Van Rossum gives object-based examples including 1,884 MJ for a three-seat sofa and 6,000 to 12,000 MJ for a car. He also lists beech wood at 18 MJ/kg and diesel oil at 42 MJ/kg. These examples are source values for inventory, not measurements of heat release rate or fire severity in a particular room.<ref name="VR-4.4" /> | Van Rossum gives object-based examples including 1,884 MJ for a three-seat sofa and 6,000 to 12,000 MJ for a car. He also lists beech wood at 18 MJ/kg and diesel oil at 42 MJ/kg. These examples are source values for inventory, not measurements of heat release rate or fire severity in a particular room.<ref name="VR-4.4" /> | ||
[[File:fse-fire-load-v3.svg|thumb|upright=1.5|alt=Sofa 1,884 MJ and car energy range 6,000 to 12,000 MJ.|Example chemical energy contents of a sofa and a car. Based on Van Rossum (2027), §4.4.]] | |||
== Variable and permanent fire load == | == Variable and permanent fire load == | ||
| Line 22: | Line 23: | ||
The distinction improves traceability but does not imply different combustion chemistry. Both groups contribute potential energy, and both need material-specific calorific values. Their treatment in a design fire can differ because contents and construction ignite and burn in different arrangements.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | The distinction improves traceability but does not imply different combustion chemistry. Both groups contribute potential energy, and both need material-specific calorific values. Their treatment in a design fire can differ because contents and construction ignite and burn in different arrangements.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | ||
[[File:fse-fire-load-v1.svg|thumb|upright=1.5|alt=Room contents and construction separated into variable and permanent fire-load groups.|Variable and permanent contributions to fire load. Based on Van Rossum (2027), §4.4.]] | |||
A complete inventory identifies what is included and excluded. Omitting concealed materials, linings or protected contents can change the estimate, while counting the same object as both contents and construction double-counts it. The system boundary should match the fire scenario.<ref name="IFEG-2.4-2" /> | A complete inventory identifies what is included and excluded. Omitting concealed materials, linings or protected contents can change the estimate, while counting the same object as both contents and construction double-counts it. The system boundary should match the fire scenario.<ref name="IFEG-2.4-2" /> | ||
| Line 30: | Line 32: | ||
Density is not a substitute for total energy. A small compartment with high density can contain less total energy than a large compartment with lower density. The required output determines whether total fire load, density or both should be reported.<ref name="IFEG-2.4-2" /> | Density is not a substitute for total energy. A small compartment with high density can contain less total energy than a large compartment with lower density. The required output determines whether total fire load, density or both should be reported.<ref name="IFEG-2.4-2" /> | ||
[[File:fse-fire-load-v2.svg|thumb|upright=1.5|alt=Two rooms with different areas illustrating total energy and energy per square metre.|Total fire load and fire-load density answer different questions. Based on Australian Building Codes Board et al. (2005), pp. 2.4-2–2.4-3.]] | |||
The reference area must be consistent. Floor area, internal surface area and burning area answer different questions. Fire-load density per floor area should not be combined with heat release rate per unit burning area as though they were the same quantity.<ref name="VR-4.6">Van Rossum (2027), §4.6.</ref><ref name="IFEG-2.4-2" /> | The reference area must be consistent. Floor area, internal surface area and burning area answer different questions. Fire-load density per floor area should not be combined with heat release rate per unit burning area as though they were the same quantity.<ref name="VR-4.6">Van Rossum (2027), §4.6.</ref><ref name="IFEG-2.4-2" /> | ||
| Line 71: | Line 74: | ||
The inventory can also change during a project or building lifecycle. Transient storage, new furnishings and alterations to combustible construction can invalidate an earlier total. A fire-load assessment should therefore identify its date and intended operating condition rather than being treated as a permanent property of the room.<ref name="IFEG-2.4-3" /><ref name="VR-4.4" /> | The inventory can also change during a project or building lifecycle. Transient storage, new furnishings and alterations to combustible construction can invalidate an earlier total. A fire-load assessment should therefore identify its date and intended operating condition rather than being treated as a permanent property of the room.<ref name="IFEG-2.4-3" /><ref name="VR-4.4" /> | ||
Review by another analyst is easier when each conversion and assumption remains visible. The source of every calorific value, the treatment of moisture, the protected-fuel allowance and the reference area should be reproducible. This allows uncertainty in the inventory to be carried into later fire-duration and structural calculations.<ref name="IFEG-2.4-2" /><ref name="VR-1.7" /> | Review by another analyst is easier when each conversion and assumption remains visible. The source of every calorific value, the treatment of moisture, the protected-fuel allowance and the reference area should be reproducible. This allows uncertainty in the inventory to be carried into later fire-duration and structural calculations.<ref name="IFEG-2.4-2" /><ref name="VR-1.7">Van Rossum (2027), §1.7.</ref> | ||
[[Time equivalence]] relates the thermal effect of a real or parametric fire to an equivalent exposure under a standard fire curve. Fire load helps determine the energy available for that comparison, but it does not define the equivalence alone. Ventilation, boundaries and heat-release history also shape thermal severity.<ref name="Cadorin-Franssen-396" /><ref name="VR-4.4" /> | [[Time equivalence]] relates the thermal effect of a real or parametric fire to an equivalent exposure under a standard fire curve. Fire load helps determine the energy available for that comparison, but it does not define the equivalence alone. Ventilation, boundaries and heat-release history also shape thermal severity.<ref name="Cadorin-Franssen-396" /><ref name="VR-4.4" /> | ||
| Line 85: | Line 88: | ||
A transparent inventory uses a table of material, quantity, calorific value and resulting energy. Values with different units are converted before being summed, and permanent and variable contributions are identified. The final total is then related to a clearly stated reference area if density is needed.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | A transparent inventory uses a table of material, quantity, calorific value and resulting energy. Values with different units are converted before being summed, and permanent and variable contributions are identified. The final total is then related to a clearly stated reference area if density is needed.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | ||
Van Rossum's warehouse example | Van Rossum's warehouse example uses a storage volume of 3,500 m³, an effective storage density of 135 kg/m³ and a calorific value of 23 MJ/kg. These inputs describe the stored inventory. The calculation below follows their conversion into energy and wood-equivalent mass.<ref name="VR-4.4" /> | ||
Wood-equivalent units provide another way to express energy, but they do not mean that the actual inventory is wood. The conversion basis must be stated, and normal SI energy units remain clearer for subsequent heat-release and duration calculations.<ref name="VR-4.4" /> | Wood-equivalent units provide another way to express energy, but they do not mean that the actual inventory is wood. The conversion basis must be stated, and normal SI energy units remain clearer for subsequent heat-release and duration calculations.<ref name="VR-4.4" /> | ||
=== Calculating the inventory === | |||
For several materials, each mass is multiplied by its net heat of combustion and the resulting energies are added. A volume-based inventory first converts stored volume to mass using the appropriate bulk density. Fire-load density then divides the total energy by the selected floor area.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | |||
<math display="block">E=\sum_i m_i H_i,\qquad m=\rho_b V,\qquad q_f=\frac{E}{A_f}</math> | |||
{| class="wikitable" | |||
! Symbol !! Description !! Unit | |||
|- | |||
| <math>E</math> || Total potential chemical energy || MJ | |||
|- | |||
| <math>m_i</math> || Mass of material i || kg | |||
|- | |||
| <math>H_i</math> || Net heat of combustion of material i || MJ/kg | |||
|- | |||
| <math>\rho_b</math> || Bulk density of the stored inventory || kg/m³ | |||
|- | |||
| <math>V</math> || Occupied storage volume || m³ | |||
|- | |||
| <math>A_f</math> || Reference floor area || m² | |||
|- | |||
| <math>q_f</math> || Fire-load density || MJ/m² | |||
|} | |||
Using the warehouse quantities above, the fuel mass is 3,500 × 135 = 472,500 kg. Multiplication by 23 MJ/kg gives 10,867,500 MJ, or approximately 1.09 × 10<sup>7</sup> MJ. Dividing by the reference wood value of 19 MJ/kg gives about 5.72 × 10<sup>5</sup> kg of wood equivalent.<ref name="VR-4.4" /> | |||
Bulk density includes the way the inventory occupies its storage volume. Substituting a solid material density for the stated storage density would describe a different inventory. Equally, the storage volume is not a floor area: a fire-load density cannot be obtained from this example without a separate area input.<ref name="VR-4.4" /><ref name="IFEG-2.4-2" /> | |||
This arithmetic represents complete combustion of the included fuel. It does not decide whether protected material becomes involved or whether all chemical energy is released inside the compartment. Those changes belong to the fire scenario and combustion model, rather than to an unexplained alteration of the calorific value.<ref name="Drysdale-1-95" /><ref name="IFEG-2.4-2" /> | |||
== Limits and common misunderstandings == | == Limits and common misunderstandings == | ||
| Line 99: | Line 129: | ||
Total theoretical energy is not a prediction of energy actually released. Moisture, incomplete combustion, container protection and suppression can reduce it, and external burning can change where it is released. The scenario boundary must be stated.<ref name="Drysdale-1-95" /><ref name="IFEG-2.4-2" /> | Total theoretical energy is not a prediction of energy actually released. Moisture, incomplete combustion, container protection and suppression can reduce it, and external burning can change where it is released. The scenario boundary must be stated.<ref name="Drysdale-1-95" /><ref name="IFEG-2.4-2" /> | ||
a larger fire load does not guarantee a higher peak temperature or faster evacuation risk. Ignition, heat release rate, spread, ventilation and occupant response determine those outcomes. Fire load is one part of the wider fire-dynamics description.<ref name="VR-4.5" /><ref name="IFEG-1.6-3">Australian Building Codes Board et al. (2005), p. 1.6-3.</ref> | |||
Where the total drives a safety decision, alternative inventories can show its influence. Variable contents, moisture and protected fractions can be varied within defensible ranges rather than assigned false certainty. The resulting change in duration or exposure reveals whether a more detailed survey is needed.<ref name="IFEG-2.4-3" /><ref name="VR-1.7" /> | Where the total drives a safety decision, alternative inventories can show its influence. Variable contents, moisture and protected fractions can be varied within defensible ranges rather than assigned false certainty. The resulting change in duration or exposure reveals whether a more detailed survey is needed.<ref name="IFEG-2.4-3" /><ref name="VR-1.7" /> | ||
| Line 107: | Line 135: | ||
== See also == | == See also == | ||
* [[Fire dynamics]] | |||
* [[Combustibility]] | * [[Combustibility]] | ||
* | * Mass timber | ||
* [[Sprinkler hazard classification]] | * [[Sprinkler hazard classification]] | ||
Latest revision as of 22:32, 2 November 2026
Fire load is the total chemical energy that would be released if all combustible material in a defined place burned completely. It is commonly expressed in megajoules and can also be related to floor area as fire-load density. The quantity describes potential energy, not the heat release rate at a particular moment.[1][2]
Fire load includes the energy content of the fuel inventory rather than only its mass or volume. Materials with different heats of combustion can therefore produce very different fire loads from the same mass. The physical arrangement and combustion conditions later determine how much of that potential energy is actually released and at what rate.[3][4]
This makes fire load useful for estimating possible fire duration, total thermal exposure and design-fire context. It does not by itself predict ignition, flame spread, peak power or the temperature history of a compartment.[2][5]
Energy content and inventory
A fire-load assessment begins by identifying combustible materials and their quantities. Mass, volume or item count can be converted into energy using an appropriate calorific value. Every material needs its own basis, because a table can express energy per kilogram, per item or per square metre.[1]
Heat of combustion is the heat released by complete oxidation of a unit quantity of fuel to stable end products. Net heat of combustion treats product water as vapour and is identified by Drysdale as the value to use in fire calculations. Its measurement basis and initial conditions must accompany the data.[6]
Values illustrate the range between materials. Drysdale's table lists propane at 46.45 kJ/g, cellulose at 16.09 kJ/g and polyethylene at 43.28 kJ/g. Equal masses therefore do not represent equal chemical energy, and actual fires can release less than these complete-oxidation values.[6][7]
Van Rossum gives object-based examples including 1,884 MJ for a three-seat sofa and 6,000 to 12,000 MJ for a car. He also lists beech wood at 18 MJ/kg and diesel oil at 42 MJ/kg. These examples are source values for inventory, not measurements of heat release rate or fire severity in a particular room.[1]
Variable and permanent fire load
Variable fire load consists of combustible contents and furnishings that can change with building use. Furniture, stored goods and other inventory fall into this group. Their quantity and arrangement can vary over the life of a compartment.[1]
Permanent fire load consists of combustible construction components. It is associated with the building itself rather than its changing contents. Timber elements and combustible finishes can therefore require a separate inventory from furniture and stored products.[1]
The distinction improves traceability but does not imply different combustion chemistry. Both groups contribute potential energy, and both need material-specific calorific values. Their treatment in a design fire can differ because contents and construction ignite and burn in different arrangements.[1][2]
A complete inventory identifies what is included and excluded. Omitting concealed materials, linings or protected contents can change the estimate, while counting the same object as both contents and construction double-counts it. The system boundary should match the fire scenario.[2]
Fire-load density
Fire load density relates energy to a reference area, commonly the internal floor area of a compartment. It is often expressed in megajoules per square metre. This normalisation supports comparison between compartments and provides an input to some structural and parametric fire methods.[2][5]
Density is not a substitute for total energy. A small compartment with high density can contain less total energy than a large compartment with lower density. The required output determines whether total fire load, density or both should be reported.[2]
The reference area must be consistent. Floor area, internal surface area and burning area answer different questions. Fire-load density per floor area should not be combined with heat release rate per unit burning area as though they were the same quantity.[8][2]
Van Rossum gives example densities of 750 to 1,000 MJ/m² for an assembly occupancy, 1,800 MJ/m² for a library and 950 MJ/m² for a residential occupancy in his source table. These values belong to the cited method and occupancy descriptions and should not replace a project-specific inventory where one is required.[1]
Moisture, protection and incomplete combustion
Moisture changes effective energy content because heat is required to evaporate water. Van Rossum notes that some values already relate to equilibrium moisture or are tabulated as net values with this correction included. Applying another correction without checking the basis can subtract the energy twice.[1][2]
Protected contents may not burn completely. Combustible material inside a steel cabinet or other fire-resistant container can have a lower effective fire load than the same material in the open. The reduction depends on fire temperature and duration, container integrity and the nature of the contents.[2]
The 2005 guidelines caution that these effects are difficult to quantify unless the container has been tested for fire resistance. Assuming full protection or zero contribution without such evidence would be unsupported. The protected and unprotected inventories should be distinguished in the assessment.[2]
Incomplete combustion also means that total theoretical energy is rarely all released in a real fire. Partially oxidised products and unburnt material retain chemical energy. Combustion efficiency changes with material and conditions, so actual energy release must be evaluated separately from the inventory.[7][9]
Fire load and heat release rate
Heat release rate is the power produced by combustion at a particular time. Fire load is energy available over the whole scenario. Power integrated over time gives energy released, but a constant power cannot be assumed without a justified design-fire model.[4][10]
A high fire load can coexist with low power when the fuel is difficult to decompose or oxygen is limited. A small fuel package can also produce high power briefly before being depleted. Peak heat release rate and total energy must therefore be assessed independently.[1][11]
Mass loss rate provides one link between them, but effective heat of combustion can vary during a test. Babrauskas demonstrates this with cedar, where the effective value changed substantially between early burning and charring. A constant conversion is not always valid.[10]
Fire duration can be estimated by dividing energy release by an assumed heat release rate only when that rate is suitably defined. Ventilation-controlled fires can extend burning beyond a simple fuel-controlled estimate, while suppression can shorten it. Any duration result therefore depends on the selected combustion model.[11][12]
Use in design fires
A Design fire needs both an energy-related context and a time-dependent description. Fire load informs what fuel is present and how long it might support burning, while a heat-release curve specifies how combustion develops. Using only one of these leaves part of the scenario undefined.[13][2]
Fire-load density can support the choice of design parameters in structural and compartment models. Cadorin and Franssen define characteristic and design fire-load densities as inputs to OZone, with the heat release rate treated separately. This illustrates the different roles of energy inventory and power in one model.[5]
Spatial arrangement also matters. Fuel distributed among several objects can ignite sequentially, producing a different curve from the same total mass arranged as one package. Protected, fixed and transient inventories should therefore be located as well as counted.[14]
Surveys of similar buildings can provide statistical fire-load densities when direct inventory is impractical. The 2005 guidelines recommend comparable use and size, sufficient buildings to address variability and, preferably, similar social and economic conditions. Published data still require appropriate sampling and evaluation.[15]
These exposure methods should be reviewed against the inventory boundary. An equivalent duration based on all theoretical fuel energy can overstate what is available if protected contents do not burn, while an incomplete inventory can understate it. The calculation should show which material contributions and combustion efficiencies were accepted.[2][7]
Ventilation can alter both the rate and location of energy release. Oxygen-limited compartments can release unburnt volatiles that burn outside, shifting some thermal exposure away from the original fire load inventory. A duration or equivalence calculation must state whether it includes that external combustion.[11][7]
The inventory can also change during a project or building lifecycle. Transient storage, new furnishings and alterations to combustible construction can invalidate an earlier total. A fire-load assessment should therefore identify its date and intended operating condition rather than being treated as a permanent property of the room.[15][1]
Review by another analyst is easier when each conversion and assumption remains visible. The source of every calorific value, the treatment of moisture, the protected-fuel allowance and the reference area should be reproducible. This allows uncertainty in the inventory to be carried into later fire-duration and structural calculations.[2][16]
Time equivalence relates the thermal effect of a real or parametric fire to an equivalent exposure under a standard fire curve. Fire load helps determine the energy available for that comparison, but it does not define the equivalence alone. Ventilation, boundaries and heat-release history also shape thermal severity.[5][1]
A Parametric fire curve represents gas temperature against time using compartment and fire parameters. Fire-load density can be one of those inputs, alongside openings and boundary properties. The resulting curve differs from a simple total-energy calculation because it describes how the environment changes.[17]
These methods are used in structural fire engineering to estimate member exposure and fire resistance. The total energy affects potential duration, while the curve determines heating rate and peak conditions. A high fire load can therefore be consistent with different structural exposures.[18]
Model scope remains important. Parametric and zone approaches make assumptions about compartment shape, combustion and ventilation. Applying them outside those conditions can produce a temperature history that looks precise but lacks a valid physical basis.[19][17]
Inventory methods and worked interpretation
A transparent inventory uses a table of material, quantity, calorific value and resulting energy. Values with different units are converted before being summed, and permanent and variable contributions are identified. The final total is then related to a clearly stated reference area if density is needed.[1][2]
Van Rossum's warehouse example uses a storage volume of 3,500 m³, an effective storage density of 135 kg/m³ and a calorific value of 23 MJ/kg. These inputs describe the stored inventory. The calculation below follows their conversion into energy and wood-equivalent mass.[1]
Wood-equivalent units provide another way to express energy, but they do not mean that the actual inventory is wood. The conversion basis must be stated, and normal SI energy units remain clearer for subsequent heat-release and duration calculations.[1]
Calculating the inventory
For several materials, each mass is multiplied by its net heat of combustion and the resulting energies are added. A volume-based inventory first converts stored volume to mass using the appropriate bulk density. Fire-load density then divides the total energy by the selected floor area.[1][2]
| Symbol | Description | Unit |
|---|---|---|
| Total potential chemical energy | MJ | |
| Mass of material i | kg | |
| Net heat of combustion of material i | MJ/kg | |
| Bulk density of the stored inventory | kg/m³ | |
| Occupied storage volume | m³ | |
| Reference floor area | m² | |
| Fire-load density | MJ/m² |
Using the warehouse quantities above, the fuel mass is 3,500 × 135 = 472,500 kg. Multiplication by 23 MJ/kg gives 10,867,500 MJ, or approximately 1.09 × 107 MJ. Dividing by the reference wood value of 19 MJ/kg gives about 5.72 × 105 kg of wood equivalent.[1]
Bulk density includes the way the inventory occupies its storage volume. Substituting a solid material density for the stated storage density would describe a different inventory. Equally, the storage volume is not a floor area: a fire-load density cannot be obtained from this example without a separate area input.[1][2]
This arithmetic represents complete combustion of the included fuel. It does not decide whether protected material becomes involved or whether all chemical energy is released inside the compartment. Those changes belong to the fire scenario and combustion model, rather than to an unexplained alteration of the calorific value.[7][2]
Limits and common misunderstandings
Fire load is not the mass of combustible material. Mass must be combined with energy content, and different units require conversion. Two inventories with the same mass can contain different chemical energy.[6]
It is also not heat release rate per unit area. Fire-load density concerns energy over a reference area, while heat-release intensity concerns power over a defined burning area. Similar unit forms do not make the concepts interchangeable.[8][2]
Total theoretical energy is not a prediction of energy actually released. Moisture, incomplete combustion, container protection and suppression can reduce it, and external burning can change where it is released. The scenario boundary must be stated.[7][2]
a larger fire load does not guarantee a higher peak temperature or faster evacuation risk. Ignition, heat release rate, spread, ventilation and occupant response determine those outcomes. Fire load is one part of the wider fire-dynamics description.[4][20]
Where the total drives a safety decision, alternative inventories can show its influence. Variable contents, moisture and protected fractions can be varied within defensible ranges rather than assigned false certainty. The resulting change in duration or exposure reveals whether a more detailed survey is needed.[15][16]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 Van Rossum (2027), §4.4.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 Australian Building Codes Board et al. (2005), pp. 2.4-2–2.4-3.
- ↑ Drysdale (2002), p. 1-92.
- ↑ 4.0 4.1 4.2 Van Rossum (2027), §4.5.
- ↑ 5.0 5.1 5.2 5.3 Cadorin and Franssen (2003), p. 396.
- ↑ 6.0 6.1 6.2 Drysdale (2002), p. 1-93.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Drysdale (2002), p. 1-95.
- ↑ 8.0 8.1 Van Rossum (2027), §4.6.
- ↑ Heskestad (2002), p. 2-2.
- ↑ 10.0 10.1 Babrauskas (2002), p. 3-1.
- ↑ 11.0 11.1 11.2 Van Rossum (2027), §4.8.
- ↑ Cadorin and Franssen (2003), pp. 400–401.
- ↑ Australian Building Codes Board et al. (2005), pp. 1.2-29–1.2-30.
- ↑ Australian Building Codes Board et al. (2005), p. 2.6-12.
- ↑ 15.0 15.1 15.2 Australian Building Codes Board et al. (2005), p. 2.4-3.
- ↑ 16.0 16.1 Van Rossum (2027), §1.7.
- ↑ 17.0 17.1 Cadorin and Franssen (2003), pp. 395–396.
- ↑ Cadorin et al. (2003), pp. 429–430.
- ↑ Van Rossum (2027), §9.2.
- ↑ Australian Building Codes Board et al. (2005), p. 1.6-3.
References
- Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Babrauskas, V. (2002). Heat release rates. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Cadorin, J.-F., & Franssen, J.-M. (2003). A tool to design steel elements submitted to compartment fires: OZone V2. Part 1: Pre- and post-flashover compartment fire model. Fire Safety Journal, 38, 395–427.
- Cadorin, J.-F., Pintea, D., Dotreppe, J.-C., & Franssen, J.-M. (2003). A tool to design steel elements submitted to compartment fires: OZone V2. Part 2: Methodology and application. Fire Safety Journal, 38, 429–451.
- Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Heskestad, G. (2002). Fire plumes, flame height, and air entrainment. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.