== Establishing a suction flow == | == Establishing a suction flow == | ||
Drafting turns an accessible static source into part of a [[Fire water supply|fire water supply]]; a [[Dry hydrant|dry hydrant]] can provide the permanent intake connection, while [[Fire apparatus|fire apparatus]] supplies the mobile pump and operating equipment. The arrangement must exclude air and preserve adequate submergence as the level falls. Losing the suction path can interrupt delivery even where substantial water remains in the source. <ref name="H_13_4_13-43_13-45" /> | Drafting turns an accessible static source into part of a [[Fire water supply|fire water supply]]; a [[Dry hydrant|dry hydrant]] can provide the permanent intake connection, while [[Fire apparatus|fire apparatus]] supplies the mobile pump and operating equipment. The arrangement must exclude air and preserve adequate submergence as the level falls. Losing the suction path can interrupt delivery even where substantial water remains in the source. <ref name="H_13_4_13-43_13-45" /> | ||
[[File:fse-drafting-v1.svg|thumb|upright=1.5|alt=Drafting: functional relationships. Measurement and water paths are distinct.|Drafting: functional relationships. Schematic explanation; dimensions are not installation instructions.]] | |||
The [[Fire pump performance curve|fire pump performance curve]] describes head delivery under stated pump conditions; [[Net positive suction head|net positive suction head]] determines whether the source and intake can support the corresponding operating flow. An [[Alternative water supply|alternative water supply]] therefore needs both quantity and withdrawal performance assessed. Increasing the discharge demand also increases intake losses, potentially making suction conditions worse. <ref name="T_4-68_4-69" /><ref name="H_13_4_13-40_13-45">Cote (2008), ch. 13.4, pp. 13-40–13-45.</ref> | The [[Fire pump performance curve|fire pump performance curve]] describes head delivery under stated pump conditions; [[Net positive suction head|net positive suction head]] determines whether the source and intake can support the corresponding operating flow. An [[Alternative water supply|alternative water supply]] therefore needs both quantity and withdrawal performance assessed. Increasing the discharge demand also increases intake losses, potentially making suction conditions worse. <ref name="T_4-68_4-69" /><ref name="H_13_4_13-40_13-45">Cote (2008), ch. 13.4, pp. 13-40–13-45.</ref> | ||
| Line 11: | Line 12: | ||
== Suction conditions and cavitation == | == Suction conditions and cavitation == | ||
Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water's vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. <ref name="H_15_6_15-91">Cote (2008), ch. 15.6, | Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water's vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. <ref name="H_15_6_15-91">Cote (2008), ch. 15.6, p. 15-91.</ref><ref name="T_4-68">Titus (2002), ch. 4-2, p. 4-68.</ref> | ||
[[File:fse-drafting-v2.svg|thumb|upright=1.5|alt=Available suction head. Measurement and water paths are distinct.|Available suction head. Schematic explanation; dimensions are not installation instructions.]] | |||
Available net positive suction head describes the installation's suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. <ref name="H_15_6_15-91_15-92">Cote (2008), ch. 15.6, pp. 15-91–15-92.</ref><ref name="T_4-68" /> | Available net positive suction head describes the installation's suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. <ref name="H_15_6_15-91_15-92">Cote (2008), ch. 15.6, pp. 15-91–15-92.</ref><ref name="T_4-68" /> | ||
| Line 37: | Line 39: | ||
== Static sources and fireground logistics == | == Static sources and fireground logistics == | ||
A natural or stored source is useful only if water can be withdrawn when the incident occurs; seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. <ref name="H_13_4_13-40_13-44" /> | A natural or stored source is useful only if water can be withdrawn when the incident occurs; seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. <ref name="H_13_4_13-40_13-44" /> | ||
[[File:fse-drafting-v3.svg|thumb|upright=1.5|alt=From static water to effective delivery. Measurement and water paths are distinct.|From static water to effective delivery. Schematic explanation; dimensions are not installation instructions.]] | |||
A dry hydrant provides a permanent suction connection to a static source; the pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. <ref name="H_13_4_13-43_13-45" /> | A dry hydrant provides a permanent suction connection to a static source; the pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. <ref name="H_13_4_13-43_13-45" /> | ||
| Line 55: | Line 58: | ||
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69" /> | A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. <ref name="H_15_6_15-91_15-98">Cote (2008), ch. 15.6, pp. 15-91–15-98.</ref><ref name="T_4-68_4-69" /> | ||
The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, | The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. <ref name="H_15_6_15-92">Cote (2008), ch. 15.6, p. 15-92.</ref> | ||
Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, | Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. <ref name="T_4-70">Titus (2002), ch. 4-2, p. 4-70.</ref><ref name="H_15_6_15-93_15-95">Cote (2008), ch. 15.6, pp. 15-93–15-95.</ref> | ||
The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" /> | The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. <ref name="H_15_6_15-91_15-99">Cote (2008), ch. 15.6, pp. 15-91–15-99.</ref><ref name="T_4-68_4-69" /> | ||
| Line 95: | Line 98: | ||
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" /> | At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81" /> | ||
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, | Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56">Titus (2002), ch. 4-2, p. 4-56.</ref><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, p. 15-59.</ref> | ||
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, | Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, p. 16-212.</ref> | ||
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81">Fleming (2002), ch. 4-3, | A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81">Fleming (2002), ch. 4-3, p. 4-81.</ref> | ||
== Calculating transport throughput == | == Calculating transport throughput == | ||
| Line 118: | Line 121: | ||
|} | |} | ||
Using the handbook's rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. <ref name="H_13_4_13-49">Cote (2008), ch. 13.4, | Using the handbook's rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. <ref name="H_13_4_13-49">Cote (2008), ch. 13.4, p. 13-49.</ref> | ||
A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions; queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. <ref name="H_13_4_13-47_13-49" /> | A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions; queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. <ref name="H_13_4_13-47_13-49" /> | ||
Latest revision as of 01:32, 16 November 2026
Drafting is the withdrawal of water from a static source through a pump suction arrangement, commonly with the water level below the pump. [1][2] The pump first needs an effective primed flow path. Atmospheric pressure, source elevation, vapour pressure and intake losses limit the available suction energy. The resulting capability is specific to the installation and operating flow, rather than a universal lifting distance. [3]
The supply assessment follows the complete route from the source to useful water at the incident. Seasonal minimum conditions, withdrawal limits, transport and initial availability can each govern the result. Total water volume is therefore different from sustained delivered flow. The mobilisation and handling involved also distinguish these arrangements from an immediately available automatic supply for a fixed sprinkler installation. [4][5] Availability can change with both season and weather. [6]
Establishing a suction flow
Drafting turns an accessible static source into part of a fire water supply; a dry hydrant can provide the permanent intake connection, while fire apparatus supplies the mobile pump and operating equipment. The arrangement must exclude air and preserve adequate submergence as the level falls. Losing the suction path can interrupt delivery even where substantial water remains in the source. [1]
The fire pump performance curve describes head delivery under stated pump conditions; net positive suction head determines whether the source and intake can support the corresponding operating flow. An alternative water supply therefore needs both quantity and withdrawal performance assessed. Increasing the discharge demand also increases intake losses, potentially making suction conditions worse. [3][7]
The intake location changes with seasonal level, ice and sediment; a route usable during a favourable inspection can become unavailable during an incident. The handbook consequently considers access and minimum source conditions alongside nominal capacity. Drafting performance belongs to that complete site arrangement, not only to the pump rating. [7]
Suction conditions and cavitation
Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water's vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. [8][9]
Available net positive suction head describes the installation's suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. [10][9]
For a large open reservoir, the following form separates atmospheric pressure, water level and suction losses; the reservoir surface velocity is treated as negligible. A positive elevation difference means that the water surface is above the pump reference. A lower surface contributes a negative term. [9]
| Symbol | Description | Unit |
|---|---|---|
| Available net positive suction head | m | |
| Absolute atmospheric and vapour pressures | Pa | |
| Water density and gravitational acceleration | kg/m³; m/s² | |
| Surface elevation, pump elevation and suction loss | m |
The lowest usable tank level can be more demanding than the initial full condition; a greater flow increases suction-pipe loss and can also increase the pump's required suction head. Warmer water increases vapour pressure, while atmospheric pressure varies with elevation. These effects explain why a universal maximum suction lift cannot represent every installation. [11][9]
The handbook illustrates a pump requiring approximately 3.05 m of suction head at 7,570 L/min and 5.49 m at 11,400 L/min. These are converted values from one illustrative manufacturer's-style curve, not general acceptance limits. Their significance is the changing requirement as flow rises. The appropriate comparison uses the actual pump data and the available head under the corresponding supply condition. [8]
Static sources and fireground logistics
A natural or stored source is useful only if water can be withdrawn when the incident occurs; seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. [6]
A dry hydrant provides a permanent suction connection to a static source; the pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. [1]
Drafting introduces limits that differ from receiving water under positive pressure; the available atmospheric-pressure head must cover lift, suction losses and the margin above vapour pressure required by the pump. Longer piping, restrictive fittings and falling source level reduce that available margin. A nominal pump capacity quoted under other conditions does not establish drafting performance at the site. [1][3]
Transporting water adds time and handling constraints; a vehicle repeatedly fills, travels, discharges and returns. Fill and dump arrangements can become bottlenecks when several vehicles share them. The fireground also needs water while these cycles develop, so an initial reserve and sustained delivery rate answer different operational questions. [12]
The same distinction applies when assessing a static source against a fire-flow demand; a pond may contain sufficient total water while its access or intake supports too little continuous withdrawal. A rapid initial discharge may exhaust a small available reserve before replenishment becomes effective. Both rate and duration are therefore assessed through the actual extraction and transport chain. [4][13]
These arrangements can support manual firefighting without constituting an automatic sprinkler supply; their dependence on mobilisation, priming, transport and connection must remain visible in the fire safety analysis. The handbook distinguishes automatic availability from water that requires human action before delivery. Treating the latter as immediately available would omit the delays that define its operation. [5][14]
Pump operation and selection
A centrifugal pump transfers shaft energy to water through a rotating impeller; its performance varies with flow, speed and pump geometry. The selected duty belongs on a curve showing this relationship, rather than being defined by a single pressure reading. The complete operating point also depends on the resistance and supply conditions of the connected installation. [15][2]
The pump head is the energy added across the pump; discharge pressure alone is not that quantity when suction pressure, elevation or velocity differ between measuring points. Horizontal pumps and vertical turbine arrangements require appropriate references for their respective configurations. A test comparison can be misleading if the water level or suction reference has changed without being recorded. [16]
A centrifugal pump normally develops its greatest head near shutoff and less head at higher flows; the closed-outlet condition therefore needs assessment for maximum system pressure. At the other end of the operating range, the remaining head must meet the required discharge pressure after losses. Driver capability and suction conditions can constrain operation even where the plotted head appears adequate. [17][3]
The handbook's account of United States NFPA 20 practice describes a rated point, a high-flow point and a shutoff limit. It reports at least 65% of rated head at 150% of rated flow, with shutoff head no greater than 140%. These are historical criteria reported in the 2008 handbook. They are not a substitute for a selected pump's actual curve or a statement of a current adopted standard. [18]
Connecting pumps in series adds their heads at a common flow; connecting them in parallel combines flow at a common head. Neither arrangement automatically doubles delivery through the installed network, because the operating intersection changes. Shared suction piping and power dependencies also remain part of the installation rather than disappearing through duplication. [19][20]
The water source must be assessed alongside the pump; a booster can overcome insufficient pressure but cannot create an absent water reserve. A powerful driver cannot correct an obstructed intake or inadequate suction conditions. Selection therefore brings together the source, suction route, performance curve, driver, controls and downstream demand. [21][3]
Pressure, flow and energy
Water pressure describes only one part of the energy available in a pipe; elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. [22]
For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections; the following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. [23]
| Symbol | Description | Unit |
|---|---|---|
| Pressure at the section | Pa | |
| Water density | kg/m³ | |
| Gravitational acceleration | m/s² | |
| Mean velocity | m/s | |
| Elevation, added pump head and head loss | m |
Pressure can decrease because water rises, because velocity increases, or because energy is dissipated; these effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. [24]
Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity; the same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. [23][25]
The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered; it is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. [26][27]
Pipe resistance and internal condition
Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section; turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. [28]
The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor; that factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. [29]
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. [30][26]
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. [31][32]
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. [33][34]
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. [24][35]
Calculating transport throughput
The average delivery from a water-carrying vehicle is the usable quantity delivered during one complete cycle divided by the cycle time; the time includes filling, loaded travel, discharge and return travel. Manoeuvring and connection delays belong in the relevant operation. Omitting them overstates the continuous supply that the vehicle can maintain. [36]
The handbook expresses this relationship with a factor allowing for less than complete delivery of the nominal load. That factor describes the assumed operation rather than changing the vehicle's physical tank volume. The equation gives a cycle average; it does not imply that discharge occurs uniformly throughout the trip. [36]
| Symbol | Description | Unit |
|---|---|---|
| Average delivered flow | L/min | |
| Nominal vehicle volume and delivery factor | L; dimensionless | |
| Fill, outbound travel, dump and return times | min |
Using the handbook's rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. [37]
A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions; queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. [12]
The demand comparison is made against sustained effective delivery and the initial water reserve; a brief high discharge rate from a portable tank is not itself a replenishment rate. Likewise, a large vehicle volume does not compensate for an indefinitely long turnaround. The calculation makes these trade-offs visible without predicting fire extinguishment from delivered volume alone. [12][13]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 Cote (2008), ch. 13.4, pp. 13-43–13-45.
- ↑ 2.0 2.1 Titus (2002), ch. 4-2, pp. 4-67–4-69.
- ↑ 3.0 3.1 3.2 3.3 3.4 Titus (2002), ch. 4-2, pp. 4-68–4-69.
- ↑ 4.0 4.1 Cote (2008), ch. 13.4, pp. 13-40–13-49.
- ↑ 5.0 5.1 Cote (2008), ch. 15.4, pp. 15-63–15-65.
- ↑ 6.0 6.1 Cote (2008), ch. 13.4, pp. 13-40–13-44.
- ↑ 7.0 7.1 Cote (2008), ch. 13.4, pp. 13-40–13-45.
- ↑ 8.0 8.1 Cote (2008), ch. 15.6, p. 15-91.
- ↑ 9.0 9.1 9.2 9.3 Titus (2002), ch. 4-2, p. 4-68.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-92.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-95.
- ↑ 12.0 12.1 12.2 Cote (2008), ch. 13.4, pp. 13-47–13-49.
- ↑ 13.0 13.1 Cote (2008), ch. 15.2, pp. 15-23–15-24.
- ↑ Cote (2008), ch. 13.4, pp. 13-37,13-47–13-49.
- ↑ Cote (2008), ch. 15.6, pp. 15-85,15-89–15-92.
- ↑ Cote (2008), ch. 15.6, pp. 15-89–15-90.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-98.
- ↑ Cote (2008), ch. 15.6, p. 15-92.
- ↑ Titus (2002), ch. 4-2, p. 4-70.
- ↑ Cote (2008), ch. 15.6, pp. 15-93–15-95.
- ↑ Cote (2008), ch. 15.6, pp. 15-91–15-99.
- ↑ Titus (2002), ch. 4-2, pp. 4-45–4-48.
- ↑ 23.0 23.1 Titus (2002), ch. 4-2, pp. 4-47–4-50.
- ↑ 24.0 24.1 Titus (2002), ch. 4-2, pp. 4-47–4-52.
- ↑ Cote (2008), ch. 16.3, pp. 16-41–16-42.
- ↑ 26.0 26.1 Fleming (2002), ch. 4-3, pp. 4-75–4-81.
- ↑ Hopkins et al. (2005), pp. xxxvii–xxxviii.
- ↑ Titus (2002), ch. 4-2, pp. 4-49–4-56.
- ↑ Titus (2002), ch. 4-2, pp. 4-50–4-53.
- ↑ Titus (2002), ch. 4-2, pp. 4-52–4-53.
- ↑ Titus (2002), ch. 4-2, p. 4-56.
- ↑ Cote (2008), ch. 15.3, p. 15-59.
- ↑ Cote (2008), ch. 15.5, pp. 15-79–15-81.
- ↑ Cote (2008), ch. 16.11, p. 16-212.
- ↑ Fleming (2002), ch. 4-3, p. 4-81.
- ↑ 36.0 36.1 Cote (2008), ch. 13.4, pp. 13-48–13-49.
- ↑ Cote (2008), ch. 13.4, p. 13-49.
References
- Cote, A. E. (Ed.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
- Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-72–4-87). National Fire Protection Association.
- Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
- Titus, J. J. (2002). Hydraulics. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-44–4-71). National Fire Protection Association.