'''Fire apparatus''' are the | '''Fire apparatus''' are the vehicles and vessels that a fire department uses to bring fire fighters, water, pumps, hose, ladders and tools to an emergency and to work from at the scene. In North America the basic apparatus is a diesel- or gasoline-engined vehicle carrying firefighting equipment. This may include a pump, hose, a water tank, an aerial ladder or elevating platform, ground ladders and portable tools.<ref name="Tutterow-12-267">Tutterow (2008), p. 12-267.</ref><ref name="Tutterow-12-280">Tutterow (2008), p. 12-280.</ref> The most common type is the pumper, or engine, whose primary purpose is to move water with adequate pressure from a source to the fire.<ref name="Wieder-13-23">Wieder (2008), p. 13-23.</ref> Other types carry long ladders, transport water, fight wildland fires or support rescue, hazardous materials and command work.<ref name="Tutterow-12-268-269">Tutterow (2008), pp. 12-268–12-269.</ref> | ||
[[File:fse-fire-apparatus-v5.jpg|thumb|upright=1.5|alt=Fire department pumper parked with its pump panel, hose bed and equipment compartments visible|A pumper, the most common type of fire apparatus, with pump operator's panel and hose bed.]] | |||
For US automotive and wildland apparatus, Tutterow (2008) describes NFPA 1901 and NFPA 1906, respectively, as design and performance standards.<ref name="Tutterow-12-267" /> Under NFPA 1901 a pumper needs a pump of at least 2850 L/min (750 gpm) and a water tank of at least 1135 L (300 gal).<ref name="Tutterow-12-268">Tutterow (2008), p. 12-268.</ref> Apparatus are heavy and complex vehicles. In a typical year, more than a quarter of on-duty fire fighter deaths in the United States occurred during response to or return from incidents.<ref name="Tutterow-12-271">Tutterow (2008), p. 12-271.</ref> The requirements and values given here are those described in the handbook of 2008. | |||
== Types of apparatus == | == Types of apparatus == | ||
Pumpers are vehicles designed for sustained pumping during structural [[firefighting]]; NFPA 1901 requires a pump, a water tank and storage for supply and attack hose.<ref name="Tutterow-12-268" /> Pumpers are also called engines, wagons or triples.<ref name="Wieder-13-24">Wieder (2008), p. 13-24.</ref> The name "triple combination" refers to the pump, hose and water tank carried together.<ref name="Tutterow-12-268" /> An initial attack apparatus, or mini-pumper, needs only a pump of 950 L/min (250 gpm) and a tank of 757 L (200 gal). It was popular in the early 1980s and was slowly re-emerging in 2008 for parking garage fires, and a few departments used it as a first responder vehicle for medical calls.<ref name="Tutterow-12-268" /> | Pumpers are vehicles designed for sustained pumping during structural [[firefighting]]; NFPA 1901 requires a pump, a water tank and storage for supply and attack hose.<ref name="Tutterow-12-268" /> Pumpers are also called engines, wagons or triples.<ref name="Wieder-13-24">Wieder (2008), p. 13-24.</ref> The name "triple combination" refers to the pump, hose and water tank carried together.<ref name="Tutterow-12-268" /> An initial attack apparatus, or mini-pumper, needs only a pump of 950 L/min (250 gpm) and a tank of 757 L (200 gal). It was popular in the early 1980s and was slowly re-emerging in 2008 for parking garage fires, and a few departments used it as a first responder vehicle for medical calls.<ref name="Tutterow-12-268" /> | ||
[[File:fse-fire-apparatus-v1.svg|thumb|upright=1.5|alt=Side view of a pumper with labelled pump, water tank, hose beds, ladders and enclosed crew cab|Main components of a pumper with NFPA 1901 minimum values as described in 2008.]] | |||
Apparatus with a power-operated, self-supporting aerial device reaching at least 15.3 m (50 ft) provide elevated firefighting and rescue capability; they are treated under [[aerial apparatus]].<ref name="Tutterow-12-268" /> Combinations are common. A pumper that also carries long ground ladders and ladder-company equipment is a quadruple combination, or quad, and adding an aerial ladder or elevating platform makes it a quint.<ref name="Tutterow-12-268" /> Tutterow (2008) warns that efficiency tends to fall when too many functions are placed on one vehicle, and that the whole apparatus is out of service when one feature needs repair.<ref name="Tutterow-12-269">Tutterow (2008), p. 12-269.</ref> | Apparatus with a power-operated, self-supporting aerial device reaching at least 15.3 m (50 ft) provide elevated firefighting and rescue capability; they are treated under [[aerial apparatus]].<ref name="Tutterow-12-268" /> Combinations are common. A pumper that also carries long ground ladders and ladder-company equipment is a quadruple combination, or quad, and adding an aerial ladder or elevating platform makes it a quint.<ref name="Tutterow-12-268" /> Tutterow (2008) warns that efficiency tends to fall when too many functions are placed on one vehicle, and that the whole apparatus is out of service when one feature needs repair.<ref name="Tutterow-12-269">Tutterow (2008), p. 12-269.</ref> | ||
| Line 15: | Line 18: | ||
A pumper draws water either from a static source, such as a lake, pond or portable dump tank, or from a pressurised source. Pressurised sources include [[fire hydrant]]s, elevated storage tanks and supply hose from another pumper.<ref name="Wieder-13-23" /> The main pump is generally centrifugal: impellers turning at 2000 to 4000 rpm give the water velocity, which the casing converts to pressure. Two-stage pumps can run in series for maximum pressure or in parallel for maximum volume.<ref name="Wieder-13-24" /> | A pumper draws water either from a static source, such as a lake, pond or portable dump tank, or from a pressurised source. Pressurised sources include [[fire hydrant]]s, elevated storage tanks and supply hose from another pumper.<ref name="Wieder-13-23" /> The main pump is generally centrifugal: impellers turning at 2000 to 4000 rpm give the water velocity, which the casing converts to pressure. Two-stage pumps can run in series for maximum pressure or in parallel for maximum volume.<ref name="Wieder-13-24" /> | ||
Pumps are rated by the flow they deliver at a net pump pressure of 1035 kPa (150 psi) when drafting through 6 m of intake hose at a lift of 3 m. They must also deliver 70 percent of that flow at 1380 kPa (200 psi) and 50 percent at 1725 kPa (250 psi).<ref name="Wieder-13-24" /> These | Pumps are rated by the flow they deliver at a net pump pressure of 1035 kPa (150 psi) when drafting through 6 m of intake hose at a lift of 3 m. They must also deliver 70 percent of that flow at 1380 kPa (200 psi) and 50 percent at 1725 kPa (250 psi).<ref name="Wieder-13-24" /> These are minimum rating points at specified pressures, not points measured on a particular pump's [[fire pump performance curve]]. Hague (2008b) uses them in the same way. A pumper rated at 3785 L/min (1000 gpm) can be expected to deliver no less than 2650 L/min at 1379 kPa and 1893 L/min at 1724 kPa.<ref name="Hague-16-197">Hague (2008b), p. 16-197.</ref> | ||
[[File:fse-fire-apparatus-v2.svg|thumb|upright=1.5|alt=Chart of required flow against net pump pressure for a 3785 L/min fire pump at three rating points|Rating points of a fire apparatus pump rated at 3785 L/min (1000 gpm).]] | |||
{| class="wikitable" | {| class="wikitable" | ||
| Line 69: | Line 73: | ||
|} | |} | ||
Typical nozzle pressures are 345 kPa (50 psi) for handline solid-stream nozzles, 552 kPa (80 psi) for master stream solid-stream nozzles and 690 kPa (100 psi) for standard spray nozzles.<ref name="Wieder-13-29" /> In Wieder's worked example, 90 m of 65 mm rubber-lined hose supplies a 32 mm solid-stream tip at 345 kPa, held 3 m above the pump.<ref name="Wieder-13-30" /> The flow is 0.0666 × 32² × √345, or 1267 L/min, so q = 12.67. The friction loss is 3.17 × 12.67² × 0.9 = 458 kPa and the elevation pressure 10 × 3 = 30 kPa. The pump discharge pressure is therefore 345 + 458 + 30 = 833 kPa, or 120 psi in the US customary version of the same example.<ref name="Wieder-13-31" | Typical nozzle pressures are 345 kPa (50 psi) for handline solid-stream nozzles, 552 kPa (80 psi) for master stream solid-stream nozzles and 690 kPa (100 psi) for standard spray nozzles.<ref name="Wieder-13-29" /> In Wieder's worked example, 90 m of 65 mm rubber-lined hose supplies a 32 mm solid-stream tip at 345 kPa, held 3 m above the pump.<ref name="Wieder-13-30" /> The flow is 0.0666 × 32² × √345, or 1267 L/min, so q = 12.67.<ref name="Wieder-13-31">Wieder (2008), p. 13-31.</ref> The friction loss is 3.17 × 12.67² × 0.9 = 458 kPa and the elevation pressure 10 × 3 = 30 kPa. The pump discharge pressure is therefore 345 + 458 + 30 = 833 kPa, or 120 psi in the US customary version of the same example.<ref name="Wieder-13-31" /> In this layout, friction loss is the largest of the three terms. | ||
[[File:fse-fire-apparatus-v3.svg|thumb|upright=1.5|alt=Pumper supplying a hose line to a nozzle 3 m higher with a bar showing pump pressure split into nozzle, friction and elevation parts|Pump discharge pressure for 90 m of 65 mm hose to a 32 mm tip 3 m above the pump: 345 + 458 + 30 = 833 kPa.]] | |||
The same reasoning decides whether apparatus can supply a building through its [[fire department connection]]. Hague (2008b) states that a standpipe system needs a permanent secondary water source if the apparatus pressure boost plus the residual supply pressure does not exceed the system demand. As a rule of thumb, buildings taller than 91.5 m (300 ft) should be checked for this.<ref name="Hague-16-196-197">Hague (2008b), pp. 16-196–16-197.</ref> He describes two remotely located connections as required for each zone of a high-rise building within the pumping range of apparatus, so that falling glass cannot cut all supply hoses.<ref name="Hague-16-196">Hague (2008b), p. 16-196.</ref> McAllister et al. (2008) describe the New York City fire department's conventional pumpers with two-stage pumps of 4 or 8 m³/min. Its high-pressure pumpers had a third stage delivering 2 m³/min at 4.8 MPa, able singly or together to supply floors up to 110 storeys.<ref name="McAllister-77">McAllister et al. (2008), p. 77.</ref> | The same reasoning decides whether apparatus can supply a building through its [[fire department connection]]. Hague (2008b) states that a standpipe system needs a permanent secondary water source if the apparatus pressure boost plus the residual supply pressure does not exceed the system demand. As a rule of thumb, buildings taller than 91.5 m (300 ft) should be checked for this.<ref name="Hague-16-196-197">Hague (2008b), pp. 16-196–16-197.</ref> He describes two remotely located connections as required for each zone of a high-rise building within the pumping range of apparatus, so that falling glass cannot cut all supply hoses.<ref name="Hague-16-196">Hague (2008b), p. 16-196.</ref> McAllister et al. (2008) describe the New York City fire department's conventional pumpers with two-stage pumps of 4 or 8 m³/min. Its high-pressure pumpers had a third stage delivering 2 m³/min at 4.8 MPa, able singly or together to supply floors up to 110 storeys.<ref name="McAllister-77">McAllister et al. (2008), p. 77.</ref> | ||
| Line 77: | Line 82: | ||
NFPA 1901 requires a pumper to carry at least 244 m (800 ft) of [[fire hose]] of 65 mm or larger and 122 m (400 ft) of 38 to 51 mm hose. Most pumpers carry at least 366 m (1200 ft) of the larger hose, and many departments have found 125 mm (5 in) the most efficient and economical supply size.<ref name="Tutterow-12-274" /> A rule of thumb relates hose size to carrying capacity at normal pressures: 946 L/min for 65 mm hose, 1893 L/min for 89 mm hose and 4921 L/min for 125 mm hose. Moving 1893 L/min over 305 m therefore takes 610 m of 65 mm hose (two lines) or 305 m of 89 mm hose.<ref name="Tutterow-12-274-275">Tutterow (2008), pp. 12-274–12-275.</ref> In 2005 NFPA required all hose to be secured against accidental deployment, prompted by the death of a child struck by hose dragged by an apparatus.<ref name="Tutterow-12-275" /> | NFPA 1901 requires a pumper to carry at least 244 m (800 ft) of [[fire hose]] of 65 mm or larger and 122 m (400 ft) of 38 to 51 mm hose. Most pumpers carry at least 366 m (1200 ft) of the larger hose, and many departments have found 125 mm (5 in) the most efficient and economical supply size.<ref name="Tutterow-12-274" /> A rule of thumb relates hose size to carrying capacity at normal pressures: 946 L/min for 65 mm hose, 1893 L/min for 89 mm hose and 4921 L/min for 125 mm hose. Moving 1893 L/min over 305 m therefore takes 610 m of 65 mm hose (two lines) or 305 m of 89 mm hose.<ref name="Tutterow-12-274-275">Tutterow (2008), pp. 12-274–12-275.</ref> In 2005 NFPA required all hose to be secured against accidental deployment, prompted by the death of a child struck by hose dragged by an apparatus.<ref name="Tutterow-12-275" /> | ||
[[File:fse-fire-apparatus-v4.svg|thumb|upright=1.5|alt=Bar chart of typical water carrying capacity of fire hose from 65 mm to 125 mm diameter|Rule-of-thumb carrying capacity of fire hose at normal operating pressures.]] | |||
Besides hose, nozzles and ground ladders, | Besides hose, nozzles and ground ladders, Tutterow (2008) lists breathing apparatus, cutting tools, ventilation fans, salvage covers, generators, lights and thermal imaging cameras as equipment firefighters may need; the complement varies by department.<ref name="Tutterow-12-280" /><ref name="Tutterow-12-281">Tutterow (2008), p. 12-281.</ref> Tutterow also notes that too many departments overload their apparatus, and advises listing every item with its weight and storage space.<ref name="Tutterow-12-270" /><ref name="Tutterow-12-281" /> NFPA 1901 sets minimum equipment allowances of 907 kg (2000 lb) for pumpers and 1136 kg (2500 lb) for aerial apparatus and quints.<ref name="Tutterow-12-270" /> Tutterow advises keeping equipment out of the cab unless it is needed during response. NFPA 1901 requires equipment carried there, apart from breathing apparatus, to be in latched compartments able to withstand 9 g longitudinally and 3 g in other directions.<ref name="Tutterow-12-281" /><ref name="Tutterow-12-272">Tutterow (2008), p. 12-272.</ref> | ||
== Road performance and crew safety == | == Road performance and crew safety == | ||
| Line 97: | Line 103: | ||
== Apparatus in fire protection planning == | == Apparatus in fire protection planning == | ||
In 2005, US local fire departments had 81,200 pumpers with a capacity of at least 500 gpm (1893 L/min).<ref name="HallCote-3-27">Hall and Cote (2008), p. 3-27.</ref> How many must respond depends on the risk. Granito | In 2005, US local fire departments had 81,200 pumpers with a capacity of at least 500 gpm (1893 L/min).<ref name="HallCote-3-27">Hall and Cote (2008), p. 3-27.</ref> How many must respond depends on the risk. In his 2008 US planning table, Granito lists a typical initial attack for low-hazard dwellings of at least two pumpers, one ladder truck, 14 fire fighters and one chief officer. He also lists a safety officer and rapid intervention team. For high-hazard occupancies such as hospitals and high-rise buildings, he lists at least four pumpers, two ladder trucks, 24 fire fighters and two chief officers. He again lists a safety officer and rapid intervention team.<ref name="Granito-12-12">Granito (2008), p. 12-12.</ref> A rule of thumb is one company for each 946 L/min (250 gpm) needed in an interior attack, plus personnel for rescue and other simultaneous tasks.<ref name="Granito-12-13">Granito (2008), p. 12-13.</ref> As an illustration, an interior attack needing 3785 L/min would call for four companies before rescue tasks are counted. | ||
In rural areas, apparatus must carry or haul much of the water. Granito (2008) gives as a minimum a pumper with a large tank and a water tank vehicle on the initial alarm. The tankers should be able to haul water from a source 1.6 km away so that at least 946 L/min can be pumped at the fire.<ref name="Granito-12-9">Granito (2008), p. 12-9.</ref> | In rural areas, apparatus must carry or haul much of the water. Granito (2008) gives as a minimum a pumper with a large tank and a water tank vehicle on the initial alarm. The tankers should be able to haul water from a source 1.6 km away so that at least 946 L/min can be pumped at the fire.<ref name="Granito-12-9">Granito (2008), p. 12-9.</ref> In Granito's 2008 account, the US Insurance Services Office grading schedule checked whether the built-up area had a first-due engine company within 2.4 km (1.5 mi), and whether apparatus pumps were tested regularly.<ref name="Granito-12-17">Granito (2008), p. 12-17.</ref> Reserve apparatus allow repairs without reducing fireground forces, but staffing them with recalled personnel may take 30 minutes or more.<ref name="Granito-12-11">Granito (2008), p. 12-11.</ref><ref name="Granito-12-13" /> | ||
Building fire engineering outside the United States treats the vehicles as part of the fire service's capability. The ''International Fire Engineering Guidelines'' note that the number of fire fighters, the type of fire appliance and the travel distance all influence operations. Equipment and procedures vary and must be confirmed with the local fire service.<ref name="IFEG-2.9-4">National Research Council of Canada et al. (2005), p. 2.9-4.</ref> The Australian Building Codes Board likewise states that control or suppression is only achieved within the capabilities of the appliances, crews, equipment and water in attendance.<ref name="ABCB-19">Australian Building Codes Board (2020a), p. 19.</ref> | Building fire engineering outside the United States treats the vehicles as part of the fire service's capability. The ''International Fire Engineering Guidelines'' note that the number of fire fighters, the type of fire appliance and the travel distance all influence operations. Equipment and procedures vary and must be confirmed with the local fire service.<ref name="IFEG-2.9-4">National Research Council of Canada et al. (2005), p. 2.9-4.</ref> The Australian Building Codes Board likewise states that control or suppression is only achieved within the capabilities of the appliances, crews, equipment and water in attendance.<ref name="ABCB-19">Australian Building Codes Board (2020a), p. 19.</ref> | ||
In New Zealand, the firefighting scenario of C/VM2 (second edition, 2025) requires access | In New Zealand, the firefighting scenario of C/VM2 (second edition, 2025) requires vehicle access to a hard-standing. An unobstructed path from there must reach within 20 m of the firefighter entrance and, where fitted, the sprinkler or hydrant system inlets. A hard-standing is a surface stable enough to carry a fire truck.<ref name="MBIE-53">Ministry of Business, Innovation and Employment (2025b), p. 53.</ref><ref name="MBIE-65">Ministry of Business, Innovation and Employment (2025b), p. 65.</ref> Water may come from a pumping appliance parked so that every point of the building is within 75 m, about three hose lengths.<ref name="MBIE-54">Ministry of Business, Innovation and Employment (2025b), p. 54.</ref> Writing about Dutch research on sofa fires, Van Rossum (2027) notes that, depending on the fire engine, crews can work at low, medium or high pressure, each with a different flow rate. Knowing the heat release of a fire allows a suitable cooling capacity to be set against it.<ref name="VR-8.6">Van Rossum (2027), §8.6.</ref> | ||
== Limits of the values == | == Limits of the values == | ||
Latest revision as of 18:51, 14 November 2026
Fire apparatus are the vehicles and vessels that a fire department uses to bring fire fighters, water, pumps, hose, ladders and tools to an emergency and to work from at the scene. In North America the basic apparatus is a diesel- or gasoline-engined vehicle carrying firefighting equipment. This may include a pump, hose, a water tank, an aerial ladder or elevating platform, ground ladders and portable tools.[1][2] The most common type is the pumper, or engine, whose primary purpose is to move water with adequate pressure from a source to the fire.[3] Other types carry long ladders, transport water, fight wildland fires or support rescue, hazardous materials and command work.[4]

For US automotive and wildland apparatus, Tutterow (2008) describes NFPA 1901 and NFPA 1906, respectively, as design and performance standards.[1] Under NFPA 1901 a pumper needs a pump of at least 2850 L/min (750 gpm) and a water tank of at least 1135 L (300 gal).[5] Apparatus are heavy and complex vehicles. In a typical year, more than a quarter of on-duty fire fighter deaths in the United States occurred during response to or return from incidents.[6] The requirements and values given here are those described in the handbook of 2008.
Types of apparatus
Pumpers are vehicles designed for sustained pumping during structural firefighting; NFPA 1901 requires a pump, a water tank and storage for supply and attack hose.[5] Pumpers are also called engines, wagons or triples.[7] The name "triple combination" refers to the pump, hose and water tank carried together.[5] An initial attack apparatus, or mini-pumper, needs only a pump of 950 L/min (250 gpm) and a tank of 757 L (200 gal). It was popular in the early 1980s and was slowly re-emerging in 2008 for parking garage fires, and a few departments used it as a first responder vehicle for medical calls.[5]
Apparatus with a power-operated, self-supporting aerial device reaching at least 15.3 m (50 ft) provide elevated firefighting and rescue capability; they are treated under aerial apparatus.[5] Combinations are common. A pumper that also carries long ground ladders and ladder-company equipment is a quadruple combination, or quad, and adding an aerial ladder or elevating platform makes it a quint.[5] Tutterow (2008) warns that efficiency tends to fall when too many functions are placed on one vehicle, and that the whole apparatus is out of service when one feature needs repair.[8]
Mobile water supply apparatus, called tankers in most of the United States, carry at least 3785 L (1000 gal) with quick-fill and quick-dump connections. They have a higher rollover rate per mile driven than any other type, and a higher rate of line-of-duty deaths from apparatus accidents.[5] Wildland apparatus under NFPA 1906 are generally smaller, often all-wheel-drive vehicles that can pump while moving.[8] Further types include mobile foam apparatus with at least 1900 L (500 gal) of foam concentrate, special service vehicles for rescue, command, air supply or lighting, airport crash trucks under NFPA 414 and fireboats.[8][2]
The vehicles match the work of the companies that crew them. The engine company is the most common company; its basic tactical role is to deliver water through hose lines, and most engine companies also carry emergency medical equipment.[9] Klaene and Sanders (2008) describe engine company work as extinguishing the fire, and truck company work as gaining entry, laddering, ventilation and evacuation. As long as the apparatus carries the right tools and the crew is trained, it does not matter which type of apparatus brings them.[10] Denlinger (2008) describes a trend towards buying apparatus with multiple capabilities and equipping companies for multiple functions.[11]
Fire pumps and their ratings
A pumper draws water either from a static source, such as a lake, pond or portable dump tank, or from a pressurised source. Pressurised sources include fire hydrants, elevated storage tanks and supply hose from another pumper.[3] The main pump is generally centrifugal: impellers turning at 2000 to 4000 rpm give the water velocity, which the casing converts to pressure. Two-stage pumps can run in series for maximum pressure or in parallel for maximum volume.[7]
Pumps are rated by the flow they deliver at a net pump pressure of 1035 kPa (150 psi) when drafting through 6 m of intake hose at a lift of 3 m. They must also deliver 70 percent of that flow at 1380 kPa (200 psi) and 50 percent at 1725 kPa (250 psi).[7] These are minimum rating points at specified pressures, not points measured on a particular pump's fire pump performance curve. Hague (2008b) uses them in the same way. A pumper rated at 3785 L/min (1000 gpm) can be expected to deliver no less than 2650 L/min at 1379 kPa and 1893 L/min at 1724 kPa.[12]
| Rated flow at 1035 kPa (150 psi) | 70 % of rated flow at 1380 kPa (200 psi) | 50 % of rated flow at 1725 kPa (250 psi) |
|---|---|---|
| 2000 L/min (500 gpm) | 1400 L/min (350 gpm) | 1000 L/min (250 gpm) |
| 3000 L/min (750 gpm) | 2100 L/min (525 gpm) | 1500 L/min (375 gpm) |
| 4000 L/min (1000 gpm) | 2800 L/min (700 gpm) | 2000 L/min (500 gpm) |
| 6000 L/min (1500 gpm) | 4200 L/min (1050 gpm) | 3000 L/min (750 gpm) |
| 8000 L/min (2000 gpm) | 5600 L/min (1400 gpm) | 4000 L/min (1000 gpm) |
| 10,000 L/min (2500 gpm) | 7000 L/min (1750 gpm) | 5000 L/min (1250 gpm) |
The smallest fire pump in the standards is 950 L/min (250 gpm), while pumps of 2850 to 7570 L/min (750 to 2000 gpm) are popular for municipal service.[1] The largest rated pump available was 11,356 L/min (3000 gpm), typically used in industrial settings such as refineries.[13] New pumps of 2850 L/min (750 gpm) or more are certified in tests witnessed by an independent third party. The pump must deliver its rated capacity from draft for 2 hours at 1035 kPa, followed by half-hour runs at the 70 and 50 percent points. A 10-minute overload test at 1138 kPa (165 psi) then demonstrates reserve engine power.[13]
Drafting relies on atmospheric pressure, which can theoretically lift water almost 10.5 m (34 ft) at sea level and drops by about 3.4 kPa for every 305 m of altitude. A pump in excellent condition should still draft some water at lifts of up to 7.6 m (25 ft), but its capacity falls as the lift increases.[7] For decades the standard pump has been mounted midships and driven from the vehicle engine through a pump transmission. Rear-mounted pumps were rising by 20 percent a year in the US market, and over 99 percent of the European market used them.[14]
Pump discharge pressure
On the fireground, the driver/operator must set a pump discharge pressure that delivers the required pressure at the nozzle. The pump has to supply the nozzle pressure, overcome friction loss in the hose layout and make up for any height difference between pump and nozzle.[15] Friction loss grows with the square of the flow and in proportion to the hose length, with a coefficient that depends on hose size and type. Elevation pressure is about 10 kPa per metre of height, a rounding of 9.81 kPa/m.[15][16] The flow through a solid-stream tip follows from its diameter and nozzle pressure.[17] In SI units the relations are:
| Symbol | Description | Unit |
|---|---|---|
| pump discharge pressure | kPa | |
| nozzle pressure | kPa | |
| friction loss in the hose layout | kPa | |
| elevation pressure (added when the nozzle is above the pump) | kPa | |
| friction loss coefficient of the hose (3.17 for 65 mm rubber-lined hose) | kPa | |
| , | flow; flow in hundreds of L/min | L/min; – |
| , | hose length; length in hundreds of metres | m; – |
| height of the nozzle above the pump | m | |
| diameter of a solid-stream nozzle tip | mm |
Typical nozzle pressures are 345 kPa (50 psi) for handline solid-stream nozzles, 552 kPa (80 psi) for master stream solid-stream nozzles and 690 kPa (100 psi) for standard spray nozzles.[15] In Wieder's worked example, 90 m of 65 mm rubber-lined hose supplies a 32 mm solid-stream tip at 345 kPa, held 3 m above the pump.[16] The flow is 0.0666 × 32² × √345, or 1267 L/min, so q = 12.67.[18] The friction loss is 3.17 × 12.67² × 0.9 = 458 kPa and the elevation pressure 10 × 3 = 30 kPa. The pump discharge pressure is therefore 345 + 458 + 30 = 833 kPa, or 120 psi in the US customary version of the same example.[18] In this layout, friction loss is the largest of the three terms.
The same reasoning decides whether apparatus can supply a building through its fire department connection. Hague (2008b) states that a standpipe system needs a permanent secondary water source if the apparatus pressure boost plus the residual supply pressure does not exceed the system demand. As a rule of thumb, buildings taller than 91.5 m (300 ft) should be checked for this.[19] He describes two remotely located connections as required for each zone of a high-rise building within the pumping range of apparatus, so that falling glass cannot cut all supply hoses.[20] McAllister et al. (2008) describe the New York City fire department's conventional pumpers with two-stage pumps of 4 or 8 m³/min. Its high-pressure pumpers had a third stage delivering 2 m³/min at 4.8 MPa, able singly or together to supply floors up to 110 storeys.[21]
Water tanks, hose and equipment
The water tank supplies the first hose streams before water from hydrants or other sources is available. NFPA 1901 requires at least 757 L (200 gal) on initial attack vehicles, 1136 L (300 gal) on pumpers and quints and 3785 L (1000 gal) on mobile water supply apparatus.[22] Most municipal pumpers carried at least 1900 L (500 gal), and rural pumpers often 2850 to 3785 L (750 to 1000 gal). All tanks need baffles to limit water movement while driving.[22] Water is heavy: with the common estimate of 4.54 kg (10 lb) per US gallon including the tank, a full 1893 L (500 gal) tank weighs about 2.27 t. Larger tanks make heavier vehicles that may have limited mobility on rural roads and bridges.[23]
NFPA 1901 requires a pumper to carry at least 244 m (800 ft) of fire hose of 65 mm or larger and 122 m (400 ft) of 38 to 51 mm hose. Most pumpers carry at least 366 m (1200 ft) of the larger hose, and many departments have found 125 mm (5 in) the most efficient and economical supply size.[14] A rule of thumb relates hose size to carrying capacity at normal pressures: 946 L/min for 65 mm hose, 1893 L/min for 89 mm hose and 4921 L/min for 125 mm hose. Moving 1893 L/min over 305 m therefore takes 610 m of 65 mm hose (two lines) or 305 m of 89 mm hose.[24] In 2005 NFPA required all hose to be secured against accidental deployment, prompted by the death of a child struck by hose dragged by an apparatus.[22]
Besides hose, nozzles and ground ladders, Tutterow (2008) lists breathing apparatus, cutting tools, ventilation fans, salvage covers, generators, lights and thermal imaging cameras as equipment firefighters may need; the complement varies by department.[2][25] Tutterow also notes that too many departments overload their apparatus, and advises listing every item with its weight and storage space.[23][25] NFPA 1901 sets minimum equipment allowances of 907 kg (2000 lb) for pumpers and 1136 kg (2500 lb) for aerial apparatus and quints.[23] Tutterow advises keeping equipment out of the cab unless it is needed during response. NFPA 1901 requires equipment carried there, apart from breathing apparatus, to be in latched compartments able to withstand 9 g longitudinally and 3 g in other directions.[25][26]
Road performance and crew safety
Road tests are run with the apparatus fully loaded. From a standing start it must reach 56 km/h (35 mph) within 25 s, hold at least 80 km/h on level ground and at least 32 km/h on grades up to 6 percent.[23] It must also stop within 10.7 m (35 ft) from 32 km/h. Secondary braking systems are required on vehicles over 16,330 kg (36,000 lb) and recommended above 14,062 kg.[23] The loaded vehicle must never exceed the gross vehicle weight rating set by the manufacturer. Many states exempted fire apparatus from weight limits, but Tutterow (2008) states that overloading is never good practice.[23]
Safety is a design issue as well as a driving one. Tutterow (2008) reports that in 2003 more US fire fighters were killed while responding to or returning from incidents than at incident scenes.[6] A national summit of the National Fallen Firefighters Foundation in February 2004 identified 16 fire fighter life safety initiatives. One of them states: "Safety must be a primary consideration in the design of apparatus and equipment".[6]
Only fully enclosed cabs with a belted seat for every rider should be specified, and fire fighters should never ride standing or on the rear or sides.[8] The New York City fire department's 1982 safety bulletin likewise ruled that the rear step is never a riding position. Even so, off-duty fire fighters were reported in one case to have ridden it to the World Trade Center in 2001.[27]
Details matter for crews wearing protective clothing and breathing apparatus in wet, icy or dark conditions. NFPA 1901 limits the first step to 610 mm and further steps to 457 mm in height, requires slip-resistant surfaces, and caps cab noise at 90 dB at 72 km/h.[6][26] Visible warning devices are described as the most effective warning, supplemented by reflective striping at least 100 mm wide.[6][26] Driver training should be based on NFPA 1002, under which accredited certification covered pumper, aerial, tiller, wildland, airport and mobile water supply apparatus.[6][28] Apparatus at an incident can themselves be lost: the collapse of the World Trade Center towers destroyed 91 FDNY vehicles, including 18 engines or pumpers and 15 ladder trucks.[29]
Procurement, maintenance and replacement
Tutterow (2008) recommends that apparatus be selected by the fire department with a team of specialists, at least a master mechanic, safety officer, driver/operator, training officer and fire fighter. The city purchasing department should ensure fair procedures rather than choose the vehicle.[25] Purchase and replacement belong in the capital budget, and a proper procurement takes several months. Many departments require three factory visits: before construction, at an intermediate stage, and for final inspection.[25] Acceptance tests should be performed within 10 days of delivery, in the community itself, so that problems arising during delivery are found.[30]
Pumps should be service tested at least annually and after major repairs, following NFPA 1911. The test pumps from draft for 20 minutes at 100 percent of rated capacity at 1035 kPa, then 10 minutes each at the 70 and 50 percent points. Engine speed, vacuum and pressure control are also checked.[31] NFPA 1911 makes safety the primary consideration in retiring apparatus. Tutterow (2008) notes at least two dozen safety features on apparatus of 2008 that were not required or available in the 1970s and 1980s.[31] Refurbishment under NFPA 1912 is an alternative, but the number of refurbished apparatus had declined over the previous 10 years.[32]
Costs are significant. Denlinger (2008) gives apparatus costs of normally 2 to 3 percent of payroll costs.[33] For volunteer departments, vehicles and equipment are the largest part of the budget, and in career departments usually the second after salaries and benefits.[34] A second national needs assessment, published in 2006, found that 49 percent of US fire apparatus were at least 15 years old. Converted vehicles made up 14 percent of apparatus in communities of under 2500 people.[35][36]
Apparatus in fire protection planning
In 2005, US local fire departments had 81,200 pumpers with a capacity of at least 500 gpm (1893 L/min).[37] How many must respond depends on the risk. In his 2008 US planning table, Granito lists a typical initial attack for low-hazard dwellings of at least two pumpers, one ladder truck, 14 fire fighters and one chief officer. He also lists a safety officer and rapid intervention team. For high-hazard occupancies such as hospitals and high-rise buildings, he lists at least four pumpers, two ladder trucks, 24 fire fighters and two chief officers. He again lists a safety officer and rapid intervention team.[38] A rule of thumb is one company for each 946 L/min (250 gpm) needed in an interior attack, plus personnel for rescue and other simultaneous tasks.[39] As an illustration, an interior attack needing 3785 L/min would call for four companies before rescue tasks are counted.
In rural areas, apparatus must carry or haul much of the water. Granito (2008) gives as a minimum a pumper with a large tank and a water tank vehicle on the initial alarm. The tankers should be able to haul water from a source 1.6 km away so that at least 946 L/min can be pumped at the fire.[40] In Granito's 2008 account, the US Insurance Services Office grading schedule checked whether the built-up area had a first-due engine company within 2.4 km (1.5 mi), and whether apparatus pumps were tested regularly.[41] Reserve apparatus allow repairs without reducing fireground forces, but staffing them with recalled personnel may take 30 minutes or more.[42][39]
Building fire engineering outside the United States treats the vehicles as part of the fire service's capability. The International Fire Engineering Guidelines note that the number of fire fighters, the type of fire appliance and the travel distance all influence operations. Equipment and procedures vary and must be confirmed with the local fire service.[43] The Australian Building Codes Board likewise states that control or suppression is only achieved within the capabilities of the appliances, crews, equipment and water in attendance.[44]
In New Zealand, the firefighting scenario of C/VM2 (second edition, 2025) requires vehicle access to a hard-standing. An unobstructed path from there must reach within 20 m of the firefighter entrance and, where fitted, the sprinkler or hydrant system inlets. A hard-standing is a surface stable enough to carry a fire truck.[45][46] Water may come from a pumping appliance parked so that every point of the building is within 75 m, about three hose lengths.[47] Writing about Dutch research on sofa fires, Van Rossum (2027) notes that, depending on the fire engine, crews can work at low, medium or high pressure, each with a different flow rate. Knowing the heat release of a fire allows a suitable cooling capacity to be set against it.[48]
Limits of the values
Most requirements here are NFPA 1901 and NFPA 1906 minimums in the editions described in 2008, and actual apparatus often exceeded them.[14][22] The standards leave options such as pump size, tank capacity and ladder length to local needs, so specifications for brush fires in southern California differ from those for northern Minnesota winters.[8] The chapters also convert units differently: the 750 gpm pump appears as 3000 L/min in Wieder's table and as 2850 L/min in Tutterow's chapter.[7][1] The friction loss coefficients are averages for each hose type, and the exact value varies by manufacturer.[16]
See also
- Aircraft rescue and firefighting
- Compressed air foam
- Drafting
- Fire station design
- Foam proportioner
- Water shuttle
Notes
- ↑ 1.0 1.1 1.2 1.3 Tutterow (2008), p. 12-267.
- ↑ 2.0 2.1 2.2 Tutterow (2008), p. 12-280.
- ↑ 3.0 3.1 Wieder (2008), p. 13-23.
- ↑ Tutterow (2008), pp. 12-268–12-269.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 Tutterow (2008), p. 12-268.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Tutterow (2008), p. 12-271.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Wieder (2008), p. 13-24.
- ↑ 8.0 8.1 8.2 8.3 8.4 Tutterow (2008), p. 12-269.
- ↑ Denlinger (2008), p. 12-63.
- ↑ Klaene and Sanders (2008), p. 13-7.
- ↑ Denlinger (2008), p. 12-64.
- ↑ Hague (2008b), p. 16-197.
- ↑ 13.0 13.1 Tutterow (2008), p. 12-273.
- ↑ 14.0 14.1 14.2 Tutterow (2008), p. 12-274.
- ↑ 15.0 15.1 15.2 Wieder (2008), p. 13-29.
- ↑ 16.0 16.1 16.2 Wieder (2008), p. 13-30.
- ↑ Wieder (2008), p. 13-28.
- ↑ 18.0 18.1 Wieder (2008), p. 13-31.
- ↑ Hague (2008b), pp. 16-196–16-197.
- ↑ Hague (2008b), p. 16-196.
- ↑ McAllister et al. (2008), p. 77.
- ↑ 22.0 22.1 22.2 22.3 Tutterow (2008), p. 12-275.
- ↑ 23.0 23.1 23.2 23.3 23.4 23.5 Tutterow (2008), p. 12-270.
- ↑ Tutterow (2008), pp. 12-274–12-275.
- ↑ 25.0 25.1 25.2 25.3 25.4 Tutterow (2008), p. 12-281.
- ↑ 26.0 26.1 26.2 Tutterow (2008), p. 12-272.
- ↑ Lawson and Vettori (2005), p. 55.
- ↑ Laughlin (2008), p. 12-170.
- ↑ Lawson and Vettori (2005), p. 103.
- ↑ Tutterow (2008), p. 12-282.
- ↑ 31.0 31.1 Tutterow (2008), p. 12-283.
- ↑ Tutterow (2008), p. 12-284.
- ↑ Denlinger (2008), p. 12-67.
- ↑ Tutterow (2008), p. 12-287.
- ↑ Jenaway (2008), p. 12-42.
- ↑ Jenaway (2008), p. 12-50.
- ↑ Hall and Cote (2008), p. 3-27.
- ↑ Granito (2008), p. 12-12.
- ↑ 39.0 39.1 Granito (2008), p. 12-13.
- ↑ Granito (2008), p. 12-9.
- ↑ Granito (2008), p. 12-17.
- ↑ Granito (2008), p. 12-11.
- ↑ National Research Council of Canada et al. (2005), p. 2.9-4.
- ↑ Australian Building Codes Board (2020a), p. 19.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 53.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 65.
- ↑ Ministry of Business, Innovation and Employment (2025b), p. 54.
- ↑ Van Rossum (2027), §8.6.
References
- Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
- Denlinger, R. F. (2008). Managing fire-rescue departments. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-51–12-78). National Fire Protection Association.
- Granito, J. A. (2008). Planning for public fire-rescue protection. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-3–12-22). National Fire Protection Association.
- Hague, D. R. (2008b). Standpipe and hose systems. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-191–16-204). National Fire Protection Association.
- Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
- Jenaway, W. F. (2008). Needs assessment and hazard analysis. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-41–12-50). National Fire Protection Association.
- Klaene, B. J., & Sanders, R. (2008). Fireground operations. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-3–13-11). National Fire Protection Association.
- Laughlin, J. W. (2008). Training programs for fire and emergency service personnel. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-161–12-175). National Fire Protection Association.
- Lawson, J. R., & Vettori, R. L. (2005). The emergency response operations (NIST NCSTAR 1-8). National Institute of Standards and Technology.
- McAllister, T. P., Gann, R. G., Averill, J. D., Gross, J. L., Grosshandler, W. L., Lawson, J. R., McGrattan, K. B., Pitts, W. M., Prasad, K. R., Sadek, F. H., & Nelson, H. E. (2008). Structural fire response and probable collapse sequence of World Trade Center Building 7 (NIST NCSTAR 1-9, Vols. 1–2). National Institute of Standards and Technology.
- Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Tutterow, R. (2008). Fire department apparatus and equipment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-267–12-287). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wieder, M. A. (2008). Fire streams. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-23–13-35). National Fire Protection Association.