The same mechanism dominates many fires at the [[wildland-urban interface]]. Smalley writes that in many such fires significant structure loss occurs primarily from ember (firebrand) exposure.<ref name="SM-13-63" /> California studies cited by Smalley found that houses with flammable roofing had an 81 % chance of being destroyed in wildfires, against 30 % for houses with nonflammable roofing.<ref name="SM-13-66" /> Of houses with flammable roofs and no maintained vegetation clearance, 96 % were destroyed. Of houses with nonflammable roofs and a maintained clearance, 14 % were destroyed.<ref name="SM-13-67">Smalley (2008), p. 13-67.</ref> A dense subdivision with wood shingle roofs several miles from the wildland can be at greater risk than ignition-resistant homes that border it.<ref name="SM-13-65">Smalley (2008), p. 13-65.</ref> | The same mechanism dominates many fires at the [[wildland-urban interface]]. Smalley writes that in many such fires significant structure loss occurs primarily from ember (firebrand) exposure.<ref name="SM-13-63" /> California studies cited by Smalley found that houses with flammable roofing had an 81 % chance of being destroyed in wildfires, against 30 % for houses with nonflammable roofing.<ref name="SM-13-66" /> Of houses with flammable roofs and no maintained vegetation clearance, 96 % were destroyed. Of houses with nonflammable roofs and a maintained clearance, 14 % were destroyed.<ref name="SM-13-67">Smalley (2008), p. 13-67.</ref> A dense subdivision with wood shingle roofs several miles from the wildland can be at greater risk than ignition-resistant homes that border it.<ref name="SM-13-65">Smalley (2008), p. 13-65.</ref> | ||
[[File:fse-roof-covering-fire-test-v3.svg|thumb|upright=1.5|alt=Bar chart of houses destroyed in California wildfires: flammable roof 81 %, nonflammable 30 %, no clearance 62 %, clearance 22 %, combined 96 % and 14 %.|Share of houses destroyed in California wildfires by roofing and vegetation clearance of at least 9 m (30 ft) | [[File:fse-roof-covering-fire-test-v3.svg|thumb|upright=1.5|alt=Bar chart of houses destroyed in California wildfires: flammable roof 81 %, nonflammable 30 %, no clearance 62 %, clearance 22 %, combined 96 % and 14 %.|Share of houses destroyed in California wildfires by roofing and vegetation clearance of at least 9 m (30 ft).]] | ||
== Test method == | == Test method == | ||
| Line 17: | Line 17: | ||
The method consists of three tests: an intermittent flame exposure test, a spread of flame test and a burning brand test.<ref name="JA-2-70" /> Only the spread of flame test is required for coverings mounted on a noncombustible deck. Each test has three levels of exposure, severe, moderate and light, which lead to Classes A, B and C.<ref name="JA-2-70" /> In the burning brand tests, Class A requires the roofing to resist ignition from a large burning array of wood sticks. Class B uses a moderate-size array and Class C a burning notched wood block.<ref name="JA-2-70" /> Rain tests are added when water may harm the fire-retardant characteristics of the covering or construction.<ref name="JA-2-70" /> | The method consists of three tests: an intermittent flame exposure test, a spread of flame test and a burning brand test.<ref name="JA-2-70" /> Only the spread of flame test is required for coverings mounted on a noncombustible deck. Each test has three levels of exposure, severe, moderate and light, which lead to Classes A, B and C.<ref name="JA-2-70" /> In the burning brand tests, Class A requires the roofing to resist ignition from a large burning array of wood sticks. Class B uses a moderate-size array and Class C a burning notched wood block.<ref name="JA-2-70" /> Rain tests are added when water may harm the fire-retardant characteristics of the covering or construction.<ref name="JA-2-70" /> | ||
[[File:fse-roof-covering-fire-test-v1.svg|thumb|upright=1.5|alt=Three side views of an inclined roof test deck: a burner flame at the lower edge, a flame front moving up the surface, and a burning wood brand on the deck.|The three exposures of the roof covering fire test on an inclined deck of about 1.0 m × 1.3 m: intermittent flame, spread of flame and burning brand | [[File:fse-roof-covering-fire-test-v1.svg|thumb|upright=1.5|alt=Three side views of an inclined roof test deck: a burner flame at the lower edge, a flame front moving up the surface, and a burning wood brand on the deck.|The three exposures of the roof covering fire test on an inclined deck of about 1.0 m × 1.3 m: intermittent flame, spread of flame and burning brand.]] | ||
Iqbal and Salley (2004) list the properties measured under ASTM E108, UL 790 and UBC 32-7 as spread of flame, intermittent flame, burning brand and flying brand. The samples they name include coatings, shingles and shakes, and insulation.<ref name="IS-C-12">Iqbal and Salley (2004), p. C-12.</ref> The construction below the covering matters. In brand and flame tests, tongue-and-groove boards and 19 mm (3/4 in.) moisture-resistant plywood perform better than square-edge sheathing with boards spaced about 6.35 mm (1/4 in.) apart. That gap is specified to simulate real conditions after the boards have shrunk.<ref name="GW-19-26">Gore Willse (2008b), p. 19-26.</ref> | Iqbal and Salley (2004) list the properties measured under ASTM E108, UL 790 and UBC 32-7 as spread of flame, intermittent flame, burning brand and flying brand. The samples they name include coatings, shingles and shakes, and insulation.<ref name="IS-C-12">Iqbal and Salley (2004), p. C-12.</ref> The construction below the covering matters. In brand and flame tests, tongue-and-groove boards and 19 mm (3/4 in.) moisture-resistant plywood perform better than square-edge sheathing with boards spaced about 6.35 mm (1/4 in.) apart. That gap is specified to simulate real conditions after the boards have shrunk.<ref name="GW-19-26">Gore Willse (2008b), p. 19-26.</ref> | ||
| Line 27: | Line 27: | ||
For the spread of flame test, Iqbal and Salley (2004) summarise the NFPA 256 limits as follows. The flame spread must stay below 1.83 m (6 ft) for Class A, below 2.44 m (8 ft) for Class B and below 3.96 m (13 ft) for Class C.<ref name="IS-C-11">Iqbal and Salley (2004), p. C-11.</ref> For all classes there must be no significant lateral flame spread and no flying brands or particles that keep flaming or glowing after reaching the floor. No flaming may appear on the underside of the deck, and the roof deck must not become exposed.<ref name="IS-C-11" /> | For the spread of flame test, Iqbal and Salley (2004) summarise the NFPA 256 limits as follows. The flame spread must stay below 1.83 m (6 ft) for Class A, below 2.44 m (8 ft) for Class B and below 3.96 m (13 ft) for Class C.<ref name="IS-C-11">Iqbal and Salley (2004), p. C-11.</ref> For all classes there must be no significant lateral flame spread and no flying brands or particles that keep flaming or glowing after reaching the floor. No flaming may appear on the underside of the deck, and the roof deck must not become exposed.<ref name="IS-C-11" /> | ||
[[File:fse-roof-covering-fire-test-v2.svg|thumb|upright=1.5|alt=Three rows for Classes A, B and C with brand symbols of decreasing size and horizontal bars of 1.83 m, 2.44 m and 3.96 m maximum flame spread.|Roof covering Classes A, B and C: exposure level, burning brand and the maximum flame spread in the spread of flame test | [[File:fse-roof-covering-fire-test-v2.svg|thumb|upright=1.5|alt=Three rows for Classes A, B and C with brand symbols of decreasing size and horizontal bars of 1.83 m, 2.44 m and 3.96 m maximum flame spread.|Roof covering Classes A, B and C: exposure level, burning brand and the maximum flame spread in the spread of flame test.]] | ||
{| class="wikitable" | {| class="wikitable" | ||
| Line 83: | Line 83: | ||
Flames above the roof reach about 1.4 times the building height, about 5.2 m. With a flame temperature of 760 °C (1,033 K), the plume radiates about 66 kW/m². Recalculating with the Stefan–Boltzmann constant gives 5.67 × 10<sup>−8</sup> × 1,033<sup>4</sup> ≈ 64.6 kW/m².<ref name="DA-18-14" /><ref name="VR-5.4" /> A moderate wind tilts the plume by 45°, and the maximum view factor becomes about 0.3. The roof beyond the parapet then receives about 0.3 × 66 ≈ 20 kW/m².<ref name="DA-18-14" /> | Flames above the roof reach about 1.4 times the building height, about 5.2 m. With a flame temperature of 760 °C (1,033 K), the plume radiates about 66 kW/m². Recalculating with the Stefan–Boltzmann constant gives 5.67 × 10<sup>−8</sup> × 1,033<sup>4</sup> ≈ 64.6 kW/m².<ref name="DA-18-14" /><ref name="VR-5.4" /> A moderate wind tilts the plume by 45°, and the maximum view factor becomes about 0.3. The roof beyond the parapet then receives about 0.3 × 66 ≈ 20 kW/m².<ref name="DA-18-14" /> | ||
[[File:fse-roof-covering-fire-test-v4.svg|thumb|upright=1.5|alt=Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.|Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition | [[File:fse-roof-covering-fire-test-v4.svg|thumb|upright=1.5|alt=Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.|Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition.]] | ||
This is well above the 12.5 kW/m² needed for pilot ignition of wood, so fire spread over the fire wall is to be expected if the wind tilts the plume towards the exposed roof.<ref name="DA-18-14" /> The received flux would fall to 12.5 kW/m² only at a view factor of about 0.19 (12.5/66).<ref name="DA-18-14" /> Davoodi notes that the risk depends on how combustible the roof surface is and on the height of the parapet. It also depends on the size of the plume, the wind and, for a roof covering that resists radiant ignition, its insulating properties and the duration of the exposing fire.<ref name="DA-18-14" /> If the roof surface is noncombustible or resists radiant ignition, the calculation turns instead to the temperature of the combustible material beneath it, an unsteady heat transfer problem.<ref name="DA-18-14" /> | This is well above the 12.5 kW/m² needed for pilot ignition of wood, so fire spread over the fire wall is to be expected if the wind tilts the plume towards the exposed roof.<ref name="DA-18-14" /> The received flux would fall to 12.5 kW/m² only at a view factor of about 0.19 (12.5/66).<ref name="DA-18-14" /> Davoodi notes that the risk depends on how combustible the roof surface is and on the height of the parapet. It also depends on the size of the plume, the wind and, for a roof covering that resists radiant ignition, its insulating properties and the duration of the exposing fire.<ref name="DA-18-14" /> If the roof surface is noncombustible or resists radiant ignition, the calculation turns instead to the temperature of the combustible material beneath it, an unsteady heat transfer problem.<ref name="DA-18-14" /> | ||
Latest revision as of 08:25, 8 November 2026
A roof covering fire test is a fire test that rates how well a roof covering resists a fire that starts outside the building. Typical threats are burning brands landing on the roof and flames spreading over its surface. In the United States the method is published as ASTM E108 and NFPA 256, Standard Methods of Fire Tests of Roof Coverings.[1] A sample roof about 1 m by 1.3 m is built at its intended slope and exposed to an intermittent flame, a spreading flame and burning brands of wood.[1] The results place the covering in Class A, B or C, for severe, moderate and light exterior fire exposure.[2]
Roofs matter because a fire in one building exposes its neighbours to radiation, convection and flying brands.[3] Roof coverings range from untreated wood shingles to built-up and prepared coverings that are effective against severe external exposure. Well-designed coverings can considerably reduce the likelihood of fire spread between buildings.[2] In many wildland fires that reach built-up areas, structure loss comes mainly from embers, and roofing is among the most critical features of a house.[4][5] Building codes therefore set a minimum roof class by location and building type.[6]
Purpose and fire experience
The test addresses two ways in which fire reaches a building from outside. Burning brands can land on a roof surface, or flames can propagate over the roof covering.[1] Firebrands are carried aloft by the upward gas flow in a fire plume and then carried by the wind to distant buildings.[7] The largest brands come from the highest burning elevations still inside the plume. How far they travel also depends on their shape, burning mode and density, on the heat release rate of the fire and on the wind speed.[7] Brands with high-drag shapes, glowing char at high temperature and low density are lofted furthest and do the most damage.[7]
Untreated wood roofs show the problem most clearly. Untreated wood shingles may be ignited by small sparks from chimneys or exposure fires, by radiated heat or by burning brands. Burning shingles then produce brands of their own, which the wind may carry to start other fires.[6] Age and humidity make wood-shingled roofs more susceptible to ignition.[6]
In a 2002 fire in San Jose, California, flying brands and embers spread fire up to half a mile (about 0.8 km) downwind. They reached an apartment and townhouse complex with wood shake roofs, and the total loss was estimated at $90 million.[8] In a 1982 fire in Anaheim, untreated wood shingles supplied secondary ignitions and firebrands in winds gusting up to 100 km/h, and 53 structures were damaged.[8]
The same mechanism dominates many fires at the wildland-urban interface. Smalley writes that in many such fires significant structure loss occurs primarily from ember (firebrand) exposure.[4] California studies cited by Smalley found that houses with flammable roofing had an 81 % chance of being destroyed in wildfires, against 30 % for houses with nonflammable roofing.[5] Of houses with flammable roofs and no maintained vegetation clearance, 96 % were destroyed. Of houses with nonflammable roofs and a maintained clearance, 14 % were destroyed.[9] A dense subdivision with wood shingle roofs several miles from the wildland can be at greater risk than ignition-resistant homes that border it.[10]
Test method
ASTM E108 and NFPA 256 are listed in the handbook as technically equivalent exterior fire tests, and UL 790, Standard Test Methods for Fire Tests of Roof Coverings, as a similar test.[11][12] The procedure measures the relative fire characteristics of roof coverings under a simulated fire that originates outside the building.[1] The chapter on building construction cites the 2005 edition of ASTM E108.[13] The covering is mounted on a deck of 1.02 m × 1.32 m (40 in. × 52 in.) set at the required incline.[1] Prepared coverings are classified as applied over square-edge wood sheathing of 1 in. (25.4 mm) nominal thickness, unless otherwise specified.[14]
The method consists of three tests: an intermittent flame exposure test, a spread of flame test and a burning brand test.[1] Only the spread of flame test is required for coverings mounted on a noncombustible deck. Each test has three levels of exposure, severe, moderate and light, which lead to Classes A, B and C.[1] In the burning brand tests, Class A requires the roofing to resist ignition from a large burning array of wood sticks. Class B uses a moderate-size array and Class C a burning notched wood block.[1] Rain tests are added when water may harm the fire-retardant characteristics of the covering or construction.[1]
Iqbal and Salley (2004) list the properties measured under ASTM E108, UL 790 and UBC 32-7 as spread of flame, intermittent flame, burning brand and flying brand. The samples they name include coatings, shingles and shakes, and insulation.[15] The construction below the covering matters. In brand and flame tests, tongue-and-groove boards and 19 mm (3/4 in.) moisture-resistant plywood perform better than square-edge sheathing with boards spaced about 6.35 mm (1/4 in.) apart. That gap is specified to simulate real conditions after the boards have shrunk.[16]
Classification and acceptance criteria
Gore Willse (2008b) describes the three classes in terms of the exposure they resist. Class A coverings are effective against severe fire exposures. They are not readily flammable, do not carry or communicate fire, give the roof deck a fairly high degree of fire protection, do not slip from position and have no flying brand hazard.[2]
Class B coverings are effective against moderate exposures and give the deck a moderate degree of protection. They may need repairs to keep their fire-retardant properties.[2] Class C coverings are effective against light exposure and give at least a slight degree of protection. They may need repairs or renewals to maintain their fire-retardant properties.[2][6]
For the spread of flame test, Iqbal and Salley (2004) summarise the NFPA 256 limits as follows. The flame spread must stay below 1.83 m (6 ft) for Class A, below 2.44 m (8 ft) for Class B and below 3.96 m (13 ft) for Class C.[17] For all classes there must be no significant lateral flame spread and no flying brands or particles that keep flaming or glowing after reaching the floor. No flaming may appear on the underside of the deck, and the roof deck must not become exposed.[17]
| Class | Exterior fire exposure | Burning brand | Spread of flame limit |
|---|---|---|---|
| A | severe | large burning array of wood sticks | less than 1.83 m (6 ft) |
| B | moderate | moderate-size burning array | less than 2.44 m (8 ft) |
| C | light | burning notched wood block | less than 3.96 m (13 ft) |
The table combines the exposure levels and brand sizes given by Janssens (2008) with the spread limits given by Iqbal and Salley (2004).[1][17] A covering can always be used for a less severe exposure than the one for which it is listed.[6] Fire testing laboratories publish the classifications of listed products.[6]
Roof coverings and their ratings
Fire-retardant roof coverings fall into several groups. Built-up coverings consist of several layers of roofing felts and insulating sheets bonded by hot or cold cements, often topped with gravel; the "tar and gravel" roof is an example.[6] Prepared coverings include fire-retardant shingles and sheets, which can be applied only to nailable roof decks with enough slope for drainage. For some classes the slope must also stay below a specified maximum.[6] Asphalt organic felt shingles, known as composition roofs, are a common prepared covering on dwellings. Noncombustible coverings such as brick, concrete, tile and slate also count as prepared coverings.[6]
The handbook's table of typical prepared coverings shows how the class follows from material and build-up. Brick, reinforced concrete, clay or concrete tile and slate of specified thickness appear under Class A. Asphalt glass fibre mat shingles reach Class A with two or more thicknesses, and Class B or C with one or more.[18][14] Fire-retardant-treated red cedar shingles and shakes appear under Class C, and shakes need at least one layer of felt underlay.[14] Prepared roofings are labelled by Underwriters Laboratories to show their classification when applied as directed.[14] Single-ply membranes are rated according to the material, whether it is fire retardant, the insulation directly below and any coating or topping.[6]
Wood shingles show the role of fire-retardant-treated wood. Treating shingles in place with fire-retardant coatings has not proved practical, and ordinary flame-resistant treatments lose their effectiveness with continued weathering.[6] Shingles impregnated with a fire-retardant solution are more durable; such shingles have been tested and carry a Class B or C rating.[6] The rain tests of the method address this, since they are required when water may adversely affect the fire-retardant characteristics.[1] A surface layer can also help. Pea gravel, large stone ballast, concrete pavers and some coatings on top of a covering can greatly improve its resistance to exterior fire exposure.[2]
Use in codes and design
In the United States, as described by Gore Willse (2008b), building codes commonly require Class A or B coverings within the fire limits of cities or wherever fire-resistive construction is required. Class C roofing is considered appropriate for other buildings, and many cities specify Class C as the minimum.[6] Untreated wood shingle roofs are prohibited by law in the congested sections of practically all large cities. Many cities and towns forbid them altogether within municipal limits.[6] Some occupancy guidance asks for the top class: for wastewater treatment plants, Wheeler (2008) recommends Class A roof coverings tested to NFPA 256.[19]
For homes near wildland, the Firewise approach described by Smalley (2008) combines ignition-resistant building materials with a defensible space created by thinning trees and brush around the house.[9] NFPA 1144, Standard for Reducing Structure Ignition Hazards from Wildland Fire, defines the wildland-urban interface by the potential for structures to be ignited by the flames and firebrands of a wildland fire.[20] The roof rating is one part of this wider set of measures.
The rating can also support an engineering analysis. Janssens describes how to confirm a safe separation distance from an outside fire source. The size of the largest firebrand that can reach a roof is estimated from the fire scenario. Suppose brands of that size cause no damage, as shown for example by the ASTM E108 rating of the roofing. Smaller brands of the same type will then not cause damage either, because their ignition heat flux is lower.[7]
The International Fire Engineering Guidelines (2005) note that the distance a burning brand may be carried by the wind is often difficult to establish. They point to BS 476 Part 3 (1975), a British test of the ignitability and fire spread of external roof surfaces under radiation and piloted ignition by flying brands.[21] The international standard ISO 12468, on the external fire exposure of roofs, is listed in the handbook as not technically equivalent to ASTM E108.[11][22]
Radiant exposure of a roof
Besides brands and flames, a roof can be ignited by radiation from a nearby fire plume. Davoodi (2008) shows how to estimate this for a roof next to a burning section of the same building. The radiation received by the roof equals the radiation emitted by the plume multiplied by a view factor, the share of the emitted radiation that reaches the target.[23][24] If the flames are thick enough to radiate as a black body, the emitted radiation follows from the flame temperature.[23]
| Symbol | Description | Unit |
|---|---|---|
| radiant heat flux received by the roof surface | kW/m² | |
| radiating intensity (emissive power) of the fire plume | kW/m² | |
| configuration factor (view factor) between plume and roof | – | |
| Stefan–Boltzmann constant, 5.67 × 10−8 | W/(m²·K⁴) | |
| absolute flame temperature | K |
Van Rossum writes the same relation in its general form, with an emissivity and the temperature of the receiving surface subtracted. With an emissivity of 1 the result differs little from Davoodi's simpler version.[24] The view factor depends on the size of the radiating surface, its distance and its orientation.[24] For a plume above a roof it also depends on the wind, which tilts the plume towards or away from the target.[23]
The result is compared with an ignition threshold. At an incident radiation of 12.5 kW/m² a wood roof can be heated enough for a small burning brand to ignite it, which is called pilot ignition.[23] Janssens gives the same value as the commonly accepted threshold for piloted ignition of wood.[25] Cholin (2008c) adds that the flux needed varies with species, moisture content, exposure time and grain orientation. Babrauskas has suggested 20 kW/m² for short exposures and 4.3 kW/m² for long ones.[26]
Worked example. Davoodi considers a frame building 3.7 m (12 ft) high and 18.3 m (60 ft) wide with a wood-surfaced roof. In the United States construction classification, what was formerly called wood-frame construction is now Type V.[13] A masonry fire wall with a 0.9 m (3 ft) parapet divides it.[23]
Flames above the roof reach about 1.4 times the building height, about 5.2 m. With a flame temperature of 760 °C (1,033 K), the plume radiates about 66 kW/m². Recalculating with the Stefan–Boltzmann constant gives 5.67 × 10−8 × 1,0334 ≈ 64.6 kW/m².[23][24] A moderate wind tilts the plume by 45°, and the maximum view factor becomes about 0.3. The roof beyond the parapet then receives about 0.3 × 66 ≈ 20 kW/m².[23]
This is well above the 12.5 kW/m² needed for pilot ignition of wood, so fire spread over the fire wall is to be expected if the wind tilts the plume towards the exposed roof.[23] The received flux would fall to 12.5 kW/m² only at a view factor of about 0.19 (12.5/66).[23] Davoodi notes that the risk depends on how combustible the roof surface is and on the height of the parapet. It also depends on the size of the plume, the wind and, for a roof covering that resists radiant ignition, its insulating properties and the duration of the exposing fire.[23] If the roof surface is noncombustible or resists radiant ignition, the calculation turns instead to the temperature of the combustible material beneath it, an unsteady heat transfer problem.[23]
Limitations
The test ranks the relative performance of roof coverings against exterior exposure; it does not address fire from inside. Gore Willse stresses that the fire performance of a roof assembly under exterior exposure is not necessarily the same as under interior exposure.[1][2] In the 1953 General Motors fire at Livonia, Michigan, asphalt in the vapour barrier beneath the insulation of a 139,582 m² steel-deck roof melted and vaporised. The vapour entered the building through the joints in the deck and burned inside.[14] FM Global classes insulated metal deck roofs as Class 1 or Class 2, by whether the above-deck components can sustain a fire on the underside of the deck. This classification is distinct from the A, B and C of the exterior test.[13]
The ratings also depend on maintenance and on the exact build-up tested. Classes B and C allow that coverings may need repairs or renewals to keep their properties, and fire-retardant treatments can lose effectiveness through weathering.[2][6] The rating applies to the tested combination of covering, sheathing and slope.[14][16]
Fire statistics give a sense of scale. In United States homes in 1999–2002, an exterior roof covering or finish was the item first ignited in about 3,700 fires a year. These fires caused direct damage of about $118 million a year.[27] Finally, the classes are United States categories. Other countries use other methods, such as BS 476 Part 3 or ISO 12468, which the handbook does not treat as technically equivalent.[11][21]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 Janssens (2008), p. 2-70.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Gore Willse (2008b), p. 19-22.
- ↑ Comly (2008), p. 11-43.
- ↑ 4.0 4.1 Smalley (2008), p. 13-63.
- ↑ 5.0 5.1 Smalley (2008), p. 13-66.
- ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 6.10 6.11 6.12 6.13 6.14 Gore Willse (2008b), p. 19-23.
- ↑ 7.0 7.1 7.2 7.3 Janssens (2008), p. 2-72.
- ↑ 8.0 8.1 Hall and Cote (2008), p. 3-13.
- ↑ 9.0 9.1 Smalley (2008), p. 13-67.
- ↑ Smalley (2008), p. 13-65.
- ↑ 11.0 11.1 11.2 Hirschler (2008a), p. 6-38.
- ↑ Hirschler (2008a), p. 6-60.
- ↑ 13.0 13.1 13.2 Gore Willse (2008b), p. 19-27.
- ↑ 14.0 14.1 14.2 14.3 14.4 14.5 Gore Willse (2008b), p. 19-25.
- ↑ Iqbal and Salley (2004), p. C-12.
- ↑ 16.0 16.1 Gore Willse (2008b), p. 19-26.
- ↑ 17.0 17.1 17.2 Iqbal and Salley (2004), p. C-11.
- ↑ Gore Willse (2008b), p. 19-24.
- ↑ Wheeler (2008), p. 9-153.
- ↑ Smalley (2008), p. 13-64.
- ↑ 21.0 21.1 National Research Council of Canada et al. (2005), p. 2.6-12.
- ↑ Hirschler (2008a), p. 6-59.
- ↑ 23.00 23.01 23.02 23.03 23.04 23.05 23.06 23.07 23.08 23.09 23.10 Davoodi (2008), p. 18-14.
- ↑ 24.0 24.1 24.2 24.3 Van Rossum (2027), §5.4.
- ↑ Janssens (2008), p. 2-69.
- ↑ Cholin (2008c), p. 6-69.
- ↑ Ahrens et al. (2008), p. 3-75.
References
- Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
- Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
- Comly, A. M., Jr. (2008). Building and site planning for fire safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-39–11-45). National Fire Protection Association.
- Davoodi, H. (2008). Confinement of fire in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-3–18-21). National Fire Protection Association.
- Gore Willse, P. J. (2008b). Types of building construction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-3–19-27). National Fire Protection Association.
- Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Janssens, M. L. (2008). Basics of fire containment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-59–2-74). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Smalley, J. C. (2008). Wildland fire management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-53–13-79). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wheeler, J. F. (2008). Protection of wastewater treatment plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-141–9-155). National Fire Protection Association.