A '''laboratory fume hood''', also called a chemical fume hood or laboratory hood, is a ventilated enclosure for handling toxic or flammable materials. Its airflow captures and dilutes their vapours and exhausts them to a safe location instead of the room.<ref name="Holmes-9-197">Holmes (2008a), p. 9-197.</ref><ref name="Anderson-9-162">Anderson (2008a), p. 9-162.</ref> In the United States its fire protection is covered by NFPA 45, ''Standard on Fire Protection for Laboratories Using Chemicals''. Modern hoods operate under negative pressure relative to the work area, with air entering the open face at 0.41 to 0.61 m/s (80 to 120 ft/min), most commonly 0.5 m/s.<ref name="Anderson-9-162" />
A '''laboratory fume hood''', also called a chemical fume hood or laboratory hood, is a ventilated enclosure for handling toxic or flammable materials. Its airflow captures and dilutes their vapours and exhausts them to a safe location instead of the room.<ref name="Holmes-9-197">Holmes (2008a), p. 9-197.</ref><ref name="Anderson-9-162">Anderson (2008a), p. 9-162.</ref> NFPA 45, ''Standard on Fire Protection for Laboratories Using Chemicals'', sets out fire-protection provisions for chemical fume hoods.<ref name="Anderson-9-160">Anderson (2008a), p. 9-160.</ref> Modern hoods operate under negative pressure relative to the work area, with air entering the open face at 0.41 to 0.61 m/s (80 to 120 ft/min), most commonly 0.5 m/s.<ref name="Anderson-9-162" />


The 20th edition of the NFPA ''Fire Protection Handbook'' (2008) describes the hood both as protection against toxic exposure and as a means of keeping flammable vapour diluted. Its exhaust flow limits the quantity of flammable liquid that can evaporate inside it before the vapour reaches its lower flammability limit.<ref name="Anderson-9-159">Anderson (2008a), p. 9-159.</ref> The handbook also notes that the space under a hood is where laboratory fires are most likely to occur.<ref name="Anderson-9-159" /> Hood exhaust ducts must be noncombustible, should not contain automatic fire dampers and should not be shut down by the building fire alarm.<ref name="Anderson-9-162" />
The 20th edition of the NFPA ''Fire Protection Handbook'' (2008) describes the hood both as protection against toxic exposure and as a means of keeping flammable vapour diluted. Under an idealised mixing assumption, its exhaust flow helps determine how much flammable liquid can evaporate before the mixed vapour reaches its lower flammability limit.<ref name="Anderson-9-159">Anderson (2008a), p. 9-159.</ref> The handbook also notes that the space under a hood is where laboratory fires are most likely to occur.<ref name="Anderson-9-159" /> Hood exhaust ducts must be noncombustible, should not contain automatic fire dampers and should not be shut down by the building fire alarm.<ref name="Anderson-9-162" />


== Purpose and principle of operation ==
== Purpose and principle of operation ==
Line 9: Line 9:


The volume of air a hood exhausts follows directly from the face velocity and the open area of the face. A flow through an opening equals the opening area multiplied by the mean velocity through it.<ref name="VR-3.6">Van Rossum (2027), §3.6.</ref> At the most common face velocity of 0.5 m/s, each square metre of open face therefore draws 0.5 m³/s, or 30 m³ per minute. By the same relation, a smaller open area at the same exhaust flow gives a higher face velocity. Energy conservation devices must be used with care: a user-accessible device must be able to restore maximum exhaust airflow at once, regardless of the sash position.<ref name="Anderson-9-162" />
The volume of air a hood exhausts follows directly from the face velocity and the open area of the face. A flow through an opening equals the opening area multiplied by the mean velocity through it.<ref name="VR-3.6">Van Rossum (2027), §3.6.</ref> At the most common face velocity of 0.5 m/s, each square metre of open face therefore draws 0.5 m³/s, or 30 m³ per minute. By the same relation, a smaller open area at the same exhaust flow gives a higher face velocity. Energy conservation devices must be used with care: a user-accessible device must be able to restore maximum exhaust airflow at once, regardless of the sash position.<ref name="Anderson-9-162" />
[[File:fse-laboratory-fume-hood-v1.svg|thumb|upright=1.5|alt=Side section of a laboratory fume hood with room air entering the open face under the sash and leaving through the exhaust duct at the top|Air enters the open face of a fume hood at the face velocity and leaves through the exhaust duct; the exhaust flow equals face area times face velocity.]]


== Exhaust system and ducts ==
== Exhaust system and ducts ==
Line 18: Line 19:


Hood exhaust must be discharged above the roof at a velocity and height that prevent re-entry into the building.<ref name="Anderson-9-162" /> Fans should suit the duty, for example with corrosion resistance or nonferrous rotating parts, and should be labelled with the laboratories they serve. Where vapours can condense on the blades, a fan with backward-curved blades limits the build-up.<ref name="Lataille-8-7" /> Each hood should have an airflow-measuring device that indicates inadequate or unsafe airflow, and hoods must be designed to contain minor spills.<ref name="Anderson-9-162" />
Hood exhaust must be discharged above the roof at a velocity and height that prevent re-entry into the building.<ref name="Anderson-9-162" /> Fans should suit the duty, for example with corrosion resistance or nonferrous rotating parts, and should be labelled with the laboratories they serve. Where vapours can condense on the blades, a fan with backward-curved blades limits the build-up.<ref name="Lataille-8-7" /> Each hood should have an airflow-measuring device that indicates inadequate or unsafe airflow, and hoods must be designed to contain minor spills.<ref name="Anderson-9-162" />
[[File:fse-laboratory-fume-hood-v2.svg|thumb|upright=1.5|alt=Schematic building section with a fume hood, exhaust duct rising to a roof fan and stack, and supply air entering the laboratory|Exhaust path of a laboratory fume hood and the replacement air supply, with the main fire safety rules.]]


== Replacement air and room pressure ==
== Replacement air and room pressure ==
Line 27: Line 29:
The fire hazard of a flammable liquid comes from its vapour, which ignites only within the flammable range between the lower and upper flammable limits.<ref name="Slye-6-197">Slye (2008), p. 6-197.</ref> The lower or lean limit is the lowest volume percentage of fuel vapour in air that supports flame propagation away from a pilot ignition source.<ref name="Kanury-2-190">Kanury (2002b), p. 2-190.</ref> In a hood, the exhaust air dilutes any vapour, and the question is how much liquid can evaporate before the mixture reaches the lower limit.
The fire hazard of a flammable liquid comes from its vapour, which ignites only within the flammable range between the lower and upper flammable limits.<ref name="Slye-6-197">Slye (2008), p. 6-197.</ref> The lower or lean limit is the lowest volume percentage of fuel vapour in air that supports flame propagation away from a pilot ignition source.<ref name="Kanury-2-190">Kanury (2002b), p. 2-190.</ref> In a hood, the exhaust air dilutes any vapour, and the question is how much liquid can evaporate before the mixture reaches the lower limit.


The handbook explains that hood interiors are generally treated as electrically unclassified, that is, as general-purpose locations under Article 500 of NFPA 70.<ref name="Anderson-9-159" /> In normal use the combination of airflow and vapour concentration does not allow a stoichiometric mixture for the specific quantities of flammable liquid considered in NFPA 45. The classification depends on the ventilation rate, the quantity of flammable material and the process.<ref name="Anderson-9-159" /> The handbook method assumes that the liquid evaporates within 1 minute and mixes perfectly with the exhaust air. The exhaust volume is then the key parameter for the maximum quantity that keeps the vapour below the [[Flammability limits|lower flammable limit]].<ref name="Anderson-9-159" />
The handbook explains that hood interiors are generally treated as electrically unclassified, that is, as general-purpose locations under Article 500 of NFPA 70.<ref name="Anderson-9-159" /> It links this classification to adequate ventilation, controlled quantities of flammable liquid and the chemical process.<ref name="Anderson-9-159" /> The lower flammable limit is the relevant boundary for the following screening calculation: avoiding a stoichiometric mixture alone would not establish that a vapour-air mixture cannot ignite.<ref name="Kanury-2-190" /> The handbook method assumes that the liquid evaporates within 1 minute and mixes perfectly with the exhaust air. The exhaust volume is then the key parameter for the quantity at which the mixed exhaust reaches the [[Flammability limits|lower flammable limit]].<ref name="Anderson-9-159" />


The calculation follows from three simple relations. The vapour volume that brings 1 minute of exhaust air to the lower flammable limit is that limit times the exhaust volume. The ideal gas law turns this vapour volume into an amount of substance, and the molar mass and liquid density turn that into a mass and volume of liquid:<ref name="Drysdale-2-9">Drysdale (2008), p. 2-9.</ref><ref name="VR-3.6" />
The calculation follows from three simple relations. The vapour volume that brings 1 minute of mixed exhaust to the lower flammable limit is that limit times the exhaust volume. The ideal gas law turns this vapour volume into an amount of substance, and the molar mass and liquid density turn that into a mass and volume of liquid:<ref name="Drysdale-2-9">Drysdale (2008), p. 2-9.</ref><ref name="VR-3.6" />


<math display="block">m_\mathrm{max} = \frac{p\,x_\mathrm{L}\,\dot V_\mathrm{e}\,t\,M}{R\,T}, \qquad V_\mathrm{liq} = \frac{m_\mathrm{max}}{\rho_\mathrm{liq}}, \qquad \dot V_\mathrm{e} = A\,v</math>
<math display="block">m_\mathrm{L} = \frac{p\,x_\mathrm{L}\,\dot V_\mathrm{e}\,t\,M}{R\,T}, \qquad V_\mathrm{liq,L} = \frac{m_\mathrm{L}}{\rho_\mathrm{liq}}, \qquad \dot V_\mathrm{e} = A\,v</math>


{| class="wikitable"
{| class="wikitable"
! Symbol !! Description !! Unit
! Symbol !! Description !! Unit
|-
|-
| <math>m_\mathrm{max}</math> || Mass of liquid that can evaporate within time t before the mixed exhaust reaches the lower flammable limit || kg
| <math>m_\mathrm{L}</math> || Mass of liquid evaporated within time t that brings perfectly mixed exhaust to the lower flammable limit || kg
|-
|-
| <math>V_\mathrm{liq}</math> || Corresponding volume of liquid || m³
| <math>V_\mathrm{liq,L}</math> || Corresponding volume of liquid at that threshold || m³
|-
|-
| <math>p</math> || Absolute pressure (101,325 Pa at sea level) || Pa
| <math>p</math> || Absolute pressure (101,325 Pa at sea level) || Pa
Line 61: Line 63:
|}
|}


'''Worked example.''' Take 1 m² of open face at 0.5 m/s, so that 30 m³ of air passes in 1 minute, at 20 °C (293 K) and 101,325 Pa. Acetone has a lower limit of 0.026 by volume and a molar mass of 58 kg/kmol.<ref name="Kanury-2-193">Kanury (2002b), p. 2-193.</ref> The permissible vapour is 0.026 × 30 = 0.78 m³, or 32 mol, which is 1.88 kg of acetone. With a liquid density of 791 kg/m³, this is about 2.3 L of liquid per minute for each square metre of open face.<ref name="Babrauskas-3-26">Babrauskas (2002b), p. 3-26.</ref> The same method gives about 2.3 L for ethanol and 1.9 L for hexane, whose lower limit is partly offset by its higher molar mass.<ref name="Kanury-2-192">Kanury (2002b), p. 2-192.</ref><ref name="Babrauskas-3-26" />
'''Worked example.''' Take 1 m² of open face at 0.5 m/s, so that 30 m³ of exhaust mixture passes in 1 minute, at 20 °C (293 K) and 101,325 Pa. Acetone has a lower limit of 0.026 by volume and a molar mass of 58 kg/kmol.<ref name="Kanury-2-193">Kanury (2002b), p. 2-193.</ref> At that threshold, acetone vapour occupies 0.026 × 30 = 0.78 m³, or about 32 mol, which is 1.88 kg of acetone. With a liquid density of 791 kg/m³, this corresponds to about 2.38 L of liquid evaporated in 1 minute per square metre of open face.<ref name="Babrauskas-3-26">Babrauskas (2002b), p. 3-26.</ref> The same method gives about 2.38 L for ethanol and 1.98 L for ''n''-hexane, whose lower limit is partly offset by its higher molar mass.<ref name="Kanury-2-192">Kanury (2002b), p. 2-192.</ref><ref name="Babrauskas-3-26" />
[[File:fse-laboratory-fume-hood-v3.svg|thumb|upright=1.5|alt=Five rising lines of solvent volume at the lower flammable limit against hood face velocity, with the usual velocity range shaded|Theoretical liquid evaporated in one minute per square metre of open face when perfectly mixed hood exhaust reaches the lower flammable limit (20 °C, 1 atm); not a permitted handling quantity.]]


The calculation also shows that one litre of liquid acetone forms about 0.33 m³ of vapour at room temperature. At the lower face velocity of 0.41 m/s the acetone value falls to about 1.9 L per square metre and minute. The method assumes constant ventilation; the handbook considers a ventilation failure at the same moment as an unexpected release of vapour above the limit to be highly unlikely.<ref name="Anderson-9-160">Anderson (2008a), p. 9-160.</ref> If larger quantities are present, an ignitable vapour could form and a fire or explosion could follow, and the hood or the room may then have to be treated as a hazardous location.<ref name="Anderson-9-159" />
The calculation also shows that one litre of liquid acetone forms about 0.33 m³ of vapour at room temperature. At the lower face velocity of 0.41 m/s the acetone threshold falls to about 1.95 L per square metre and minute. These results describe a perfectly mixed exhaust at the lower flammable limit; they are not permissible handling quantities or a prediction of the actual evaporation rate. Vapour concentrations near the liquid can be higher than the exhaust average.<ref name="Kanury-2-189">Kanury (2002b), p. 2-189.</ref> The method assumes constant ventilation; the handbook considers a ventilation failure at the same moment as an unexpected release of vapour above the limit to be highly unlikely.<ref name="Anderson-9-160" /> If larger quantities are present, an ignitable vapour could form and a fire or explosion could follow, and the hood or the room may then have to be treated as a hazardous location.<ref name="Anderson-9-159" />


== Fire protection of hoods ==
== Fire protection of hoods ==
Automatic fire dampers should not be located in laboratory hood exhaust ducts.<ref name="Anderson-9-162" /> This differs from ordinary air-conditioning ducts, where a [[fire damper]] closes the opening when a duct passes through a fire barrier rated above 1 hour, usually released by a fusible link.<ref name="Webb-10-73">Webb (2008), p. 10-73.</ref><ref name="Webb-10-74">Webb (2008), p. 10-74.</ref> Likewise, the building fire alarm system should not be interlocked to shut down hood exhaust, because that could cause a dangerous build-up of flammable or toxic vapours.<ref name="Anderson-9-162" /> Where ventilation is critical during hazardous work, uninterrupted or emergency power may be required for the hoods.<ref name="Anderson-9-159" />
Automatic fire dampers should not be located in laboratory hood exhaust ducts.<ref name="Anderson-9-162" /> This differs from ordinary air-conditioning ducts, where a [[fire damper]] closes the opening when a duct passes through a fire barrier rated above 1 hour, usually released by a fusible link.<ref name="Webb-10-73">Webb (2008), p. 10-73.</ref><ref name="Webb-10-74">Webb (2008), p. 10-74.</ref> Likewise, the building fire alarm system should not be interlocked to shut down hood exhaust, because that could cause a dangerous build-up of flammable or toxic vapours.<ref name="Anderson-9-162" /> Where ventilation is critical during hazardous work, uninterrupted or emergency power may be required for the hoods.<ref name="Anderson-9-159" />


A hood that is used properly contains no hazardous vapours in the sense of the model building codes, so hoods are exempt from requirements for automatic fire protection.<ref name="Anderson-9-162" /> NFPA 45 requires automatic protection in a hood only where a hazard assessment shows a need, or where an existing hood used for flammable liquids has an interior flame spread index above 25.<ref name="Anderson-9-160" /> Where protection is extended to a hood, tests showed sprinklers with water mist nozzles to be the most effective option when nonthermal damage outside the hood is a concern. Clean agents are less suitable, because fire tests in the United Kingdom showed them breaking down into significant toxic by-products, and the hood must be shut down for them to work.<ref name="Anderson-9-160" /> Any automatic system that operates should send a signal to a constantly monitored station in accordance with NFPA 72.
A properly used hood is treated as containing no “hazardous vapours” under the model building-code definition cited by the handbook; this does not mean that no flammable or toxic vapour can be present. On that basis, automatic fire protection is not generally required inside hoods or their exhaust systems.<ref name="Anderson-9-162" /> The handbook describes two exceptions under NFPA 45 (2004). A hood needs automatic protection if a hazard assessment calls for it, or if an existing hood used for flammable liquids has an interior flame spread index above 25.<ref name="Anderson-9-160" />


[[Chemical incompatibility]] between water and water-reactive materials calls for special precautions against an inadvertent discharge in hoods where such materials are used.<ref name="Anderson-9-160" /> Even so, when a hood is burning with a flammable liquid fire, the reaction with water, even with sodium metal, is not severe enough to rule out water. This assumes that the hood is not used for significant open storage. Solvents should not be stored under a hood at all, because that is the location where fires are most likely to occur in laboratories.<ref name="Anderson-9-159" />
Where protection is extended to a hood, tests showed sprinklers with water mist nozzles to be the most effective option when nonthermal damage outside the hood is a concern. Clean agents are less suitable, because fire tests in the United Kingdom showed them breaking down into significant toxic by-products, and the hood must be shut down for them to work.<ref name="Anderson-9-160" /> Any automatic system that operates should send a signal to a constantly monitored station in accordance with NFPA 72.
 
[[Chemical incompatibility]] between water and water-reactive materials calls for special precautions against an inadvertent discharge in hoods where such materials are used.<ref name="Anderson-9-160" /> For the flammable-liquid hood fire considered by the 2008 handbook, the authors judge that a reaction with water, even involving sodium metal, does not by itself rule out water-based protection. This assumes that the hood is not used for significant out-of-container storage.<ref name="Anderson-9-160" /> Solvents should not be stored under a hood at all, because that is the location where fires are most likely to occur in laboratories.<ref name="Anderson-9-159" />


The position of the hood also matters for escape. In a [[chemical laboratory]], a hood located next to the primary means of egress is one of the situations in which NFPA 45 requires a second means of access to an exit.<ref name="Anderson-9-158" /> Class I flammable liquids in containers of up to 19 L (5 gal) should be dispensed in a chemical fume hood. The alternative is an area ventilated to keep vapour below 25 percent of the lower flammable limit.<ref name="Anderson-9-164">Anderson (2008a), p. 9-164.</ref>
The position of the hood also matters for escape. In a [[chemical laboratory]], a hood located next to the primary means of egress is one of the situations in which NFPA 45 requires a second means of access to an exit.<ref name="Anderson-9-158" /> Class I flammable liquids in containers of up to 19 L (5 gal) should be dispensed in a chemical fume hood. The alternative is an area ventilated to keep vapour below 25 percent of the lower flammable limit.<ref name="Anderson-9-164">Anderson (2008a), p. 9-164.</ref>
Line 82: Line 87:
Every laboratory hood should be listed in an inventory with its last inspection date, inspection interval, average face velocity and the location of its exhaust fan and controls.<ref name="Anderson-9-162" /> Hoods should be tested and inspected after installation, after modification and at least annually. A lockout procedure with signs at the hood shows when a hood is out of service. Laboratory staff should be trained to recognise unsafe conditions and to arrange for repairs.<ref name="Anderson-9-162" />
Every laboratory hood should be listed in an inventory with its last inspection date, inspection interval, average face velocity and the location of its exhaust fan and controls.<ref name="Anderson-9-162" /> Hoods should be tested and inspected after installation, after modification and at least annually. A lockout procedure with signs at the hood shows when a hood is out of service. Laboratory staff should be trained to recognise unsafe conditions and to arrange for repairs.<ref name="Anderson-9-162" />


These requirements describe US practice as summarised in the 2008 handbook and may differ in later editions and in other countries. The vapour calculation above is a screening estimate that assumes perfect mixing and evaporation within 1 minute.<ref name="Anderson-9-159" /> Flammability limits also depend on temperature.<ref name="Kanury-2-189">Kanury (2002b), p. 2-189.</ref> The handbook gives the method in outline only; the full rationale and calculations are in the informational part of NFPA 45. Heavier-than-air vapours are generally best removed through exhaust openings near the floor, and lighter ones near the top of the room, hood or enclosure.<ref name="Lataille-8-7" />
These requirements describe US practice as summarised in the 2008 handbook and may differ in later editions and in other countries. The vapour calculation above is a screening estimate that assumes perfect mixing and evaporation within 1 minute.<ref name="Anderson-9-159" /> Flammability limits also depend on temperature.<ref name="Kanury-2-189" /> The handbook gives the method in outline only; the full rationale and calculations are in the informational part of NFPA 45. Heavier-than-air vapours are generally best removed through exhaust openings near the floor, and lighter ones near the top of the room, hood or enclosure.<ref name="Lataille-8-7" />


== See also ==
== See also ==

Latest revision as of 08:31, 13 November 2026

A laboratory fume hood, also called a chemical fume hood or laboratory hood, is a ventilated enclosure for handling toxic or flammable materials. Its airflow captures and dilutes their vapours and exhausts them to a safe location instead of the room.[1][2] NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, sets out fire-protection provisions for chemical fume hoods.[3] Modern hoods operate under negative pressure relative to the work area, with air entering the open face at 0.41 to 0.61 m/s (80 to 120 ft/min), most commonly 0.5 m/s.[2]

The 20th edition of the NFPA Fire Protection Handbook (2008) describes the hood both as protection against toxic exposure and as a means of keeping flammable vapour diluted. Under an idealised mixing assumption, its exhaust flow helps determine how much flammable liquid can evaporate before the mixed vapour reaches its lower flammability limit.[4] The handbook also notes that the space under a hood is where laboratory fires are most likely to occur.[4] Hood exhaust ducts must be noncombustible, should not contain automatic fire dampers and should not be shut down by the building fire alarm.[2]

Purpose and principle of operation

A hood is similar to a laboratory bench, except that an enclosure and an exhaust system are added to remove vapours.[1] When activities involve toxic or flammable materials in quantities that cannot be handled safely in the open work area, they should be carried out in a hood.[2] The air drawn through the face mixes with and dilutes the vapours and carries them to a safe location. One aim is to prevent exposure of personnel to toxic or odorous materials during normal work.[5] Vapours from normal laboratory work are exhausted with nonrecirculated air through hoods and other local exhaust.[5]

Other ventilated enclosures serve different purposes and cannot replace a laboratory hood. A canopy hood exhausts heat, water vapour, odours and other nonhazardous materials. A laminar flow cabinet provides filtered airflow over the work surface, and a biological cabinet protects personnel, product and the environment.[5]

The volume of air a hood exhausts follows directly from the face velocity and the open area of the face. A flow through an opening equals the opening area multiplied by the mean velocity through it.[6] At the most common face velocity of 0.5 m/s, each square metre of open face therefore draws 0.5 m³/s, or 30 m³ per minute. By the same relation, a smaller open area at the same exhaust flow gives a higher face velocity. Energy conservation devices must be used with care: a user-accessible device must be able to restore maximum exhaust airflow at once, regardless of the sash position.[2]

Side section of a laboratory fume hood with room air entering the open face under the sash and leaving through the exhaust duct at the top
Air enters the open face of a fume hood at the face velocity and leaves through the exhaust duct; the exhaust flow equals face area times face velocity.

Exhaust system and ducts

A hood is connected to a local industrial exhaust system. The handbook shows a laboratory exhaust system serving cabinet-type and bench-type fume hoods, with a centrifugal exhaust fan, ductwork, a manual balancing damper and a fan discharge stack.[7] An industrial version includes a vertical fume scrubber. Air ducts of hoods must be noncombustible and designed to stay at negative pressure relative to the area outside the duct.[2] Combustible duct linings must have a flame spread index of 25 or less in the NFPA 255 test, and duct systems are designed to NFPA 91.

Ducts that carry flammable vapours need to withstand some fire exposure, because flash fires or explosions can occur inside them.[8] Continuously welded joints prevent leakage where vapours can condense. Such ducts should never be concealed in a wall or ceiling, and they should end outdoors where the vapours cannot be ignited. Frequent cleaning of ducts and filters reduces both the intensity of a duct fire and the risk of self-heating of deposits.[8]

Corrosive fumes govern the choice of duct material. Heavier-gauge metal, protective coatings, special linings or stainless steel may be used.[8] Plastic ducts are acceptable only if the corrosive vapours are nonflammable and the plastic has a flame spread rating of 25 or less and a smoke-developed rating of 50 or less. Where plastic ducts are used, automatic fire protection is needed in the ducts and at the hood or other intake.[9]

Hood exhaust must be discharged above the roof at a velocity and height that prevent re-entry into the building.[2] Fans should suit the duty, for example with corrosion resistance or nonferrous rotating parts, and should be labelled with the laboratories they serve. Where vapours can condense on the blades, a fan with backward-curved blades limits the build-up.[8] Each hood should have an airflow-measuring device that indicates inadequate or unsafe airflow, and hoods must be designed to contain minor spills.[2]

Schematic building section with a fume hood, exhaust duct rising to a roof fan and stack, and supply air entering the laboratory
Exhaust path of a laboratory fume hood and the replacement air supply, with the main fire safety rules.

Replacement air and room pressure

A laboratory must be ventilated continuously and is normally kept at negative pressure relative to the nonlaboratory areas of the building.[2] Supply air must not carry toxic or flammable vapours back into the room, so fresh air intakes are placed remote from the exhaust discharges. The disposition of room air is governed by NFPA 90A. Depending on the chemicals and operations, ventilation rates might be reduced outside working hours when the rooms are unoccupied.[2]

The air removed by the hoods has to be replaced. Replacement air, or makeup air, is the air brought into a space to limit pressure differences so that an exhaust process can work as designed.[10] For commercial kitchen hoods, the handbook states that the makeup system must run whenever the exhaust runs, match the exhausted quantity and not disturb the hood.[11] In a laboratory, the handbook points to the consequence of an imbalance. If the supply air stops while the hoods keep exhausting, the room can reach such a negative pressure that the exit door becomes extremely hard to open.[12]

Flammable vapours and electrical classification

The fire hazard of a flammable liquid comes from its vapour, which ignites only within the flammable range between the lower and upper flammable limits.[13] The lower or lean limit is the lowest volume percentage of fuel vapour in air that supports flame propagation away from a pilot ignition source.[14] In a hood, the exhaust air dilutes any vapour, and the question is how much liquid can evaporate before the mixture reaches the lower limit.

The handbook explains that hood interiors are generally treated as electrically unclassified, that is, as general-purpose locations under Article 500 of NFPA 70.[4] It links this classification to adequate ventilation, controlled quantities of flammable liquid and the chemical process.[4] The lower flammable limit is the relevant boundary for the following screening calculation: avoiding a stoichiometric mixture alone would not establish that a vapour-air mixture cannot ignite.[14] The handbook method assumes that the liquid evaporates within 1 minute and mixes perfectly with the exhaust air. The exhaust volume is then the key parameter for the quantity at which the mixed exhaust reaches the lower flammable limit.[4]

The calculation follows from three simple relations. The vapour volume that brings 1 minute of mixed exhaust to the lower flammable limit is that limit times the exhaust volume. The ideal gas law turns this vapour volume into an amount of substance, and the molar mass and liquid density turn that into a mass and volume of liquid:[15][6]

mL=pxLV˙etMRT,Vliq,L=mLρliq,V˙e=Av

Symbol Description Unit
mL Mass of liquid evaporated within time t that brings perfectly mixed exhaust to the lower flammable limit kg
Vliq,L Corresponding volume of liquid at that threshold m³
p Absolute pressure (101,325 Pa at sea level) Pa
xL Lower flammable limit as a volume fraction –
V˙e Hood exhaust flow m³/s
t Evaporation time assumed by the method (60 s) s
M Molar mass of the vapour kg/mol
R Ideal gas constant, 8.314 J/(mol·K)
T Absolute temperature of the exhaust air K
ρliq Density of the liquid kg/m³
A Open face area of the hood m²
v Face velocity m/s

Worked example. Take 1 m² of open face at 0.5 m/s, so that 30 m³ of exhaust mixture passes in 1 minute, at 20 °C (293 K) and 101,325 Pa. Acetone has a lower limit of 0.026 by volume and a molar mass of 58 kg/kmol.[16] At that threshold, acetone vapour occupies 0.026 × 30 = 0.78 m³, or about 32 mol, which is 1.88 kg of acetone. With a liquid density of 791 kg/m³, this corresponds to about 2.38 L of liquid evaporated in 1 minute per square metre of open face.[17] The same method gives about 2.38 L for ethanol and 1.98 L for n-hexane, whose lower limit is partly offset by its higher molar mass.[18][17]

Five rising lines of solvent volume at the lower flammable limit against hood face velocity, with the usual velocity range shaded
Theoretical liquid evaporated in one minute per square metre of open face when perfectly mixed hood exhaust reaches the lower flammable limit (20 °C, 1 atm); not a permitted handling quantity.

The calculation also shows that one litre of liquid acetone forms about 0.33 m³ of vapour at room temperature. At the lower face velocity of 0.41 m/s the acetone threshold falls to about 1.95 L per square metre and minute. These results describe a perfectly mixed exhaust at the lower flammable limit; they are not permissible handling quantities or a prediction of the actual evaporation rate. Vapour concentrations near the liquid can be higher than the exhaust average.[19] The method assumes constant ventilation; the handbook considers a ventilation failure at the same moment as an unexpected release of vapour above the limit to be highly unlikely.[3] If larger quantities are present, an ignitable vapour could form and a fire or explosion could follow, and the hood or the room may then have to be treated as a hazardous location.[4]

Fire protection of hoods

Automatic fire dampers should not be located in laboratory hood exhaust ducts.[2] This differs from ordinary air-conditioning ducts, where a fire damper closes the opening when a duct passes through a fire barrier rated above 1 hour, usually released by a fusible link.[20][21] Likewise, the building fire alarm system should not be interlocked to shut down hood exhaust, because that could cause a dangerous build-up of flammable or toxic vapours.[2] Where ventilation is critical during hazardous work, uninterrupted or emergency power may be required for the hoods.[4]

A properly used hood is treated as containing no “hazardous vapours” under the model building-code definition cited by the handbook; this does not mean that no flammable or toxic vapour can be present. On that basis, automatic fire protection is not generally required inside hoods or their exhaust systems.[2] The handbook describes two exceptions under NFPA 45 (2004). A hood needs automatic protection if a hazard assessment calls for it, or if an existing hood used for flammable liquids has an interior flame spread index above 25.[3]

Where protection is extended to a hood, tests showed sprinklers with water mist nozzles to be the most effective option when nonthermal damage outside the hood is a concern. Clean agents are less suitable, because fire tests in the United Kingdom showed them breaking down into significant toxic by-products, and the hood must be shut down for them to work.[3] Any automatic system that operates should send a signal to a constantly monitored station in accordance with NFPA 72.

Chemical incompatibility between water and water-reactive materials calls for special precautions against an inadvertent discharge in hoods where such materials are used.[3] For the flammable-liquid hood fire considered by the 2008 handbook, the authors judge that a reaction with water, even involving sodium metal, does not by itself rule out water-based protection. This assumes that the hood is not used for significant out-of-container storage.[3] Solvents should not be stored under a hood at all, because that is the location where fires are most likely to occur in laboratories.[4]

The position of the hood also matters for escape. In a chemical laboratory, a hood located next to the primary means of egress is one of the situations in which NFPA 45 requires a second means of access to an exit.[12] Class I flammable liquids in containers of up to 19 L (5 gal) should be dispensed in a chemical fume hood. The alternative is an area ventilated to keep vapour below 25 percent of the lower flammable limit.[22]

Perchloric acid and special-purpose hoods

Perchloric acid needs dedicated hoods. It is widely used in analytical laboratories, it greatly increases the burning rate of organic substances, and explosions have occurred at wood and plastic laboratory hoods after long exposure to its vapours.[23] Hoods for perchloric acid must be designed and identified for that purpose and fitted with a water spray system with collection of the wash-down water.[2] A perchloric acid hood may only be used for other work after testing shows that it is free of residual perchlorates.

Hoods in facilities handling radioactive materials follow similar fire protection and ventilation requirements to glove boxes. For laboratory exhaust hoods, however, the handbook refers to NFPA 45.[1] Where such hoods need filters to prevent the spread of radioactive materials, filters with a low degree of combustibility are desirable.

Inspection, testing and limitations

Every laboratory hood should be listed in an inventory with its last inspection date, inspection interval, average face velocity and the location of its exhaust fan and controls.[2] Hoods should be tested and inspected after installation, after modification and at least annually. A lockout procedure with signs at the hood shows when a hood is out of service. Laboratory staff should be trained to recognise unsafe conditions and to arrange for repairs.[2]

These requirements describe US practice as summarised in the 2008 handbook and may differ in later editions and in other countries. The vapour calculation above is a screening estimate that assumes perfect mixing and evaporation within 1 minute.[4] Flammability limits also depend on temperature.[19] The handbook gives the method in outline only; the full rationale and calculations are in the informational part of NFPA 45. Heavier-than-air vapours are generally best removed through exhaust openings near the floor, and lighter ones near the top of the room, hood or enclosure.[8]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Holmes (2008a), p. 9-197.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 Anderson (2008a), p. 9-162.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Anderson (2008a), p. 9-160.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 Anderson (2008a), p. 9-159.
  5. ↑ 5.0 5.1 5.2 Anderson (2008a), p. 9-161.
  6. ↑ 6.0 6.1 Van Rossum (2027), §3.6.
  7. ↑ Lataille (2008), p. 8-9.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 Lataille (2008), p. 8-7.
  9. ↑ Lataille (2008), p. 8-8.
  10. ↑ Demers (2008b), p. 10-78.
  11. ↑ Demers (2008b), p. 10-88.
  12. ↑ 12.0 12.1 Anderson (2008a), p. 9-158.
  13. ↑ Slye (2008), p. 6-197.
  14. ↑ 14.0 14.1 Kanury (2002b), p. 2-190.
  15. ↑ Drysdale (2008), p. 2-9.
  16. ↑ Kanury (2002b), p. 2-193.
  17. ↑ 17.0 17.1 Babrauskas (2002b), p. 3-26.
  18. ↑ Kanury (2002b), p. 2-192.
  19. ↑ 19.0 19.1 Kanury (2002b), p. 2-189.
  20. ↑ Webb (2008), p. 10-73.
  21. ↑ Webb (2008), p. 10-74.
  22. ↑ Anderson (2008a), p. 9-164.
  23. ↑ Davenport (2008), p. 7-52.

References

  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
  • Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Holmes, W. D. (2008a). Nuclear facilities. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-191–9-201). National Fire Protection Association.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Webb, W. A. (2008). Air-Conditioning and ventilating systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-69–10-76). National Fire Protection Association.