Bouchard (2008) distinguishes two principal types, pressure systems and suction systems, and combinations of both.<ref name="BO-8-39" /> A pressure system moves the material with air above atmospheric pressure. It consists of a blower that draws air through a filter, an airlock feeder that introduces the material, the piping or ducts, and an air-material separator. A suction system works below atmospheric pressure. It consists of a material and air intake, the piping or ducts, an air-material separator, and a suction fan or blower.<ref name="BO-8-39" /> Noncombustible gases may be used instead of air or mixed with it.<ref name="BO-8-39" /> | Bouchard (2008) distinguishes two principal types, pressure systems and suction systems, and combinations of both.<ref name="BO-8-39" /> A pressure system moves the material with air above atmospheric pressure. It consists of a blower that draws air through a filter, an airlock feeder that introduces the material, the piping or ducts, and an air-material separator. A suction system works below atmospheric pressure. It consists of a material and air intake, the piping or ducts, an air-material separator, and a suction fan or blower.<ref name="BO-8-39" /> Noncombustible gases may be used instead of air or mixed with it.<ref name="BO-8-39" /> | ||
[[File:fse-pneumatic-conveying-system-v1.svg|thumb|upright=1.5|alt=Two schematics: a pressure conveying system with blower and airlock feeder, and a suction system with intake and suction fan|Pressure and suction pneumatic conveying systems.]] | |||
A second distinction is the ratio of solids to air. Ural and Garzia (2008) define the solids loading ratio as the average mass of solids divided by the mass of air in the transfer line. In dense phase conveying the air velocity is down near 600 ft/min (3 m/s) and the solids loading ratio exceeds 30. In dilute phase conveying the air moves at about 2200 to 3600 ft/min (11 to 18 m/s), with a solids loading ratio below 15.<ref name="UG-17-157">Ural and Garzia (2008), p. 17-157.</ref> In woodworking dust collection systems the conveying velocity might be several thousand feet per minute.<ref name="CH-9-21">Cholin (2008d), p. 9-21.</ref> Sparks travel down such ducts often at speeds as high as 6000 ft/min (30 m/s).<ref name="CH-9-23">Cholin (2008d), p. 9-23.</ref> | A second distinction is the ratio of solids to air. Ural and Garzia (2008) define the solids loading ratio as the average mass of solids divided by the mass of air in the transfer line. In dense phase conveying the air velocity is down near 600 ft/min (3 m/s) and the solids loading ratio exceeds 30. In dilute phase conveying the air moves at about 2200 to 3600 ft/min (11 to 18 m/s), with a solids loading ratio below 15.<ref name="UG-17-157">Ural and Garzia (2008), p. 17-157.</ref> In woodworking dust collection systems the conveying velocity might be several thousand feet per minute.<ref name="CH-9-21">Cholin (2008d), p. 9-21.</ref> Sparks travel down such ducts often at speeds as high as 6000 ft/min (30 m/s).<ref name="CH-9-23">Cholin (2008d), p. 9-23.</ref> | ||
| Line 51: | Line 52: | ||
The same relation shows how wide the range of loading ratios in use is. A loading ratio of 15 marks the upper end of dilute phase. On the same no-slip assumption, such a stream would carry about 15 × 1.2 = 18 kg/m³ (own calculation), far above the typical upper explosive limit of dusts of 2,000 to 6,000 g/m³.<ref name="ZS-3-403">Zalosh (2002), p. 3-403.</ref> | The same relation shows how wide the range of loading ratios in use is. A loading ratio of 15 marks the upper end of dilute phase. On the same no-slip assumption, such a stream would carry about 15 × 1.2 = 18 kg/m³ (own calculation), far above the typical upper explosive limit of dusts of 2,000 to 6,000 g/m³.<ref name="ZS-3-403">Zalosh (2002), p. 3-403.</ref> | ||
[[File:fse-pneumatic-conveying-system-v2.svg|thumb|upright=1.5|alt=Log-log chart of dust concentration against solids loading ratio with shaded explosive range and dense and dilute phase regions|Average dust concentration against solids loading ratio for air at 20 °C and 1 bar.]] | |||
== Ignition sources in conveying systems == | == Ignition sources in conveying systems == | ||
| Line 80: | Line 82: | ||
Active systems include chemical barriers, automatic fast-acting mechanical valves, and actuated float and pinch valves.<ref name="UG-17-159" /> Their design rests on three times: the time to detect the explosion, the time to create the barrier, and the time the flame needs to reach the barrier.<ref name="UG-17-160-161">Ural and Garzia (2008), pp. 17-160–17-161.</ref> If the flame arrives first, the isolation fails. Flame speed is the hardest of the three to predict, and no scientifically valid, universally accepted method for flame acceleration in industrial pipes exists. Manufacturers therefore rely on simplified proprietary correlations based on limited data.<ref name="UG-17-162">Ural and Garzia (2008), p. 17-162.</ref> | Active systems include chemical barriers, automatic fast-acting mechanical valves, and actuated float and pinch valves.<ref name="UG-17-159" /> Their design rests on three times: the time to detect the explosion, the time to create the barrier, and the time the flame needs to reach the barrier.<ref name="UG-17-160-161">Ural and Garzia (2008), pp. 17-160–17-161.</ref> If the flame arrives first, the isolation fails. Flame speed is the hardest of the three to predict, and no scientifically valid, universally accepted method for flame acceleration in industrial pipes exists. Manufacturers therefore rely on simplified proprietary correlations based on limited data.<ref name="UG-17-162">Ural and Garzia (2008), p. 17-162.</ref> | ||
[[File:fse-pneumatic-conveying-system-v3.svg|thumb|upright=1.5|alt=Conveying line between a feed hopper and a collector with rotary valve, deflagration detector, fast-acting valve and flame front diverter|Isolation devices on a pneumatic conveying line and the timing condition for an active barrier.]] | |||
== Spark detection and limits of protection == | == Spark detection and limits of protection == | ||
Latest revision as of 08:53, 9 November 2026
A pneumatic conveying system is an enclosed system of pipes or ducts in which powders, chips or other small particles are carried by a stream of air or another gas.[1] The gas moves fast enough to keep the material suspended, and an air-material separator at the end of the line removes the solids from the gas.[1] Such systems are common in woodworking, grain milling, plastics processing, metalworking and powder coating.[2][3][4][5][6]
Their main fire hazard follows directly from how they work: they can place combustible dust in air at explosive concentrations quickly and easily.[1] A Dust explosion that starts in a conveying line or in the collector at its end can travel through the pipes to other equipment and gather strength on the way.[7] The Fire Protection Handbook (2008) describes US practice of that time. It used conductive and grounded ducts, separators outside the building, inert gas where needed, explosion relief on ducts, and isolation devices that stop flame travelling between items of equipment.[1][8][9]
Principle and system types
Bouchard (2008) distinguishes two principal types, pressure systems and suction systems, and combinations of both.[1] A pressure system moves the material with air above atmospheric pressure. It consists of a blower that draws air through a filter, an airlock feeder that introduces the material, the piping or ducts, and an air-material separator. A suction system works below atmospheric pressure. It consists of a material and air intake, the piping or ducts, an air-material separator, and a suction fan or blower.[1] Noncombustible gases may be used instead of air or mixed with it.[1]
A second distinction is the ratio of solids to air. Ural and Garzia (2008) define the solids loading ratio as the average mass of solids divided by the mass of air in the transfer line. In dense phase conveying the air velocity is down near 600 ft/min (3 m/s) and the solids loading ratio exceeds 30. In dilute phase conveying the air moves at about 2200 to 3600 ft/min (11 to 18 m/s), with a solids loading ratio below 15.[10] In woodworking dust collection systems the conveying velocity might be several thousand feet per minute.[11] Sparks travel down such ducts often at speeds as high as 6000 ft/min (30 m/s).[12]
The applications are wide. In woodworking, pneumatic conveying systems pull sander dust towards a Dust collector, and a high-power fan blows the chips from a wood hog through a conveying duct to a storage silo.[2][13] Wood waste may later be conveyed to the boiler by a pneumatic system or a screw conveyor. In rotary drum dryers the hot flue gas itself conveys the wood particles through the dryer, and a cyclone separates them at the outlet.[14]
The grain industry stores and handles grain in facilities such as a Grain elevator. Its milling portion uses pneumatic conveying extensively, because it confines finely ground products in complex plants with many pickup and delivery points.[3] Static build-up and discharge is a concern there if the systems are not properly grounded and maintained.[3] In metalworking, hoods over the work area are connected by ductwork to a central separator such as a cyclone, a bag collector, a wet collector or an electrostatic precipitator.[5]
Why conveying lines are an explosion hazard
A dust cloud can only deflagrate when the dust concentration lies above the minimum explosible concentration (MEC). For most wood particulates the MEC is about 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).[11] Dust concentrations above the MEC are experienced routinely in conveying systems, as well as in dust collectors, dryers, grinders and silos.[15] German records for 1965 to 1985 show that 78 percent of dust explosions began in this kind of process equipment.[15]
Conveying can also make the dust finer. Sawdust, router chips and shavings are often regarded as less hazardous because of their size, but pneumatic conveying wears the particles down and produces fine dust that can deflagrate.[16] Plastic moulding pellets are free from the dust explosion hazard as delivered, yet fines are generated by abrasion when the pellets travel through a long pneumatic conveying line.[4] Ouellette (2008) therefore treats dust explosions as possible wherever larger granules are conveyed pneumatically.[4]
Many systems are designed to run well below the MEC. Woodworking dust collection systems are generally designed for dust concentrations well below the minimum explosible limit, but a very deep cut at a sander can push the duct concentration above the MEC.[2] When the system runs well below the MEC, a deflagration cannot propagate through the duct. At or above the MEC, the duct must be treated as a deflagrable environment.[11] Metal dust systems should be designed so that the fine dust concentration never approaches the MEC, and their ductwork should contain the pressure of an explosion without failing.[5]
Even a line that is safely lean does not remove the hazard at its end. When metal powder is conveyed in air below the MEC, the suspension must still pass through the explosive range in the collector, unless the dust is collected in a liquid.[1] Any dry collector in an air conveying system must therefore be treated as an explosion hazard containing a dust-air mixture in the explosive range.[1] Leaks are a further problem. In powder coating plants, the hose and pipe connections of pneumatic transfer equipment are checked routinely, because a broken connection could blow powder into the workspace outside the enclosure.[6]
Dust concentration and solids loading
The average dust concentration in a conveying line follows from a simple mass balance. The mass flow of solids is divided by the volume flow of conveying gas. The SFPE Handbook uses this relation to judge whether the outlet stream of a coal pulveriser lies in the explosive range:[17]
Ural and Garzia (2008) define the solids loading ratio by mass of solids and air in the transfer line.[10] If the solids move at about the same speed as the air, this equals the ratio of the two mass flows. The air density then links it to the concentration (own derivation from the two definitions):
| Symbol | Description | Unit |
|---|---|---|
| Average dust concentration in the conveying gas | kg/m³ | |
| Mass flow rate of conveyed solids | kg/s | |
| Volume flow rate of conveying air | m³/s | |
| Mass flow rate of conveying air | kg/s | |
| Density of the conveying air | kg/m³ | |
| Solids loading ratio | – |
The relations give averages for steady flow. They say nothing about local accumulations, start-up and shutdown, or the concentration gradient inside a collector, where deflagrable zones exist even when the line itself is lean.[18] The air density depends on temperature and pressure. At 20 °C and 1 bar it is about 1,205 g/m³ (1.2 kg/m³).[19]
Worked example. The SFPE Handbook example considers two pulverisers with the same airflow of 7.1 m³/s. Pulveriser A is fed with 1.9 kg/s of bituminous coal and Pulveriser B with 13.9 kg/s.[17] The outlet concentrations are 1.9/7.1 = 0.27 kg/m³ and 13.9/7.1 = 1.96 kg/m³. The first lies well within the explosive limits of typical bituminous coal, while the second is close to the reported upper explosive limit of coal, 2 to 4 kg/m³.[17] With an air density of 1.2 kg/m³, the solids loading ratios are 0.27/1.2 = 0.22 and 1.96/1.2 = 1.6. Both ratios lie far below the value of 15 that Ural and Garzia (2008) give as the upper end of dilute phase conveying. The example gives no air velocity, so the phase is classified by loading ratio only.[10]
The same relation shows how wide the range of loading ratios in use is. A loading ratio of 15 marks the upper end of dilute phase. On the same no-slip assumption, such a stream would carry about 15 × 1.2 = 18 kg/m³ (own calculation), far above the typical upper explosive limit of dusts of 2,000 to 6,000 g/m³.[20]
Ignition sources in conveying systems
Sparks and embers from the process are the main ignition source in woodworking conveying systems. Process-generated ignitions enter the dust collection system together with the wood particulate from the machines.[11] Stones and tramp metal that enter the duct heat up as they collide with the steel walls and can cause ignition where they come to rest in the hopper of a cyclone or collector.[21] Mechanical sparks, presumably from impact or friction, were the most frequent ignition source in the German dust explosion records, and impact sparks are often attributable to tramp metal in conveying systems or grinders.[15]
Static electricity is the second typical source. Pulverised material passing through chutes or pneumatic conveyors is one of the classic ways in which electric charges are separated.[22] The chance of generating static increases when heated or dry materials are conveyed pneumatically.[23] A resistance to ground as high as 1000 MΩ may give an adequate leakage path in many cases. Where charge is generated rapidly, as in pneumatic transport, a resistance as low as 1 MΩ may be required.[24] Propagating brush discharges from insulating surfaces have ignited dust clouds and the dust inside a pneumatic transport system that used thin-walled insulating hose.[25]
The energy stored on an insulated conductor, such as an ungrounded silo during filling and unloading, is given by the capacitor relation . Here E is the spark energy in joules, C the capacitance in farads and V the voltage before discharge.[17] The SFPE Handbook considers a silo with a capacitance of 500 picofarads that stores a powder with a minimum ignition energy of 50 mJ for capacitive sparks. The voltage needed is = √(2 × 0.050 / 500 × 10−12) ≈ 14 kV. A voltage of this size may indeed be generated by the continuous impact and friction of the powder during filling and unloading.[17] The SFPE Handbook also notes that the minimum ignition energy and the minimum ignition temperature both increase with the velocity of the dust-air mixture.[17]
Light metal powders bring a chemical ignition source. Grinding and transport keep exposing fresh metal surface, which oxidises at once in an exothermic reaction. A fine particle with a large new surface can heat itself to its ignition point when suddenly exposed to air.[1] Fans are a mechanical source in any system. For that reason the design should never draw the dust through the fan before the final collector.[8]
Design and construction in US practice
Bouchard (2008) summarises US recommendations of the time for the conveying ducts. They are made of nonferrous, minimum-sparking metal or of nonmagnetic, minimum-sparking stainless steel, and they are electrically bonded and grounded.[1] Plastic or other nonconductive liners are not desirable but may be needed for some materials. Where ducts or liners are combustible, automatic sprinklers inside the ducts are often strongly recommended.[1] For metal powder systems conveyed in air, the whole system and especially the collector should be bonded and grounded, with less than 5 ohms resistance to ground.[1]
A minimum conveying velocity is kept throughout the system, so that dust cannot accumulate and powder that drops out during an unplanned stop is picked up again. Ducts exposed to weather should be moisture-tight, because moisture can react with metal dust and produce heat.[1] Where warm gas enters cold ducts and collectors, insulation or heating prevents condensation.[8] Sight glasses should be avoided where possible. If used, they must be noncombustible, carry none of the system weight and keep the electrical bonding continuous.[8]
Fan blades and housings are made of conductive, nonsparking metal such as bronze, nonsparking stainless steel or aluminium.[8] Personnel should not come within 50 ft (15 m) of the fan while it runs, so the fan is shut down and locked out for oiling, inspection and maintenance. Fan bearings should have temperature or vibration monitoring wired to an alarm, and fans are preferably located outside all manufacturing buildings.[8] Air-material separators should also be outside the building, with lightning protection and positive choke devices on the material outlets.[8] Exhaust air goes outside unless it is recirculated directly into the conveying system. The separators are noncombustible, with low-hazard cloth filters in grounded metal enclosures and no ledges where dust can settle.[8]
Inert gas is recommended wherever the powder concentration may come within the explosive range. Nitrogen, argon or helium is used, with a limited oxygen content based on the explosive properties of the particles, and with a dew point that prevents condensation.[1] The inert gas for magnesium systems should not contain carbon dioxide, and oxygen limits of 3 to 5 percent are maintained in aluminium powder systems using controlled flue gas. A continuous monitor must alarm when the oxygen content leaves the safe range.[1] A completely oxygen-free gas is not used for light metal powders, because the unreacted surfaces would later react violently with air; a small controlled oxygen content lets them oxidise slowly.[1]
Explosion relief can be provided by vents on the ducts, closed by antiflashback swing valves or rupture diaphragms and led to the outside.[8] Where a ruptured duct could cause damage, the duct is designed for an internal working pressure of at least 100 psi (690 kPa), in case the vent does not relieve the pressure. Where a burst would harm nothing, the duct may be built light so that it fails as an auxiliary vent.[8]
Flame propagation and isolation
A pipe that carries a flammable mixture can act as a fuse. If the mixture ignites at one end, the flame can run through the pipe and ignite the process unit at the other end, and its speed keeps increasing as it travels.[7] If the mixture is detonable, the flame can undergo a deflagration-to-detonation transition, with pressures of about 25 times the initial pressure and reflected pressures up to 50 times.[7] Deflagration flame fronts generally move at least ten times faster than the conveying air, so the airflow does little to stop propagation back towards the building.[26]
Flame propagation in dust-carrying pipes is somewhat unpredictable. Pipes smaller than 100 mm (4 in.) in diameter are far less likely to carry a flame than larger pipes. Dense phase transfer is also much less likely to propagate a flame than dilute phase transfer.[10] In controlled experiments with 150 mm piping, propagation occurred as rarely as one time in ten, even in dilute phase systems. Metal dusts and other dusts with a high deflagration index propagate more readily through small pipes.[7] Ural and Garzia (2008) consider isolation generally necessary for interconnected equipment, unless a qualified risk analysis based on probability and consequence shows that the risk is acceptable.[10]
Explosion isolation devices for conveying lines are either passive or active. Passive devices include rotary valves, flame front diverters, float valves, flame arresters and liquid seals. The handbook lists float valves, flame arresters and liquid seals for gases only, and flame arresters are not suitable for dust service.[7][9] Rotary valves, as material chokes, can stop flame passage under certain conditions but do not always stop burning embers.[9] Flame front diverters vent the deflagration where the flow turns through 180 degrees,[7] but in most tests they did not completely stop propagation.[9] Lataille (2008) also notes that screw conveyors or rotary feeds at suitable points act as a choke that helps stop the spread of a flash fire.[27]
Active systems include chemical barriers, automatic fast-acting mechanical valves, and actuated float and pinch valves.[9] Their design rests on three times: the time to detect the explosion, the time to create the barrier, and the time the flame needs to reach the barrier.[28] If the flame arrives first, the isolation fails. Flame speed is the hardest of the three to predict, and no scientifically valid, universally accepted method for flame acceleration in industrial pipes exists. Manufacturers therefore rely on simplified proprietary correlations based on limited data.[29]
Spark detection and limits of protection
Where a line runs below the MEC, a Spark detection and extinguishing system can quench burning particles before they reach a collector or silo.[11] Before wood particulate enters silos, bunkers or bins, it is usually monitored by spark detection coupled with an intermittent water spray on the in-feed conveyor. Some systems instead switch diverter valves that send the flow to a safe fire dump.[30] Such systems work only below the MEC. In a deflagrable duct, the flame front would pass the extinguishing unit before the spray was established, and ducts in which a deflagration can occur must be protected with deflagration venting or suppression.[31]
See also
- Woodworking facility
- Inerting
- Deflagration-to-detonation transition
- Minimum ignition energy
- Explosion venting
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 Bouchard (2008), p. 8-39.
- ↑ 2.0 2.1 2.2 Cholin (2008d), p. 9-10.
- ↑ 3.0 3.1 3.2 Maness and Sargent (2008), p. 9-89.
- ↑ 4.0 4.1 4.2 Ouellette (2008), p. 9-61.
- ↑ 5.0 5.1 5.2 Dobbs (2008), p. 9-70.
- ↑ 6.0 6.1 Scarbrough (2008b), p. 9-35.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Ural and Garzia (2008), p. 17-158.
- ↑ 8.00 8.01 8.02 8.03 8.04 8.05 8.06 8.07 8.08 8.09 Bouchard (2008), p. 8-40.
- ↑ 9.0 9.1 9.2 9.3 9.4 Ural and Garzia (2008), p. 17-159.
- ↑ 10.0 10.1 10.2 10.3 10.4 Ural and Garzia (2008), p. 17-157.
- ↑ 11.0 11.1 11.2 11.3 11.4 Cholin (2008d), p. 9-21.
- ↑ Cholin (2008d), p. 9-23.
- ↑ Cholin (2008d), p. 9-11.
- ↑ Cholin (2008d), p. 9-8.
- ↑ 15.0 15.1 15.2 Zalosh (2008), p. 2-100.
- ↑ Cholin (2008c), p. 6-67.
- ↑ 17.0 17.1 17.2 17.3 17.4 17.5 Zalosh (2002), p. 3-405.
- ↑ Cholin (2008d), p. 9-14.
- ↑ Drysdale (2008), p. 2-9.
- ↑ Zalosh (2002), p. 3-403.
- ↑ Cholin (2008d), p. 9-15.
- ↑ Scarbrough (2008a), p. 11-60.
- ↑ Bouchard (2008), p. 8-36.
- ↑ Scarbrough (2008a), p. 11-61.
- ↑ Scarbrough (2008a), p. 11-65.
- ↑ Cholin (2008d), p. 9-22.
- ↑ Lataille (2008), p. 8-11.
- ↑ Ural and Garzia (2008), pp. 17-160–17-161.
- ↑ Ural and Garzia (2008), p. 17-162.
- ↑ Cholin (2008d), p. 9-6.
- ↑ Cholin (2008d), p. 9-24.
References
- Bouchard, J. K. (2008). Materials-Handling equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-31–8-41). National Fire Protection Association.
- Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
- Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
- Dobbs, P. G. (2008). Metalworking processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-67–9-72). National Fire Protection Association.
- Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
- Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
- Maness, J. E., & Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-85–9-103). National Fire Protection Association.
- Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
- Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
- Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
- Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.