Line 12: Line 12:
== Role in fire growth ==
== Role in fire growth ==
Fire hazard is related to fire size, and the burning rate, measured as the [[heat release rate]], is the single most important parameter that sets that size.<ref name="HB-18-23" /> Wall and ceiling linings may act like fuses that spread flames to other objects. They also offer a large, unbroken surface for [[Flame spread|flame spread]], and as the burning area grows, so does the heat release rate. A poorly performing finish can release enough energy by itself to create a hot gas layer.<ref name="HB-18-23" />
Fire hazard is related to fire size, and the burning rate, measured as the [[heat release rate]], is the single most important parameter that sets that size.<ref name="HB-18-23" /> Wall and ceiling linings may act like fuses that spread flames to other objects. They also offer a large, unbroken surface for [[Flame spread|flame spread]], and as the burning area grows, so does the heat release rate. A poorly performing finish can release enough energy by itself to create a hot gas layer.<ref name="HB-18-23" />
[[File:fse-interior-finish-v1.svg|thumb|upright=1.5|alt=Two room sections: with a combustible lining, flames run up the wall and along the ceiling; with a noncombustible lining, the fire stays at the first item.|A combustible wall and ceiling lining can act like a fuse: flames spread from the first item up the wall and along the ceiling, and the hot layer heats the rest of the room (left). With a noncombustible lining the fire stays near the first item for longer (right).]]


Hirschler (2008b) describes four ways in which interior finish affects fire hazard. It can speed up the build-up to flashover, extend the fire by flame spread, add fuel and produce smoke and toxic gases.<ref name="HB-18-37">Hirschler (2008b), p. 18-37.</ref> The most desirable finish is dense, noncombustible and a good conductor of heat. It adds no fuel, offers no path for flame spread and produces little or no smoke.<ref name="HB-18-37" />
Hirschler (2008b) describes four ways in which interior finish affects fire hazard. It can speed up the build-up to flashover, extend the fire by flame spread, add fuel and produce smoke and toxic gases.<ref name="HB-18-37">Hirschler (2008b), p. 18-37.</ref> The most desirable finish is dense, noncombustible and a good conductor of heat. It adds no fuel, offers no path for flame spread and produces little or no smoke.<ref name="HB-18-37" />
Line 29: Line 30:


The [[room corner test]] was developed to assess finishes in a realistic room. Laboratories began using corner tests around 1970, with a 2.44 m (8 ft) high corner, a ceiling of the same material and a wood crib for ignition.<ref name="HB-18-29" /> Modern versions use a room of about 2.4 m × 3.7 m × 2.4 m high with a door in one short wall. The material lines three walls, three walls and the ceiling, or the ceiling only.<ref name="HA-6-49">Hirschler (2008a), p. 6-49.</ref> A gas burner stands against the walls in a rear corner, and a hood collects the combustion products to measure heat release by oxygen consumption.<ref name="JA-3-39">Janssens (2002), p. 3-39.</ref><ref name="HB-18-30">Hirschler (2008b), p. 18-30.</ref> ISO 9705 is the European reference scenario for surface linings, and NFPA 286 is a slightly different version of it.<ref name="MS-2-41">Madrzykowski and Stroup (2008), p. 2-41.</ref>
The [[room corner test]] was developed to assess finishes in a realistic room. Laboratories began using corner tests around 1970, with a 2.44 m (8 ft) high corner, a ceiling of the same material and a wood crib for ignition.<ref name="HB-18-29" /> Modern versions use a room of about 2.4 m × 3.7 m × 2.4 m high with a door in one short wall. The material lines three walls, three walls and the ceiling, or the ceiling only.<ref name="HA-6-49">Hirschler (2008a), p. 6-49.</ref> A gas burner stands against the walls in a rear corner, and a hood collects the combustion products to measure heat release by oxygen consumption.<ref name="JA-3-39">Janssens (2002), p. 3-39.</ref><ref name="HB-18-30">Hirschler (2008b), p. 18-30.</ref> ISO 9705 is the European reference scenario for surface linings, and NFPA 286 is a slightly different version of it.<ref name="MS-2-41">Madrzykowski and Stroup (2008), p. 2-41.</ref>
[[File:fse-interior-finish-v2.svg|thumb|upright=1.5|alt=Isometric room 2.4 by 3.7 by 2.4 m with lined walls and ceiling, a gas burner in the rear corner, a door in the short front wall and a hood.|Layout of a room-corner test such as NFPA 286 or ISO 9705: the material lines three walls and the ceiling, a gas burner stands in a rear corner and a hood outside the door collects the smoke to measure heat release.]]


{| class="wikitable"
{| class="wikitable"
Line 42: Line 44:


The 2006 editions of the United States codes set pass criteria for NFPA 286. Flames must not reach the ceiling during the 40 kW exposure, and during the 160 kW exposure they must not reach the outer edges of the specimen. Flashover must not occur, the peak heat release rate must not exceed 800 kW and, for new installations, the total smoke release must not exceed 1,000 m².<ref name="HB-18-31" /> A smoke criterion is needed because 10 of 84 materials in five test series combined low heat release with very high smoke release. The 1,000 m² limit is roughly equivalent to a smoke developed index of 450.<ref name="HB-18-32" />
The 2006 editions of the United States codes set pass criteria for NFPA 286. Flames must not reach the ceiling during the 40 kW exposure, and during the 160 kW exposure they must not reach the outer edges of the specimen. Flashover must not occur, the peak heat release rate must not exceed 800 kW and, for new installations, the total smoke release must not exceed 1,000 m².<ref name="HB-18-31" /> A smoke criterion is needed because 10 of 84 materials in five test series combined low heat release with very high smoke release. The 1,000 m² limit is roughly equivalent to a smoke developed index of 450.<ref name="HB-18-32" />
[[File:fse-interior-finish-v3.svg|thumb|upright=1.5|alt=Step chart of burner output over 20 minutes: NFPA 265 40 then 150 kW, NFPA 286 40 then 160 kW, ISO 9705 100 then 300 kW; dashed 800 kW limit.|Burner heat release programmes of the NFPA 265, NFPA 286 and ISO 9705 room-corner tests, with the NFPA 286 limit of 800 kW peak heat release for the whole room.]]


A survey of 25 materials tested both ways shows how differently the two methods rank products. Five materials with a flame spread index of 200 or less caused flashover in the room-corner test. Fourteen Class A materials released less than 400 kW, but two other Class A materials released more.<ref name="HB-18-31" /> In the European Union, the [[Single Burning Item test]] (EN 13823) exposes two vertical wings, 0.5 m and 1 m wide and 1.5 m high, in a corner to a 30 kW propane burner.<ref name="HA-6-48">Hirschler (2008a), p. 6-48.</ref>
A survey of 25 materials tested both ways shows how differently the two methods rank products. Five materials with a flame spread index of 200 or less caused flashover in the room-corner test. Fourteen Class A materials released less than 400 kW, but two other Class A materials released more.<ref name="HB-18-31" /> In the European Union, the [[Single Burning Item test]] (EN 13823) exposes two vertical wings, 0.5 m and 1 m wide and 1.5 m high, in a corner to a 30 kW propane burner.<ref name="HA-6-48">Hirschler (2008a), p. 6-48.</ref>
Line 136: Line 139:


For a Group 3 lining with a known ISO 9705 result, the growth rate is medium if the time to 1 MW is at least 5 minutes and fast if it is shorter.<ref name="ABCB-B4-50">Australian Building Codes Board (2020a), Data Sheet B4, p. 50.</ref> A generic Group 3 lining is taken as medium in the reference building but as fast in a proposed solution. The data sheets expect this approach to give conservative results for most scenarios.<ref name="ABCB-B4-51" />
For a Group 3 lining with a known ISO 9705 result, the growth rate is medium if the time to 1 MW is at least 5 minutes and fast if it is shorter.<ref name="ABCB-B4-50">Australian Building Codes Board (2020a), Data Sheet B4, p. 50.</ref> A generic Group 3 lining is taken as medium in the reference building but as fast in a proposed solution. The data sheets expect this approach to give conservative results for most scenarios.<ref name="ABCB-B4-51" />
[[File:fse-interior-finish-v4.svg|thumb|upright=1.5|alt=Five parabolic heat release curves from ultra-slow to ultra-fast crossing a 1,055 kW line at 1,228, 600, 300, 150 and 75 s.|Design t-squared fires assigned to wall and ceiling lining groups in the Australian Fire Safety Verification Method, with the times at which they reach 1,055 kW.]]


=== Worked example ===
=== Worked example ===

Latest revision as of 08:25, 8 November 2026

Interior finish is the set of materials that form the exposed interior surfaces of walls, ceilings and floors in a building, such as plaster, gypsum wallboard, wood panelling, wall coverings, acoustic tiles and floor coverings.[1] Outside North America the same materials are usually called interior linings or lining materials.[1] Interior finish matters in fire because combustible wall and ceiling linings can act like a fuse. They carry flames away from the item first ignited, add fuel and raise the heat release rate until the room may reach flashover.[2]

In the United States, interior finish is regulated by NFPA 101, the Life Safety Code, and by NFPA 5000.[1] Both codes classify wall and ceiling finishes by their flame spread index in the Steiner tunnel test or accept them on the basis of a room-corner fire test.[3] Requirements are stricter in exits and corridors and in occupancies whose occupants cannot escape without help.[4] In Europe, New Zealand and Australia, lining classes are linked to the time to flashover in a full-scale room test with a burner in one corner.[5][6][7] The subject has shaped fire testing itself, because several finishes with good tunnel results proved hazardous in real fires and in room tests.[8]

Definition and scope

Most United States codes, including NFPA 101 and NFPA 5000, define interior finish as "the exposed surfaces of walls, ceilings, and floors within buildings".[1] The definition excludes concealed or inaccessible surfaces and furnishings, even when these are fastened in place. Interior wall finish also covers columns and fixed or movable walls and partitions. Typical materials are wood, plaster, wallboard, acoustic tile, wall and ceiling coverings, plastics and insulating materials.[1] Interior floor finish, such as carpet and floor tiles, is treated separately. It is generally a less severe fire problem, because heat and smoke rise.[1]

The boundary with furnishings is not always sharp. Some regulators treat countertops and built-in cabinets as finish, while fixed booth seating in a restaurant is usually not classified as finish.[1] Interior trim, such as mouldings, baseboards, handrails and door frames, is regulated as finish but more leniently when it covers less than 10 % of the aggregate wall and ceiling area. This "10 percent rule" assumes evenly spread trim without the continuity needed for flames to travel.[1] Movable partitions of office work stations also count as finish. In NIST tests, work stations with 1.5 m (5 ft) high textile-covered partitions reached a large fire size within 300 to 600 seconds.[1]

Interior finish is one of the main subjects of reaction to fire testing, together with furnishings and consumer products. Reaction-to-fire tests measure the heat and smoke that a product releases and how fast flame spreads over it. Fire resistance tests, by contrast, assess whether an assembly such as a wall stops a fire from penetrating into the next compartment.[9]

Role in fire growth

Fire hazard is related to fire size, and the burning rate, measured as the heat release rate, is the single most important parameter that sets that size.[2] Wall and ceiling linings may act like fuses that spread flames to other objects. They also offer a large, unbroken surface for flame spread, and as the burning area grows, so does the heat release rate. A poorly performing finish can release enough energy by itself to create a hot gas layer.[2]

Two room sections: with a combustible lining, flames run up the wall and along the ceiling; with a noncombustible lining, the fire stays at the first item.
A combustible wall and ceiling lining can act like a fuse: flames spread from the first item up the wall and along the ceiling, and the hot layer heats the rest of the room (left). With a noncombustible lining the fire stays near the first item for longer (right).

Hirschler (2008b) describes four ways in which interior finish affects fire hazard. It can speed up the build-up to flashover, extend the fire by flame spread, add fuel and produce smoke and toxic gases.[10] The most desirable finish is dense, noncombustible and a good conductor of heat. It adds no fuel, offers no path for flame spread and produces little or no smoke.[10]

Flashover is driven by thermal radiation from the heated ceiling and upper walls back to the room contents. Combustible finish lowers the heat release rate needed for flashover and shortens the time to reach it.[10] Flashover is likely once the upper gas layer reaches about 600 °C, and the more combustible the lining, the smaller the fire needed.[11] Thermal properties matter as well. An insulating finish reduces heat loss to the walls and ceiling and so reduces both the time and the heat release rate needed for flashover.[10] A lightweight insulating material with a low thermal inertia heats up quickly at its surface, which can lead to fast ignition if it is combustible.[12]

Position adds to the effect. On a vertical surface, upward flame spread preheats the material above the burning zone, so that the fire spreads faster.[13] Watts (2008b) names flames reaching the ceiling as the single event that best represents the fire growth hazard of a room. Where combustible finish is present, that hazard is usually comparatively high.[14] In 75 residential sprinkler tests of 1979 and 1980, heat and toxic gases built up particularly fast when the fire started in a corner of the room or near curtains. Combustible and noncombustible finishes gave clearly different results.[15]

Interior finish is rarely the first item ignited. In United States home fires of 1999 to 2002, it was the first item ignited in about 6 % of fires. These fires caused about 9 % of civilian deaths and about 10 % of direct property damage.[10] Two nightclub fires with inadequate finish as the first item ignited show the extreme case: West Warwick, Rhode Island, in 2003 with 100 deaths and Buenos Aires in 2004 with 193 deaths.[2][1] More often, finish becomes involved once a fire has grown. Multiple layers of wall coverings contributed to fire growth in multiple-death fires in a hotel in Cambridge, Ohio, in 1979 and an Atlanta office building in 1989.[10]

Full-scale studies also show the limits of this contribution. Burning furnishings often create lethal conditions in the room of origin before the wall finish is seriously involved.[15] After flashover, however, hot gases leaving the room can ignite combustible finish in adjoining spaces and endanger occupants remote from the fire.[10]

Fire tests for wall and ceiling finish

The traditional United States test is the Steiner tunnel test, standardised as NFPA 255, ASTM E84 and UL 723.[3] A specimen about 7.3 m (24 ft) long forms the tunnel ceiling and is exposed to an 89 kW gas flame for 10 minutes. Flame spread is compared with red oak flooring, assigned 100, and a cement board, assigned 0, and a photometer gives the smoke developed index on the same scale.[3][16]

The tunnel works well for traditional materials that are not very thin and stay in place during the test.[3] It often gives falsely favourable results for materials that melt and drip and for thin films. A high flame spread index, however, almost always indicates mediocre or poor performance.[17] Foam plastic insulation can achieve a low index and still spread flames readily in actual fires.[8] In the 1980s, researchers at the University of California, Berkeley, found that wall coverings with tunnel ratings as low as 15 sometimes caused flashover in room-corner tests.[18]

The room corner test was developed to assess finishes in a realistic room. Laboratories began using corner tests around 1970, with a 2.44 m (8 ft) high corner, a ceiling of the same material and a wood crib for ignition.[18] Modern versions use a room of about 2.4 m × 3.7 m × 2.4 m high with a door in one short wall. The material lines three walls, three walls and the ceiling, or the ceiling only.[19] A gas burner stands against the walls in a rear corner, and a hood collects the combustion products to measure heat release by oxygen consumption.[20][21] ISO 9705 is the European reference scenario for surface linings, and NFPA 286 is a slightly different version of it.[22]

Isometric room 2.4 by 3.7 by 2.4 m with lined walls and ceiling, a gas burner in the rear corner, a door in the short front wall and a hood.
Layout of a room-corner test such as NFPA 286 or ISO 9705: the material lines three walls and the ceiling, a gas burner stands in a rear corner and a hood outside the door collects the smoke to measure heat release.
Room-corner tests for interior finish (as described in the 2008 edition of the Fire Protection Handbook)[17][23][24]
Test Surfaces lined Burner exposure Notes
NFPA 265 Three walls 40 kW for 5 min, then 150 kW for 10 min Flame does not reach the ceiling, so used only for textile and expanded vinyl wall coverings
NFPA 286 Three walls and the ceiling 40 kW for 5 min, then 160 kW for 10 min, burner flush against both walls Flames reach the ceiling and run 457–610 mm (18–24 in.) along it
ISO 9705, ASTM E2257 Walls and ceiling 100 kW for 10 min, then 300 kW for 10 min Most severe of the three

The 2006 editions of the United States codes set pass criteria for NFPA 286. Flames must not reach the ceiling during the 40 kW exposure, and during the 160 kW exposure they must not reach the outer edges of the specimen. Flashover must not occur, the peak heat release rate must not exceed 800 kW and, for new installations, the total smoke release must not exceed 1,000 m².[17] A smoke criterion is needed because 10 of 84 materials in five test series combined low heat release with very high smoke release. The 1,000 m² limit is roughly equivalent to a smoke developed index of 450.[23]

Step chart of burner output over 20 minutes: NFPA 265 40 then 150 kW, NFPA 286 40 then 160 kW, ISO 9705 100 then 300 kW; dashed 800 kW limit.
Burner heat release programmes of the NFPA 265, NFPA 286 and ISO 9705 room-corner tests, with the NFPA 286 limit of 800 kW peak heat release for the whole room.

A survey of 25 materials tested both ways shows how differently the two methods rank products. Five materials with a flame spread index of 200 or less caused flashover in the room-corner test. Fourteen Class A materials released less than 400 kW, but two other Class A materials released more.[17] In the European Union, the Single Burning Item test (EN 13823) exposes two vertical wings, 0.5 m and 1 m wide and 1.5 m high, in a corner to a 30 kW propane burner.[25]

Classification in United States codes

NFPA 101 and NFPA 5000, in their 2006 editions as described by Hirschler (2008b), classify wall and ceiling finish by the tunnel results. Because replicate tunnel tests vary, flame spread indices are usually rounded to the nearest multiple of 5. Differences of 10 to 20 points are unlikely to show in real fires.[8]

Interior wall and ceiling finish classes in NFPA 101 and NFPA 5000 (2006 editions)[8]
Class Flame spread index Smoke developed index
A 0–25 0–450
B 26–75 0–450
C 76–200 0–450

The flame spread limit depends on location because the heat from a spreading flame mainly affects people close to it. Exit enclosures, where escape routes are most restricted, have the strictest limits.[8] Smoke can obscure exit paths far from the fire, so one smoke developed index limit of 450 applies to all classes. That limit stems from research in which tunnel smoke was discharged into a 142 m³ (5,000 ft³) room with exit signs.[8] The two indices are not directly related: one material had a flame spread index of 490 and a smoke developed index of 57, another 44 and 1,387.[8]

The required class also depends on the occupancy. Health care is among the most restrictive, because patients often cannot act for their own safety.[4] Selected rows of the Life Safety Code (2006) table illustrate the pattern.

Selected interior wall and ceiling finish requirements, NFPA 101 (2006)[4]
Occupancy Exits Exit access corridors Other spaces
Assembly, new, more than 300 occupants A A or B A or B
Health care, new A A; B on lower portion of corridor wall A; B in small individual rooms
Hotels and dormitories, new A A or B A, B, or C
One- and two-family dwellings A, B, or C A, B, or C A, B, or C
Industrial A or B A, B, or C A, B, or C

Automatic sprinklers relax these limits. The annex of NFPA 101 allows Class C finish where Class B is required and Class B where Class A is required, except in new detention and correctional occupancies.[4] This trade-off differs from the one in the International Building Code.[18] A material that passes NFPA 286 under the code criteria may be used anywhere in a building.[26]

The codes single out several materials. Very thin coverings under 0.9 mm (1/28 in.), such as single layers of paint, are exempt if they reach Class A on fibre cement board, because they behave like their substrate.[27] Cellular or foam plastics are not allowed as interior finish unless fire tests substantiate their behaviour for the intended use.[28] Foam plastic trim needs a density of at least 320 kg/m³ (20 lb/ft³) and a Class B rating. It may be no more than 12.7 mm (1/2 in.) thick and 102 mm (4 in.) wide.[28]

Floor finish is classified by the critical radiant flux in the flooring radiant panel test. Class I requires at least 4.5 kW/m² (0.45 W/cm²) and Class II at least 2.2 kW/m² (0.22 W/cm²).[27] Other United States regimes set their own limits. The HUD Code for manufactured homes lowered its ceiling limit from a flame spread index of 200 to 75 in 1984.[29] On United States domestic vessels, approved interior finishes need a flame spread of 20 or less and a smoke developed rating of 10 or less.[30]

Classification in other countries

In the European Union, reaction-to-fire classes are tied to expected behaviour in a room. In the concept behind the Euroclass system, as summarised by Hirschler (2008a), Classes A1, A2 and B correspond to no flashover in the ISO 9705 room. Class C corresponds to flashover after 10 minutes, Class D to flashover after 2 to 10 minutes and Class E to flashover before 2 minutes.[5] The actual classification combines the Single Burning Item test with small-flame, noncombustibility and heat of combustion tests in EN 13501-1.[19]

In New Zealand, clause C3.4 of the Building Code, as presented in the C/VM2 commentary of 2013, regulates internal surface linings by Material Group Number. Linings are exposed in ISO 9705 to 100 kW for 10 minutes and then 300 kW for 10 minutes. Flashover is the moment when the heat release rate reaches 1 MW in a 3.6 m × 2.4 m × 2.4 m room.[6]

Material Group Numbers in New Zealand clause C3.4 (C/VM2 commentary, 2013)[6][31]
Group Number Behaviour in ISO 9705 Typical materials
1 No flashover in 20 minutes Plasterboard and similar low-hazard materials
2 No flashover in 10 minutes Many fire-retardant-treated timbers
3 No flashover in 2 minutes Ordinary timber and similar products
4 Flashover within 2 minutes Exposed polyurethane foams; not acceptable in occupied spaces

Wall and ceiling materials in exitways of unsprinklered buildings must meet Group Number 1-S, while Group Number 1 or 2 is accepted with sprinklers.[32] The clause aims to keep fire growth within the design fire of Verification Method C/VM2. The commentary cites the Cocoanut Grove, MGM Grand and Station nightclub fires as examples of rapid spread over combustible surfaces.[6] In Australia, group numbers determined to AS 5637 are used in the same way within the Fire Safety Verification Method.[7]

Use in fire safety engineering

Performance-based designs need a design fire that reflects the linings. The Australian Fire Safety Verification Method data sheets use a reference scenario aligned with ISO 9705. An item in a room corner burns at 100 kW for 10 minutes and then at 300 kW for another 10 minutes, unless the fire spreads to the linings.[7] The group number of the lining then selects a t-squared fire based on the time at which the total heat release rate exceeds 1,000 kW.[7][33] In a t-squared fire the heat release rate grows with the square of the time:

Q˙=αt2⇒t=Q˙/α

Symbols
Symbol Description Unit
Q˙ Heat release rate of the design fire kW
α Fire growth parameter kW/s² (= kJ/s³)
t Time from the start of fire growth s
Design t-squared fires per lining group in the Australian Fire Safety Verification Method data sheets (2020)[33]
Group number Fire description α (kW/s²) Approximate time to 1,055 kW (s)
1 Ultra-slow 0.0007 1,228
2 Slow 0.00293 600
3 (reference building) Medium 0.0117 300
3 (performance solution) Fast 0.047 150
4 Ultra-fast 0.188 75

For a Group 3 lining with a known ISO 9705 result, the growth rate is medium if the time to 1 MW is at least 5 minutes and fast if it is shorter.[34] A generic Group 3 lining is taken as medium in the reference building but as fast in a proposed solution. The data sheets expect this approach to give conservative results for most scenarios.[33]

Five parabolic heat release curves from ultra-slow to ultra-fast crossing a 1,055 kW line at 1,228, 600, 300, 150 and 75 s.
Design t-squared fires assigned to wall and ceiling lining groups in the Australian Fire Safety Verification Method, with the times at which they reach 1,055 kW.

Worked example

The data sheets give a typical case: a performance solution proposes Group 3 linings where the reference building requires Group 2 linings.[35] The reference building uses the slow fire with α = 0.00293 kW/s², and the generic Group 3 proposal uses the fast fire with α = 0.047 kW/s².[33] The time to reach 1,055 kW follows from the equation above:

tGroup 2=1055/0.00293≈600 s,tGroup 3=1055/0.047≈150 s

The proposed linings bring the 1 MW stage forward from about 10 minutes to about 2.5 minutes, about four times sooner. Two minutes after ignition, the reference fire releases about 42 kW and the Group 3 fire about 677 kW. Such a change in group number affects the time to flashover, the time to untenable conditions and the proportion of fully developed fires.[35]

The linings also add to the fire load. The characteristic fire loads in the data sheets exclude linings, so the contribution of Group 2 to 4 linings must be added. Unless otherwise justified, all combustible linings are assumed to be consumed in a fully developed fire.[36] A fire-retardant coating is acceptable as a minor variation only if the coated lining reaches the same or a lower group number for the design life of the building.[37]

Room-corner results can also be predicted from bench-scale data. Combustible finish is harder to treat than free-standing items, because the burning area is hard to predict before flashover.[38] The EUREFIC model predicts the ISO 9705 result from cone calorimeter data. It only covers the standard ISO 9705 room and burner, with the same material on walls and ceiling.[24] Several investigators have predicted room-corner results well with cone data and flame spread equations.[39] Bench-scale data were not yet accepted for regulation in the United States around 2007, but room-corner data can serve as input to fire models.[3][23]

Installation and application effects

NFPA 101 (2006) requires classification on tests that simulate actual installations.[16] Vinyl wall coverings that will be glued to gypsum board, for example, must be tested on gypsum board, because its paper facing and the adhesive affect fire behaviour.[16] A thin finish on a noncombustible substrate may present little hazard, because the substrate absorbs heat. On a combustible backing, both layers may ignite and spread flame much faster than either alone.[10][40]

Thickness and layering matter too. Wood panelling 6.4 mm (1/4 in.) thick or less spreads flame more readily over furring strips with an air space than over a solid substrate.[40] Up to two layers of paint, with a dry film of about 0.18 mm, do not change the fire properties of a surface.[40] Marburger (2008) stresses that finishes are also fuels. One layer of vinyl wall covering adds little, but several layers of wall covering or carpet change the hazard dramatically.[41] Partial delamination is perhaps the worst case, because the loosened material ignites more easily and exposes the substrate.[40]

Location on the wall also counts. Experiments in a 16.76 m long corridor exposed the ceiling and upper walls to about 788 °C (1450 °F). A wall covering with a flame spread index of 90 was safe with a ceiling index of at most 25 when limited to the lower 1.2 m (4 ft).[15] Some Class A ceilings even increased flame spread on the walls, because they insulated better than ceilings with an index of zero.[15]

Limitations and misconceptions

A low flame spread index does not guarantee good behaviour in a real fire. The tunnel compares products under one standard exposure, and its index does not necessarily correlate with fire behaviour.[16] Lightweight materials with low thermal inertia, dripping thermoplastics and multilayer systems deserve suspicion, because each layer may pass while the complete system performs much worse.[8] Noncombustibility alone does not define a safe finish either, as the insulating Class A ceilings in the corridor experiments showed.[15] Polystyrene ceiling tiles can perform acceptably by falling away early, but if they fall too early they may hinder escape.[40]

The room-corner test is closer to real fires, but the codes use it mainly as pass or fail and do not use the measured heat release history for classification.[17] Hirschler (2008b) judges that testing as practised around 2007 was probably adequate to eliminate the poorest performers, while the room-corner test remained underused.[15] The United States requirements in this article reflect the 2006 code editions described in the 2008 handbook. The New Zealand and Australian schemes reflect the 2013 commentary and the 2020 data sheets, and later editions may differ.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Hirschler (2008b), p. 18-24.
  2. ↑ 2.0 2.1 2.2 2.3 Hirschler (2008b), p. 18-23.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Hirschler (2008b), p. 18-25.
  4. ↑ 4.0 4.1 4.2 4.3 Hirschler (2008b), p. 18-28.
  5. ↑ 5.0 5.1 Hirschler (2008a), p. 6-51.
  6. ↑ 6.0 6.1 6.2 6.3 Ministry of Business, Innovation and Employment (2013), p. 19.
  7. ↑ 7.0 7.1 7.2 7.3 Australian Building Codes Board (2020a), Data Sheet B4, p. 48.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 Hirschler (2008b), p. 18-27.
  9. ↑ Hirschler (2008a), p. 6-37.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 10.5 10.6 10.7 Hirschler (2008b), p. 18-37.
  11. ↑ Davoodi (2008), p. 18-4.
  12. ↑ Van Rossum (2027), §5.2.
  13. ↑ Van Rossum (2027), §4.3.
  14. ↑ Watts (2008b), p. 1-164.
  15. ↑ 15.0 15.1 15.2 15.3 15.4 15.5 Hirschler (2008b), p. 18-39.
  16. ↑ 16.0 16.1 16.2 16.3 Hirschler (2008b), p. 18-26.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 Hirschler (2008b), p. 18-31.
  18. ↑ 18.0 18.1 18.2 Hirschler (2008b), p. 18-29.
  19. ↑ 19.0 19.1 Hirschler (2008a), p. 6-49.
  20. ↑ Janssens (2002), p. 3-39.
  21. ↑ Hirschler (2008b), p. 18-30.
  22. ↑ Madrzykowski and Stroup (2008), p. 2-41.
  23. ↑ 23.0 23.1 23.2 Hirschler (2008b), p. 18-32.
  24. ↑ 24.0 24.1 Babrauskas (2002b), p. 3-31.
  25. ↑ Hirschler (2008a), p. 6-48.
  26. ↑ Lathrop (2008a), p. 4-75.
  27. ↑ 27.0 27.1 Hirschler (2008b), p. 18-35.
  28. ↑ 28.0 28.1 Hirschler (2008b), p. 18-36.
  29. ↑ Paoletti (2008), p. 20-68.
  30. ↑ Eberly (2008), p. 21-173.
  31. ↑ Ministry of Business, Innovation and Employment (2013), p. 21.
  32. ↑ Ministry of Business, Innovation and Employment (2013), p. 18.
  33. ↑ 33.0 33.1 33.2 33.3 Australian Building Codes Board (2020a), Data Sheet B4, p. 51.
  34. ↑ Australian Building Codes Board (2020a), Data Sheet B4, p. 50.
  35. ↑ 35.0 35.1 Australian Building Codes Board (2020a), Data Sheet B4, p. 47.
  36. ↑ Australian Building Codes Board (2020a), Data Sheet B4, p. 52.
  37. ↑ Australian Building Codes Board (2020b), p. 84.
  38. ↑ Babrauskas (2002b), p. 3-30.
  39. ↑ Quintiere (2002b), p. 2-254.
  40. ↑ 40.0 40.1 40.2 40.3 40.4 Hirschler (2008b), p. 18-38.
  41. ↑ Marburger (2008), p. 20-107.

References

  • Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
  • Australian Building Codes Board. (2020b). Handbook: Fire Safety Verification Method (Print version 1.1).
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Davoodi, H. (2008). Confinement of fire in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-3–18-21). National Fire Protection Association.
  • Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Janssens, M. (2002). Calorimetry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-38–3-62). National Fire Protection Association; Society of Fire Protection Engineers.
  • Lathrop, J. K. (2008a). Concepts of egress design. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 4-69–4-91). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Marburger, B. L. (2008). Business occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-105–20-113). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Paoletti, K. M. (2008). Manufactured housing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-63–20-71). National Fire Protection Association.
  • Quintiere, J. G. (2002b). Surface flame spread. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-246–2-257). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Watts, J. M., Jr. (2008b). Systems approach to fire-safe building design. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-157–1-170). National Fire Protection Association.