The insulating property itself drives the hazard. A material with a low thermal inertia heats up quickly at its surface, which can lead to fast ignition if it is combustible; lightweight insulation is the typical example.<ref name="VR-5.2">Van Rossum (2027), §5.2.</ref> With the property values of ''Introduction to Fire Safety Engineering'', the product of conductivity, density and specific heat is about 950 J²/(m⁴·K²·s) for polyurethane foam. That is roughly 340 times less than for oak, so the foam surface heats up far faster under the same exposure.<ref name="VR-5.5" />
The insulating property itself drives the hazard. A material with a low thermal inertia heats up quickly at its surface, which can lead to fast ignition if it is combustible; lightweight insulation is the typical example.<ref name="VR-5.2">Van Rossum (2027), §5.2.</ref> With the property values of ''Introduction to Fire Safety Engineering'', the product of conductivity, density and specific heat is about 950 J²/(m⁴·K²·s) for polyurethane foam. That is roughly 340 times less than for oak, so the foam surface heats up far faster under the same exposure.<ref name="VR-5.5" />
[[File:fse-foam-plastic-insulation-v1.svg|thumb|upright=1.5|alt=Bar chart on a log scale: thermal inertia of polyurethane foam about 31, softwood 505, oak 569, gypsum plaster 762 and concrete 2,012.|Thermal inertia (square root of conductivity × density × specific heat) of polyurethane foam compared with common building materials. The low value of the foam means that its surface heats up very quickly. Based on Van Rossum (2027), §5.2 and §5.5.]]
[[File:fse-foam-plastic-insulation-v1.svg|thumb|upright=1.5|alt=Bar chart on a log scale: thermal inertia of polyurethane foam about 31, softwood 505, oak 569, gypsum plaster 762 and concrete 2,012.|Thermal inertia (square root of conductivity × density × specific heat) of polyurethane foam compared with common building materials. The low value of the foam means that its surface heats up very quickly.]]


Fire retardants help mainly against small exposures. They can be very effective in preventing ignition from low-level, short flame and heat exposures. Under severe exposure, such as a fully developed room fire, treated and untreated plastics typically behave alike.<ref name="BC-6-229" />
Fire retardants help mainly against small exposures. They can be very effective in preventing ignition from low-level, short flame and heat exposures. Under severe exposure, such as a fully developed room fire, treated and untreated plastics typically behave alike.<ref name="BC-6-229" />
Line 49: Line 49:


Red oak needs about 80 s under the same flux, and a polystyrene foam at the low end of its range about 55 s. At 50 kW/m² the times fall to about 2.2 s for the foam and 11 s for red oak.<ref name="TE-3-83" /><ref name="TE-3-87" /><ref name="TE-3-88" /> A polyurethane foam at the top of the range, with a critical heat flux of 40 kW/m², would not ignite at all at 25 kW/m² and would need about 490 s at 50 kW/m². The spread of values within one chemical family is therefore large. The example assumes thermally thick behaviour and ignores the substrate and any facing, so it serves only to compare materials.
Red oak needs about 80 s under the same flux, and a polystyrene foam at the low end of its range about 55 s. At 50 kW/m² the times fall to about 2.2 s for the foam and 11 s for red oak.<ref name="TE-3-83" /><ref name="TE-3-87" /><ref name="TE-3-88" /> A polyurethane foam at the top of the range, with a critical heat flux of 40 kW/m², would not ignite at all at 25 kW/m² and would need about 490 s at 50 kW/m². The spread of values within one chemical family is therefore large. The example assumes thermally thick behaviour and ignores the substrate and any facing, so it serves only to compare materials.
[[File:fse-foam-plastic-insulation-v2.svg|thumb|upright=1.5|alt=Log-scale chart of time to ignition against heat flux: the most ignitable polyurethane foam ignites fastest, then polystyrene foam, then red oak.|Time to ignition of thermally thick materials against external heat flux, from the critical heat flux and thermal response parameter of each material. The foam curves use the most ignitable values of their ranges. Based on Tewarson (2002), pp. 3-83, 3-87 and 3-88.]]
[[File:fse-foam-plastic-insulation-v2.svg|thumb|upright=1.5|alt=Log-scale chart of time to ignition against heat flux: the most ignitable polyurethane foam ignites fastest, then polystyrene foam, then red oak.|Time to ignition of thermally thick materials against external heat flux, from the critical heat flux and thermal response parameter of each material. The foam curves use the most ignitable values of their ranges.]]


== Behaviour in corners and at full scale ==
== Behaviour in corners and at full scale ==
Line 57: Line 57:


Later tests at Underwriters Laboratories compared tunnel results with a 9.1 kg (20 lb) wood crib fire in a full-size corner. This crib gave about the same severity as the 88 kW tunnel burner, with a heat flux of about 11 kW/m².<ref name="BC-6-226" /> Four materials with the same tunnel flame spread classification of 18 behaved very differently in the corner.
Later tests at Underwriters Laboratories compared tunnel results with a 9.1 kg (20 lb) wood crib fire in a full-size corner. This crib gave about the same severity as the 88 kW tunnel burner, with a heat flux of about 11 kW/m².<ref name="BC-6-226" /> Four materials with the same tunnel flame spread classification of 18 behaved very differently in the corner.
[[File:fse-foam-plastic-insulation-v3.svg|thumb|upright=1.5|alt=Bar chart: glass fibre, fibreboard and particleboard affected 24 to 37 % of the corner; polyurethane spray foam 85 % and polystyrene board 76 %.|Share of the wall and ceiling area affected in a full-size corner test with a 9.1 kg wood crib, for materials with low tunnel flame spread ratings (18 for the first four, 3 for the polystyrene board). Based on Benedetti and Colonna (2008), p. 6-226.]]
[[File:fse-foam-plastic-insulation-v3.svg|thumb|upright=1.5|alt=Bar chart: glass fibre, fibreboard and particleboard affected 24 to 37 % of the corner; polyurethane spray foam 85 % and polystyrene board 76 %.|Share of the wall and ceiling area affected in a full-size corner test with a 9.1 kg wood crib, for materials with low tunnel flame spread ratings (18 for the first four, 3 for the polystyrene board).]]


{| class="wikitable"
{| class="wikitable"
Line 72: Line 72:
|}
|}


In a heat release rate calorimeter at 30 kW/m², the first three materials released about 3 kW/m², but the polyurethane spray foam released 25 times as much.<ref name="BC-6-226" /> A 51 mm fire-retardant extruded polystyrene board reached a tunnel flame spread classification of only 3. Its smoke developed classification was 785, however, and 76 % of the wall and ceiling area of the corner was affected.<ref name="BC-6-226" /> FM Global and Underwriters Laboratories also ran large corner tests on cellular plastics. Their corners were up to 7.6 m (25 ft) high, with wing walls up to 15.4 m (50 ft) long, and they also assessed sprinklers and thermal barriers.<ref name="HB-18-29">Hirschler (2008b), p. 18-29.</ref>
In a heat release rate calorimeter at 30 kW/m², the first three materials released about 3 kW/m², but the polyurethane spray foam released 25 times as much.<ref name="BC-6-226" /> A 51 mm fire-retardant extruded polystyrene board reached a tunnel flame spread classification of only 3. Its smoke developed classification was 785, however, and 76 % of the wall and ceiling area of the corner was affected.<ref name="BC-6-226" /> FM Global and Underwriters Laboratories also ran large corner tests on cellular plastics. Their corners were up to 7.6 m (25 ft) high, with wing walls up to 15.2 m (50 ft) long, and they also assessed sprinklers and thermal barriers.<ref name="HB-18-29">Hirschler (2008b), p. 18-29.</ref>


== Fire testing ==
== Fire testing ==
Line 85: Line 85:


The model building codes described in the 2008 handbook require foam used as interior wall insulation to be covered with a thermal barrier, such as 12.7 mm (½ in.) ordinary gypsum board. Foam in masonry cavity walls, around foundations, under slabs on the ground and, under certain conditions, in roofs is generally accepted without a thermal barrier. In all cases the foam must have a smoke developed index of no more than 450 and a flame spread index of no more than 75 in the tunnel test.<ref name="BC-6-229" /> In buildings other than noncombustible or fire-resistive types, foam-cored steel or aluminium exterior panels are permitted if the core has a flame spread index of 25 or less and the building is sprinklered.<ref name="BC-6-229" />
The model building codes described in the 2008 handbook require foam used as interior wall insulation to be covered with a thermal barrier, such as 12.7 mm (½ in.) ordinary gypsum board. Foam in masonry cavity walls, around foundations, under slabs on the ground and, under certain conditions, in roofs is generally accepted without a thermal barrier. In all cases the foam must have a smoke developed index of no more than 450 and a flame spread index of no more than 75 in the tunnel test.<ref name="BC-6-229" /> In buildings other than noncombustible or fire-resistive types, foam-cored steel or aluminium exterior panels are permitted if the core has a flame spread index of 25 or less and the building is sprinklered.<ref name="BC-6-229" />
[[File:fse-foam-plastic-insulation-v4.svg|thumb|upright=1.5|alt=Wall section with foam insulation behind 12.7 mm gypsum board, plus sketches of foam in a masonry cavity, under a slab and in a roof.|Foam plastic used as interior wall insulation behind a thermal barrier of 12.7 mm gypsum board (left), and locations where the model codes described in the 2008 handbook generally accept foam without a thermal barrier (right). Based on Benedetti and Colonna (2008), p. 6-229.]]
[[File:fse-foam-plastic-insulation-v4.svg|thumb|upright=1.5|alt=Wall section with foam insulation behind 12.7 mm gypsum board, plus sketches of foam in a masonry cavity, under a slab and in a roof.|Foam plastic used as interior wall insulation behind a thermal barrier of 12.7 mm gypsum board (left), and locations where the model codes described in the 2008 handbook generally accept foam without a thermal barrier (right).]]


Other parts of the handbook give related rules. For one- and two-family dwellings, building regulations limit foam plastic insulation to a flame spread classification of 75 and require 12.7 mm gypsum board or another thermal barrier.<ref name="SU-19-62">Sumathipala (2008), p. 19-62.</ref> In cold stores, polyurethane and polystyrene insulation should be protected by a thermal barrier or by 12.7 mm of cement plaster on metal lath. For polystyrene, 12.7 mm Type X gypsum board or 19 mm fire-retardant plywood is also mentioned. Burning cork or foam insulation in these buildings can generate temperatures high enough to weaken structural steel.<ref name="JM-20-166" /> Foam plastic interior trim is permitted only in limited amounts, with a density of at least 320 kg/m³ to exclude lightweight foams.<ref name="HB-18-36" />
Other parts of the handbook give related rules. For one- and two-family dwellings, building regulations limit foam plastic insulation to a flame spread classification of 75 and require 12.7 mm gypsum board or another thermal barrier.<ref name="SU-19-62">Sumathipala (2008), p. 19-62.</ref> In cold stores, polyurethane and polystyrene insulation should be protected by a thermal barrier or by 12.7 mm of cement plaster on metal lath. For polystyrene, 12.7 mm Type X gypsum board or 19 mm fire-retardant plywood is also mentioned. Burning cork or foam insulation in these buildings can generate temperatures high enough to weaken structural steel.<ref name="JM-20-166" /> Foam plastic interior trim is permitted only in limited amounts, with a density of at least 320 kg/m³ to exclude lightweight foams.<ref name="HB-18-36" />

Latest revision as of 00:45, 16 November 2026

Foam plastic insulation is thermal insulation made of cellular plastics, also called foamed or expanded plastics, such as rigid polyurethane and polystyrene foam. It is supplied as boards, poured in place or sprayed on, and it combines very low weight with exceptional resistance to heat transfer.[1][2] The same properties make it a severe fire hazard when it is left exposed. Its low resistance to excessive heat and its ease of ignition contrast sharply with its value as an insulator.[2] In a room corner, exposed foam on walls and ceiling can spread fire rapidly from an ignition source as small as a waste basket.[2]

Foam plastic insulation is a standard example of a material that the traditional tunnel test can misjudge. Fire-retardant grades can achieve a low flame spread index in the Steiner tunnel test and still spread flames readily in real fires.[3][1] In the United States, building codes as described in the 2008 Fire Protection Handbook therefore require exposed foam to be covered by a 15-minute thermal barrier, such as gypsum board.[4] The alternative is to show acceptable behaviour in a full-scale room-corner fire test.[5][6] Exposed cellular polyurethane and polystyrene contributed to rapid fire spread in several widely publicised fires, including two nightclub fires in 2003 and 2004.[1]

Materials and forms

Cellular plastics have been in widespread use since the 1960s.[2] Lightweight foam plastics typically have densities of 16 to 48 kg/m³ (1 to 3 lb/ft³).[1] For comparison, Introduction to Fire Safety Engineering lists polyurethane foam with a density of 20 kg/m³ and a thermal conductivity of 0.034 W/(m·K), against 800 kg/m³ and 0.17 W/(m·K) for oak.[7] Foam insulation is installed in walls and ceilings, in cavity walls, under floor slabs, in roofs and in cold stores.[4][8]

Like other plastics, the common foams belong to different polymer classes. In the classification of Benedetti and Colonna (2008), polyurethane and phenolics are thermosets, whereas polystyrene is a thermoplastic.[9] A thermoset, once cured, is substantially infusible and insoluble, while a thermoplastic softens when heated and hardens again when cooled.[9] The difference between thermoplastics and thermosets shows in fire. Thermoplastic articles tend to melt and flow, which can either remove the material from the flame or produce flaming, tar-like drips that start secondary fires.[2]

Polystyrene foam is produced from polystyrene beads that contain pentane, a flammable gas, as a blowing agent.[10] It is used as insulation, as foamed-in-place insulation and as the core of construction panels faced with plywood, plastic or aluminium.[11] Such sandwich panel systems, with a combustible foam core between metal facings, raise their own testing problems.[12] Polyurethane foam, in sheets or foamed in place, and polystyrene foam are two common insulation materials in cold-storage warehouses.[8]

Fire behaviour

Untreated rigid polyurethane foam ignites readily from common ignition sources and burns rapidly.[2] Fire-retardant grades resist localised, temporary ignition sources in most fire environments. Under sustained heat and flame they still burn, but more slowly, and often stop burning when the external flame is removed. Treated and untreated urethane foams both produce dense smoke.[2]

Untreated rigid polystyrene foam also ignites easily and burns vigorously. It produces dense black smoke and a very black, viscous melt that can burn with the intensity of a flammable liquid.[2] Fire-retardant treatment inhibits ignition, and the treated foam tends to shrink away from a fixed heat source without igniting. The heat of combustion of polystyrene, about 42 MJ/kg, is roughly 50 % higher than that of urethane foam, about 28 MJ/kg.[2]

The insulating property itself drives the hazard. A material with a low thermal inertia heats up quickly at its surface, which can lead to fast ignition if it is combustible; lightweight insulation is the typical example.[13] With the property values of Introduction to Fire Safety Engineering, the product of conductivity, density and specific heat is about 950 J²/(m⁴·K²·s) for polyurethane foam. That is roughly 340 times less than for oak, so the foam surface heats up far faster under the same exposure.[7]

Bar chart on a log scale: thermal inertia of polyurethane foam about 31, softwood 505, oak 569, gypsum plaster 762 and concrete 2,012.
Thermal inertia (square root of conductivity × density × specific heat) of polyurethane foam compared with common building materials. The low value of the foam means that its surface heats up very quickly.

Fire retardants help mainly against small exposures. They can be very effective in preventing ignition from low-level, short flame and heat exposures. Under severe exposure, such as a fully developed room fire, treated and untreated plastics typically behave alike.[4]

Smoke and toxic gases add to the hazard. Urethane foams generally obscure visibility within a fraction of a minute, and under flaming exposure the smoke usually appears within 15 seconds.[2] Pre-flashover soot yields quoted in Introduction to Fire Safety Engineering are 0.23 kg/kg for polyurethane and 0.195 kg/kg for expanded polystyrene, against 0.015 kg/kg for wood.[14] Rigid polyurethane foam releases significant hydrogen cyanide even under nonflaming decomposition below about 400 °C. Its toxic potency is then 3 to 8 times that of typical combustion products.[15]

Ignition: worked example

Tewarson (2002) describes the ignitability of a material with two properties measured in bench-scale apparatus. The critical heat flux is the external heat flux at or below which the material cannot generate a combustible mixture. The thermal response parameter expresses its resistance to doing so; the higher both values, the longer the material takes to ignite.[16] For a thermally thick material, the inverse square root of the time to ignition is a linear function of the heat flux above the critical value:[17]

1tig=q˙′'e−CHFTRPwithTRP=ΔTigkρcpπ/4

Symbols
Symbol Description Unit
tig Time to ignition s
q˙′'e External heat flux on the surface kW/m²
CHF Critical heat flux kW/m²
TRP Thermal response parameter kW·s1/2/m²
ΔTig Ignition temperature minus ambient temperature K
k,ρ,cp Thermal conductivity, density and specific heat of the material kW/(m·K), g/m³, kJ/(g·K)

Tewarson's tables give polyurethane foams a critical heat flux of 13 to 40 kW/m² and a thermal response parameter of 55 to 221 kW·s1/2/m². For polystyrene foams the values are 10 to 15 kW/m² and 111 to 317 kW·s1/2/m², and for red oak 10 kW/m² and 134 kW·s1/2/m².[18][19] Average heat fluxes in room-corner tests typically lie between 25 and 50 kW/m².[20] At 25 kW/m², a polyurethane foam at the most ignitable end of the range (13 kW/m², 55 kW·s1/2/m²) ignites after about:

tig=(5525−13)2≈21 s

Red oak needs about 80 s under the same flux, and a polystyrene foam at the low end of its range about 55 s. At 50 kW/m² the times fall to about 2.2 s for the foam and 11 s for red oak.[17][18][19] A polyurethane foam at the top of the range, with a critical heat flux of 40 kW/m², would not ignite at all at 25 kW/m² and would need about 490 s at 50 kW/m². The spread of values within one chemical family is therefore large. The example assumes thermally thick behaviour and ignores the substrate and any facing, so it serves only to compare materials.

Log-scale chart of time to ignition against heat flux: the most ignitable polyurethane foam ignites fastest, then polystyrene foam, then red oak.
Time to ignition of thermally thick materials against external heat flux, from the critical heat flux and thermal response parameter of each material. The foam curves use the most ignitable values of their ranges.

Behaviour in corners and at full scale

Some cellular plastics that resist burning under most exposures behave very differently when their surfaces face each other and exchange radiant heat. The combination of low thermal conductivity, high heat release rate and rapid degradation produces a fast upward flame front in a room corner.[2] When the ceiling is insulated with the same exposed foam, the corner fire spreads rapidly across the underside of the ceiling. This has happened with ignition sources as small as a waste basket fire, and FM Global Research devised a corner test to reproduce the exposure.[2][5]

A 1969 study by Underwriters Laboratories analysed 34 fires in which rigid cellular plastics had been used as building materials. A high rate of flame spread was reported in 8 of 21 fires, especially with sprayed-on polyurethane and rigid polyurethane boards. Tunnel flame spread ratings of some of these materials ranged from 5 to 1,375.[2] Fire behaviour also depended on whether foam covered both walls and ceiling or the walls only.[2]

Later tests at Underwriters Laboratories compared tunnel results with a 9.1 kg (20 lb) wood crib fire in a full-size corner. This crib gave about the same severity as the 88 kW tunnel burner, with a heat flux of about 11 kW/m².[5] Four materials with the same tunnel flame spread classification of 18 behaved very differently in the corner.

Bar chart: glass fibre, fibreboard and particleboard affected 24 to 37 % of the corner; polyurethane spray foam 85 % and polystyrene board 76 %.
Share of the wall and ceiling area affected in a full-size corner test with a 9.1 kg wood crib, for materials with low tunnel flame spread ratings (18 for the first four, 3 for the polystyrene board).
Four materials with the same tunnel flame spread classification of 18 in a full-size corner test (Underwriters Laboratories, as reported by Benedetti and Colonna, 2008)[5]
Material Smoke developed classification Wall and ceiling area affected
89 mm glass fibre blanket insulation 3 24 %
12.7 mm fire-retardant wood fibreboard ceiling panels 4 37 %
12.7 mm fire-retardant wood particleboard 37 25 %
51 mm fire-retardant polyurethane spray foam on asbestos cement board, 35.2 kg/m³ 935 85 %

In a heat release rate calorimeter at 30 kW/m², the first three materials released about 3 kW/m², but the polyurethane spray foam released 25 times as much.[5] A 51 mm fire-retardant extruded polystyrene board reached a tunnel flame spread classification of only 3. Its smoke developed classification was 785, however, and 76 % of the wall and ceiling area of the corner was affected.[5] FM Global and Underwriters Laboratories also ran large corner tests on cellular plastics. Their corners were up to 7.6 m (25 ft) high, with wing walls up to 15.2 m (50 ft) long, and they also assessed sprinklers and thermal barriers.[21]

Fire testing

Building and fire codes identify foam plastic insulation as a material for which the tunnel test protocol is not appropriate.[22] Small-scale tests such as the oxygen index test and UL 94 are now used mainly for product development and production control. Their small ignition sources make them unsuitable for judging behaviour in a room fire.[6] Small "Bunsen burner" tests were once used to call some plastics "self-extinguishing", yet the same materials showed flash burning in real fires.[2]

For exposed foam, the handbook calls for tests representative of actual use. Room-corner tests such as NFPA 265, NFPA 286, ISO 9705 and ASTM E2257 have been used to evaluate foam plastic insulation.[23] All use a gas burner in a corner of a small room, as described in room corner test. ISO 9705 and ASTM E2257 are the most severe, with 100 kW for the first 10 minutes and 300 kW for the next 10 minutes.[23] A room-corner method developed for foam-insulated garage doors is referenced in the 2006 edition of NFPA 5000. It is notable because its heat and smoke release limits are linked to the actual fire hazard.[23]

In New Zealand, the C/VM2 commentary of 2013 places exposed polyurethane foams in Material Group Number 4, the worst class, because they reach flashover within 2 minutes in ISO 9705. Such materials are considered potentially hazardous as room linings and are not acceptable in occupied spaces.[24] Metal-faced sandwich panels with a combustible core pose a particular testing problem. In the European Single Burning Item test, the 31 kW burner flame described by Madrzykowski and Stroup (2008) does not supply enough heat flux to penetrate the metal facing. Such panels have therefore not given the same result as in the ISO 9705 room.[12] For exterior insulation and finish systems containing foam, NFPA 285 uses an intermediate-scale, two-storey test structure to assess vertical and lateral flame propagation.[25]

Regulation and protection

In the United States, NFPA 101 and NFPA 5000 do not allow cellular or foam plastics as interior finish unless actual fire tests substantiate their behaviour for the intended use.[1] The Products Research Committee administered a trust fund set up by makers of cellular plastics. In its final report of 1980, after five years of work, it concluded that building codes appropriately required a 15-minute thermal barrier or an NFPA 286 room-corner test for exposed foam.[5][6] The handbook describes the result as the control of exposed polyurethane and polystyrene by fire-retardant additives combined with thermal barriers installed in the field.[26]

The model building codes described in the 2008 handbook require foam used as interior wall insulation to be covered with a thermal barrier, such as 12.7 mm (½ in.) ordinary gypsum board. Foam in masonry cavity walls, around foundations, under slabs on the ground and, under certain conditions, in roofs is generally accepted without a thermal barrier. In all cases the foam must have a smoke developed index of no more than 450 and a flame spread index of no more than 75 in the tunnel test.[4] In buildings other than noncombustible or fire-resistive types, foam-cored steel or aluminium exterior panels are permitted if the core has a flame spread index of 25 or less and the building is sprinklered.[4]

Wall section with foam insulation behind 12.7 mm gypsum board, plus sketches of foam in a masonry cavity, under a slab and in a roof.
Foam plastic used as interior wall insulation behind a thermal barrier of 12.7 mm gypsum board (left), and locations where the model codes described in the 2008 handbook generally accept foam without a thermal barrier (right).

Other parts of the handbook give related rules. For one- and two-family dwellings, building regulations limit foam plastic insulation to a flame spread classification of 75 and require 12.7 mm gypsum board or another thermal barrier.[27] In cold stores, polyurethane and polystyrene insulation should be protected by a thermal barrier or by 12.7 mm of cement plaster on metal lath. For polystyrene, 12.7 mm Type X gypsum board or 19 mm fire-retardant plywood is also mentioned. Burning cork or foam insulation in these buildings can generate temperatures high enough to weaken structural steel.[8] Foam plastic interior trim is permitted only in limited amounts, with a density of at least 320 kg/m³ to exclude lightweight foams.[1]

Protection by a covering layer is limited in time, and the thermal barrier required by United States codes is a 15-minute barrier.[5] Introduction to Fire Safety Engineering gives a steady-state example of a facade with 150 mm of polyurethane foam between two 65 mm masonry leaves, exposed to a 900 °C fully developed fire. Because the foam provides almost all of the thermal resistance, its warm face would reach about 875 °C once a steady state is established.[13]

Fire incidents

Foam insulation used for sound control or decoration has contributed to some of the deadliest recent fires. The fire at the Station nightclub in West Warwick, Rhode Island, on 20 February 2003 was ignited by indoor pyrotechnics. Foam sound insulation around the stage, which did not limit flame spread and smoke production, is believed to have contributed to its rapid spread.[28] The fire killed 100 people, and a nightclub fire in Buenos Aires on 30 December 2004 killed 193. Inadequate interior finish was the first item ignited in both.[29] In the C/VM2 commentary, the Station nightclub fire is one of three examples of how quickly fire can spread over combustible surface materials.[30]

Limitations and misconceptions

A low flame spread classification, such as 25 or less, does not ensure limited combustibility of exposed foam. Large exposed areas of cellular plastics in interior construction or decoration must be considered extremely hazardous.[31] Exposed foam on ceilings and walls, in air-handling plenums, in shafts, in voids inside walls and above suspended ceilings should be avoided. Automatic sprinklers cannot be assumed to control the hazard, and fire-retardant paint, intumescent or not, is unlikely to give satisfactory results.[4]

Fire retardants do not make foam noncombustible. They improve resistance to small, short exposures, but in a fully developed fire treated and untreated foams behave alike, and fire-retardant chemicals can increase smoke production.[4][2] The heat content of a foam is also a poor guide to its hazard. The potential heat of a plastic is of little significance in fire protection engineering; the rate at which heat is released matters more.[6]

Finally, the hazard depends on the whole system rather than on the foam alone. Each layer of a system may pass a test while the complete system performs much worse.[3] Room-corner and full-scale tests are more indicative of real behaviour than the tunnel test, because they expose the product as installed to a realistic ignition source.[23] The requirements described here are those reported in the 2008 edition of the Fire Protection Handbook and in the 2013 New Zealand commentary; later code editions may differ.

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Hirschler (2008b), p. 18-36.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 Benedetti and Colonna (2008), p. 6-225.
  3. ↑ 3.0 3.1 Hirschler (2008b), p. 18-27.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Benedetti and Colonna (2008), p. 6-229.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Benedetti and Colonna (2008), p. 6-226.
  6. ↑ 6.0 6.1 6.2 6.3 Benedetti and Colonna (2008), p. 6-227.
  7. ↑ 7.0 7.1 Van Rossum (2027), §5.5.
  8. ↑ 8.0 8.1 8.2 J. Moore (2008), p. 20-166.
  9. ↑ 9.0 9.1 Benedetti and Colonna (2008), p. 6-210.
  10. ↑ Benedetti and Colonna (2008), p. 6-221.
  11. ↑ Benedetti and Colonna (2008), p. 6-222.
  12. ↑ 12.0 12.1 Madrzykowski and Stroup (2008), p. 2-40.
  13. ↑ 13.0 13.1 Van Rossum (2027), §5.2.
  14. ↑ Van Rossum (2027), §6.2.
  15. ↑ Purser (2002), p. 2-98.
  16. ↑ Tewarson (2002), p. 3-82.
  17. ↑ 17.0 17.1 Tewarson (2002), p. 3-83.
  18. ↑ 18.0 18.1 Tewarson (2002), p. 3-87.
  19. ↑ 19.0 19.1 Tewarson (2002), p. 3-88.
  20. ↑ Janssens (2002), p. 3-41.
  21. ↑ Hirschler (2008b), p. 18-29.
  22. ↑ Hirschler (2008b), p. 18-25.
  23. ↑ 23.0 23.1 23.2 23.3 Hirschler (2008b), p. 18-32.
  24. ↑ Ministry of Business, Innovation and Employment (2013), p. 21.
  25. ↑ Janssens (2008), p. 2-69.
  26. ↑ Benedetti and Colonna (2008), p. 6-209.
  27. ↑ Sumathipala (2008), p. 19-62.
  28. ↑ Miller and Roether (2008), p. 20-93.
  29. ↑ Hirschler (2008b), p. 18-23.
  30. ↑ Ministry of Business, Innovation and Employment (2013), p. 19.
  31. ↑ Benedetti and Colonna (2008), p. 6-228.

References

  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Janssens, M. (2002). Calorimetry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-38–3-62). National Fire Protection Association; Society of Fire Protection Engineers.
  • Janssens, M. L. (2008). Basics of fire containment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-59–2-74). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Sumathipala, K. (2008). Structural fire safety in one- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-59–19-64). National Fire Protection Association.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.