The flame is stopped by cooling. Hot flaming gas that leaves the enclosure has to pass along a narrow path, such as the threads of a screwed joint. In passing, it loses so much heat that only cooled gas, no longer able to cause ignition, reaches the outside.<ref name="Milatovich-8-169" /> Beyler (2002b) describes the same effect: the openings are made small enough that the flame loses sufficient heat as it passes through and is quenched.<ref name="Beyler-2-181" /> Because the hot gases still expand through the opening, they could autoignite outside if the gap were too wide.<ref name="Beyler-2-182" /> The same principle is used in a [[Flame arrester|flame arrester]], which passes the gas flow through small passageways so that a flame is quenched thermally.<ref name="Ural-17-158">Ural and Garzia (2008), p. 17-158.</ref> | The flame is stopped by cooling. Hot flaming gas that leaves the enclosure has to pass along a narrow path, such as the threads of a screwed joint. In passing, it loses so much heat that only cooled gas, no longer able to cause ignition, reaches the outside.<ref name="Milatovich-8-169" /> Beyler (2002b) describes the same effect: the openings are made small enough that the flame loses sufficient heat as it passes through and is quenched.<ref name="Beyler-2-181" /> Because the hot gases still expand through the opening, they could autoignite outside if the gap were too wide.<ref name="Beyler-2-182" /> The same principle is used in a [[Flame arrester|flame arrester]], which passes the gas flow through small passageways so that a flame is quenched thermally.<ref name="Ural-17-158">Ural and Garzia (2008), p. 17-158.</ref> | ||
[[File:fse-explosionproof-equipment-v1.svg|thumb|upright=1.5|alt=Cross-section of an explosionproof enclosure with an internal explosion and hot gas cooled along a threaded joint before it escapes|Principle of an explosionproof enclosure.]] | |||
Gas and vapour mixtures differ in how easily a flame passes through a joint, in the pressure they develop inside the enclosure after ignition and in their ignition temperature. For that reason the handbook states that explosionproof equipment should be tested and listed for the gas groups for which it is used.<ref name="Milatovich-8-171" /> Equipment for Class I locations must also be designed to operate at full load. Motors that are likely to be overloaded must run under overload without surface temperatures above the ignition temperature of the gas or vapour.<ref name="Milatovich-8-171" /> | Gas and vapour mixtures differ in how easily a flame passes through a joint, in the pressure they develop inside the enclosure after ignition and in their ignition temperature. For that reason the handbook states that explosionproof equipment should be tested and listed for the gas groups for which it is used.<ref name="Milatovich-8-171" /> Equipment for Class I locations must also be designed to operate at full load. Motors that are likely to be overloaded must run under overload without surface temperatures above the ignition temperature of the gas or vapour.<ref name="Milatovich-8-171" /> | ||
| Line 33: | Line 34: | ||
'''Worked example.''' Tests at the most favourable electrode spacing show that optimum mixtures of saturated hydrocarbon vapours and gases in air need about 0.25 mJ to ignite.<ref name="Scarbrough-11-61">Scarbrough (2008a), p. 11-61.</ref> Rearranging the relation gives <math>d_{\parallel} = \sqrt{E_{\min}/0.06} = \sqrt{0.25/0.06} \approx 2.0</math> mm. The quenching diameter in a tube is then about 2.0/0.65 ≈ 3.1 mm. With the MESG taken as half the quenching distance, the safe gap is roughly 1.0 mm.<ref name="Beyler-2-182" /> This suggests that the flame paths of an enclosure for such gases would have to be narrower than about one millimetre. The result is only an estimate of the order of magnitude: actual gas groups are assigned from standard tests, not from this correlation.<ref name="Ural-17-151">Ural and Garzia (2008), p. 17-151.</ref> | '''Worked example.''' Tests at the most favourable electrode spacing show that optimum mixtures of saturated hydrocarbon vapours and gases in air need about 0.25 mJ to ignite.<ref name="Scarbrough-11-61">Scarbrough (2008a), p. 11-61.</ref> Rearranging the relation gives <math>d_{\parallel} = \sqrt{E_{\min}/0.06} = \sqrt{0.25/0.06} \approx 2.0</math> mm. The quenching diameter in a tube is then about 2.0/0.65 ≈ 3.1 mm. With the MESG taken as half the quenching distance, the safe gap is roughly 1.0 mm.<ref name="Beyler-2-182" /> This suggests that the flame paths of an enclosure for such gases would have to be narrower than about one millimetre. The result is only an estimate of the order of magnitude: actual gas groups are assigned from standard tests, not from this correlation.<ref name="Ural-17-151">Ural and Garzia (2008), p. 17-151.</ref> | ||
[[File:fse-explosionproof-equipment-v2.svg|thumb|upright=1.5|alt=Log-log line of minimum ignition energy against quenching distance with the point 0.25 mJ at 2.0 mm marked|Minimum ignition energy against parallel-plate quenching distance for hydrocarbon–air mixtures.]] | |||
== Gas groups and temperature classes == | == Gas groups and temperature classes == | ||
| Line 61: | Line 63: | ||
The table shows that group and temperature class are separate questions. Hydrogen is in Group B but has a fairly high ignition temperature of 400 °C, while diethyl ether is in Group C yet ignites at 160 °C. A Group C enclosure for diethyl ether must therefore carry a marking of T3C or a lower temperature.<ref name="Milatovich-8-165" /><ref name="Milatovich-8-169" /> Carbon disulfide, with an ignition temperature of only 90 °C, carries a footnote in the handbook table instead of a group letter and needs a T6 marking.<ref name="Milatovich-8-165" /> | The table shows that group and temperature class are separate questions. Hydrogen is in Group B but has a fairly high ignition temperature of 400 °C, while diethyl ether is in Group C yet ignites at 160 °C. A Group C enclosure for diethyl ether must therefore carry a marking of T3C or a lower temperature.<ref name="Milatovich-8-165" /><ref name="Milatovich-8-169" /> Carbon disulfide, with an ignition temperature of only 90 °C, carries a footnote in the handbook table instead of a group letter and needs a T6 marking.<ref name="Milatovich-8-165" /> | ||
[[File:fse-explosionproof-equipment-v3.svg|thumb|upright=1.5|alt=Temperature scale with classes T1 to T6 and markers for the autoignition temperatures of seven gases|Temperature classes T1 to T6 compared with autoignition temperatures of selected gases.]] | |||
== Use in US hazardous locations == | == Use in US hazardous locations == | ||
| Line 73: | Line 76: | ||
== Alternatives and limits == | == Alternatives and limits == | ||
Besides explosionproof construction, the handbook describes several alternatives. A [[Purged and pressurised enclosure|purged and pressurised enclosure]] keeps the flammable atmosphere out with clean air or an inert gas under positive pressure, following NFPA 496.<ref name="Milatovich-8-171" /><ref name="Milatovich-8-172" /> Ural and Garzia (2008) add that unrated electrical equipment can be used in hazardous areas when it is contained in such an enclosure.<ref name="Ural-17-151" /> Intrinsically safe systems are a third option. In an intrinsically safe circuit, no spark or thermal effect can release enough energy under normal or abnormal conditions to ignite the specified mixture in air.<ref name="Milatovich-8-172" /> | Besides explosionproof construction, the handbook describes several alternatives. A [[Purged and pressurised enclosure|purged and pressurised enclosure]] keeps the flammable atmosphere out with clean air or an inert gas under positive pressure, following NFPA 496.<ref name="Milatovich-8-171" /><ref name="Milatovich-8-172" /> Ural and Garzia (2008) add that unrated electrical equipment can be used in hazardous areas when it is contained in such an enclosure.<ref name="Ural-17-151" /> Intrinsically safe systems are a third option. In an intrinsically safe circuit, no spark or thermal effect can release enough energy under normal or abnormal conditions to ignite the specified mixture in air.<ref name="Milatovich-8-172" /> | ||
[[File:fse-explosionproof-equipment-v4.svg|thumb|upright=1.5|alt=Flowchart with four options for electrical equipment in a Class I Division 1 location|Options for electrical equipment in a US Class I, Division 1 location.]] | |||
The simplest measure is often layout. The amount of explosionproof, purged or intrinsically safe equipment can be reduced by placing much of the electrical equipment in nonhazardous areas. The extent of the hazardous areas is normally set by the codes and standards for the specific flammable liquids, gases or solids.<ref name="Milatovich-8-172" /> | The simplest measure is often layout. The amount of explosionproof, purged or intrinsically safe equipment can be reduced by placing much of the electrical equipment in nonhazardous areas. The extent of the hazardous areas is normally set by the codes and standards for the specific flammable liquids, gases or solids.<ref name="Milatovich-8-172" /> | ||
Latest revision as of 08:46, 9 November 2026
Explosionproof equipment is electrical equipment housed in an enclosure that can withstand an explosion of a specified gas or vapour inside it without letting the flame escape and ignite the flammable atmosphere around it.[1][2] The enclosure does not keep the gas out. It accepts that gas will enter and may ignite. It is built strong enough to contain the resulting pressure, and its joints cool the escaping gases until they can no longer cause ignition.[3][4] Its outer surface must also stay cooler than the ignition temperature of the surrounding gas.[2]
In the United States, the National Electrical Code (NEC), as summarised in the 2008 handbook, requires explosionproof or equivalent equipment for motors, luminaires and switches in Class I, Division 1 locations.[5] Each item is tested and listed for a gas group and marked with a temperature class.[6] Explosionproof construction is one of several ways to control electrical ignition sources; purged and pressurised enclosures, intrinsically safe circuits and careful layout are the main alternatives.[3][7]
Definition
In the SFPE Handbook of Fire Protection Engineering, Beyler (2002b) names three ways to prevent an explosion from starting. A flammable mixture can be avoided, or ignition sources stronger than the minimum ignition energy can be excluded. Otherwise the ignition source can be placed in an enclosure that does not let the flame propagate outside.[1] Low-power equipment can sometimes be designed so that even its worst fault cannot release the minimum ignition energy of a given gas; such equipment is called intrinsically safe. Where that is not feasible, the equipment may be housed in an explosion-proof enclosure, which will not allow propagation of the flame out of the enclosure.[1]
The NEC gives a more formal definition, which Milatovich (2008) quotes in the handbook. Explosionproof apparatus is "Apparatus enclosed in a case that is capable of withstanding an explosion of a specified gas or vapor that may occur within it". The case must also prevent "the ignition of a specified gas or vapor surrounding the enclosure by sparks, flashes or explosion of the gas or vapor within". Finally, the apparatus "operates at such an external temperature that a surrounding flammable atmosphere will not be ignited thereby".[2] The words "specified gas or vapor" matter: an enclosure is explosionproof only for the gases it was tested for.[3]
In practice the term is tied to the US system of hazardous area classification. Milatovich (2008) notes that equipment for Class I, Division 1 locations, as defined in the NEC, is sometimes referred to as explosionproof equipment.[3] The spellings "explosion-proof" and "explosionproof" are both used in the sources for the same concept.[1][3]
How the enclosure works
An explosionproof enclosure is designed on the assumption that the surrounding gas or vapour and air mixture will enter it and may be ignited inside. To stop the flame from reaching the atmosphere outside, the enclosure must meet three conditions. It must arrest the flame at joints and other openings, and it must resist the internal pressure without rupture or serious distortion. Its external surface must not become hot enough to ignite the surrounding gas.[3]
The flame is stopped by cooling. Hot flaming gas that leaves the enclosure has to pass along a narrow path, such as the threads of a screwed joint. In passing, it loses so much heat that only cooled gas, no longer able to cause ignition, reaches the outside.[5] Beyler (2002b) describes the same effect: the openings are made small enough that the flame loses sufficient heat as it passes through and is quenched.[1] Because the hot gases still expand through the opening, they could autoignite outside if the gap were too wide.[4] The same principle is used in a flame arrester, which passes the gas flow through small passageways so that a flame is quenched thermally.[8]
Gas and vapour mixtures differ in how easily a flame passes through a joint, in the pressure they develop inside the enclosure after ignition and in their ignition temperature. For that reason the handbook states that explosionproof equipment should be tested and listed for the gas groups for which it is used.[3] Equipment for Class I locations must also be designed to operate at full load. Motors that are likely to be overloaded must run under overload without surface temperatures above the ignition temperature of the gas or vapour.[3]
Quenching distance and safe gap
The width of a gap that will stop a flame is linked to how easily the mixture ignites. The quenching distance is measured with a pair of flanged electrodes, which are parallel plates, in the gas mixture. If the mixture can still be ignited between the plates, their separation is greater than the quenching distance.[4] For parallel plates the quenching distance is 65 percent of the quenching diameter in a circular tube.[4] For a number of hydrocarbon and air mixtures, Beyler (2002b) expresses the relation between the minimum ignition energy and the quenching distance as follows:[4]
| Symbol | Description | Unit |
|---|---|---|
| Minimum ignition energy of the mixture in air | mJ | |
| Quenching distance between parallel plates in air | mm |
The relation was derived from data for hydrocarbon and air mixtures, with both quantities measured in air.[4] The ignition energy of near-stoichiometric mixtures in air is typically a few tenths of a millijoule, while near the flammable limits it rises sharply.[1] A second, practical quantity is the maximum experimental safe gap (MESG), the gap through which a flame cannot pass in a standard test.[8] Beyler (2002b) reports that the MESG for most hydrocarbons is approximately half the quenching distance.[4]
Worked example. Tests at the most favourable electrode spacing show that optimum mixtures of saturated hydrocarbon vapours and gases in air need about 0.25 mJ to ignite.[9] Rearranging the relation gives mm. The quenching diameter in a tube is then about 2.0/0.65 ≈ 3.1 mm. With the MESG taken as half the quenching distance, the safe gap is roughly 1.0 mm.[4] This suggests that the flame paths of an enclosure for such gases would have to be narrower than about one millimetre. The result is only an estimate of the order of magnitude: actual gas groups are assigned from standard tests, not from this correlation.[10]
Gas groups and temperature classes
For approval testing and area classification, the NEC groups flammable gases and dusts by their characteristics. In the synopsis by Ural and Garzia (2008), Class I gases fall into Group A (acetylene), Group B (hydrogen), Group C (ethylene) and Group D (propane).[2][10] Class II dusts fall into Group E (metal dusts), Group F (carbonaceous dusts such as coal and charcoal) and Group G (dusts such as flour, grain, wood, plastics and chemicals).[10] The gas groups are based on the MESG and on the minimum igniting current ratio (MIC). The NEC sets the group designations, while NFPA 497 defines the MESG and MIC values for each group.[10] A motor rated for Class I, Division 1, Group D is therefore suitable where a propane-like gas is likely to be present.[10] The NUREG-1805 fire dynamics tools for US nuclear plants use the same group examples and note that MESG is determined by the International Electrotechnical Commission test IEC 79-1A.[11]
Determining the group of a new gas involves measuring explosion pressures and the maximum safe clearance of a clamped joint under several conditions, and comparing the results with gases already evaluated.[6] Explosion pressure, MESG, minimum ignition energy and ignition temperature show no consistent relationship. The tests for group and for temperature class are therefore independent of each other.[6]
The second property is the ignition temperature: the minimum temperature needed to start self-sustained combustion, independent of a heating element. It is always higher than the flashpoint.[6] Listed equipment is marked with its class, group and operating temperature or temperature range. The range is shown by an identification number on the nameplate, and the marked temperature must not exceed the ignition temperature of the gas or vapour present.[6] The identification numbers run from T1, for a maximum surface temperature of 450 °C, to T6, for 85 °C, with intermediate classes such as T2A and T3C.[5]
| Gas or vapour | NEC group | Autoignition temperature (°C) | Highest permissible class (maximum surface temperature) |
|---|---|---|---|
| Methane | D | 537 | T1 (450 °C) |
| Propane | D | 450 | T1 (450 °C) |
| Hydrogen | B | 400 | T2 (300 °C) |
| Acetylene | A | 305 | T2 (300 °C) |
| Hexane | D | 225 | T2D (215 °C) |
| Diethyl ether | C | 160 | T3C (160 °C) |
| Carbon disulfide | see note | 90 | T6 (85 °C) |
The table shows that group and temperature class are separate questions. Hydrogen is in Group B but has a fairly high ignition temperature of 400 °C, while diethyl ether is in Group C yet ignites at 160 °C. A Group C enclosure for diethyl ether must therefore carry a marking of T3C or a lower temperature.[12][5] Carbon disulfide, with an ignition temperature of only 90 °C, carries a footnote in the handbook table instead of a group letter and needs a T6 marking.[12]
Use in US hazardous locations
The handbook summarises the classification of Article 500 of the NEC. Hazardous locations are divided into three classes by the kind of material (gases and vapours, combustible dusts, and fibres and flyings) and into two divisions by the likelihood that the hazard is present.[2] An additional zone method, consistent with the rules of the International Electrotechnical Commission (IEC), is described in Article 505 of the NEC.[2] Electrical equipment can be an ignition source in these areas. Motors, switches, lights and heaters may be powerful ignition sources, which is why such equipment is rated for the atmosphere in which it may be used.[10]
In Class I, Division 1 locations, ignitable concentrations of gas or vapour can exist under normal operation, during repair or maintenance, or when a breakdown releases gas and damages electrical equipment at the same time. Motors, luminaires, most switches, circuit breakers and similar equipment there must be of the explosionproof or purged type, approved for Class I and the proper group.[5] Approved intrinsically safe equipment may also be used, usually for low-energy control, signal and instrumentation circuits.[5]
In Class I, Division 2 locations, the flammable material is normally kept in closed systems or kept below ignitable levels by ventilation. Ordinary motors without brushes or switching contacts are generally acceptable there.[5][13] Devices that make or break ignition-capable currents in normal operation must be explosionproof, have hermetically sealed contacts or have contacts immersed in oil. Lamps that operate above the ignition temperature of the gas need explosionproof or purged enclosures, a point that links the topic to luminaire fire hazards.[13] Portable lamps must always be of a type suitable for Class I, Division 1.[13]
Dust and fibre locations use a different principle. Class II, Division 1 equipment must be dust-ignitionproof, and its surface temperature in service must not exceed the ignition temperature of the dust.[13] Dust-ignitionproof and dust-tight enclosures are not intended to resist an internal dust explosion. They are tested in specific dust and air mixtures and checked for overheating when blanketed with dust or lint.[7] In Class III, Division 1 locations, surface temperatures must not exceed 165 °C (329 °F) for equipment that cannot be overloaded and 120 °C (248 °F) for equipment such as motors that can.[3] These requirements are those of the NEC as described in the 2008 handbook; the handbook does not name the NEC edition.
Alternatives and limits
Besides explosionproof construction, the handbook describes several alternatives. A purged and pressurised enclosure keeps the flammable atmosphere out with clean air or an inert gas under positive pressure, following NFPA 496.[3][7] Ural and Garzia (2008) add that unrated electrical equipment can be used in hazardous areas when it is contained in such an enclosure.[10] Intrinsically safe systems are a third option. In an intrinsically safe circuit, no spark or thermal effect can release enough energy under normal or abnormal conditions to ignite the specified mixture in air.[7]
The simplest measure is often layout. The amount of explosionproof, purged or intrinsically safe equipment can be reduced by placing much of the electrical equipment in nonhazardous areas. The extent of the hazardous areas is normally set by the codes and standards for the specific flammable liquids, gases or solids.[7]
The protection is limited to the gases and conditions for which the enclosure was tested. Equipment must be approved for Class I and for the proper group of the gas present, so a Group D listing does not cover a Group B (hydrogen) or Group A (acetylene) atmosphere.[5][3] Its temperature marking must not exceed the ignition temperature of the gas or vapour present.[6] The handbook requirements describe US practice around 2007 and 2008. The sources used here do not describe the IEC equipment protection methods in detail, apart from noting that the NEC zone method is consistent with IEC rules.[2]
Related terms and misconceptions
Several similar terms are easily confused with explosionproof. For years the NEC used the term "vaportight" for equipment for damp and dusty locations. The term was dropped because many users assumed that such equipment was safe in Class I, II or III locations. It was replaced by "enclosed and gasketed".[14] In the same way, "flameproof" applied to treated fabrics and decorations is described as misleading and open to misunderstanding and abuse, and the handbook advises against it.[15]
The word also appears in process vessel design. Explosion protection standards allow a vessel to be designed either to prevent rupture while allowing permanent deformation, which the handbook calls "explosionproof/shock-resistant", or to prevent permanent deformation, which it calls "explosion-pressure/shock-resistant".[16] This is a pressure containment concept for vessels, not a rating for electrical equipment.
Other sectors use their own terms. In US coal mines, electrical equipment where methane may be present must be "permissible" or intrinsically safe. Permissible equipment has been tested by the federal government, and explosionproof enclosures are among its typical features.[17] On boats, Eberly (2008) states that all ac and dc electrical equipment in a gasoline engine space, or in any space with fuel line fittings, must be "ignition protected". This has the same performance objective as explosionproof equipment on shore but is less stringent and does not require hazardous location wiring.[18]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Beyler (2002b), p. 2-181.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 Milatovich (2008), p. 8-164.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 Milatovich (2008), p. 8-171.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Beyler (2002b), p. 2-182.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Milatovich (2008), p. 8-169.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Milatovich (2008), p. 8-168.
- ↑ 7.0 7.1 7.2 7.3 7.4 Milatovich (2008), p. 8-172.
- ↑ 8.0 8.1 Ural and Garzia (2008), p. 17-158.
- ↑ Scarbrough (2008a), p. 11-61.
- ↑ 10.0 10.1 10.2 10.3 10.4 10.5 10.6 Ural and Garzia (2008), p. 17-151.
- ↑ Iqbal and Salley (2004), p. B-24.
- ↑ 12.0 12.1 12.2 Milatovich (2008), pp. 8-165–8-166.
- ↑ 13.0 13.1 13.2 13.3 Milatovich (2008), p. 8-170.
- ↑ Milatovich (2008), p. 8-162.
- ↑ Shaw (2008), p. 6-130.
- ↑ Ural and Garzia (2008), p. 17-154.
- ↑ L. J. Moore (2008), p. 9-217.
- ↑ Eberly (2008), p. 21-156.
References
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
- Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
- Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
- Shaw, J. R. (2008). Fire-Retardant and flame-resistant treatment of cellulosic materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-129–6-139). National Fire Protection Association.
- Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.