The handbook paraphrases NFPA 51B for when a fire watch is needed. Trained fire watchers are required wherever a significant fire could develop. They are also required where appreciable quantities of combustibles lie within 10.6 m (35 ft), even if shielded.<ref name="Manz-9-80" /> Wall or floor openings within 10.6 m that expose combustibles in adjacent areas also call for a fire watcher. So do combustibles on the far side of partitions, ceilings or roofs that heat from the work could ignite.<ref name="Manz-9-80" /> Where combustibles cannot be moved beyond 10.6 m, they are protected with fire-resistant guards, and a trained fire watcher with extinguishing equipment is provided.<ref name="Manz-9-79" />
The handbook paraphrases NFPA 51B for when a fire watch is needed. Trained fire watchers are required wherever a significant fire could develop. They are also required where appreciable quantities of combustibles lie within 10.6 m (35 ft), even if shielded.<ref name="Manz-9-80" /> Wall or floor openings within 10.6 m that expose combustibles in adjacent areas also call for a fire watcher. So do combustibles on the far side of partitions, ceilings or roofs that heat from the work could ignite.<ref name="Manz-9-80" /> Where combustibles cannot be moved beyond 10.6 m, they are protected with fire-resistant guards, and a trained fire watcher with extinguishing equipment is provided.<ref name="Manz-9-79" />
[[File:fse-fire-watch-v1.svg|thumb|upright=1.5|alt=Section of a room with a welder, a 10.6 m radius around the work, shielded combustibles, a floor opening and combustibles behind a wall, with a fire watcher|Conditions within 10.6 m (35 ft) of hot work that call for a trained fire watcher.]]


Where the fire watch stands matters. On construction sites the fire watch should be placed to observe where falling hot materials land, which may be outside the area of the cutting or welding itself.<ref name="Davis-11-52">Davis (2008a), p. 11-52.</ref> During roofing, a fire watch may also be needed under the roof, with a portable extinguisher or a water-charged hose line for small fires started by hot slag or sparks when steel deck is welded.<ref name="Davis-11-54" /> The area under torch-applied roofing should be checked frequently, and security guards should pay extra attention to areas where hot work was done on the previous shift.<ref name="Davis-11-54" /> These measures form part of [[construction site fire safety]], where torches cause one of the largest shares of fires.<ref name="Davis-11-51">Davis (2008a), p. 11-51.</ref>
Where the fire watch stands matters. On construction sites the fire watch should be placed to observe where falling hot materials land, which may be outside the area of the cutting or welding itself.<ref name="Davis-11-52">Davis (2008a), p. 11-52.</ref> During roofing, a fire watch may also be needed under the roof, with a portable extinguisher or a water-charged hose line for small fires started by hot slag or sparks when steel deck is welded.<ref name="Davis-11-54" /> The area under torch-applied roofing should be checked frequently, and security guards should pay extra attention to areas where hot work was done on the previous shift.<ref name="Davis-11-54" /> These measures form part of [[construction site fire safety]], where torches cause one of the largest shares of fires.<ref name="Davis-11-51">Davis (2008a), p. 11-51.</ref>
Line 40: Line 41:


Woodworking facilities receive the longest rule. Small pellets of molten metal fly off during welding, and if they land on combustible material, it often takes several hours for the fire to develop.<ref name="Cholin-9-17" /> The handbook notes that buildings burn down every year because of latent sparks from welding. It therefore recommends a fire watch for at least two hours after welding ends, regardless of how small the repair is.<ref name="Cholin-9-17" /> For torch-applied roofing, the US National Roofing Contractors Association likewise recommends a minimum 2-hour fire watch after the work, including checks of both roof surfaces for smouldering.<ref name="Davis-11-54" />
Woodworking facilities receive the longest rule. Small pellets of molten metal fly off during welding, and if they land on combustible material, it often takes several hours for the fire to develop.<ref name="Cholin-9-17" /> The handbook notes that buildings burn down every year because of latent sparks from welding. It therefore recommends a fire watch for at least two hours after welding ends, regardless of how small the repair is.<ref name="Cholin-9-17" /> For torch-applied roofing, the US National Roofing Contractors Association likewise recommends a minimum 2-hour fire watch after the work, including checks of both roof surfaces for smouldering.<ref name="Davis-11-54" />
[[File:fse-fire-watch-v2.svg|thumb|upright=1.5|alt=Bars: 30-minute check without a watcher; 30-minute watches in storage and cultural buildings; two-hour watches in woodworking and roofing|Fire-watch periods and the no-watcher follow-up check in different chapters of the 2008 handbook.]]


== Smouldering and delayed ignition ==
== Smouldering and delayed ignition ==
Line 57: Line 59:
== Fire watches in fire risk analysis ==
== Fire watches in fire risk analysis ==
The fire risk method for US nuclear power plants, NUREG/CR-6850, treats a fire watch explicitly. Its detection and suppression event tree credits prompt detection only when a continuous fire watch is assigned to an operation or a high-sensitivity smoke detection system is installed.<ref name="Nowlen-P-3">Nowlen et al. (2005b), p. P-3.</ref> A roving fire watch counts only as delayed detection. Prompt suppression refers specifically to suppression by a fire watch and may be credited only in hot work fire scenarios.<ref name="Nowlen-P-3" /><ref name="Nowlen-P-4" /> The method notes that, in practice, welding is the only place where continuous fire watches can be credited.<ref name="Nowlen-C-10">Nowlen et al. (2005b), p. C-10.</ref>
The fire risk method for US nuclear power plants, NUREG/CR-6850, treats a fire watch explicitly. Its detection and suppression event tree credits prompt detection only when a continuous fire watch is assigned to an operation or a high-sensitivity smoke detection system is installed.<ref name="Nowlen-P-3">Nowlen et al. (2005b), p. P-3.</ref> A roving fire watch counts only as delayed detection. Prompt suppression refers specifically to suppression by a fire watch and may be credited only in hot work fire scenarios.<ref name="Nowlen-P-3" /><ref name="Nowlen-P-4" /> The method notes that, in practice, welding is the only place where continuous fire watches can be credited.<ref name="Nowlen-C-10">Nowlen et al. (2005b), p. C-10.</ref>
[[File:fse-fire-watch-v4.svg|thumb|upright=1.5|alt=Simplified event tree: continuous fire watch gives prompt detection and prompt suppression; otherwise automatic or delayed detection, incl. roving watch|Simplified detection and suppression event tree of NUREG/CR-6850, showing where a continuous and a roving fire watch are credited.]]


With a continuous fire watch present, the probability of prompt detection is taken as 1.0. The probability that prompt suppression fails is read from a suppression curve for welding fires at the estimated time to target damage.<ref name="Nowlen-P-6">Nowlen et al. (2005b), p. P-6.</ref> That curve is based on 19 fire events in US plants, of which only two lasted longer than 20 minutes.<ref name="Nowlen-P-7">Nowlen et al. (2005b), p. P-7.</ref> The method models the suppression time as exponentially distributed. The probability that a fire is still not suppressed at time ''t'' then depends only on a constant suppression rate.<ref name="Nowlen-P-8">Nowlen et al. (2005b), p. P-8.</ref>
With a continuous fire watch present, the probability of prompt detection is taken as 1.0. The probability that prompt suppression fails is read from a suppression curve for welding fires at the estimated time to target damage.<ref name="Nowlen-P-6">Nowlen et al. (2005b), p. P-6.</ref> That curve is based on 19 fire events in US plants, of which only two lasted longer than 20 minutes.<ref name="Nowlen-P-7">Nowlen et al. (2005b), p. P-7.</ref> The method models the suppression time as exponentially distributed. The probability that a fire is still not suppressed at time ''t'' then depends only on a constant suppression rate.<ref name="Nowlen-P-8">Nowlen et al. (2005b), p. P-8.</ref>
Line 75: Line 78:


For welding fires, the mean rate is 0.19 per minute, with a 5th to 95th percentile range of 0.13 to 0.27 per minute. The generic ''all fires'' curve has a rate of 0.08 per minute.<ref name="Nowlen-P-9">Nowlen et al. (2005b), p. P-9.</ref> A 2010 supplement revised the welding rate to 0.188 per minute and the all-fires rate to 0.067 per minute.<ref name="Hyslop-14-11">Hyslop et al. (2010), p. 14-11.</ref> As a worked example, consider a hot work fire under a cable tray whose target cables would be damaged after 10 minutes. With a continuous fire watch, the model's failure probability of prompt suppression is e<sup>−0.19 × 10</sup> = 0.150, or 0.067 to 0.273 across the rate percentile range.
For welding fires, the mean rate is 0.19 per minute, with a 5th to 95th percentile range of 0.13 to 0.27 per minute. The generic ''all fires'' curve has a rate of 0.08 per minute.<ref name="Nowlen-P-9">Nowlen et al. (2005b), p. P-9.</ref> A 2010 supplement revised the welding rate to 0.188 per minute and the all-fires rate to 0.067 per minute.<ref name="Hyslop-14-11">Hyslop et al. (2010), p. 14-11.</ref> As a worked example, consider a hot work fire under a cable tray whose target cables would be damaged after 10 minutes. With a continuous fire watch, the model's failure probability of prompt suppression is e<sup>−0.19 × 10</sup> = 0.150, or 0.067 to 0.273 across the rate percentile range.
[[File:fse-fire-watch-v3.svg|thumb|upright=1.5|alt=Line chart of non-suppression probability against time: welding curve with fire watch falls to 0.15 at 10 min, generic all-fires curve to 0.45|Modelled probability of non-suppression, exp(−λt), for prompt suppression of welding fires with a fire watch and the generic all-fires curve in US nuclear plants.]]


For comparison, the all-fires rate of 0.08 per minute would give e<sup>−0.08 × 10</sup> = 0.45 at the same time.<ref name="Nowlen-P-9" /> That value still excludes the time needed to detect the fire and for the fire brigade to arrive.<ref name="Nowlen-P-9" /> The revised 2010 table gives 0.153 for welding fires at 10 minutes, falling to 0.024 at 20 minutes.<ref name="Hyslop-14-10">Hyslop et al. (2010), p. 14-10.</ref> For context, the generic frequency of transient fires caused by welding and cutting in the control, auxiliary and reactor buildings of a US plant ''at power'' is 9.7 × 10<sup>−3</sup> per reactor-year.<ref name="Nowlen-6-3">Nowlen et al. (2005b), p. 6-3.</ref> A hot work fire that a fire watch puts out quickly still counts as a potentially challenging fire in this data if it had clearly started and could have grown.<ref name="Nowlen-C-9">Nowlen et al. (2005b), p. C-9.</ref>
For comparison, the all-fires rate of 0.08 per minute would give e<sup>−0.08 × 10</sup> = 0.45 at the same time.<ref name="Nowlen-P-9" /> That value still excludes the time needed to detect the fire and for the fire brigade to arrive.<ref name="Nowlen-P-9" /> The revised 2010 table gives 0.153 for welding fires at 10 minutes, falling to 0.024 at 20 minutes.<ref name="Hyslop-14-10">Hyslop et al. (2010), p. 14-10.</ref> For context, the generic frequency of transient fires caused by welding and cutting in the control, auxiliary and reactor buildings of a US plant ''at power'' is 9.7 × 10<sup>−3</sup> per reactor-year.<ref name="Nowlen-6-3">Nowlen et al. (2005b), p. 6-3.</ref> A hot work fire that a fire watch puts out quickly still counts as a potentially challenging fire in this data if it had clearly started and could have grown.<ref name="Nowlen-C-9">Nowlen et al. (2005b), p. C-9.</ref>

Latest revision as of 08:28, 13 November 2026

A fire watch is one or more trained persons assigned to watch an activity or area for fire, as additional or compensatory coverage when the normal level of protection is temporarily not enough.[1] A common case is hot work such as welding and cutting, where the fire watch looks out for sparks and hot slag during the work and for some time afterwards.[2][3] A fire watch is also used as a compensatory measure while sprinkler or gaseous extinguishing systems are out of service.[4][5] The persons involved should be trained to recognise fire hazards, to use fire extinguishers and to follow the notification procedures.[1] Post-work fire watches or checks in the 2008 handbook range from at least 30 minutes to at least 2 hours, because sparks can start smouldering fires that break out much later.[3][6] In fire risk analysis for nuclear power plants, a continuous fire watch is the only form of prompt manual suppression that may be credited, and only for hot work fires.[7]

Definition and roles

The NFPA Fire Protection Handbook treats the fire watch as one of three parties in hot work, with the operator who does the work and the permit-authorising individual (PAI) who approves it.[8] The permit process has three steps: recognising the hazard, evaluating it and controlling it. Assigning a fire watch is one of the controls, together with moving the work or the combustibles and isolating the combustibles.[8] Workers, their supervisors or PAIs and facility management share the responsibility for fire safety.[2] This makes the fire watch an organisational measure within fire safety management.[8]

The fire watch should be trained in the use of the fire protection equipment and in the facility's emergency communication procedures.[9] One of the four factors the handbook asks to keep in mind with hot work is supervision, including whether a designated fire watch supports the operator.[9] When hot work is contracted out, contractor and client should agree beforehand on the type of work, the persons assigned as fire watch, the emergency notification procedure and the available manual firefighting tools.[9] Charged and operable fire extinguishers must be readily available at the work.[3]

Two rules recur throughout the handbook. The first is that the fire watch has no other duties while watching: guidance for roofing work and for cultural buildings states this explicitly.[10][11] The second is that the fire watch stays after the work ends, long enough to discover any hidden fire.[11] In audits of industrial facilities, inspectors check whether PAIs and fire watch personnel have been trained and whether recent hot work fires were investigated.[12]

Fire watch during hot work

Hot work is defined in NFPA 51B as work involving burning, welding or a similar operation that is capable of initiating fires or explosions. It includes cutting, welding, grinding, powder-driven fasteners, thawing pipes, hot riveting and torch-applied roofing.[13] Cutting and certain arc welding operations produce literally thousands of ignition sources in the form of sparks and hot slag.[9] Sparks from cutting, particularly oxy-fuel gas cutting, are more hazardous than welding sparks because they are more numerous and travel further, jet-propelled by the oxygen or air stream.[14] Sparks and slag can also fly or roll long distances into concealed spaces, insulation, ceiling voids or ductwork, where they may smoulder undetected for hours.[9]

The handbook paraphrases NFPA 51B for when a fire watch is needed. Trained fire watchers are required wherever a significant fire could develop. They are also required where appreciable quantities of combustibles lie within 10.6 m (35 ft), even if shielded.[2] Wall or floor openings within 10.6 m that expose combustibles in adjacent areas also call for a fire watcher. So do combustibles on the far side of partitions, ceilings or roofs that heat from the work could ignite.[2] Where combustibles cannot be moved beyond 10.6 m, they are protected with fire-resistant guards, and a trained fire watcher with extinguishing equipment is provided.[14]

Section of a room with a welder, a 10.6 m radius around the work, shielded combustibles, a floor opening and combustibles behind a wall, with a fire watcher
Conditions within 10.6 m (35 ft) of hot work that call for a trained fire watcher.

Where the fire watch stands matters. On construction sites the fire watch should be placed to observe where falling hot materials land, which may be outside the area of the cutting or welding itself.[15] During roofing, a fire watch may also be needed under the roof, with a portable extinguisher or a water-charged hose line for small fires started by hot slag or sparks when steel deck is welded.[10] The area under torch-applied roofing should be checked frequently, and security guards should pay extra attention to areas where hot work was done on the previous shift.[10] These measures form part of construction site fire safety, where torches cause one of the largest shares of fires.[16]

Worker cutting steel with sparks falling while a second person stands nearby holding a fire extinguisher and watching the sparks
A fire watch with an extinguisher stands by during cutting and watches where the sparks land.

How long the watch lasts

The recommended duration of a fire watch after hot work differs between sources and occupancies. When no watcher was required, the handbook's NFPA 51B paraphrase calls for a careful check of the work area and adjacent areas. This check lasts at least half an hour after welding or cutting, to detect possible smouldering fires.[3] The checking period should be extended when conditions seem more hazardous.[3] The permit-authorising individual should make a final check for fires half an hour after the work when no watcher was required.[2] Several occupancy chapters specify fire-watch periods.

Fire watch or check after hot work: durations given in the 2008 handbook
Situation Follow-up after the work Chapter
General hot work when no watcher was required (NFPA 51B paraphrase) Check at least 30 min; extend when more hazardous Manz and Blank, p. 9-81
Storage occupancies Present at all times during the work and at least 30 min after J. Moore, p. 20-161
Libraries, museums and places of worship Continuous, no other duties; at least 30 min after torch use McDaniel, p. 20-185
Woodworking facilities At least 2 h after welding, however small the repair Cholin, p. 9-17
Torch-applied roofing (US National Roofing Contractors Association) At least 2 h, checking top and bottom roof surfaces Davis, p. 11-54
Mining and mineral processing As long as necessary to guard against smouldering fires L. J. Moore, p. 9-217

In storage occupancies, the fire watch must be present throughout the work and for at least 30 minutes after its completion, and portable extinguishers or small hose lines must be ready before the work starts.[17] In libraries, museums and places of worship, a fire watch of one or more trained persons should be on site continuously while the work is done.[11] It should monitor the area for at least 30 minutes after torches have been used.[11] In mining and mineral processing, a fire watch should be posted for as long as necessary to guard against smouldering fires, particularly with rubber-lined equipment.[18]

Woodworking facilities receive the longest rule. Small pellets of molten metal fly off during welding, and if they land on combustible material, it often takes several hours for the fire to develop.[6] The handbook notes that buildings burn down every year because of latent sparks from welding. It therefore recommends a fire watch for at least two hours after welding ends, regardless of how small the repair is.[6] For torch-applied roofing, the US National Roofing Contractors Association likewise recommends a minimum 2-hour fire watch after the work, including checks of both roof surfaces for smouldering.[10]

Bars: 30-minute check without a watcher; 30-minute watches in storage and cultural buildings; two-hour watches in woodworking and roofing
Fire-watch periods and the no-watcher follow-up check in different chapters of the 2008 handbook.

Smouldering and delayed ignition

The long durations follow from the nature of smouldering. Combustion takes two forms, flaming and smouldering.[19] Smouldering is a slow, low-temperature, flameless combustion, sustained by the heat released when oxygen attacks the surface of a solid fuel directly.[20] It is hazardous for two reasons. It converts much more of the fuel to toxic compounds than flaming does, and it offers a path to flaming from heat sources too weak to cause a flame directly.[20] Finely divided, permeable fuels such as sawdust favour smouldering, because they combine a large surface area with good thermal insulation.[20]

Smouldering is slow. For layers of wood sawdust in still air, Palmer's results indicate that smouldering takes about two weeks to work up through a layer 1 m deep.[21] With a weak forced air flow through the fuel bed, measured smoulder velocities for several fuels are of the order of 10−4 m/s, about 0.36 m per hour.[22] Thin layers resist smouldering. In still air, the minimum depth for sustained smouldering was about 10 mm for small beech or pine sawdust particles but only 1 mm for very fine cork dust.[23]

These properties explain the guidance. A spark that lands in sawdust, in insulation or in deposits inside a duct can smoulder for hours before flames appear.[9][6] A fire watch that ends when the welder leaves may therefore miss the fire it was meant to catch. Consistent with this, the handbook asks the fire watch to remain after the hot work has been completed, and the woodworking and roofing rules extend the watch to at least two hours.[10][6]

Fire watch for impaired protection

The second main use of a fire watch is to compensate for fire protection that is out of service, as part of impairment management. A fire protection system impairment programme has three aspects: identifying and reporting the impaired system, minimising the impairment, and providing contingencies such as shutting down operations, a fire watch or portable equipment.[24] The handbook warns that many large-loss fires began in facilities where an improperly managed impairment allowed a minor fire to grow unchecked.[24]

For water-based systems, the building owner should appoint an impairment coordinator who supervises the work from shutdown to restoration, with closed valves tagged.[4] Shutdowns should be planned for idle periods, and a fire watch may be needed to help detect any fire while the systems are off.[25] If a system must be out of service for four hours or more in a 24-hour period, additional measures should be considered. These include evacuating the building, a temporary water supply, a fire watch or an approved fire prevention programme, in consultation with the owner and the authority having jurisdiction.[4]

The same principle appears elsewhere. When a carbon dioxide system is locked out for safety, an adequate fire watch should be established to deal with any fire during the lockout.[5] During renovation, a fire watch posted near the main control valve can restore a shut-down system if fire breaks out.[26] Fire watches are also set after a fire. At a records centre in 2000 and at the Shearon Harris nuclear plant in 1989, they were posted once the fires were out.[27][28] At Palo Verde Unit 2 in 1996, during a refuelling outage, a fire watch detected smoke in a control room panel at 5:00 a.m.[29]

Fire watches in fire risk analysis

The fire risk method for US nuclear power plants, NUREG/CR-6850, treats a fire watch explicitly. Its detection and suppression event tree credits prompt detection only when a continuous fire watch is assigned to an operation or a high-sensitivity smoke detection system is installed.[30] A roving fire watch counts only as delayed detection. Prompt suppression refers specifically to suppression by a fire watch and may be credited only in hot work fire scenarios.[30][7] The method notes that, in practice, welding is the only place where continuous fire watches can be credited.[31]

Simplified event tree: continuous fire watch gives prompt detection and prompt suppression; otherwise automatic or delayed detection, incl. roving watch
Simplified detection and suppression event tree of NUREG/CR-6850, showing where a continuous and a roving fire watch are credited.

With a continuous fire watch present, the probability of prompt detection is taken as 1.0. The probability that prompt suppression fails is read from a suppression curve for welding fires at the estimated time to target damage.[32] That curve is based on 19 fire events in US plants, of which only two lasted longer than 20 minutes.[33] The method models the suppression time as exponentially distributed. The probability that a fire is still not suppressed at time t then depends only on a constant suppression rate.[34]

Pns(t)=Pr⁡(T>t)=e−λt

Symbol Description Unit
Pns(t) Probability that the fire is not suppressed by time t –
T Time at which the fire is suppressed (random variable) min
t Time available, usually the time to target damage min
λ Mean suppression rate for the fire type 1/min

For welding fires, the mean rate is 0.19 per minute, with a 5th to 95th percentile range of 0.13 to 0.27 per minute. The generic all fires curve has a rate of 0.08 per minute.[35] A 2010 supplement revised the welding rate to 0.188 per minute and the all-fires rate to 0.067 per minute.[36] As a worked example, consider a hot work fire under a cable tray whose target cables would be damaged after 10 minutes. With a continuous fire watch, the model's failure probability of prompt suppression is e−0.19 × 10 = 0.150, or 0.067 to 0.273 across the rate percentile range.

Line chart of non-suppression probability against time: welding curve with fire watch falls to 0.15 at 10 min, generic all-fires curve to 0.45
Modelled probability of non-suppression, exp(−λt), for prompt suppression of welding fires with a fire watch and the generic all-fires curve in US nuclear plants.

For comparison, the all-fires rate of 0.08 per minute would give e−0.08 × 10 = 0.45 at the same time.[35] That value still excludes the time needed to detect the fire and for the fire brigade to arrive.[35] The revised 2010 table gives 0.153 for welding fires at 10 minutes, falling to 0.024 at 20 minutes.[37] For context, the generic frequency of transient fires caused by welding and cutting in the control, auxiliary and reactor buildings of a US plant at power is 9.7 × 10−3 per reactor-year.[38] A hot work fire that a fire watch puts out quickly still counts as a potentially challenging fire in this data if it had clearly started and could have grown.[39]

The same thinking is applied to other compensatory measures. When a very early warning fire detection system is out of service, the 2010 supplement names a continuous hot-work-type fire watch as a compensatory measure that may be judged equivalent.[40] Without such a measure, the supplement's example says that four days out of service would reduce the system's effectiveness by an order of magnitude, and even one day by a factor of about 3.[40] For an alert from such a system, the method assumes that a qualified continuous "flash watch", similar to a hot work fire watch, is posted at the affected cabinet.[41]

Limits and common misconceptions

A fire watch is a human measure and shares the limits of other administrative controls. Its value depends on training, on attention and on being posted at all, and the handbook notes that most damaging hot work fires occur when proper guidelines are not followed.[13] The nuclear fire risk method restricts its credit to continuous fire watches during hot work, because other uses are very plant specific.[31] The welding curve also applies only while the fire is small. Once a fire has spread to secondary combustibles and needs more than the fire watch, other suppression curves apply.[32]

A common misconception is that the welder or a helper can act as fire watch while also doing other work. The handbook's guidance for roofing and for cultural buildings states that the fire watch should have no other duties.[10][11] Another is that a fire watch ends when the hot work ends. All the hot work guidance summarised above requires the watch, or at least a check, to continue after the work, from 30 minutes up to two hours or "as long as necessary".[3][6][18]

The durations are recommendations from a 2008 US handbook and the documents it summarises, and they differ between occupancies.[3][6] None of the handbook chapters consulted derives them from a calculation of smouldering times. The name also has a second meaning: "Firewatch" is the title of a column in the NFPA Journal that profiles notable fires.[42]

See also

Notes

  1. ↑ 1.0 1.1 Iqbal and Salley (2004), p. F-29.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Manz and Blank (2008), p. 9-80.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Manz and Blank (2008), p. 9-81.
  4. ↑ 4.0 4.1 4.2 Hague (2008a), p. 16-221.
  5. ↑ 5.0 5.1 Wysocki (2008), p. 17-8.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 Cholin (2008d), p. 9-17.
  7. ↑ 7.0 7.1 Nowlen et al. (2005b), p. P-4.
  8. ↑ 8.0 8.1 8.2 Snyder (2008), p. 12-187.
  9. ↑ 9.0 9.1 9.2 9.3 9.4 9.5 Manz and Blank (2008), p. 9-74.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 10.5 Davis (2008a), p. 11-54.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 McDaniel (2008), p. 20-185.
  12. ↑ Snyder (2008), p. 12-189.
  13. ↑ 13.0 13.1 Manz and Blank (2008), p. 9-73.
  14. ↑ 14.0 14.1 Manz and Blank (2008), p. 9-79.
  15. ↑ Davis (2008a), p. 11-52.
  16. ↑ Davis (2008a), p. 11-51.
  17. ↑ J. Moore (2008), p. 20-161.
  18. ↑ 18.0 18.1 L. J. Moore (2008), p. 9-217.
  19. ↑ Van Rossum (2027), §4.1.
  20. ↑ 20.0 20.1 20.2 Ohlemiller (2002), p. 2-200.
  21. ↑ Ohlemiller (2002), p. 2-201.
  22. ↑ Ohlemiller (2002), p. 2-202.
  23. ↑ Ohlemiller (2002), p. 2-205.
  24. ↑ 24.0 24.1 Snyder (2008), p. 12-180.
  25. ↑ Hague (2008a), p. 16-208.
  26. ↑ Davis (2008a), p. 11-56.
  27. ↑ Beals (2008), p. 9-116.
  28. ↑ Iqbal and Salley (2004), p. H-19.
  29. ↑ Iqbal and Salley (2004), p. H-24.
  30. ↑ 30.0 30.1 Nowlen et al. (2005b), p. P-3.
  31. ↑ 31.0 31.1 Nowlen et al. (2005b), p. C-10.
  32. ↑ 32.0 32.1 Nowlen et al. (2005b), p. P-6.
  33. ↑ Nowlen et al. (2005b), p. P-7.
  34. ↑ Nowlen et al. (2005b), p. P-8.
  35. ↑ 35.0 35.1 35.2 Nowlen et al. (2005b), p. P-9.
  36. ↑ Hyslop et al. (2010), p. 14-11.
  37. ↑ Hyslop et al. (2010), p. 14-10.
  38. ↑ Nowlen et al. (2005b), p. 6-3.
  39. ↑ Nowlen et al. (2005b), p. C-9.
  40. ↑ 40.0 40.1 Hyslop et al. (2010), p. 13-9.
  41. ↑ Hyslop et al. (2010), p. 13-6.
  42. ↑ Ahrens and Stewart (2008), p. 3-57.

References

  • Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
  • Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-105–9-117). National Fire Protection Association.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
  • Hague, D. R. (2008a). Care and maintenance of water-based extinguishing systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-205–16-222). National Fire Protection Association.
  • Hyslop, J. S., Kratchman, J., Siu, N., Afshar, C., Najafi, B., Joglar, F., Li, Y., Henneke, D., & Warner, M. (2010). Fire probabilistic risk assessment methods enhancements: Supplement 1 to NUREG/CR-6850 and EPRI 1011989 (NUREG/CR-6850, Supplement 1; EPRI 1019259). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Manz, A. F., & Blank, M. E. (2008). Welding, cutting, and other hot work. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-73–9-83). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.
  • Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.