A '''stadium and arena''' is a large assembly venue in which seating, standing areas and connected circulation routes accommodate spectators. Its fire-safety assessment combines the audience arrangement with construction, smoke conditions and operation. The SFPE Handbook treats movement through rows, aisles, stairs and doors as a connected system with changing demand and capacity.<ref name="NM-3-367–3-372">Nelson and Mowrer (2002), pp. 3-367–3-372.</ref> | A '''stadium and arena''' is a large assembly venue in which seating, standing areas and connected circulation routes accommodate spectators. Its fire-safety assessment combines the audience arrangement with construction, smoke conditions and operation. The Society of Fire Protection Engineers (SFPE) Handbook treats movement through rows, aisles, stairs and doors as a connected system with changing demand and capacity.<ref name="NM-3-367–3-372">Nelson and Mowrer (2002), pp. 3-367–3-372.</ref> | ||
The NFPA Fire Protection Handbook gives particular attention to seating clearances, smoke protection, combustible grandstands and material beneath the seating. A large open volume can provide space above occupants for smoke accumulation. That benefit depends on the geometry and fire scenario and does not establish that every route remains usable.<ref name="NFPA-§20.9,pp.20-88–20-89;§20.20,p.20-223">Cote et al. (2008), §20.9, pp. 20-88–20-89; §20.20, p. 20-223.</ref> | The National Fire Protection Association (NFPA) Fire Protection Handbook gives particular attention to seating clearances, smoke protection, combustible grandstands and material beneath the seating. A large open volume can provide space above occupants for smoke accumulation. That benefit depends on the geometry and fire scenario and does not establish that every route remains usable.<ref name="NFPA-§20.9,pp.20-88–20-89;§20.20,p.20-223">Cote et al. (2008), §20.9, pp. 20-88–20-89; §20.20, p. 20-223.</ref> | ||
[[Assembly occupancy]] provides the occupancy context, while [[Crowd management|crowd management]] addresses the distribution and movement of people throughout the event. The [[Occupant load|occupant load]] is one input to this assessment. Local concentrations and changing layouts also require attention, particularly when the venue hosts several kinds of event.<ref name="NFPA-§20.9,pp.20-88–20-89;§4.4,pp.4-101–4-102">Cote et al. (2008), §20.9, pp. 20-88–20-89; §4.4, pp. 4-101–4-102.</ref> | [[Assembly occupancy]] provides the occupancy context, while [[Crowd management|crowd management]] addresses the distribution and movement of people throughout the event. The [[Occupant load|occupant load]] is one input to this assessment. Local concentrations and changing layouts also require attention, particularly when the venue hosts several kinds of event.<ref name="NFPA-§20.9,pp.20-88–20-89;§4.4,pp.4-101–4-102">Cote et al. (2008), §20.9, pp. 20-88–20-89; §4.4, pp. 4-101–4-102.</ref> | ||
| Line 8: | Line 8: | ||
Fixed seating organises the audience into rows, but each person must still reach an aisle and a usable exit. The NFPA handbook connects row clearances, aisle dimensions and travel distance. The complete route may include stepped aisles, concourses and stairs; a satisfactory dimension at the final door does not resolve a restriction between the seat and that door.<ref name="NFPA-§20.9,pp.20-88–20-89">Cote et al. (2008), §20.9, pp. 20-88–20-89.</ref> | Fixed seating organises the audience into rows, but each person must still reach an aisle and a usable exit. The NFPA handbook connects row clearances, aisle dimensions and travel distance. The complete route may include stepped aisles, concourses and stairs; a satisfactory dimension at the final door does not resolve a restriction between the seat and that door.<ref name="NFPA-§20.9,pp.20-88–20-89">Cote et al. (2008), §20.9, pp. 20-88–20-89.</ref> | ||
[[File:fse-stadium-and-arena-v1.svg|thumb|upright=1.5|alt=Stadium and arena: seating, stands and the connected escape routes, showing the relationships described in the text.|Seating, stands and the connected escape routes in the assessment of Stadium and arena.]] | |||
[[Effective width]] belongs to the particular movement model used for those route elements. Nelson and Mowrer distinguish physical clear width from model boundary allowances. Geometry and the selected flow coefficient should remain consistent; a wide concourse cannot be represented as equivalent to every stair, doorway or seating passage connected to it.<ref name="NM-3-368–3-372">Nelson and Mowrer (2002), pp. 3-368–3-372.</ref> | [[Effective width]] belongs to the particular movement model used for those route elements. Nelson and Mowrer distinguish physical clear width from model boundary allowances. Geometry and the selected flow coefficient should remain consistent; a wide concourse cannot be represented as equivalent to every stair, doorway or seating passage connected to it.<ref name="NM-3-368–3-372">Nelson and Mowrer (2002), pp. 3-368–3-372.</ref> | ||
| Line 20: | Line 21: | ||
[[Smoke control]] can protect the audience and escape paths in an enclosed arena. The NFPA handbook describes engineered systems and the use of a large volume to keep smoke above occupied levels during the relevant period. Smoke-protected seating is a performance condition within the cited code framework. It is not established solely by the height of the roof.<ref name="NFPA-§20.9,pp.20-88–20-89" /><ref name="Milke-4-292–4-295">Milke (2002), pp. 4-292–4-295.</ref> | [[Smoke control]] can protect the audience and escape paths in an enclosed arena. The NFPA handbook describes engineered systems and the use of a large volume to keep smoke above occupied levels during the relevant period. Smoke-protected seating is a performance condition within the cited code framework. It is not established solely by the height of the roof.<ref name="NFPA-§20.9,pp.20-88–20-89" /><ref name="Milke-4-292–4-295">Milke (2002), pp. 4-292–4-295.</ref> | ||
[[File:fse-stadium-and-arena-v2.svg|thumb|upright=1.5|alt=Stadium and arena: smoke protection and changing event conditions, showing the relationships described in the text.|Smoke protection and changing event conditions in the assessment of Stadium and arena.]] | |||
The fire location affects how smoke reaches the audience volume. A fire beneath a stand or within an adjoining area can follow a different path from a fire on the main floor. Milke's SFPE treatment distinguishes direct and communicating-space plumes. The analysis should retain these physical differences rather than apply one plume arrangement to every location.<ref name="Milke-4-299–4-302">Milke (2002), pp. 4-299–4-302.</ref><ref name="NFPA-§20.9,p.20-89;§20.20,p.20-223">Cote et al. (2008), §20.9, p. 20-89; §20.20, p. 20-223.</ref> | The fire location affects how smoke reaches the audience volume. A fire beneath a stand or within an adjoining area can follow a different path from a fire on the main floor. Milke's SFPE treatment distinguishes direct and communicating-space plumes. The analysis should retain these physical differences rather than apply one plume arrangement to every location.<ref name="Milke-4-299–4-302">Milke (2002), pp. 4-299–4-302.</ref><ref name="NFPA-§20.9,p.20-89;§20.20,p.20-223">Cote et al. (2008), §20.9, p. 20-89; §20.20, p. 20-223.</ref> | ||
| Line 31: | Line 33: | ||
== Maximum specific flow and route type == | == Maximum specific flow and route type == | ||
For | For Nelson and Mowrer's quadratic specific-flow expression, the maximum occurs at a density of one divided by twice the density coefficient. Substituting 0.266 gives approximately 1.88 persons/m². Nelson and Mowrer round the corresponding location to 1.9 persons/m²; their tabulated maximum for level routes is approximately 1.3 persons/(s·m).<ref name="specificflow_NM-371">Nelson and Mowrer (2002), p. 3-371, equations 4–8 and Table 3-14.5.</ref> | ||
The maximum is a feature of the particular speed–density curve. It is not the highest density that the route can contain. Nor does it mean that everybody moves fastest at that density; people move faster at lower densities, but fewer people are available to pass each metre of width.<ref name="specificflow_NM-370">Nelson and Mowrer (2002), pp. 3-370–3-371.</ref><ref name="specificflow_NM-371" /> | The maximum is a feature of the particular speed–density curve. It is not the highest density that the route can contain. Nor does it mean that everybody moves fastest at that density; people move faster at lower densities, but fewer people are available to pass each metre of width.<ref name="specificflow_NM-370">Nelson and Mowrer (2002), pp. 3-370–3-371.</ref><ref name="specificflow_NM-371" /> | ||
| Line 41: | Line 43: | ||
The same curve can associate a particular submaximum flow with two different densities; one state has fewer people moving faster; the other has more people moving slowly. A flow count alone therefore does not identify the crowd's density or speed. Additional information is needed to distinguish the two possible states.<ref name="specificflow_NM-371" /> | The same curve can associate a particular submaximum flow with two different densities; one state has fewer people moving faster; the other has more people moving slowly. A flow count alone therefore does not identify the crowd's density or speed. Additional information is needed to distinguish the two possible states.<ref name="specificflow_NM-371" /> | ||
The rounded density limits should also be interpreted with the equation. With the | The rounded density limits should also be interpreted with the equation. With the density coefficient of 0.266, the expression's algebraic zero occurs at approximately 3.76 persons/m²; this corresponds to the chapter's rounded upper limit near 3.8 persons/m². The negative values obtained by continuing the expression beyond that point have no physical meaning in this movement model.<ref name="specificflow_NM-370" /> | ||
== Transitions, queues and changing conditions == | == Transitions, queues and changing conditions == | ||
| Line 92: | Line 94: | ||
Evaluation should begin with the number and distribution of occupants. Different groups may start in different spaces and need different levels of assistance. Their routes should be traced separately where those differences affect preparation, travel or the place of safety.<ref name="meansofescap_Proulx-3-350" /> | Evaluation should begin with the number and distribution of occupants. Different groups may start in different spaces and need different levels of assistance. Their routes should be traced separately where those differences affect preparation, travel or the place of safety.<ref name="meansofescap_Proulx-3-350" /> | ||
[[File:fse-stadium-and-arena-v3.svg|thumb|upright=1.5|alt=Stadium and arena: engineering evaluation, showing the relationships described in the text.|Engineering evaluation in the assessment of Stadium and arena.]] | |||
Each proposed route should be checked as a continuous chain. The review includes the initial room, successive passages, doors, protected elements and final destination. A nominal exit on the plan does not establish that every part of that chain remains available during a fire.<ref name="meansofescap_CVM2-37">Ministry of Business, Innovation and Employment (2025), p. 37.</ref> | Each proposed route should be checked as a continuous chain. The review includes the initial room, successive passages, doors, protected elements and final destination. A nominal exit on the plan does not establish that every part of that chain remains available during a fire.<ref name="meansofescap_CVM2-37">Ministry of Business, Innovation and Employment (2025), p. 37.</ref> | ||
| Line 104: | Line 107: | ||
Evidence from drills can reveal how the route and procedures operate together. Queue locations, unclear signs, door operation and staff directions can be observed in the actual layout. The drill's warning and population conditions must accompany any comparison with a fire scenario.<ref name="meansofescap_Proulx-3-349">Proulx (2002), pp. 3-348–3-350.</ref> | Evidence from drills can reveal how the route and procedures operate together. Queue locations, unclear signs, door operation and staff directions can be observed in the actual layout. The drill's warning and population conditions must accompany any comparison with a fire scenario.<ref name="meansofescap_Proulx-3-349">Proulx (2002), pp. 3-348–3-350.</ref> | ||
== Notes == | == Notes == | ||
Latest revision as of 00:50, 16 November 2026
A stadium and arena is a large assembly venue in which seating, standing areas and connected circulation routes accommodate spectators. Its fire-safety assessment combines the audience arrangement with construction, smoke conditions and operation. The Society of Fire Protection Engineers (SFPE) Handbook treats movement through rows, aisles, stairs and doors as a connected system with changing demand and capacity.[1]
The National Fire Protection Association (NFPA) Fire Protection Handbook gives particular attention to seating clearances, smoke protection, combustible grandstands and material beneath the seating. A large open volume can provide space above occupants for smoke accumulation. That benefit depends on the geometry and fire scenario and does not establish that every route remains usable.[2]
Assembly occupancy provides the occupancy context, while crowd management addresses the distribution and movement of people throughout the event. The occupant load is one input to this assessment. Local concentrations and changing layouts also require attention, particularly when the venue hosts several kinds of event.[3]
Seating, stands and the connected escape routes
Fixed seating organises the audience into rows, but each person must still reach an aisle and a usable exit. The NFPA handbook connects row clearances, aisle dimensions and travel distance. The complete route may include stepped aisles, concourses and stairs; a satisfactory dimension at the final door does not resolve a restriction between the seat and that door.[4]
Effective width belongs to the particular movement model used for those route elements. Nelson and Mowrer distinguish physical clear width from model boundary allowances. Geometry and the selected flow coefficient should remain consistent; a wide concourse cannot be represented as equivalent to every stair, doorway or seating passage connected to it.[5]
Loose seating can change position during use. The NFPA handbook discusses arranging and connecting chairs so that the intended aisles remain clear. The operating layout therefore matters alongside the approved drawing; an event with temporary chairs should be assessed in that configuration, including the routes from all seating blocks.[6]
Standing audiences create another distribution. The handbook describes festival seating as accommodation without conventional seats and identifies the potential for high local density. Demand can also develop before the performance as people seek preferred positions. Crowd crush prevention consequently includes arrival, circulation and departure as well as a fire alarm response.[7]
Grandstands need structural capacity for their intended loads and reliable guardrails; the NFPA special-structures chapter also addresses combustible construction and separation of large combustible stands. The structural and escape functions are connected: people depend on the seating structure and its routes while leaving. The classification should describe the actual construction rather than the venue's name alone.[8]
Smoke protection and changing event conditions
Smoke control can protect the audience and escape paths in an enclosed arena. The NFPA handbook describes engineered systems and the use of a large volume to keep smoke above occupied levels during the relevant period. Smoke-protected seating is a performance condition within the cited code framework. It is not established solely by the height of the roof.[4][9]
The fire location affects how smoke reaches the audience volume. A fire beneath a stand or within an adjoining area can follow a different path from a fire on the main floor. Milke's SFPE treatment distinguishes direct and communicating-space plumes. The analysis should retain these physical differences rather than apply one plume arrangement to every location.[10][11]
Material beneath seating can create an exposure that is less visible during normal use. The NFPA handbook identifies storage, concession uses and accumulated refuse as concerns. Combustible waste contributed to the Bradford stadium fire discussed in the source; inspection and housekeeping therefore include the underside of stands, not only the occupied seating surface.[11]
Exhibitions and other events can add temporary structures and combustible displays. The handbook warns that booths with ceilings can obstruct sprinkler discharge; a sports configuration and an exhibition configuration therefore need separate attention to the protection and escape arrangement. The permanent shell does not determine all hazards created by the temporary use.[12]
Event staff need communication and surveillance arrangements that cover the whole venue. The NFPA crowd-management chapter connects advance planning with observation during operation. Information about a developing queue or blocked route must reach those controlling demand; the same organisation supports an orderly response when fire or another emergency changes the available routes.[13]
Maximum specific flow and route type
For Nelson and Mowrer's quadratic specific-flow expression, the maximum occurs at a density of one divided by twice the density coefficient. Substituting 0.266 gives approximately 1.88 persons/m². Nelson and Mowrer round the corresponding location to 1.9 persons/m²; their tabulated maximum for level routes is approximately 1.3 persons/(s·m).[14]
The maximum is a feature of the particular speed–density curve. It is not the highest density that the route can contain. Nor does it mean that everybody moves fastest at that density; people move faster at lower densities, but fewer people are available to pass each metre of width.[15][14]
Stairs have different coefficients and maximum flows in the cited tables; their values depend on the riser and tread configuration represented by the source data. The chapter gives lower maximum specific flows for its listed stairs than for level routes. Substituting the level-route coefficient into a stair calculation would therefore change the model being applied.[15][14]
Speed on stairs is measured along the line of movement. Vertical storey height alone is not the distance travelled, and travel across landings must also be included. The same distinction applies when translating a stair flow into a travel-time estimate; a consistent specific-flow calculation does not remove the need to define the route geometry correctly.[15]
The same curve can associate a particular submaximum flow with two different densities; one state has fewer people moving faster; the other has more people moving slowly. A flow count alone therefore does not identify the crowd's density or speed. Additional information is needed to distinguish the two possible states.[14]
The rounded density limits should also be interpreted with the equation. With the density coefficient of 0.266, the expression's algebraic zero occurs at approximately 3.76 persons/m²; this corresponds to the chapter's rounded upper limit near 3.8 persons/m². The negative values obtained by continuing the expression beyond that point have no physical meaning in this movement model.[15]
Transitions, queues and changing conditions
A route commonly includes several elements in series. People may pass from a room into a corridor, through a door and onto a stair. The density and speed can change at each transition even when the same total flow continues. Consequently, assigning one specific-flow value to the entire route can conceal the controlling restriction.[14][16]
At a merge, incoming total flows are added before comparison with downstream capacity. Specific flows cannot simply be added without accounting for their respective widths. Each incoming specific flow must first be multiplied by its effective width. The resulting total is then assessed against the downstream maximum total flow.[16]
Conservation does not determine how people from competing routes share access; Nelson and Mowrer describe outcomes ranging from shared entry to dominance by one incoming stream. They propose examining different dominance assumptions where the sequence matters. Equal division at a merge is therefore an additional assumption, rather than an inevitable consequence of the flow equations.[16]
When arrivals vary, passage time cannot always be found by dividing the entire population by one maximum rate. The exit may initially be underused, later operate near capacity, and finally empty after the queue clears. Tracking arrivals and departures preserves this sequence. It also distinguishes a capacity limit from an average flow over the whole evacuation.[17][16]
A local reduction in width also changes the space available upstream as a queue develops; the arriving rate can then change because upstream density and speed change. Maintaining the original approach flow indefinitely would ignore that feedback. Nelson and Mowrer's treatment of transitions therefore connects the calculation of each route segment with the neighbouring segments.[17][16]
Interpretation and limitations
The hydraulic relationships summarise observations with empirical scatter; Nelson and Mowrer caution that a calculated movement time is a model result, not a guaranteed actual time. Behaviour, route choice and interruptions can affect the realised flow. Such effects remain relevant when specific-flow equations are embedded in more extensive evacuation modelling.[18][19]
Population characteristics also matter. The ABCB data sheets explicitly state that their doorway-flow equation is not suitable for people with mobility impairment. Their speed discussion requires further reductions for older people and those with restricted mobility. A general-population maximum cannot be used as evidence that an assisted evacuation will achieve the same throughput.[20][21]
Much of the movement evidence discussed by Nelson and Mowrer concerns smoke-free conditions. Smoke can reduce visibility and affect the eyes, changing movement performance. Their discussion distinguishes these influences from crowd density; applying an unobstructed flow curve does not establish either movement capability or acceptable exposure in a smoke-filled route.[16]
A numerical maximum describes movement under the model's assumptions; it is not a complete performance criterion. The same throughput can be associated with different queue locations and different waiting times for particular groups. Merge dominance can especially affect which occupants leave first. Total discharge alone cannot describe those differences in individual experience.[14][16]
A useful interpretation therefore preserves the complete chain of assumptions. The population, density range, route type, effective width and arrival pattern must match the calculation. Its result describes flow under those stated conditions. Claims about total evacuation performance require the remaining time components and the conditions along the route to be assessed as well.[18][17][21]
Purpose and route continuity
The central purpose is timely movement away from a threat. A route begins where occupants may be present and continues through the connected spaces and components leading to safety. Every link must be usable, because a failure near the destination can defeat an otherwise adequate path.[22][23] The threatened end deserves particular attention; Proulx distinguishes an emphasis on exit capacity from an emphasis on the decisions and conditions facing occupants at the start. A route with a safe discharge does not help if occupants cannot recognise or reach it in time.[24]
A place of safety must suit the intended occupants. The 2005 International Fire Engineering Guidelines (IFEG) give an example performance framework for this destination. It describes protection from untenable conditions, suitable communication and enough space for those expected to use it. The destination is therefore part of the escape provision, not an undefined endpoint beyond the exit.[25]
Evacuation uses these provisions within a timed human response. Warning, interpretation and preparation occur before directed travel, and queues can occur along the way. The physical route must be assessed together with those stages rather than in isolation.[26][27]
Route continuity also includes doors and other operating elements. A door that cannot open in the required condition interrupts the path just as a physical obstruction would. Management and maintenance must preserve the route's intended operation.[28]
Occupants and regulatory context
Occupant characteristics affect route length, preparation, speed and assistance. A route suitable for awake, familiar and independently mobile adults may not serve sleeping occupants or people needing support. The design population should be defined explicitly.[29]
Building regulations establish jurisdiction-specific objectives and performance criteria for escape. They can address route number, size, obstruction, protection, illumination and signage. These requirements must be read with the relevant edition and building type.[22]
IFEG reproduces historical New Zealand performance criteria for escape routes. These address route size, obstruction, length, fire-spread resistance, findability, illumination and safe use. They illustrate related design functions; the excerpt is not presented as the current text of New Zealand law.[22]
C/VM2 provides one verification method within the New Zealand context. Its 2025 travel and flow procedures include particular inputs and restrictions, such as door-flow provisions. Those values belong to the method and should not be treated as international defaults.[23]
The applicable safety systems can change the escape analysis. Suppression, smoke control and compartmentation may limit exposure, but their required operation must be supported. A design should not rely on an ideal system state while ignoring failure or maintenance.[28][30]
Engineering evaluation
Evaluation should begin with the number and distribution of occupants. Different groups may start in different spaces and need different levels of assistance. Their routes should be traced separately where those differences affect preparation, travel or the place of safety.[29]
Each proposed route should be checked as a continuous chain. The review includes the initial room, successive passages, doors, protected elements and final destination. A nominal exit on the plan does not establish that every part of that chain remains available during a fire.[31]
Alternative routes should be assessed for independence from the same threat. Two paths that share a smoke-affected space or an impaired component may not offer the intended choice. The Canadian code intentions reproduced in IFEG connect alternative exits with reduced delay and obstruction risks.[32]
The relevant fire conditions should be stated. A fire in an occupied room, a fire blocking an exit and smoke entering a protected route create different demands. C/VM2's exit-blocking scenario provides a specific example of testing whether a viable route remains.[31]
Timing should include detection, notification, preparation and movement. Route geometry and flow capacity affect only some of those stages. An assessment that starts when occupants reach the corridor would miss the time needed to recognise and respond to the event.[26]
The safety systems assumed in the analysis should be identified. Suppression, compartmentation, smoke control and emergency power can alter route conditions, but their functions depend on equipment and maintenance. Their failure modes may require a separate scenario or sensitivity check.[30][33]
Evidence from drills can reveal how the route and procedures operate together. Queue locations, unclear signs, door operation and staff directions can be observed in the actual layout. The drill's warning and population conditions must accompany any comparison with a fire scenario.[34]
Notes
- ↑ Nelson and Mowrer (2002), pp. 3-367–3-372.
- ↑ Cote et al. (2008), §20.9, pp. 20-88–20-89; §20.20, p. 20-223.
- ↑ Cote et al. (2008), §20.9, pp. 20-88–20-89; §4.4, pp. 4-101–4-102.
- ↑ 4.0 4.1 Cote et al. (2008), §20.9, pp. 20-88–20-89.
- ↑ Nelson and Mowrer (2002), pp. 3-368–3-372.
- ↑ Cote et al. (2008), §20.9, p. 20-88.
- ↑ Cote et al. (2008), §20.9, pp. 20-88–20-89; §4.4, pp. 4-94–4-96.
- ↑ Cote et al. (2008), §20.20, p. 20-223.
- ↑ Milke (2002), pp. 4-292–4-295.
- ↑ Milke (2002), pp. 4-299–4-302.
- ↑ 11.0 11.1 Cote et al. (2008), §20.9, p. 20-89; §20.20, p. 20-223.
- ↑ Cote et al. (2008), §20.9, p. 20-89.
- ↑ Cote et al. (2008), §4.4, pp. 4-101–4-102.
- ↑ 14.0 14.1 14.2 14.3 14.4 14.5 Nelson and Mowrer (2002), p. 3-371, equations 4–8 and Table 3-14.5.
- ↑ 15.0 15.1 15.2 15.3 Nelson and Mowrer (2002), pp. 3-370–3-371.
- ↑ 16.0 16.1 16.2 16.3 16.4 16.5 16.6 Nelson and Mowrer (2002), p. 3-372.
- ↑ 17.0 17.1 17.2 Nelson and Mowrer (2002), p. 3-369.
- ↑ 18.0 18.1 Nelson and Mowrer (2002), pp. 3-367–3-368.
- ↑ Nelson and Mowrer (2002), pp. 3-368–3-369.
- ↑ Australian Building Codes Board (2020), p. 278, §1.5.2.
- ↑ 21.0 21.1 Australian Building Codes Board (2020), p. 280, Table 21 and §1.5.3.
- ↑ 22.0 22.1 22.2 Australian Building Codes Board et al. (2005), p. 1.2-18.
- ↑ 23.0 23.1 Ministry of Business, Innovation and Employment (2025), pp. 32–33.
- ↑ Proulx (2002), pp. 3-342–3-343.
- ↑ Australian Building Codes Board et al. (2005), p. 1.2-15.
- ↑ 26.0 26.1 Australian Building Codes Board et al. (2005), pp. 2.8-1–2.8-2.
- ↑ Proulx (2002), pp. 3-347–3-348.
- ↑ 28.0 28.1 Australian Building Codes Board et al. (2005), pp. 1.8-13–1.8-14.
- ↑ 29.0 29.1 Proulx (2002), p. 3-350.
- ↑ 30.0 30.1 Australian Building Codes Board (2020), pp. 131–132.
- ↑ 31.0 31.1 Ministry of Business, Innovation and Employment (2025), p. 37.
- ↑ Australian Building Codes Board et al. (2005), pp. 1.2-16–1.2-17.
- ↑ Razza and Grill (2005), pp. 3–4.
- ↑ Proulx (2002), pp. 3-348–3-350.
References
- Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines. Australian Building Codes Board.
- Australian Building Codes Board. (2020). Fire safety verification method: Data sheets (Handbook annex, Print version 1.1).
- Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
- Milke, J. A. (2002). Smoke management in covered malls and atria. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-292–4-310). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2025). C protection from fire: Verification method C/VM2 (2nd ed.).
- Nelson, H. E., & Mowrer, F. W. (2002). Emergency movement. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-367–3-380). National Fire Protection Association.
- Proulx, G. (2002). Movement of people: The evacuation timing. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-342–3-366). National Fire Protection Association.
- Razza, J. C., & Grill, R. A. (2005). Comparison of the 1968 and current (2003) New York City building code provisions (NIST NCSTAR 1-1F). National Institute of Standards and Technology.