== The ten protection classes ==
== The ten protection classes ==
The FSRS sorts property into class groupings that depend on two conditions: a recognised fire department within reach and a recognised water supply near the property. The table summarises the groupings as described by Granito (2008), who also notes that the 5-mile limit applies in most states, not in all.<ref name="Granito-12-16" />
The FSRS sorts property into class groupings that depend on two conditions: a recognised fire department within reach and a recognised water supply near the property. The table summarises the groupings as described by Granito (2008), who also notes that the 5-mile limit applies in most states, not in all.<ref name="Granito-12-16" />
[[File:fse-public-protection-classification-v2.svg|thumb|upright=1.5|alt=Flowchart from fire station distance and water supply to Class 10, Class 9, Class 8B or Classes 1 to 8|Class groupings of the Public Protection Classification as described in 2008.]]


{| class="wikitable"
{| class="wikitable"
Line 47: Line 48:
== How a community is graded ==
== How a community is graded ==
Each grading survey involves an extensive review of fire department records, field surveys of the city and testing of fire protection equipment and municipal water systems.<ref name="Granito-12-16" /> The public fire suppression part of the schedule has three major items with fixed weights.<ref name="Granito-12-17" />
Each grading survey involves an extensive review of fire department records, field surveys of the city and testing of fire protection equipment and municipal water systems.<ref name="Granito-12-16" /> The public fire suppression part of the schedule has three major items with fixed weights.<ref name="Granito-12-17" />
[[File:fse-public-protection-classification-v1.svg|thumb|upright=1.5|alt=Horizontal stacked bar of 100 percent split into 10 percent alarms, 50 percent fire department and 40 percent water supply|Weight of the three items in a city's FSRS grading.]]


{| class="wikitable"
{| class="wikitable"
Line 62: Line 64:


The fire department item carries half of the grade, so the [[Fire department organisation|organisation and resources of the fire department]] weigh most. The schedule considers a first-alarm assignment to be at least two engine companies and one ladder-service company to all structure fires.<ref name="Granito-12-17" /> ISO checks whether the built-on area of the city has a first-due engine company within 1.5 mi (2.4 km) and a ladder-service company within 2.5 mi (4 km).<ref name="Granito-12-17" /> It also checks pump tests and equipment inventories, and it reviews records of training, of the number of fire fighters who respond to structure fires and of documented prefire planning.<ref name="Granito-12-17" /> According to Tutterow (2008), ISO requires pumpers to meet the general criteria of NFPA 1901, that is, a pump capacity of 750 gpm (2,850 L/min).<ref name="Tutterow-12-267">Tutterow (2008), p. 12-267.</ref>
The fire department item carries half of the grade, so the [[Fire department organisation|organisation and resources of the fire department]] weigh most. The schedule considers a first-alarm assignment to be at least two engine companies and one ladder-service company to all structure fires.<ref name="Granito-12-17" /> ISO checks whether the built-on area of the city has a first-due engine company within 1.5 mi (2.4 km) and a ladder-service company within 2.5 mi (4 km).<ref name="Granito-12-17" /> It also checks pump tests and equipment inventories, and it reviews records of training, of the number of fire fighters who respond to structure fires and of documented prefire planning.<ref name="Granito-12-17" /> According to Tutterow (2008), ISO requires pumpers to meet the general criteria of NFPA 1901, that is, a pump capacity of 750 gpm (2,850 L/min).<ref name="Tutterow-12-267">Tutterow (2008), p. 12-267.</ref>
[[File:fse-public-protection-classification-v3.svg|thumb|upright=1.5|alt=Schematic street plan with an engine station, a ladder station, a building and a hydrant, with the FSRS distance criteria|Distance criteria in the FSRS: first-due engine within 1.5 mi, ladder-service company within 2.5 mi and hydrants counted up to 1,000 ft.]]


For the water supply item, ISO examines whether enough capacity, flow and pressure at 20 psi (138 kPa) residual pressure are available at selected sites. The item covers the supply works, the mains feeding the hydrants, and the installation, maintenance and inspection of hydrants. The supply works and the pipe distribution system together account for 35 % of the entire city grading.<ref name="Granito-12-17" /> The field representative checks that water is available beyond the city's maximum daily consumption and observes fire-flow tests at representative locations. The representative also counts the distribution of each [[Fire hydrant|fire hydrant]] up to 1,000 ft (305 m) from representative categories of property. The size, type, installation and operating condition of the hydrants are considered as well.<ref name="Granito-12-17" />
For the water supply item, ISO examines whether enough capacity, flow and pressure at 20 psi (138 kPa) residual pressure are available at selected sites. The item covers the supply works, the mains feeding the hydrants, and the installation, maintenance and inspection of hydrants. The supply works and the pipe distribution system together account for 35 % of the entire city grading.<ref name="Granito-12-17" /> The field representative checks that water is available beyond the city's maximum daily consumption and observes fire-flow tests at representative locations. The representative also counts the distribution of each [[Fire hydrant|fire hydrant]] up to 1,000 ft (305 m) from representative categories of property. The size, type, installation and operating condition of the hydrants are considered as well.<ref name="Granito-12-17" />
[[File:fse-public-protection-classification-v5.jpg|thumb|upright=1.5|alt=Water flowing from an open fire hydrant during a flow test, with a gauge held in the stream|A fire-flow test at a hydrant; the FSRS field survey observes such tests at representative locations.]]


A city can maximise its credits by preparing for the evaluation, with current maps, inventories, equipment test records and personnel reports ready for the field representative.<ref name="Granito-12-17" /> The completed process gives ratings for each area that are translated into an insurance rate for the community. It also helps to develop "improvement statements" that point to deficiencies in staffing, [[Fire water supply|water supply]], equipment, apparatus, pumping capacity and aerial capacity.<ref name="Jenaway-12-48" />
A city can maximise its credits by preparing for the evaluation, with current maps, inventories, equipment test records and personnel reports ready for the field representative.<ref name="Granito-12-17" /> The completed process gives ratings for each area that are translated into an insurance rate for the community. It also helps to develop "improvement statements" that point to deficiencies in staffing, [[Fire water supply|water supply]], equipment, apparatus, pumping capacity and aerial capacity.<ref name="Jenaway-12-48" />
Line 104: Line 109:
On one side of this building, a class 2 building stands 11 to 30 ft (about 3 to 9 m) away. Its facing wall has unprotected openings and is four storeys high, two storeys above the two-storey subject building. At 60 ft long, the length-height of the exposed portion above the subject wall is 60 × 2 = 120.<ref name="Wenzel-15-27" />
On one side of this building, a class 2 building stands 11 to 30 ft (about 3 to 9 m) away. Its facing wall has unprotected openings and is four storeys high, two storeys above the two-storey subject building. At 60 ft long, the length-height of the exposed portion above the subject wall is 60 × 2 = 120.<ref name="Wenzel-15-27" />


With the subject wall of masonry with openings, Table 15.2.3 of the handbook gives <math>X = 0.16</math>, so the combined exposure and communication factor is 1.16. The table gives <math>X = 0</math> when the exposed wall is no higher than the subject wall.<ref name="Wenzel-15-27" /> The needed fire flow is 2,205 × 0.85 × 1.16 ≈ 2,174 gpm, rounded to 2,250 gpm (8,516 L/min).<ref name="Wenzel-15-25" /><ref name="Wenzel-15-29">Wenzel (2008b), p. 15-29.</ref> This is below 3,500 gpm, so the building falls under Section I and is rated with the class of its community.<ref name="Granito-12-17" />
With a blank masonry facing wall on the subject building, Table 15.2.3 of the handbook gives <math>X = 0.16</math>, so the combined exposure and communication factor is 1.16. The table gives <math>X = 0</math> when the exposed wall is no higher than the subject wall.<ref name="Wenzel-15-27" /> The needed fire flow is 2,205 × 0.85 × 1.16 ≈ 2,174 gpm, rounded to 2,250 gpm (8,516 L/min).<ref name="Wenzel-15-25" /><ref name="Wenzel-15-29">Wenzel (2008b), p. 15-29.</ref> This is below 3,500 gpm, so the building falls under Section I and is rated with the class of its community.<ref name="Granito-12-17" />


The ISO formula has a limited scope. Frank (2008) notes that it rests primarily on the water needed to contain a fully involved structure and to prevent spread to adjacent structures. It is not suitable for finding the manual application rate needed to extinguish a growing fire.<ref name="Frank-17-34">Frank (2008), p. 17-34.</ref> Wenzel adds that the amount of water needed to control a fire in a given property cannot be established in precise terms.<ref name="Wenzel-15-30">Wenzel (2008b), p. 15-30.</ref> For larger facilities, ISO may already have analysed the needed fire flow in detail, which fire departments can use in pre-incident planning.<ref name="Norman-12-305">Norman (2008), p. 12-305.</ref>
The ISO formula has a limited scope. Frank (2008) notes that it rests primarily on the water needed to contain a fully involved structure and to prevent spread to adjacent structures. It is not suitable for finding the manual application rate needed to extinguish a growing fire.<ref name="Frank-17-34">Frank (2008), p. 17-34.</ref> Wenzel adds that the amount of water needed to control a fire in a given property cannot be established in precise terms.<ref name="Wenzel-15-30">Wenzel (2008b), p. 15-30.</ref> For larger facilities, ISO may already have analysed the needed fire flow in detail, which fire departments can use in pre-incident planning.<ref name="Norman-12-305">Norman (2008), p. 12-305.</ref>
Line 112: Line 117:


For specifically rated commercial properties, ISO's SCOPES reviews and correlates construction, occupancy, exposures and private and public fire protection. The public fire protection is represented by the PPC number.<ref name="Granito-12-16" /> This correlation gives a rate relativity for the individual property, to which affiliated companies add their cost of doing business and their profit margins.<ref name="Granito-12-16" /> Watts describes SCOPES as the most commonly used insurance rating schedule in the United States. An occupancy charge is multiplied by a basic building grade, which reflects the fire resistance of walls, floors and roofs. The product is then modified for exposure and for protection such as portable extinguishers and fire alarm systems.<ref name="Watts-5-127" />
For specifically rated commercial properties, ISO's SCOPES reviews and correlates construction, occupancy, exposures and private and public fire protection. The public fire protection is represented by the PPC number.<ref name="Granito-12-16" /> This correlation gives a rate relativity for the individual property, to which affiliated companies add their cost of doing business and their profit margins.<ref name="Granito-12-16" /> Watts describes SCOPES as the most commonly used insurance rating schedule in the United States. An occupancy charge is multiplied by a basic building grade, which reflects the fire resistance of walls, floors and roofs. The product is then modified for exposure and for protection such as portable extinguishers and fire alarm systems.<ref name="Watts-5-127" />
[[File:fse-public-protection-classification-v4.svg|thumb|upright=1.5|alt=Flow diagram from the FSRS survey to the PPC number and from there to class rates and to SCOPES, ending in the fire insurance rate|How the PPC number feeds fire insurance rating.]]


With improved ratings, insurers that subscribe to the ISO system usually lower commercial and residential premiums to reflect the projected decrease in loss severity.<ref name="Granito-12-15" /> Granito stresses that a better class lowers rates and premiums "theoretically", which is generally true for a specifically rated commercial property.<ref name="Granito-12-17" /> Other factors also enter the premium, such as extinguishers, detection and alarm systems, smoke control and, most importantly, automatic sprinklers. The loss costs to insurers in the city or county count as well.<ref name="Granito-12-17" /> Individual companies may also file "rate deviations" from the standard rates with state insurance commissions, based on their own loss experience and reserves.<ref name="Granito-12-17-18">Granito (2008), pp. 12-17–12-18.</ref>
With improved ratings, insurers that subscribe to the ISO system usually lower commercial and residential premiums to reflect the projected decrease in loss severity.<ref name="Granito-12-15" /> Granito stresses that a better class lowers rates and premiums "theoretically", which is generally true for a specifically rated commercial property.<ref name="Granito-12-17" /> Other factors also enter the premium, such as extinguishers, detection and alarm systems, smoke control and, most importantly, automatic sprinklers. The loss costs to insurers in the city or county count as well.<ref name="Granito-12-17" /> Individual companies may also file "rate deviations" from the standard rates with state insurance commissions, based on their own loss experience and reserves.<ref name="Granito-12-17-18">Granito (2008), pp. 12-17–12-18.</ref>

Latest revision as of 00:37, 16 November 2026

The Public Protection Classification (PPC) is a class number from 1 to 10 that the Insurance Services Office (ISO) gives a US community to express the capability of its public fire suppression system. Class 1 stands for an exemplary system and Class 10 for one that does not meet the criteria of ISO's grading schedule, the Fire Suppression Rating Schedule (FSRS).[1][2] The schedule was written to help calculate fire insurance rates, not to judge property loss prevention or life safety.[1] It grades three things: how alarms are received and handled (10 % of the grade), the fire department (50 %) and the water supply (40 %).[3]

Classes 1 to 8 describe protected property, Class 9 semiprotected property and Class 10 unprotected property, mainly according to the distance to a fire station and to a recognised water supply.[2] As described in the 2008 edition of the NFPA Fire Protection Handbook, ISO prepared PPC reports for more than 43,000 fire protection districts, and the schedule was not used outside the United States.[1] Insurers that subscribe to the ISO system usually lower premiums when a community's class improves. In a 2001 survey, most fire chiefs also reported using the number to plan and budget for changes in their fire protection.[1]

Definition and purpose

In the FSRS, the class number expresses a city's "fire suppression potential capability", which ISO derives from a field survey and a quantitative analysis of the findings.[2] In the words of Granito (2008), the FSRS "simply defines different levels of public fire suppression capabilities" that are credited in the fire insurance rates of individual properties.[2] The class number therefore does not set a premium by itself. It is one of several inputs from which an insurance rate is built, as described under fire insurance rating below.

The purpose of the schedule is to aid in the calculation of fire insurance rates; it is not intended for property loss prevention or life safety purposes.[1] It reviews those features of public fire protection that have a significant effect on limiting damage once a fire has occurred.[1][2] The schedule gives credit for the fire protection that exists, instead of a debit for what is not in place.[1] Older schedules calculated deficiencies item by item; the current schedule instead determines a percentage of adequacy for each item.[2]

ISO serves the insurance market with statistical, actuarial, underwriting and claims data and other services. Through its PPC Program, it evaluated municipal fire protection efforts in communities throughout the United States.[4] The rated units are fire protection districts, such as counties, cities, towns, villages and fire districts. A district may run its own fire department or contract with an existing department for fire suppression.[2] Each PPC report rests on a city grading evaluation by one of ISO's regional field representatives, who are trained in the FSRS.[2] ISO typically reviewed a community whenever there was an indication of changes that could lead to a revised class number.[1]

Granito gives two slightly different accounts of where the schedule applied. One passage names 48 states, with Louisiana and Washington using an earlier edition.[1] A later passage says that ISO surveyed in 45 of the 50 states and that Mississippi and Washington State used the 1974 edition. Hawaii, Idaho and Louisiana ran the current edition through state rating organisations, while the District of Columbia and New York City were not graded with the FSRS.[2] Wenzel (2008b) summarises the coverage as all but a few states.[5]

Origins and development

The National Board of Fire Underwriters (NBFU) began fire protection surveys of municipalities as early as 1889 and intensified this work in 1904, after a conflagration in Baltimore, Maryland.[5] Its Grading Schedule for Municipal Fire Protection gave municipalities a guideline to classify their fire defences and physical conditions, and the gradings were used to set base rates for fire insurance.[1] The schedule was continued by the NBFU's successor, the American Insurance Association, and then by ISO.[1] Because the NBFU was not an insurance rating organisation, these earlier schedules were somewhat independent of the rating of individual properties.[2]

For many years, the original NBFU formula served as a guide to the fire flow needed in downtown business districts. It gave the fire flow G in US gallons per minute (gpm) from the population P in thousands only:[5]

G=1020P(1−0.01P)

As an illustration, a town of 10,000 inhabitants (P=10) gives about 3,120 gpm (11,800 L/min). As cities became more decentralised, a formula based on population became a less reliable guide outside the downtown area. In 1948, A. C. Hutson of the NBFU suggested estimating fire flows for the other sections of cities from the type of construction and the area of a building. This approach eventually led to the ISO rating system.[5]

The 1974 edition of the municipal schedule had more categories and items than the schedule in use in 2008, and it was still applied in two states.[1] The 1980 edition brought sweeping changes with a revised FSRS, and further changes followed in 1995, 1998 and 2003.[1] Since the 2003 revisions, a property within 5 road miles (8 km) of a fire station may, under certain circumstances, receive credit for a minimal water supply of 4,000 gal (15,140 L). This applies even where a municipal water system is lacking.[1][6] On the commercial side, ISO introduced the Commercial Fire Rating Schedule from 1975, which was later replaced by the Specific Commercial Property Evaluation Schedule (SCOPES).[2]

The ten protection classes

The FSRS sorts property into class groupings that depend on two conditions: a recognised fire department within reach and a recognised water supply near the property. The table summarises the groupings as described by Granito (2008), who also notes that the 5-mile limit applies in most states, not in all.[2]

Flowchart from fire station distance and water supply to Class 10, Class 9, Class 8B or Classes 1 to 8
Class groupings of the Public Protection Classification as described in 2008.
Public Protection Classification groupings in the FSRS (Granito, 2008, p. 12-16; metric values as printed)
Class Grouping Main conditions
1 to 8 Protected property Recognised fire department with engine company response limited to 5 travel miles (8 km) in most states; recognised water system delivering at least 250 gpm (946 L/min) for 2 hours from each credited hydrant
8B Better than Class 8 apart from water Fire protection delivery system superior to Class 8, but no water supply system able to deliver the FSRS minimum of 250 gpm (946 L/min) for 2 hours
9 Semiprotected property Recognised fire department generally within 5 travel miles (8 km), but the structure is more than 1,000 ft (305 m) from a recognised water supply
10 Unprotected property Generally more than 5 travel miles (8 km) from a recognised fire station, whatever the water supply

In Classes 1 to 8, the minimum supply of 250 gpm (946 L/min) for 2 hours from each credited hydrant also sets the minimum that a recognised water system must deliver.[2] As an illustration, 250 gpm for 2 hours amounts to 30,000 gal, or about 114 m³, per credited hydrant. Within the protected range, the number follows from the quantitative grading of the items described in the next section.[2]

Class 9 covers structures that a recognised fire department can reach but that lie far from a recognised water supply. The FSRS provides a documented method for fire departments to deliver water to fire sites with mobile water tankers, so that such structures can qualify for a protected class.[2] According to Granito, water delivery demonstration projects improved Class 9 districts all the way to Class 4.[2] This matches his wider view that successful rural protection planning comes down to response times and the availability of water.[7]

Class 10 is the unprotected class for structural property. Only a few insurers would write policies for Class 10 property, and where cover was available, the rates were very high compared with other classes.[2] In rural areas, Granito notes, some properties may have to depend entirely on their own private fire protection and on help from forestry agencies or distant fire departments.[6]

How a community is graded

Each grading survey involves an extensive review of fire department records, field surveys of the city and testing of fire protection equipment and municipal water systems.[2] The public fire suppression part of the schedule has three major items with fixed weights.[3]

Horizontal stacked bar of 100 percent split into 10 percent alarms, 50 percent fire department and 40 percent water supply
Weight of the three items in a city's FSRS grading.
Weight of the three items in a city's overall FSRS grading (Granito, 2008, p. 12-17)
FSRS section Item Share of the grading Examples of what ISO examines
400 Receiving and handling fire alarms 10 % Telephone service, incoming lines, operators on duty, dispatch circuits
500 Fire department 50 % Engine and ladder-service companies, their distribution, equipment, training and records
600 Water supply 40 % Supply works, mains, hydrants, fire-flow tests

For the first item, ISO evaluates the alarm and dispatch centre. It looks at the telephone service capability, the number of incoming lines, the listing of emergency numbers in the telephone book and the number of operators on duty at all times.[3] The review also covers the dispatch circuits and the electronic methods used to tell fire fighters where an incident is. ISO uses NFPA 1221, the standard for emergency services communications systems, as a guide.[3]

The fire department item carries half of the grade, so the organisation and resources of the fire department weigh most. The schedule considers a first-alarm assignment to be at least two engine companies and one ladder-service company to all structure fires.[3] ISO checks whether the built-on area of the city has a first-due engine company within 1.5 mi (2.4 km) and a ladder-service company within 2.5 mi (4 km).[3] It also checks pump tests and equipment inventories, and it reviews records of training, of the number of fire fighters who respond to structure fires and of documented prefire planning.[3] According to Tutterow (2008), ISO requires pumpers to meet the general criteria of NFPA 1901, that is, a pump capacity of 750 gpm (2,850 L/min).[8]

Schematic street plan with an engine station, a ladder station, a building and a hydrant, with the FSRS distance criteria
Distance criteria in the FSRS: first-due engine within 1.5 mi, ladder-service company within 2.5 mi and hydrants counted up to 1,000 ft.

For the water supply item, ISO examines whether enough capacity, flow and pressure at 20 psi (138 kPa) residual pressure are available at selected sites. The item covers the supply works, the mains feeding the hydrants, and the installation, maintenance and inspection of hydrants. The supply works and the pipe distribution system together account for 35 % of the entire city grading.[3] The field representative checks that water is available beyond the city's maximum daily consumption and observes fire-flow tests at representative locations. The representative also counts the distribution of each fire hydrant up to 1,000 ft (305 m) from representative categories of property. The size, type, installation and operating condition of the hydrants are considered as well.[3]

Water flowing from an open fire hydrant during a flow test, with a gauge held in the stream
A fire-flow test at a hydrant; the FSRS field survey observes such tests at representative locations.

A city can maximise its credits by preparing for the evaluation, with current maps, inventories, equipment test records and personnel reports ready for the field representative.[3] The completed process gives ratings for each area that are translated into an insurance rate for the community. It also helps to develop "improvement statements" that point to deficiencies in staffing, water supply, equipment, apparatus, pumping capacity and aerial capacity.[4]

Needed fire flow and the two sections of the schedule

The FSRS has two major sections. Section I gives the class for all class-rated properties and for specifically rated properties in a city with a needed fire flow of 3,500 gpm (13,248 L/min) or less.[1][3] Section II covers specifically rated properties with a larger needed fire flow, which are evaluated individually.[1][3] Both the AWWA (American Water Works Association) and ISO suggest 3,500 gpm as the upper limit for general public protection. Large facilities or severe hazards needing up to 12,000 gpm (45,420 L/min) should be analysed individually.[9]

Wenzel (2008b) calls the method in the FSRS probably the most widely recommended way to estimate fire flow for a specific structure. It was designed for insurance rating, and its results are generally considered a good estimate.[10] For a building with one set of factors, the method multiplies construction, occupancy, and exposure and communication factors. The construction factor grows with effective floor area and depends on construction class. The last factor accounts for neighbouring buildings and for passageways through which fire can travel between buildings:[10][11]

NFF=CO(X+P)

C=18FA

(X+P)=1+∑i=1n(Xi+Pi)≤1.75

Symbol Description Unit
NFF Needed fire flow gpm
C Construction factor, at least 500 gpm and at most 8,000 gpm (construction classes 1 and 2) or 6,000 gpm (classes 3 to 6 and any one-storey building) gpm
F Construction coefficient: 1.5 frame, 1.0 joisted masonry, 0.8 noncombustible or masonry noncombustible, 0.6 modified fire resistive or fire resistive –
A Effective building area: the largest floor plus, for construction classes 1 to 4, 50 % of all other floors ft²
O Occupancy factor: 0.75 (C-1, noncombustible), 0.85 (C-2, limited combustible), 1.00 (C-3, combustible), 1.15 (C-4, free burning), 1.25 (C-5, rapid burning) –
Xi Exposure factor for side i, from separation distance, the facing walls and the length-height of the exposed wall –
Pi Communication factor for side i, for passageways to other buildings; 0 without openings –
n Number of sides of the subject building –

The formula uses US units; 1 gpm is 3.785 L/min and 1 ft² is 0.0929 m².[11][12] The result is rounded to the nearest 250 gpm below 2,500 gpm and to the nearest 500 gpm above. A wood roof adds 500 gpm, and the needed fire flow is kept between 500 and 12,000 gpm. Habitational buildings use the calculated value up to a maximum of 3,500 gpm.[11]

As a worked example, constructed here as an illustration, consider a two-storey office building of joisted masonry (F=1.0) with floors of 10,000 ft² (929 m²). The effective area is 10,000 + 0.5 × 10,000 = 15,000 ft² (1,394 m²), so C=18×1.0×15,000≈2,205 gpm.[11] Offices are occupancy class C-2, so O=0.85.[12]

On one side of this building, a class 2 building stands 11 to 30 ft (about 3 to 9 m) away. Its facing wall has unprotected openings and is four storeys high, two storeys above the two-storey subject building. At 60 ft long, the length-height of the exposed portion above the subject wall is 60 × 2 = 120.[9]

With a blank masonry facing wall on the subject building, Table 15.2.3 of the handbook gives X=0.16, so the combined exposure and communication factor is 1.16. The table gives X=0 when the exposed wall is no higher than the subject wall.[9] The needed fire flow is 2,205 × 0.85 × 1.16 ≈ 2,174 gpm, rounded to 2,250 gpm (8,516 L/min).[11][13] This is below 3,500 gpm, so the building falls under Section I and is rated with the class of its community.[3]

The ISO formula has a limited scope. Frank (2008) notes that it rests primarily on the water needed to contain a fully involved structure and to prevent spread to adjacent structures. It is not suitable for finding the manual application rate needed to extinguish a growing fire.[14] Wenzel adds that the amount of water needed to control a fire in a given property cannot be established in precise terms.[15] For larger facilities, ISO may already have analysed the needed fire flow in detail, which fire departments can use in pre-incident planning.[16]

Role in fire insurance rating

Watts (2002) explains that fire insurance rates are promulgated as class rates and specific rates. Class rates apply to all properties in a category, and dwellings are the most common example. Specific rates come from a schedule that measures the relative quantity of fire hazard, a process called schedule rating that is typically used for institutions, manufacturing properties and businesses.[17] According to Granito, the PPC number is a rate variable for most class-related properties, in addition to construction and occupancy.[2]

For specifically rated commercial properties, ISO's SCOPES reviews and correlates construction, occupancy, exposures and private and public fire protection. The public fire protection is represented by the PPC number.[2] This correlation gives a rate relativity for the individual property, to which affiliated companies add their cost of doing business and their profit margins.[2] Watts describes SCOPES as the most commonly used insurance rating schedule in the United States. An occupancy charge is multiplied by a basic building grade, which reflects the fire resistance of walls, floors and roofs. The product is then modified for exposure and for protection such as portable extinguishers and fire alarm systems.[17]

Flow diagram from the FSRS survey to the PPC number and from there to class rates and to SCOPES, ending in the fire insurance rate
How the PPC number feeds fire insurance rating.

With improved ratings, insurers that subscribe to the ISO system usually lower commercial and residential premiums to reflect the projected decrease in loss severity.[1] Granito stresses that a better class lowers rates and premiums "theoretically", which is generally true for a specifically rated commercial property.[3] Other factors also enter the premium, such as extinguishers, detection and alarm systems, smoke control and, most importantly, automatic sprinklers. The loss costs to insurers in the city or county count as well.[3] Individual companies may also file "rate deviations" from the standard rates with state insurance commissions, based on their own loss experience and reserves.[18]

Use in community fire protection planning

Although the schedule was built for insurers, fire departments also used it as a yardstick. In a January 2001 survey of 502 US fire chiefs and fire department officials, 92 % said that their PPC number directly reflected the improvements made in their community.[1] They named saving lives and property (90 %), saving money on fire insurance (67 %) and planning and budgeting for changes in fire protection (61 %) as important local uses.[1] ISO's Community Outreach Program also collected information on essential fire protection features, which Granito expected to give benchmarking data for communities.[1]

Granito places the PPC among several ways of judging public fire protection, which had long been applied with inconsistent methods and criteria.[1] Judgements about the adequacy of local prevention and emergency response can be made by local authorities, ISO representatives, fire department accreditation teams or other experts. Fire insurance premiums for homes and commercial property most often reflect periodic assessments of local fire protection.[19] Granito also notes that the fire department accreditation programme is entirely voluntary.[1]

Jenaway (2008) lists ISO among the information sources for a fire department's needs assessment. The FSRS shows which hydrants were tested and compares the water needed with the water available, which indicates a surplus or a need at specific locations.[20][4] ISO's individual property sprinkler reports show whether a sprinkler system suits its hazard and has enough water.[4] Jenaway also notes that a department's existing deployment may have originated from ISO requirements, community growth or other causes.[20]

The PPC touches two parts of the total cost of fire to a community, which Granito defines as fire loss plus prevention, suppression and fire insurance costs.[1] For the United States in 1997, Ramachandran (2002b) gives $19.4 billion for career fire departments and $7.0 billion for net fire insurance. The second item means the administrative costs of fire insurance, including profits. Both belong to a core total of $68.2 billion, not adjusted for inflation.[21]

Limitations and interpretation

The PPC measures suppression capability for insurance purposes, not the overall fire safety of a community. Granito states that the schedule is not for property loss prevention or life safety purposes.[1] In his view, community fire protection must also include locally adopted codes, built-in protection, inspection programmes and public education. A fire department's suppression capability can never fully compensate for missing built-in protection.[22][23] The 2001 survey quoted above reflects the views of fire officials themselves.[1]

The link between class and premium is also loose. It holds "theoretically", depends on many other rating factors and can be changed by an insurer's own rate deviations.[3][18] The 5-mile limit on engine company response applies "in most states" rather than everywhere, and the editions in use differed between states.[2] Granito also warns, in general, that benchmarking between communities requires cautious application. The number of site-specific variables may be so high that comparisons prove confusing.[23]

All values and practices in this article describe the schedule as reported in the 2008 handbook, with FSRS editions up to 2003 and a survey from 2001.[1] The schedule is a US insurance instrument, and Granito notes that it was not used in other nations.[1] The reference work on the schedule cited in the handbook is the Fire Suppression Rating Schedule Handbook by Hickey, published by the Society of Fire Protection Engineers in 2002.[24]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 1.25 1.26 Granito (2008), p. 12-15.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 Granito (2008), p. 12-16.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 Granito (2008), p. 12-17.
  4. ↑ 4.0 4.1 4.2 4.3 Jenaway (2008), p. 12-48.
  5. ↑ 5.0 5.1 5.2 5.3 Wenzel (2008b), p. 15-32.
  6. ↑ 6.0 6.1 Granito (2008), p. 12-9.
  7. ↑ Granito (2008), p. 12-10.
  8. ↑ Tutterow (2008), p. 12-267.
  9. ↑ 9.0 9.1 9.2 Wenzel (2008b), p. 15-27.
  10. ↑ 10.0 10.1 Wenzel (2008b), p. 15-24.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 Wenzel (2008b), p. 15-25.
  12. ↑ 12.0 12.1 Wenzel (2008b), p. 15-26.
  13. ↑ Wenzel (2008b), p. 15-29.
  14. ↑ Frank (2008), p. 17-34.
  15. ↑ Wenzel (2008b), p. 15-30.
  16. ↑ Norman (2008), p. 12-305.
  17. ↑ 17.0 17.1 Watts (2002), p. 5-127.
  18. ↑ 18.0 18.1 Granito (2008), pp. 12-17–12-18.
  19. ↑ Granito (2008), p. 12-21.
  20. ↑ 20.0 20.1 Jenaway (2008), p. 12-47.
  21. ↑ Ramachandran (2002b), p. 5-80.
  22. ↑ Granito (2008), p. 12-5.
  23. ↑ 23.0 23.1 Granito (2008), p. 12-7.
  24. ↑ Granito (2008), p. 12-22.

References

  • Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
  • Granito, J. A. (2008). Planning for public fire-rescue protection. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-3–12-22). National Fire Protection Association.
  • Jenaway, W. F. (2008). Needs assessment and hazard analysis. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-41–12-50). National Fire Protection Association.
  • Norman, J. (2008). Pre-Incident planning for emergency response. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-299–12-308). National Fire Protection Association.
  • Ramachandran, G. (2002b). Measuring fire consequences in economic terms (J. R. Hall Jr., Rev.). In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-79–5-92). National Fire Protection Association; Society of Fire Protection Engineers.
  • Tutterow, R. (2008). Fire department apparatus and equipment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-267–12-287). National Fire Protection Association.
  • Watts, J. M., Jr. (2002). Fire risk indexing. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-125–5-142). National Fire Protection Association; Society of Fire Protection Engineers.
  • Wenzel, L. J. (2008b). Water supply requirements for public supply systems. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 15-23–15-33). National Fire Protection Association.