.
  25. ↑ Cote et al. (2008), chapter 17.4, pp. 17-47–17-49.
  26. ↑ Cote et al. (2008), chapter 17.4, pp. 17-46–17-49.
  27. ↑ Cote et al. (2008), chapter 17.4, pp. 17-48–17-49, 17-67.
  28. ↑ Cote et al. (2008), chapter 17.4, pp. 17-68–17-69.
  29. ↑ 29.0 29.1 National Research Council of Canada et al. (2005), §0.3.2.6–0.3.2.8; pp. 0.3-6–0.3-7.
  30. ↑ Cote et al. (2008), chapter 17.4, pp. 17-64, 17-68.
  31. ↑ Cote et al. (2008), chapter 17.3, pp. 17-32–17-33.
  32. ↑ Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.
  33. ↑ Cote et al. (2008), chapter 17.3, pp. 17-32–17-33, 17-36–17-38.
  34. ↑ Cote et al. (2008), chapter 17.4, pp. 17-45–17-49.
  35. ↑ Australian Building Codes Board (2022), §2.12.2; p. 19.

References

  • Australian Building Codes Board. (2022). Fire Safety Verification Method Standard 2022.
  • Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire Protection Handbook (20th ed.). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International Fire Engineering Guidelines (2005 ed.). Australian Building Codes Board.
  • Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr., & J. M. Watts, Jr. (Eds.), SFPE Handbook of Fire Protection Engineering (3rd ed., chapter 4-4, pp. 4-88–4-122). National Fire Protection Association.