'''Darcy-Weisbach equation''' is an equation that calculates distributed pipe head loss from friction factor, pipe geometry and mean flow velocity. <ref name="T_4-50_4-52">Titus (2002), ch. 4-2, pp. 4-50–4-52.</ref> Its friction factor depends on Reynolds number and, in turbulent flow, relative pipe roughness. The method keeps fluid viscosity visible through the flow-regime calculation. This distinguishes it from empirical water-only relations, although both still require reliable information about the actual pipe and flow. <ref name="T_4-50_4-53">Titus (2002), ch. 4-2, pp. 4-50–4-53.</ref>
'''Darcy-Weisbach equation''' is an equation that calculates distributed pipe head loss from friction factor, pipe geometry and mean flow velocity. <ref name="T_4-50_4-52">Titus (2002), ch. 4-2, pp. 4-50–4-52.</ref> Its friction factor depends on Reynolds number and, in turbulent flow, relative pipe roughness. The method keeps fluid viscosity visible through the flow-regime calculation. This distinguishes it from empirical water-only relations, although both still require reliable information about the actual pipe and flow. <ref name="T_4-50_4-53">Titus (2002), ch. 4-2, pp. 4-50–4-53.</ref>


The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. <ref name="T_4-47_4-56">Titus (2002), ch. 4-2, pp. 4-47–4-56.</ref><ref name="F_4-81_4-83">Fleming (2002), ch. 4-3, pp. 4-81–4-83.</ref> Static pressure and flowing pressure describe different conditions. <ref name="F_4-81">Fleming (2002), ch. 4-3, pp. 4-81.</ref>
The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. <ref name="T_4-47_4-56">Titus (2002), ch. 4-2, pp. 4-47–4-56.</ref><ref name="F_4-81_4-83">Fleming (2002), ch. 4-3, pp. 4-81–4-83.</ref> Static pressure and flowing pressure describe different conditions. <ref name="F_4-81">Fleming (2002), ch. 4-3, p. 4-81.</ref>


== Flow regime and factor convention ==
== Flow regime and factor convention ==
[[Hydraulic calculation]] uses the equation to quantify [[Friction loss|friction loss]] along a defined route. [[Turbulence]] changes the relationship between wall condition, velocity and resistance. The [[Hazen-Williams formula]] instead represents water-service behaviour through an empirical coefficient. The choice of method must follow the fluid and operating conditions being represented. <ref name="T_4-49_4-53">Titus (2002), ch. 4-2, pp. 4-49–4-53.</ref>
[[Hydraulic calculation]] uses the equation to quantify [[Friction loss|friction loss]] along a defined route; [[Turbulence|turbulence]] changes the relationship between wall condition, velocity and resistance. The [[Hazen-Williams formula]] instead represents water-service behaviour through an empirical coefficient. The choice of method must follow the fluid and operating conditions being represented. <ref name="T_4-49_4-53">Titus (2002), ch. 4-2, pp. 4-49–4-53.</ref>
[[File:fse-darcy-weisbach-equation-v1.svg|thumb|upright=1.5|alt=Darcy-Weisbach equation: functional relationships. Measurement and water paths are distinct.|Darcy-Weisbach equation: functional relationships. Schematic explanation; dimensions are not installation instructions.]]


The [[Bernoulli equation]] provides the surrounding energy balance. Darcy-Weisbach supplies a loss term within that balance rather than replacing elevation, pressure and velocity terms. A more detailed friction model cannot correct an omitted supply segment or an incorrect pressure datum. The network description and the resistance calculation must both represent the installation. <ref name="T_4-47_4-52">Titus (2002), ch. 4-2, pp. 4-47–4-52.</ref>
The [[Bernoulli equation]] provides the surrounding energy balance; Darcy-Weisbach supplies a loss term within that balance rather than replacing elevation, pressure and velocity terms. A more detailed friction model cannot correct an omitted supply segment or an incorrect pressure datum. The network description and the resistance calculation must both represent the installation. <ref name="T_4-47_4-52">Titus (2002), ch. 4-2, pp. 4-47–4-52.</ref>


A [[Water mist system|water mist system]] can have a hydraulic arrangement different from a conventional sprinkler system. Its presence does not by itself justify transferring sprinkler-specific empirical assumptions. Titus's treatment makes fluid properties and flow regime explicit when selecting a loss method. No particular mist-system pressure, nozzle demand or installation criterion follows from the Darcy-Weisbach equation alone. <ref name="T_4-50_4-53" /><ref name="H_16_9_16-181">Cote (2008), ch. 16.9, pp. 16-181.</ref>
A [[Water mist system|water mist system]] can have a hydraulic arrangement different from a conventional sprinkler system; its presence does not by itself justify transferring sprinkler-specific empirical assumptions. Titus's treatment makes fluid properties and flow regime explicit when selecting a loss method. No particular mist-system pressure, nozzle demand or installation criterion follows from the Darcy-Weisbach equation alone. <ref name="T_4-50_4-53" /><ref name="H_16_9_16-181">Cote (2008), ch. 16.9, p. 16-181.</ref>


== Applying the Darcy-Weisbach relation ==
== Applying the Darcy-Weisbach relation ==
The Darcy-Weisbach relation describes distributed pipe loss using mean velocity and a friction factor. The factor represents the effect of the flow regime and pipe condition. Reynolds number connects velocity and diameter with the fluid's kinematic viscosity. Relative roughness compares the wall's characteristic roughness with the internal diameter. <ref name="T_4-49_4-52">Titus (2002), ch. 4-2, pp. 4-49–4-52.</ref>
The Darcy-Weisbach relation describes distributed pipe loss using mean velocity and a friction factor; the factor represents the effect of the flow regime and pipe condition. Reynolds number connects velocity and diameter with the fluid's kinematic viscosity. Relative roughness compares the wall's characteristic roughness with the internal diameter. <ref name="T_4-49_4-52">Titus (2002), ch. 4-2, pp. 4-49–4-52.</ref>
[[File:fse-darcy-weisbach-equation-v2.svg|thumb|upright=1.5|alt=Selecting a friction factor. Measurement and water paths are distinct.|Selecting a friction factor. Schematic explanation; dimensions are not installation instructions.]]


The equation below gives head loss in metres of the flowing fluid. Pressure loss follows by multiplying head loss by density and gravitational acceleration. The factor is the Darcy friction factor used in the cited handbook equation. Keeping its convention explicit prevents confusion with other friction-factor definitions. <ref name="T_4-50_4-52" />
The equation below gives head loss in metres of the flowing fluid; pressure loss follows by multiplying head loss by density and gravitational acceleration. The factor is the Darcy friction factor used in the cited handbook equation. Keeping its convention explicit prevents confusion with other friction-factor definitions. <ref name="T_4-50_4-52" />


<math display="block">h_f=f\frac{L}{D}\frac{v^2}{2g},\qquad Re=\frac{vD}{\nu}</math>
<math display="block">h_f=f\frac{L}{D}\frac{v^2}{2g},\qquad Re=\frac{vD}{\nu}</math>
Line 29: Line 31:
|}
|}


For laminar pipe flow below a Reynolds number of about 2,000, Titus gives the factor as 64 divided by Reynolds number. Transitional flow does not have the same simple certainty. In turbulent flow, roughness and Reynolds number determine the appropriate factor through correlations or a Moody diagram. A constant factor cannot be assumed valid through every change of flow or liquid condition. <ref name="T_4-50_4-53" />
For laminar pipe flow below a Reynolds number of about 2,000, Titus gives the factor as 64 divided by Reynolds number; transitional flow does not have the same simple certainty. In turbulent flow, roughness and Reynolds number determine the appropriate factor through correlations or a Moody diagram. A constant factor cannot be assumed valid through every change of flow or liquid condition. <ref name="T_4-50_4-53" />


Titus's comparison example uses approximately 1,893 L/min in a 102.26 mm internal bore over 30.48 m. With the stated friction factor of 0.0188, recalculation gives approximately 4.21 m of head loss. These values are converted from the example's original customary units. The result differs from its Hazen-Williams example because the selected assumptions represent resistance differently. <ref name="T_4-56">Titus (2002), ch. 4-2, pp. 4-56.</ref>
Titus's comparison example uses approximately 1,893 L/min in a 102.26 mm internal bore over 30.48 m. With the stated friction factor of 0.0188, recalculation gives approximately 4.21 m of head loss. These values are converted from the example's original customary units. The result differs from its Hazen-Williams example because the selected assumptions represent resistance differently. <ref name="T_4-56">Titus (2002), ch. 4-2, p. 4-56.</ref>


The method still requires a defensible pipe model. Deposits, local restrictions and uncertain internal diameter can dominate uncertainty even when the formula is correct. Local fitting losses are added through appropriate coefficients or compatible equivalent lengths. Elevation changes remain energy terms rather than being counted as friction. <ref name="T_4-47_4-56" /><ref name="H_15_5_15-80_15-81">Cote (2008), ch. 15.5, pp. 15-80–15-81.</ref>
The method still requires a defensible pipe model; deposits, local restrictions and uncertain internal diameter can dominate uncertainty even when the formula is correct. Local fitting losses are added through appropriate coefficients or compatible equivalent lengths. Elevation changes remain energy terms rather than being counted as friction. <ref name="T_4-47_4-56" /><ref name="H_15_5_15-80_15-81">Cote (2008), ch. 15.5, pp. 15-80–15-81.</ref>


== Pipe resistance and internal condition ==
== Pipe resistance and internal condition ==
Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section. Turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. <ref name="T_4-49_4-56">Titus (2002), ch. 4-2, pp. 4-49–4-56.</ref>
Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section; turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. <ref name="T_4-49_4-56">Titus (2002), ch. 4-2, pp. 4-49–4-56.</ref>
[[File:fse-darcy-weisbach-equation-v3.svg|thumb|upright=1.5|alt=Distributed and local resistance. Measurement and water paths are distinct.|Distributed and local resistance. Schematic explanation; dimensions are not installation instructions.]]


The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor. That factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. <ref name="T_4-50_4-53" />
The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor; that factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. <ref name="T_4-50_4-53" />


At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85. Doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81">Fleming (2002), ch. 4-3, pp. 4-75–4-81.</ref>
At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. <ref name="T_4-52_4-53">Titus (2002), ch. 4-2, pp. 4-52–4-53.</ref><ref name="F_4-75_4-81">Fleming (2002), ch. 4-3, pp. 4-75–4-81.</ref>


Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits. Equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56" /><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, pp. 15-59.</ref>
Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. <ref name="T_4-56" /><ref name="H_15_3_15-59">Cote (2008), ch. 15.3, p. 15-59.</ref>


Age and deposits introduce further uncertainty. Corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, pp. 16-212.</ref>
Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. <ref name="H_15_5_15-79_15-81">Cote (2008), ch. 15.5, pp. 15-79–15-81.</ref><ref name="H_16_11_16-212">Cote (2008), ch. 16.11, p. 16-212.</ref>


A sound comparison keeps elevation, flow and valve state consistent between observations. A high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81" />
A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. <ref name="T_4-47_4-52" /><ref name="F_4-81" />


== Applying the Hazen-Williams relation ==
== Applying the Hazen-Williams relation ==
The Hazen-Williams relation represents pipe friction through an empirical water-flow equation. Titus explains that its coefficient is fitted to flow behaviour rather than derived from a complete fluid-property model. Water temperature and the range of pipe conditions therefore matter to its interpretation. It is not a general-purpose equation for every liquid used in fire protection. <ref name="T_4-52_4-53" />
The Hazen-Williams relation represents pipe friction through an empirical water-flow equation; Titus explains that its coefficient is fitted to flow behaviour rather than derived from a complete fluid-property model. Water temperature and the range of pipe conditions therefore matter to its interpretation. It is not a general-purpose equation for every liquid used in fire protection. <ref name="T_4-52_4-53" />


The following form expresses the pressure loss through a straight length in kilopascals. It is obtained by converting Titus's bar-per-metre form and multiplying by pipe length. Flow is in litres per minute and actual internal diameter is in millimetres. Changing those units without changing the constant produces a different and incorrect calculation. <ref name="T_4-52">Titus (2002), ch. 4-2, pp. 4-52.</ref>
The following form expresses the pressure loss through a straight length in kilopascals; it is obtained by converting Titus's bar-per-metre form and multiplying by pipe length. Flow is in litres per minute and actual internal diameter is in millimetres. Changing those units without changing the constant produces a different and incorrect calculation. <ref name="T_4-52">Titus (2002), ch. 4-2, p. 4-52.</ref>


<math display="block">\Delta p=6.05\times10^7\frac{LQ^{1.85}}{C^{1.85}D^{4.87}}</math>
<math display="block">\Delta p=6.05\times10^7\frac{LQ^{1.85}}{C^{1.85}D^{4.87}}</math>
Line 67: Line 70:
Titus compares methods using a flow of approximately 1,893 L/min through 30.48 m of pipe with a 102.26 mm internal diameter. Using a C-factor of 100 gives approximately 69.4 kPa loss by this formula. The example demonstrates the method with stated inputs; it does not prescribe that coefficient for every steel pipe. Different condition assumptions produce different predictions for the same nominal pipe. <ref name="T_4-56" />
Titus compares methods using a flow of approximately 1,893 L/min through 30.48 m of pipe with a 102.26 mm internal diameter. Using a C-factor of 100 gives approximately 69.4 kPa loss by this formula. The example demonstrates the method with stated inputs; it does not prescribe that coefficient for every steel pipe. Different condition assumptions produce different predictions for the same nominal pipe. <ref name="T_4-56" />


Sensitivity can be illustrated without selecting another installation. Doubling flow at fixed diameter and C-factor multiplies the calculated loss by approximately 3.61. Reducing C from 120 to 80 multiplies loss by approximately 2.12 at unchanged flow. These recalculated ratios follow directly from the exponents and help explain why condition and demand assumptions matter. Titus cautions that Hazen-Williams becomes unsuitable for coefficients appreciably below 100, particularly for very rough pipes. The C-factor comparison therefore illustrates equation sensitivity rather than validating a severely deteriorated installation. <ref name="T_4-52_4-54">Titus (2002), ch. 4-2, pp. 4-52–4-54.</ref><ref name="H_15_3_15-53">Cote (2008), ch. 15.3, pp. 15-53.</ref>
Sensitivity can be illustrated without selecting another installation. Doubling flow at fixed diameter and C-factor multiplies the calculated loss by approximately 3.61. Reducing C from 120 to 80 multiplies loss by approximately 2.12 at unchanged flow. These recalculated ratios follow directly from the exponents and help explain why condition and demand assumptions matter. Titus cautions that Hazen-Williams becomes unsuitable for coefficients appreciably below 100, particularly for very rough pipes. The C-factor comparison therefore illustrates equation sensitivity rather than validating a severely deteriorated installation. <ref name="T_4-52_4-54">Titus (2002), ch. 4-2, pp. 4-52–4-54.</ref><ref name="H_15_3_15-53">Cote (2008), ch. 15.3, p. 15-53.</ref>


The formula describes distributed resistance, not every possible obstruction. A partially closed valve or a lodged object can create a concentrated restriction that needs separate representation. Corrosion may affect both roughness and bore, while internal debris can move during testing or operation. Treating all these effects as an arbitrary change to C can hide the physical defect being investigated. <ref name="H_15_5_15-79_15-81" /><ref name="H_16_11_16-212" />
The formula describes distributed resistance, not every possible obstruction; a partially closed valve or a lodged object can create a concentrated restriction that needs separate representation. Corrosion may affect both roughness and bore, while internal debris can move during testing or operation. Treating all these effects as an arbitrary change to C can hide the physical defect being investigated. <ref name="H_15_5_15-79_15-81" /><ref name="H_16_11_16-212" />


== Pressure, flow and energy ==
== Pressure, flow and energy ==
Water pressure describes only one part of the energy available in a pipe. Elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. <ref name="T_4-45_4-48">Titus (2002), ch. 4-2, pp. 4-45–4-48.</ref>
Water pressure describes only one part of the energy available in a pipe; elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. <ref name="T_4-45_4-48">Titus (2002), ch. 4-2, pp. 4-45–4-48.</ref>


For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections. The following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. <ref name="T_4-47_4-50">Titus (2002), ch. 4-2, pp. 4-47–4-50.</ref>
For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections; the following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. <ref name="T_4-47_4-50">Titus (2002), ch. 4-2, pp. 4-47–4-50.</ref>


<math display="block">\frac{p_1}{\rho g}+\frac{v_1^2}{2g}+z_1+H_p=\frac{p_2}{\rho g}+\frac{v_2^2}{2g}+z_2+h_L</math>
<math display="block">\frac{p_1}{\rho g}+\frac{v_1^2}{2g}+z_1+H_p=\frac{p_2}{\rho g}+\frac{v_2^2}{2g}+z_2+h_L</math>
Line 92: Line 95:
|}
|}


Pressure can decrease because water rises, because velocity increases, or because energy is dissipated. These effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. <ref name="T_4-47_4-52" />
Pressure can decrease because water rises, because velocity increases, or because energy is dissipated; these effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. <ref name="T_4-47_4-52" />


Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity. The same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. <ref name="T_4-47_4-50" /><ref name="H_16_3_16-41_16-42">Cote (2008), ch. 16.3, pp. 16-41–16-42.</ref>
Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity; the same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. <ref name="T_4-47_4-50" /><ref name="H_16_3_16-41_16-42">Cote (2008), ch. 16.3, pp. 16-41–16-42.</ref>


The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered. It is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. <ref name="F_4-75_4-81" /><ref name="N_xxxvii_xxxviii">Hopkins et al. (2005), pp. xxxvii–xxxviii.</ref>
The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered; it is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. <ref name="F_4-75_4-81" /><ref name="N_xxxvii_xxxviii">Hopkins et al. (2005), pp. xxxvii–xxxviii.</ref>


== Measuring the available supply ==
== Measuring the available supply ==
A supply test relates an observed discharge to the pressure remaining elsewhere in the connected system. The initial static reading describes the condition before the test discharge begins. The residual reading describes the pressure while the measured discharge is flowing. Both belong to the same test arrangement and must be recorded with its location and operating conditions. <ref name="F_4-81" /><ref name="H_15_3_15-46_15-47">Cote (2008), ch. 15.3, pp. 15-46–15-47.</ref>
A supply test relates an observed discharge to the pressure remaining elsewhere in the connected system; the initial static reading describes the condition before the test discharge begins. The residual reading describes the pressure while the measured discharge is flowing. Both belong to the same test arrangement and must be recorded with its location and operating conditions. <ref name="F_4-81" /><ref name="H_15_3_15-46_15-47">Cote (2008), ch. 15.3, pp. 15-46–15-47.</ref>


The flowing outlet and the pressure observation have different functions. A pitot measurement in an appropriate free jet supports an estimate of outlet flow. A gauge at the residual hydrant measures pressure in the distribution system during that discharge. Substituting jet pressure for residual system pressure confuses two different physical quantities. <ref name="H_15_3_15-46_15-47" /><ref name="F_4-81" />
The flowing outlet and the pressure observation have different functions; a pitot measurement in an appropriate free jet supports an estimate of outlet flow. A gauge at the residual hydrant measures pressure in the distribution system during that discharge. Substituting jet pressure for residual system pressure confuses two different physical quantities. <ref name="H_15_3_15-46_15-47" /><ref name="F_4-81" />


The discharge estimate depends on outlet geometry and the coefficient representing its losses. A disturbed or nonuniform jet makes a single point reading less representative. Probe alignment and position also influence the measurement. For some discharge devices, a calibrated nozzle or suitable flowmeter provides a more appropriate method than applying a simple pitot relation. <ref name="H_15_3_15-46_15-47" />
The discharge estimate depends on outlet geometry and the coefficient representing its losses; a disturbed or nonuniform jet makes a single point reading less representative. Probe alignment and position also influence the measurement. For some discharge devices, a calibrated nozzle or suitable flowmeter provides a more appropriate method than applying a simple pitot relation. <ref name="H_15_3_15-46_15-47" />


Test results describe a network state, rather than an unlimited promise of future supply. Domestic demand, pumps, source levels and closed valves can change that state. The pressure reference must also be carried correctly to the building calculation. A test performed at a different elevation or upstream of additional resistance needs hydraulic interpretation before comparison with system demand. <ref name="H_15_2_15-23_15-24">Cote (2008), ch. 15.2, pp. 15-23–15-24.</ref><ref name="F_4-81_4-83" />
Test results describe a network state, rather than an unlimited promise of future supply; domestic demand, pumps, source levels and closed valves can change that state. The pressure reference must also be carried correctly to the building calculation. A test performed at a different elevation or upstream of additional resistance needs hydraulic interpretation before comparison with system demand. <ref name="H_15_2_15-23_15-24">Cote (2008), ch. 15.2, pp. 15-23–15-24.</ref><ref name="F_4-81_4-83" />


A main-drain test provides a different kind of evidence. The handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. <ref name="H_16_11_16-210_16-211">Cote (2008), ch. 16.11, pp. 16-210–16-211.</ref>
A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. <ref name="H_16_11_16-210_16-211">Cote (2008), ch. 16.11, pp. 16-210–16-211.</ref>


Pump testing likewise separates a start test from a flow-performance test. Running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. <ref name="H_16_11_16-220">Cote (2008), ch. 16.11, pp. 16-220.</ref>
Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. <ref name="H_16_11_16-220">Cote (2008), ch. 16.11, p. 16-220.</ref>


== Corrosion, deposits and diagnosis ==
== Corrosion, deposits and diagnosis ==
Microbiologically influenced corrosion describes microbial participation in corrosion processes. Organisms and their biofilms can change local chemistry and establish conditions that promote metal loss. The presence of bacteria does not by itself prove that they caused a particular failure. The handbook explicitly distinguishes evidence of organisms from a defensible diagnosis of their role. <ref name="H_15_5_15-75_15-78_15-81">Cote (2008), ch. 15.5, pp. 15-75,15-78–15-81.</ref>
Microbiologically influenced corrosion describes microbial participation in corrosion processes; organisms and their biofilms can change local chemistry and establish conditions that promote metal loss. The presence of bacteria does not by itself prove that they caused a particular failure. The handbook explicitly distinguishes evidence of organisms from a defensible diagnosis of their role. <ref name="H_15_5_15-75_15-78_15-81">Cote (2008), ch. 15.5, pp. 15-75,15-78–15-81.</ref>


Biofilms can create local differences in oxygen concentration and other chemical conditions. Deposits may maintain an aggressive local environment even after a treatment reduces viable organisms. A high microbial count is therefore not a direct measurement of corrosion rate. A low count at one sampling time likewise does not reconstruct the previous history of an affected pipe. <ref name="H_15_5_15-79_15-81" />
Biofilms can create local differences in oxygen concentration and other chemical conditions; deposits may maintain an aggressive local environment even after a treatment reduces viable organisms. A high microbial count is therefore not a direct measurement of corrosion rate. A low count at one sampling time likewise does not reconstruct the previous history of an affected pipe. <ref name="H_15_5_15-79_15-81" />


Both wet and dry sprinkler arrangements can be affected by internal deterioration. A dry system can retain water in low points and expose that water to oxygen in the gas supply. Water chemistry and deposits also matter in wet systems. Plastic components can experience biological fouling even though the same metallic corrosion mechanism does not apply to the plastic itself. <ref name="H_15_5_15-79_15-81" /><ref name="H_16_11_16-211_16-212">Cote (2008), ch. 16.11, pp. 16-211–16-212.</ref>
Both wet and dry sprinkler arrangements can be affected by internal deterioration; a dry system can retain water in low points and expose that water to oxygen in the gas supply. Water chemistry and deposits also matter in wet systems. Plastic components can experience biological fouling even though the same metallic corrosion mechanism does not apply to the plastic itself. <ref name="H_15_5_15-79_15-81" /><ref name="H_16_11_16-211_16-212">Cote (2008), ch. 16.11, pp. 16-211–16-212.</ref>


The consequences need separate description. Wall loss can lead to leakage or loss of integrity, while deposits increase resistance or reduce the effective bore. Detached material can migrate and obstruct a smaller downstream opening. No single roughness coefficient represents every combination of these effects. The hydraulic model and the assessment of physical condition therefore answer complementary questions. <ref name="H_15_5_15-80_15-81" /><ref name="T_4-50_4-53" /><ref name="H_16_11_16-212" />
The consequences need separate description; wall loss can lead to leakage or loss of integrity, while deposits increase resistance or reduce the effective bore. Detached material can migrate and obstruct a smaller downstream opening. No single roughness coefficient represents every combination of these effects. The hydraulic model and the assessment of physical condition therefore answer complementary questions. <ref name="H_15_5_15-80_15-81" /><ref name="T_4-50_4-53" /><ref name="H_16_11_16-212" />


A useful investigation combines observations of the metal, deposits, water chemistry and microbiology. The handbook cautions against assigning cause from a single test result. Cleaning and treatment also require separate evaluation because removing organisms does not restore lost wall thickness. The remaining installation must still meet its structural and hydraulic functions. <ref name="H_15_5_15-80_15-81" />
A useful investigation combines observations of the metal, deposits, water chemistry and microbiology; the handbook cautions against assigning cause from a single test result. Cleaning and treatment also require separate evaluation because removing organisms does not restore lost wall thickness. The remaining installation must still meet its structural and hydraulic functions. <ref name="H_15_5_15-80_15-81" />


The maintenance implication is broader than finding a chemical treatment. Source-water condition, retained water, internal debris and future inspection all affect continued performance. Treatment concentrations can be difficult to control in intermittently flowing sprinkler networks. The available handbook discussion explains these limitations without providing a current product-specific treatment specification. <ref name="H_15_5_15-81">Cote (2008), ch. 15.5, pp. 15-81.</ref><ref name="I_1_7-8">National Research Council of Canada et al. (2005), pp. 1.7-8.</ref>
The maintenance implication is broader than finding a chemical treatment; source-water condition, retained water, internal debris and future inspection all affect continued performance. Treatment concentrations can be difficult to control in intermittently flowing sprinkler networks. The available handbook discussion explains these limitations without providing a current product-specific treatment specification. <ref name="H_15_5_15-81">Cote (2008), ch. 15.5, p. 15-81.</ref><ref name="I_1_7-8">National Research Council of Canada et al. (2005), p. 1.7-8.</ref>


== See also ==
== See also ==

Latest revision as of 01:31, 16 November 2026

Darcy-Weisbach equation is an equation that calculates distributed pipe head loss from friction factor, pipe geometry and mean flow velocity. [1] Its friction factor depends on Reynolds number and, in turbulent flow, relative pipe roughness. The method keeps fluid viscosity visible through the flow-regime calculation. This distinguishes it from empirical water-only relations, although both still require reliable information about the actual pipe and flow. [2]

The underlying hydraulic assessment follows water from a defined source to its intended outlet. Elevation, velocity changes and irreversible losses must be distinguished. Observations also need the flow and network conditions under which they were obtained. A mathematically correct result can still be misleading if a source condition, connecting segment or component loss has been omitted from the description. [3][4] Static pressure and flowing pressure describe different conditions. [5]

Flow regime and factor convention

Hydraulic calculation uses the equation to quantify friction loss along a defined route; turbulence changes the relationship between wall condition, velocity and resistance. The Hazen-Williams formula instead represents water-service behaviour through an empirical coefficient. The choice of method must follow the fluid and operating conditions being represented. [6]

Darcy-Weisbach equation: functional relationships. Measurement and water paths are distinct.
Darcy-Weisbach equation: functional relationships. Schematic explanation; dimensions are not installation instructions.

The Bernoulli equation provides the surrounding energy balance; Darcy-Weisbach supplies a loss term within that balance rather than replacing elevation, pressure and velocity terms. A more detailed friction model cannot correct an omitted supply segment or an incorrect pressure datum. The network description and the resistance calculation must both represent the installation. [7]

A water mist system can have a hydraulic arrangement different from a conventional sprinkler system; its presence does not by itself justify transferring sprinkler-specific empirical assumptions. Titus's treatment makes fluid properties and flow regime explicit when selecting a loss method. No particular mist-system pressure, nozzle demand or installation criterion follows from the Darcy-Weisbach equation alone. [2][8]

Applying the Darcy-Weisbach relation

The Darcy-Weisbach relation describes distributed pipe loss using mean velocity and a friction factor; the factor represents the effect of the flow regime and pipe condition. Reynolds number connects velocity and diameter with the fluid's kinematic viscosity. Relative roughness compares the wall's characteristic roughness with the internal diameter. [9]

Selecting a friction factor. Measurement and water paths are distinct.
Selecting a friction factor. Schematic explanation; dimensions are not installation instructions.

The equation below gives head loss in metres of the flowing fluid; pressure loss follows by multiplying head loss by density and gravitational acceleration. The factor is the Darcy friction factor used in the cited handbook equation. Keeping its convention explicit prevents confusion with other friction-factor definitions. [1]

hf=fLDv22g,Re=vDν

Symbol Description Unit
hf,L,D Head loss, length and internal diameter m
f,Re Darcy friction factor and Reynolds number dimensionless
v,g Mean velocity and gravitational acceleration m/s; m/s²
ν Kinematic viscosity m²/s

For laminar pipe flow below a Reynolds number of about 2,000, Titus gives the factor as 64 divided by Reynolds number; transitional flow does not have the same simple certainty. In turbulent flow, roughness and Reynolds number determine the appropriate factor through correlations or a Moody diagram. A constant factor cannot be assumed valid through every change of flow or liquid condition. [2]

Titus's comparison example uses approximately 1,893 L/min in a 102.26 mm internal bore over 30.48 m. With the stated friction factor of 0.0188, recalculation gives approximately 4.21 m of head loss. These values are converted from the example's original customary units. The result differs from its Hazen-Williams example because the selected assumptions represent resistance differently. [10]

The method still requires a defensible pipe model; deposits, local restrictions and uncertain internal diameter can dominate uncertainty even when the formula is correct. Local fitting losses are added through appropriate coefficients or compatible equivalent lengths. Elevation changes remain energy terms rather than being counted as friction. [3][11]

Pipe resistance and internal condition

Moving water loses mechanical energy through interaction with pipe walls and through changes in direction or section; turbulent mixing contributes to this dissipation. The resistance depends on the actual internal bore and its condition, not simply the name printed on the pipe. Valves, elbows, entries and other fittings introduce additional local losses. [12]

Distributed and local resistance. Measurement and water paths are distinct.
Distributed and local resistance. Schematic explanation; dimensions are not installation instructions.

The Darcy-Weisbach equation expresses distributed loss through a dimensionless friction factor; that factor depends on the flow regime and, for turbulent flow, on relative roughness. The Hazen-Williams formula instead uses an empirical coefficient for water service. These methods describe related hydraulic behaviour, but their coefficients do not have interchangeable meanings. [2]

At fixed diameter and roughness coefficient, Hazen-Williams loss increases approximately with flow raised to the power 1.85; doubling flow therefore produces considerably more than twice the loss. Increasing bore has a strong opposite effect because diameter appears with an exponent of 4.87. This explains why a short restricted connection can materially influence an otherwise generous water supply. [13][14]

Fittings can be represented by local resistance coefficients or by equivalent pipe lengths where the selected method permits; equivalent length is a calculation device, not an extra measured length on the drawing. Its use must remain consistent with the pipe and friction assumptions behind the published value. A special valve's measured pressure-loss curve may provide a better representation than a generic fitting allowance. [10][15]

Age and deposits introduce further uncertainty; corrosion can increase roughness, reduce the effective bore and release material that later obstructs a smaller passage. These mechanisms are distinct, so changing a roughness coefficient does not necessarily represent a local blockage. Inspection findings and flow measurements help determine whether the calculation still describes the installation. [16][17]

A sound comparison keeps elevation, flow and valve state consistent between observations; a high static pressure can coexist with poor flowing performance because frictional loss emerges when water moves. Conversely, a pressure difference caused by elevation does not establish pipe deterioration. The interpretation depends on the physical route and the condition under which each reading was taken. [7][5]

Applying the Hazen-Williams relation

The Hazen-Williams relation represents pipe friction through an empirical water-flow equation; Titus explains that its coefficient is fitted to flow behaviour rather than derived from a complete fluid-property model. Water temperature and the range of pipe conditions therefore matter to its interpretation. It is not a general-purpose equation for every liquid used in fire protection. [13]

The following form expresses the pressure loss through a straight length in kilopascals; it is obtained by converting Titus's bar-per-metre form and multiplying by pipe length. Flow is in litres per minute and actual internal diameter is in millimetres. Changing those units without changing the constant produces a different and incorrect calculation. [18]

Δp=6.05×107LQ1.85C1.85D4.87

Symbol Description Unit
Δp,L Frictional pressure loss and pipe length kPa; m
Q,D Water flow and actual internal diameter L/min; mm
C Empirical Hazen-Williams coefficient dimensionless

Titus compares methods using a flow of approximately 1,893 L/min through 30.48 m of pipe with a 102.26 mm internal diameter. Using a C-factor of 100 gives approximately 69.4 kPa loss by this formula. The example demonstrates the method with stated inputs; it does not prescribe that coefficient for every steel pipe. Different condition assumptions produce different predictions for the same nominal pipe. [10]

Sensitivity can be illustrated without selecting another installation. Doubling flow at fixed diameter and C-factor multiplies the calculated loss by approximately 3.61. Reducing C from 120 to 80 multiplies loss by approximately 2.12 at unchanged flow. These recalculated ratios follow directly from the exponents and help explain why condition and demand assumptions matter. Titus cautions that Hazen-Williams becomes unsuitable for coefficients appreciably below 100, particularly for very rough pipes. The C-factor comparison therefore illustrates equation sensitivity rather than validating a severely deteriorated installation. [19][20]

The formula describes distributed resistance, not every possible obstruction; a partially closed valve or a lodged object can create a concentrated restriction that needs separate representation. Corrosion may affect both roughness and bore, while internal debris can move during testing or operation. Treating all these effects as an arbitrary change to C can hide the physical defect being investigated. [16][17]

Pressure, flow and energy

Water pressure describes only one part of the energy available in a pipe; elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. [21]

For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections; the following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. [22]

p1ρg+v122g+z1+Hp=p2ρg+v222g+z2+hL

Symbol Description Unit
p Pressure at the section Pa
ρ Water density kg/m³
g Gravitational acceleration m/s²
v Mean velocity m/s
z,Hp,hL Elevation, added pump head and head loss m

Pressure can decrease because water rises, because velocity increases, or because energy is dissipated; these effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. [7]

Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity; the same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. [22][23]

The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered; it is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. [14][24]

Measuring the available supply

A supply test relates an observed discharge to the pressure remaining elsewhere in the connected system; the initial static reading describes the condition before the test discharge begins. The residual reading describes the pressure while the measured discharge is flowing. Both belong to the same test arrangement and must be recorded with its location and operating conditions. [5][25]

The flowing outlet and the pressure observation have different functions; a pitot measurement in an appropriate free jet supports an estimate of outlet flow. A gauge at the residual hydrant measures pressure in the distribution system during that discharge. Substituting jet pressure for residual system pressure confuses two different physical quantities. [25][5]

The discharge estimate depends on outlet geometry and the coefficient representing its losses; a disturbed or nonuniform jet makes a single point reading less representative. Probe alignment and position also influence the measurement. For some discharge devices, a calibrated nozzle or suitable flowmeter provides a more appropriate method than applying a simple pitot relation. [25]

Test results describe a network state, rather than an unlimited promise of future supply; domestic demand, pumps, source levels and closed valves can change that state. The pressure reference must also be carried correctly to the building calculation. A test performed at a different elevation or upstream of additional resistance needs hydraulic interpretation before comparison with system demand. [26][4]

A main-drain test provides a different kind of evidence; the handbook uses changes from previous static and flowing readings to identify possible deterioration or obstruction. This is useful for detecting change, but it does not independently establish the full sprinkler demand. Test opening, supply state and instrument condition affect whether successive observations are comparable. [27]

Pump testing likewise separates a start test from a flow-performance test; running successfully without substantial discharge demonstrates some operating functions but does not establish the entire pump curve. Flowing observations across the relevant operating range give evidence about delivery capability. The handbook describes retaining records so that deterioration and the ability to meet system demand can be assessed. [28]

Corrosion, deposits and diagnosis

Microbiologically influenced corrosion describes microbial participation in corrosion processes; organisms and their biofilms can change local chemistry and establish conditions that promote metal loss. The presence of bacteria does not by itself prove that they caused a particular failure. The handbook explicitly distinguishes evidence of organisms from a defensible diagnosis of their role. [29]

Biofilms can create local differences in oxygen concentration and other chemical conditions; deposits may maintain an aggressive local environment even after a treatment reduces viable organisms. A high microbial count is therefore not a direct measurement of corrosion rate. A low count at one sampling time likewise does not reconstruct the previous history of an affected pipe. [16]

Both wet and dry sprinkler arrangements can be affected by internal deterioration; a dry system can retain water in low points and expose that water to oxygen in the gas supply. Water chemistry and deposits also matter in wet systems. Plastic components can experience biological fouling even though the same metallic corrosion mechanism does not apply to the plastic itself. [16][30]

The consequences need separate description; wall loss can lead to leakage or loss of integrity, while deposits increase resistance or reduce the effective bore. Detached material can migrate and obstruct a smaller downstream opening. No single roughness coefficient represents every combination of these effects. The hydraulic model and the assessment of physical condition therefore answer complementary questions. [11][2][17]

A useful investigation combines observations of the metal, deposits, water chemistry and microbiology; the handbook cautions against assigning cause from a single test result. Cleaning and treatment also require separate evaluation because removing organisms does not restore lost wall thickness. The remaining installation must still meet its structural and hydraulic functions. [11]

The maintenance implication is broader than finding a chemical treatment; source-water condition, retained water, internal debris and future inspection all affect continued performance. Treatment concentrations can be difficult to control in intermittently flowing sprinkler networks. The available handbook discussion explains these limitations without providing a current product-specific treatment specification. [31][32]

See also

Notes

  1. ↑ 1.0 1.1 Titus (2002), ch. 4-2, pp. 4-50–4-52.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Titus (2002), ch. 4-2, pp. 4-50–4-53.
  3. ↑ 3.0 3.1 Titus (2002), ch. 4-2, pp. 4-47–4-56.
  4. ↑ 4.0 4.1 Fleming (2002), ch. 4-3, pp. 4-81–4-83.
  5. ↑ 5.0 5.1 5.2 5.3 Fleming (2002), ch. 4-3, p. 4-81.
  6. ↑ Titus (2002), ch. 4-2, pp. 4-49–4-53.
  7. ↑ 7.0 7.1 7.2 Titus (2002), ch. 4-2, pp. 4-47–4-52.
  8. ↑ Cote (2008), ch. 16.9, p. 16-181.
  9. ↑ Titus (2002), ch. 4-2, pp. 4-49–4-52.
  10. ↑ 10.0 10.1 10.2 Titus (2002), ch. 4-2, p. 4-56.
  11. ↑ 11.0 11.1 11.2 Cote (2008), ch. 15.5, pp. 15-80–15-81.
  12. ↑ Titus (2002), ch. 4-2, pp. 4-49–4-56.
  13. ↑ 13.0 13.1 Titus (2002), ch. 4-2, pp. 4-52–4-53.
  14. ↑ 14.0 14.1 Fleming (2002), ch. 4-3, pp. 4-75–4-81.
  15. ↑ Cote (2008), ch. 15.3, p. 15-59.
  16. ↑ 16.0 16.1 16.2 16.3 Cote (2008), ch. 15.5, pp. 15-79–15-81.
  17. ↑ 17.0 17.1 17.2 Cote (2008), ch. 16.11, p. 16-212.
  18. ↑ Titus (2002), ch. 4-2, p. 4-52.
  19. ↑ Titus (2002), ch. 4-2, pp. 4-52–4-54.
  20. ↑ Cote (2008), ch. 15.3, p. 15-53.
  21. ↑ Titus (2002), ch. 4-2, pp. 4-45–4-48.
  22. ↑ 22.0 22.1 Titus (2002), ch. 4-2, pp. 4-47–4-50.
  23. ↑ Cote (2008), ch. 16.3, pp. 16-41–16-42.
  24. ↑ Hopkins et al. (2005), pp. xxxvii–xxxviii.
  25. ↑ 25.0 25.1 25.2 Cote (2008), ch. 15.3, pp. 15-46–15-47.
  26. ↑ Cote (2008), ch. 15.2, pp. 15-23–15-24.
  27. ↑ Cote (2008), ch. 16.11, pp. 16-210–16-211.
  28. ↑ Cote (2008), ch. 16.11, p. 16-220.
  29. ↑ Cote (2008), ch. 15.5, pp. 15-75,15-78–15-81.
  30. ↑ Cote (2008), ch. 16.11, pp. 16-211–16-212.
  31. ↑ Cote (2008), ch. 15.5, p. 15-81.
  32. ↑ National Research Council of Canada et al. (2005), p. 1.7-8.

References

  • Cote, A. E. (Ed.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
  • Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-72–4-87). National Fire Protection Association.
  • Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines. Australian Building Codes Board.
  • Titus, J. J. (2002). Hydraulics. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-44–4-71). National Fire Protection Association.