== Summary ==
== Summary ==
Sprinkler draft curtain method: a 457 mm (18 in.) deep draft stop under the floor to which the escalator ascends, with a row of sprinklers outside it, not more than 1.83 m (6 ft) apart and 152 to 305 mm (6 to 12 in.) from the draft stop. Based on Donoghue (2008), p. 10-65.
Sprinkler draft curtain method: a 457 mm (18 in.) deep draft stop under the floor to which the escalator ascends, with a row of sprinklers outside it, not more than 1.83 m (6 ft) apart and 152 to 305 mm (6 to 12 in.) from the draft stop.


Original illustration for [[Escalator fire protection]].
Original illustration for [[Escalator fire protection]].

Latest revision as of 08:53, 13 November 2026

Summary

Sprinkler draft curtain method: a 457 mm (18 in.) deep draft stop under the floor to which the escalator ascends, with a row of sprinklers outside it, not more than 1.83 m (6 ft) apart and 152 to 305 mm (6 to 12 in.) from the draft stop.

Original illustration for Escalator fire protection.

  • Alt text: Section and plan of an escalator opening ringed by a 457 mm draft stop with sprinklers at most 1.83 m apart just outside it

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.