Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60 | Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60. | ||
Original illustration for [[Transformer fire]]. | Original illustration for [[Transformer fire]]. | ||
Latest revision as of 09:33, 13 November 2026
Summary
Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60.
Original illustration for Transformer fire.
- Alt text: Radiant heat flux versus distance from a 9 MW transformer oil pool fire for radiative fractions 0.30 and 0.60, with cable damage criteria