== Definitions and principle ==
== Definitions and principle ==
The definitions above are those of Scarbrough (2008a) in the handbook chapter on electrostatic ignition sources; neither the SFPE Handbook nor ''Introduction to Fire Safety Engineering'' defines the terms separately.<ref name="Sc-11-62" /> A conductive object can be grounded directly or by bonding it to another conductive object that is already grounded.<ref name="Sc-11-62" /> Some objects are inherently bonded or grounded by their contact with the earth, such as underground piping or large storage tanks resting on the ground.<ref name="Sc-11-62" /> Artificial conducting paths are needed where natural conditions, including humidity, do not ensure a conductive path that prevents static accumulation.<ref name="Sc-11-62" />
The definitions above are those of Scarbrough (2008a) in the handbook chapter on electrostatic ignition sources; neither the SFPE Handbook nor ''Introduction to Fire Safety Engineering'' defines the terms separately.<ref name="Sc-11-62" /> A conductive object can be grounded directly or by bonding it to another conductive object that is already grounded.<ref name="Sc-11-62" /> Some objects are inherently bonded or grounded by their contact with the earth, such as underground piping or large storage tanks resting on the ground.<ref name="Sc-11-62" /> Artificial conducting paths are needed where natural conditions, including humidity, do not ensure a conductive path that prevents static accumulation.<ref name="Sc-11-62" />
[[File:fse-bonding-and-grounding-v1.svg|thumb|upright=1.5|alt=Two metal drums joined by a bond wire, one drum connected by a ground wire to an earth rod, and a large tank resting on the ground|Bonding equalises the potential between conductive objects; grounding equalises it with the earth.]]


The principle is that a spark needs a potential difference across a gap.<ref name="Sc-11-61">Scarbrough (2008a), p. 11-61.</ref> Iqbal and Salley (2004) note that a static spark can occur only when there is no other path of greater conductivity, by bonding or grounding, through which the potential difference can equalise.<ref name="IS-F-62" /> Zalosh (2002) lists grounding of equipment to prevent electrostatic discharges as a typical way to eliminate ignition sources in explosion protection.<ref name="Z-3-402">Zalosh (2002), p. 3-402.</ref> Bonding and grounding work on conductors. On a nonconductor, charge stays where it was formed, and even an earthed conductor brought close discharges only a limited area.<ref name="Sc-11-60">Scarbrough (2008a), p. 11-60.</ref>
The principle is that a spark needs a potential difference across a gap.<ref name="Sc-11-61">Scarbrough (2008a), p. 11-61.</ref> Iqbal and Salley (2004) note that a static spark can occur only when there is no other path of greater conductivity, by bonding or grounding, through which the potential difference can equalise.<ref name="IS-F-62" /> Zalosh (2002) lists grounding of equipment to prevent electrostatic discharges as a typical way to eliminate ignition sources in explosion protection.<ref name="Z-3-402">Zalosh (2002), p. 3-402.</ref> Bonding and grounding work on conductors. On a nonconductor, charge stays where it was formed, and even an earthed conductor brought close discharges only a limited area.<ref name="Sc-11-60">Scarbrough (2008a), p. 11-60.</ref>
Line 14: Line 15:


'''Worked example.''' Resistance is the ratio of voltage to current.<ref name="Sc-11-67" /> A conductor charged by a steady current ''I'' and drained through a resistance ''R'' therefore settles at a potential:
'''Worked example.''' Resistance is the ratio of voltage to current.<ref name="Sc-11-67" /> A conductor charged by a steady current ''I'' and drained through a resistance ''R'' therefore settles at a potential:
[[File:fse-bonding-and-grounding-v2.svg|thumb|upright=1.5|alt=Logarithmic resistance scale from 1 ohm to 10 gigaohm with bands for power fault paths and static leakage paths|Resistance to ground for power faults and static control, with the OSHA belting surface-resistivity limit shown separately.]]


<math display="block">V = I\,R</math>
<math display="block">V = I\,R</math>
Line 27: Line 29:
|}
|}


With a static charging current of 1 µA, a 1 MΩ ground holds the conductor at only 1 V, while a 1,000 MΩ path lets it rise to 1,000 V.<ref name="Sc-11-62" /> A 500 pF conductor, the capacitance Zalosh (2002) assumes for a silo, then stores ½''CV''<sup>2</sup> = ½ × 500 × 10<sup>−12</sup> × 1,000<sup>2</sup> = 0.25 mJ.<ref name="Z-3-405">Zalosh (2002), p. 3-405.</ref><ref name="Sc-11-61" /> That equals the [[minimum ignition energy]] of about 0.25 mJ for optimum saturated hydrocarbon vapours, which shows why fast charging calls for a lower resistance.<ref name="Sc-11-61" /> The same 1 MΩ path is useless for a power fault. On a 120 V circuit it passes only 120 µA, whereas a path of 6 Ω or less is needed even to pass the 20 A rating of a receptacle circuit.<ref name="Mi-8-143">Milatovich (2008), p. 8-143.</ref><ref name="Mi-8-161">Milatovich (2008), p. 8-161.</ref> The ratio between the two requirements is more than 100,000.
With a static charging current of 1 µA, a 1 MΩ ground holds the conductor at only 1 V, while a 1,000 MΩ path lets it rise to 1,000 V.<ref name="Sc-11-62" /> A 500 pF conductor, the capacitance Zalosh (2002) assumes for a silo, then stores ½''CV''<sup>2</sup> = ½ × 500 × 10<sup>−12</sup> × 1,000<sup>2</sup> = 0.25 mJ.<ref name="Z-3-405">Zalosh (2002), p. 3-405.</ref><ref name="Sc-11-61" /> That equals the [[minimum ignition energy]] of about 0.25 mJ for optimum saturated hydrocarbon vapours, which shows why fast charging calls for a lower resistance.<ref name="Sc-11-61" /> The same 1 MΩ path is useless for a power fault. A small US service supplies 120/240 V, and lighting and receptacle circuits are usually rated 15 or 20 A.<ref name="Mi-8-143">Milatovich (2008), p. 8-143.</ref><ref name="Mi-8-146">Milatovich (2008), p. 8-146.</ref> As an Ohm's-law illustration, a 1 MΩ path on a 120 V circuit passes only 120 µA. Merely carrying 20 A would need no more than 120 V / 20 A = 6 Ω. The actual criterion is stricter: a breaker trips only when the current exceeds its rating, and the fault-path impedance must be low enough for the fuse or circuit breaker to operate quickly.<ref name="Mi-8-146" /><ref name="Mi-8-142" /> The two resistance levels differ by a factor of more than 100,000.


== Bonding and grounding for static control ==
== Bonding and grounding for static control ==
Line 37: Line 39:


== Tank vehicles and loading racks ==
== Tank vehicles and loading racks ==
Ordile (2008) describes US loading practice in the 2008 handbook.<ref name="Or-7-30">Ordile (2008), p. 7-30.</ref> Bonding against static sparks must be provided at all stations where Class I liquids are loaded or unloaded, between the fill pipe or piping and the tank vehicle.<ref name="Or-7-30" /> The connection should be made before the dome covers are opened and remain until filling is complete and all covers are closed and secured.<ref name="Or-7-30" /> Closed metal piping systems are inherently bonded to the vehicle and need no special bonding.<ref name="Or-7-30" /> Bonding is not required for Class II and Class III liquids at ambient temperature, or for products without a static-accumulating tendency, such as asphalts, crude oils and water-soluble liquids.<ref name="Or-7-30" />
Ordile (2008) describes US loading practice in the 2008 handbook.<ref name="Or-7-30">Ordile (2008), p. 7-30.</ref> Bonding against static sparks must be provided at all stations where Class I liquids are loaded or unloaded, between the fill pipe or piping and the tank vehicle.<ref name="Or-7-30" /> The connection should be made before the dome covers are opened and remain until filling is complete and all covers are closed and secured.<ref name="Or-7-30" /> Closed metal piping systems for loading and unloading can eliminate the need for special bonding, because the piping is inherently bonded to the vehicle.<ref name="Or-7-30" /> Bonding is not required for Class II and Class III liquids at ambient temperature, or for products without a static-accumulating tendency, such as asphalts, crude oils and water-soluble liquids.<ref name="Or-7-30" />
[[File:fse-bonding-and-grounding-v3.svg|thumb|upright=1.5|alt=Loading rack with a fill pipe bonded to a tank vehicle, a tank car fill pipe bonded to the rail and an insulating section in the incoming pipeline|Bonding at a loading rack for Class I liquids and protection against stray currents at a tank car station.]]


Bonding alone does not make transfer safe. To reduce static ignitions, the delivery rate should be slowed until the fill pipe is covered, and a relaxation time of at least 30 s should be provided downstream of a filter.<ref name="Or-7-30" /> Where stray currents may be present at tank car stations, the fill pipe can be permanently bonded to at least one rail and to the rack structure.<ref name="Or-7-30" /> Insulating sections in the pipes entering the rack then isolate the rack piping from the pipelines.<ref name="Or-7-30" /> Ordile (2008) refers to NFPA 77 and API Standard 2003 for further detail.<ref name="Or-7-30" />
Bonding alone does not make transfer safe. To reduce static ignitions, the delivery rate should be slowed until the fill pipe is covered, and a relaxation time of at least 30 s should be provided downstream of a filter.<ref name="Or-7-30" /> Where stray currents may be present at tank car stations, the fill pipe can be permanently bonded to at least one rail and to the rack structure.<ref name="Or-7-30" /> Insulating sections in the pipes entering the rack then isolate the rack piping from the pipelines.<ref name="Or-7-30" /> Ordile (2008) refers to NFPA 77 and API Standard 2003 for further detail.<ref name="Or-7-30" />


== Process equipment ==
== Process equipment ==
In electrostatic spray finishing, the elements of the fluid transfer and spray system and the workpiece are bonded together.<ref name="Sb-9-34">Scarbrough (2008b), p. 9-34.</ref> Every other conductive object within 3 m (10 ft) of charged elements is included, and the bond is then grounded.<ref name="Sb-9-34" /> The spray operator is grounded by gripping the grounded gun with a bare hand or by wearing shoes with conductive soles on a grounded floor.<ref name="Sb-9-34" /> Non-electrostatic air and airless spray equipment also generates charge, so the apparatus and the sprayed object must be bonded and grounded.<ref name="Sb-9-34" /> Airless spray guns are grounded through a wire or conductive layer in the fluid hose.<ref name="Sb-9-28">Scarbrough (2008b), p. 9-28.</ref> All piping, pumps and supply and receiving vessels must be grounded and bonded during fluid transfer.<ref name="Sb-9-33">Scarbrough (2008b), p. 9-33.</ref> Residue on conveyors can act as electrical insulation and interfere with workpiece grounding.<ref name="Sb-9-34" />
In US spray-finishing practice as described by Scarbrough (2008b), electrostatic ignition is prevented by bonding together the elements of the fluid transfer and spray system and the workpiece.<ref name="Sb-9-34">Scarbrough (2008b), p. 9-34.</ref> Every other conductive object within 3 m (10 ft) of charged elements is included, and the bond is then grounded.<ref name="Sb-9-34" /> The spray operator is grounded by gripping the grounded gun with a bare hand or by wearing shoes with conductive soles on a grounded floor.<ref name="Sb-9-34" /> Non-electrostatic air and airless spray equipment also generates charge, so the apparatus and the sprayed object must be bonded and grounded.<ref name="Sb-9-34" /> Airless spray guns are grounded through a wire or conductive layer in the fluid hose.<ref name="Sb-9-28">Scarbrough (2008b), p. 9-28.</ref> All piping, pumps and supply and receiving vessels must be grounded and bonded during fluid transfer.<ref name="Sb-9-33">Scarbrough (2008b), p. 9-33.</ref> Residue on conveyors can act as electrical insulation and interfere with workpiece grounding.<ref name="Sb-9-34" />
[[File:fse-bonding-and-grounding-v4.svg|thumb|upright=1.5|alt=Plan view of an electrostatic spray station with a 3 metre bonding circle around the charged gun, bonded workpiece, pump and containers, and a grounded operator|Electrostatic spray finishing: everything conductive within 3 m (10 ft) of charged elements is bonded and grounded, and so is the operator.]]


Other equipment follows the same logic. An insulated section of an exhaust duct carrying flammable vapours or dusts can accumulate charge and discharge to the adjoining section at a joint, so such ducts should be bonded and grounded.<ref name="La-8-14">Lataille (2008), p. 8-14.</ref> All machinery and conveyor parts should be bonded and grounded, and belts can be made of conductive material or fitted with a grounded static collector.<ref name="Bo-8-36">Bouchard (2008), p. 8-36.</ref> Where stock moving through a dryer generates static, all conductive parts of the dryer should be bonded and grounded.<ref name="Os-8-91">Ostrowski (2008a), p. 8-91.</ref> In plastics plants, static tinsel must be grounded, and people who handle plastic parts must be grounded so that their body voltage does not rise with every touch.<ref name="Ou-9-62">Ouellette (2008), p. 9-62.</ref> For grain bucket elevators, US OSHA rules described by Maness and Sargent (2008) call for belting with a surface resistivity below 100 MΩ.<ref name="MS-9-98">Maness and Sargent (2008), p. 9-98.</ref>
Other equipment follows the same logic. An insulated section of an exhaust duct carrying flammable vapours or dusts can accumulate charge and discharge to the adjoining section at a joint, so such ducts should be bonded and grounded.<ref name="La-8-14">Lataille (2008), p. 8-14.</ref> All machinery and conveyor parts should be bonded and grounded, and belts can be made of conductive material or fitted with a grounded static collector.<ref name="Bo-8-36">Bouchard (2008), p. 8-36.</ref> Where stock moving through a dryer generates static, all conductive parts of the dryer should be bonded and grounded.<ref name="Os-8-91">Ostrowski (2008a), p. 8-91.</ref> In plastics plants, static tinsel must be grounded, and people who handle plastic parts must be grounded so that their body voltage does not rise with every touch.<ref name="Ou-9-62">Ouellette (2008), p. 9-62.</ref> For grain bucket elevators, US OSHA rules described by Maness and Sargent (2008) call for belting with a surface resistivity below 100 MΩ.<ref name="MS-9-98">Maness and Sargent (2008), p. 9-98.</ref>
Line 49: Line 53:


== Electrical system grounding ==
== Electrical system grounding ==
In building wiring, dangerous voltages can be imposed by lightning, accidental contact with a high-voltage primary system, insulation breakdown in transformers, surface leakage due to dirt or moisture, or a loose wire.<ref name="Mi-8-142" /> The National Electrical Code, cited in the handbook from its 2005 edition, deals with this by grounding one conductor of the system and all exposed noncurrent-carrying metal parts.<ref name="Mi-8-142" /> Fault current then has a low-resistance path through the equipment grounding conductor that operates the fuse or circuit breaker.<ref name="Mi-8-142" /> The impedance of that path must be low enough for the overcurrent device to operate quickly.<ref name="Mi-8-142" /> Metal armour of cables, raceways, boxes, cabinets and fittings must be grounded; Article 250 of the code contains the general requirements.<ref name="Mi-8-142" />
In building wiring, dangerous voltages can be imposed by lightning, accidental contact with a high-voltage primary system, insulation breakdown in transformers, surface leakage due to dirt or moisture, or a loose wire.<ref name="Mi-8-142" /> The National Electrical Code, cited in the handbook from its 2005 edition,<ref name="Mi-8-127">Milatovich (2008), p. 8-127.</ref> deals with this by grounding one conductor of the system and all exposed noncurrent-carrying metal parts.<ref name="Mi-8-142" /> Fault current then has a low-resistance path through the equipment grounding conductor that operates the fuse or circuit breaker.<ref name="Mi-8-142" /> The impedance of that path must be low enough for the overcurrent device to operate quickly.<ref name="Mi-8-142" /> Metal armour of cables, raceways, boxes, cabinets and fittings must be grounded; Article 250 of the code contains the general requirements.<ref name="Mi-8-142" />


The code, as summarised by Milatovich (2008), also requires grounding of exposed metal parts likely to become energised in two cases.<ref name="Mi-8-143" /> These are where people stand on the ground or on metal, and where equipment runs at more than 150 V to ground.<ref name="Mi-8-143" /> Cord- and plug-connected appliances such as refrigerators, washers and portable motor-operated tools are included, unless double insulation gives equivalent protection.<ref name="Mi-8-143" /> The electrodes available at a building, such as metal water pipe, building steel and concrete-encased electrodes, must be bonded together into one grounding electrode system.<ref name="Mi-8-143" /> A metal underground water pipe may serve if at least 3.0 m (10 ft) is in direct contact with the earth.<ref name="Mi-8-143" /> It must be supplemented by another electrode in case it is later replaced by plastic pipe.<ref name="Mi-8-143" /> Bonding jumpers must bridge insulated joints and equipment likely to be removed for repair.<ref name="Mi-8-143" />
The code, as summarised by Milatovich (2008), also requires grounding of exposed metal parts likely to become energised in two cases.<ref name="Mi-8-143" /> These are where people stand on the ground or on metal, and where equipment runs at more than 150 V to ground.<ref name="Mi-8-143" /> Cord- and plug-connected appliances such as refrigerators, washers and portable motor-operated tools are included, unless double insulation gives equivalent protection.<ref name="Mi-8-143" /> The electrodes available at a building, such as metal water pipe, building steel and concrete-encased electrodes, must be bonded together into one grounding electrode system.<ref name="Mi-8-143" /> A metal underground water pipe may serve if at least 3.0 m (10 ft) is in direct contact with the earth.<ref name="Mi-8-143" /> It must be supplemented by another electrode in case it is later replaced by plastic pipe.<ref name="Mi-8-143" /> Bonding jumpers must bridge insulated joints and equipment likely to be removed for repair.<ref name="Mi-8-143" />
[[File:fse-bonding-and-grounding-v5.svg|thumb|upright=1.5|alt=Schematic of a meter, service panel, neutral bonding point, water pipe electrode and supplemental ground rod|Grounding and bonding at a small 120/240 V service, with a water pipe electrode and a supplemental electrode.]]


== Lightning protection ==
== Lightning protection ==
Lightning potentials have been estimated as high as 15 million volts, and the rapid changes in current induce hazardous charges.<ref name="Ca-11-73" /> NFPA 780, as described by Caloggero (2008), therefore requires bonding of metallic masses as part of any [[lightning protection system]].<ref name="Ca-11-73" /> The bonds keep all conductive components at the same potential and minimise arcing between them.<ref name="Ca-11-73" /> Ground connections are essential, and every effort should be made to provide ample contact with the earth.<ref name="Ca-11-76" /> A down conductor run inside an iron pipe for mechanical protection must be bonded to the pipe at both ends, because the pipe otherwise chokes the conductor and raises its impedance.<ref name="Ca-11-76" />
Lightning potentials have been estimated as high as 15 million volts, and the rapid changes in current induce hazardous charges.<ref name="Ca-11-73" /> NFPA 780, as described by Caloggero (2008), therefore requires bonding of metallic masses as part of any [[lightning protection system]].<ref name="Ca-11-73" /> The bonds keep all conductive components at the same potential and minimise arcing between them.<ref name="Ca-11-73" /> Ground connections are essential, and every effort should be made to provide ample contact with the earth.<ref name="Ca-11-76" /> A down conductor run inside an iron pipe for mechanical protection must be bonded to the pipe at both ends, because the pipe otherwise chokes the conductor and raises its impedance.<ref name="Ca-11-76" />


Where soil is poor, ground rings and buried networks are used, and for new construction on sandy soil a concrete-encased electrode, made of reinforcing bars in the foundation footing, is recommended.<ref name="Ca-11-76-77">Caloggero (2008), pp. 11-76–11-77.</ref> Electrical and lightning bonding meet in some places. Elevator rails may be bonded to a lightning protection down conductor, but the down conductor may not run in the hoistway and the rails may not serve as one.<ref name="Mi-8-161" />
Where soil is poor, ground rings and buried networks are used, and for new construction on sandy soil a concrete-encased electrode, made of reinforcing bars in the foundation footing, is recommended.<ref name="Ca-11-76-77">Caloggero (2008), pp. 11-76–11-77.</ref> Electrical and lightning bonding meet in some places. Elevator rails may be bonded to a lightning protection down conductor, but the down conductor may not run in the hoistway and the rails may not serve as one.<ref name="Mi-8-161">Milatovich (2008), p. 8-161.</ref>


== Limitations ==
== Limitations ==

Latest revision as of 09:06, 9 November 2026

Bonding and grounding are two related ways of connecting conductive objects so that dangerous voltage differences cannot build up between them.[1] Bonding connects two or more conductive objects to each other by a conductor, which removes any potential difference between them.[1] Grounding, also called earthing, connects one or more conductive objects to the earth, which removes the potential difference between them and the ground; it is a specific form of bonding.[1] In fire protection the connections serve three purposes. They drain static electricity before it can spark, provide a low-resistance path that lets a fuse or circuit breaker clear an electrical fault, and keep metal parts at one potential during a lightning strike.[1][2][3] A spark that jumps between two unbonded conductors can be an ignition source for flammable vapours and dusts.[4]

Each purpose sets its own resistance requirement. For static control a path of about 1 MΩ is enough, whereas power and lightning grounds must be far lower.[1] Any ground good enough for power circuits or lightning protection is therefore more than adequate for static.[1] This article follows US practice as summarised in the Fire Protection Handbook (2008).[5] The handbook refers to NFPA 77 for static electricity, the National Electrical Code (NFPA 70) for building wiring and NFPA 780 for lightning protection.[5][2][3]

Definitions and principle

The definitions above are those of Scarbrough (2008a) in the handbook chapter on electrostatic ignition sources; neither the SFPE Handbook nor Introduction to Fire Safety Engineering defines the terms separately.[1] A conductive object can be grounded directly or by bonding it to another conductive object that is already grounded.[1] Some objects are inherently bonded or grounded by their contact with the earth, such as underground piping or large storage tanks resting on the ground.[1] Artificial conducting paths are needed where natural conditions, including humidity, do not ensure a conductive path that prevents static accumulation.[1]

Two metal drums joined by a bond wire, one drum connected by a ground wire to an earth rod, and a large tank resting on the ground
Bonding equalises the potential between conductive objects; grounding equalises it with the earth.

The principle is that a spark needs a potential difference across a gap.[6] Iqbal and Salley (2004) note that a static spark can occur only when there is no other path of greater conductivity, by bonding or grounding, through which the potential difference can equalise.[4] Zalosh (2002) lists grounding of equipment to prevent electrostatic discharges as a typical way to eliminate ignition sources in explosion protection.[7] Bonding and grounding work on conductors. On a nonconductor, charge stays where it was formed, and even an earthed conductor brought close discharges only a limited area.[8]

Resistance requirements

For static electricity the currents in bond connections are very small, of the order of microamperes, so even the smallest wires can carry them.[1] If the resistance to ground is below 1 MΩ, no practical system accumulates charge fast enough to ignite ordinary gases, vapours or dusts.[6] A resistance as high as 1,000 MΩ may give an adequate leakage path in many cases, but fast charge generation, as in pneumatic transport, may need 1 MΩ.[6] These high-resistance paths should be tested at 500 V or more, so that thin films of paint or grease or small air gaps break down and the reading is correct.[6]

For electrical power circuits, the resistance must be low enough to ensure that the fuse or circuit breaker operates under fault conditions.[1] For lightning, the resistance to ground is not critical as such, but resistance and surge impedance must be low enough to prevent side flashes between the down conductor and other grounded objects.[9] This is why a ground designed for power or lightning protection is more than adequate for static control, while the reverse is not true.[1]

Worked example. Resistance is the ratio of voltage to current.[5] A conductor charged by a steady current I and drained through a resistance R therefore settles at a potential:

Logarithmic resistance scale from 1 ohm to 10 gigaohm with bands for power fault paths and static leakage paths
Resistance to ground for power faults and static control, with the OSHA belting surface-resistivity limit shown separately.

V=IR

Symbol Description Unit
V Potential of the conductor relative to ground V
I Charging current, or fault current A
R Resistance of the bond or ground path Ω

With a static charging current of 1 µA, a 1 MΩ ground holds the conductor at only 1 V, while a 1,000 MΩ path lets it rise to 1,000 V.[1] A 500 pF conductor, the capacitance Zalosh (2002) assumes for a silo, then stores ½CV2 = ½ × 500 × 10−12 × 1,0002 = 0.25 mJ.[10][6] That equals the minimum ignition energy of about 0.25 mJ for optimum saturated hydrocarbon vapours, which shows why fast charging calls for a lower resistance.[6] The same 1 MΩ path is useless for a power fault. A small US service supplies 120/240 V, and lighting and receptacle circuits are usually rated 15 or 20 A.[11][12] As an Ohm's-law illustration, a 1 MΩ path on a 120 V circuit passes only 120 µA. Merely carrying 20 A would need no more than 120 V / 20 A = 6 Ω. The actual criterion is stricter: a breaker trips only when the current exceeds its rating, and the fault-path impedance must be low enough for the fuse or circuit breaker to operate quickly.[12][2] The two resistance levels differ by a factor of more than 100,000.

Bonding and grounding for static control

A bond or ground must have adequate mechanical strength, corrosion resistance and flexibility for its service, because the wires must withstand the rigours of the workplace.[1] Since low resistance is not needed, nearly any conductor size is satisfactory electrically.[1] Solid conductors suit fixed connections and flexible conductors suit bonds that are connected and disconnected often.[1] Some users prefer uninsulated conductors because defects are easy to see; insulated conductors should be checked for continuity at regular intervals.[1] Connections are made with pressure-type ground clamps, brazing or welding, and battery, magnetic or other special clamps ensure good metal-to-metal contact.[1] Substantial conductors are needed where a ground wire might also have to carry current from power circuits or a lightning protection system.[1][13]

When a flammable liquid is poured into a container, contact should be made between the filling nozzle and the container before flow starts and kept until filling ends.[13] Any potential difference is then dissipated before filling begins and cannot form during it.[13] Scarbrough (2008a) recommends three arrangements for bonding containers during filling.[14] With a conducting hose and the nozzle in contact with the container, no other bonding is necessary.[14] A container on an insulating support of 106 Ω or more needs a bond wire.[14] One on a conducting support of less than 106 Ω, such as metal strips fastened to the floor, is grounded through the support.[14] Ordile (2008) adds that bonding should be provided between the dispensing equipment and the container being filled, and that safety cans are preferred for handling small quantities of flammable and combustible liquids.[15]

A metal can standing on an insulating surface shows why grounding matters.[14] The charged liquid inside attracts an opposite charge to the inner wall and leaves a free charge of the same sign on the outside.[14] That charge can spark from the edge of the fill opening to a grounded fill pipe, as is suspected when gasoline cans are filled on the plastic bedliner of a pickup truck.[14] Placing the can on the ground lets the charge leak to earth.[14]

Tank vehicles and loading racks

Ordile (2008) describes US loading practice in the 2008 handbook.[16] Bonding against static sparks must be provided at all stations where Class I liquids are loaded or unloaded, between the fill pipe or piping and the tank vehicle.[16] The connection should be made before the dome covers are opened and remain until filling is complete and all covers are closed and secured.[16] Closed metal piping systems for loading and unloading can eliminate the need for special bonding, because the piping is inherently bonded to the vehicle.[16] Bonding is not required for Class II and Class III liquids at ambient temperature, or for products without a static-accumulating tendency, such as asphalts, crude oils and water-soluble liquids.[16]

Loading rack with a fill pipe bonded to a tank vehicle, a tank car fill pipe bonded to the rail and an insulating section in the incoming pipeline
Bonding at a loading rack for Class I liquids and protection against stray currents at a tank car station.

Bonding alone does not make transfer safe. To reduce static ignitions, the delivery rate should be slowed until the fill pipe is covered, and a relaxation time of at least 30 s should be provided downstream of a filter.[16] Where stray currents may be present at tank car stations, the fill pipe can be permanently bonded to at least one rail and to the rack structure.[16] Insulating sections in the pipes entering the rack then isolate the rack piping from the pipelines.[16] Ordile (2008) refers to NFPA 77 and API Standard 2003 for further detail.[16]

Process equipment

In US spray-finishing practice as described by Scarbrough (2008b), electrostatic ignition is prevented by bonding together the elements of the fluid transfer and spray system and the workpiece.[17] Every other conductive object within 3 m (10 ft) of charged elements is included, and the bond is then grounded.[17] The spray operator is grounded by gripping the grounded gun with a bare hand or by wearing shoes with conductive soles on a grounded floor.[17] Non-electrostatic air and airless spray equipment also generates charge, so the apparatus and the sprayed object must be bonded and grounded.[17] Airless spray guns are grounded through a wire or conductive layer in the fluid hose.[18] All piping, pumps and supply and receiving vessels must be grounded and bonded during fluid transfer.[19] Residue on conveyors can act as electrical insulation and interfere with workpiece grounding.[17]

Plan view of an electrostatic spray station with a 3 metre bonding circle around the charged gun, bonded workpiece, pump and containers, and a grounded operator
Electrostatic spray finishing: everything conductive within 3 m (10 ft) of charged elements is bonded and grounded, and so is the operator.

Other equipment follows the same logic. An insulated section of an exhaust duct carrying flammable vapours or dusts can accumulate charge and discharge to the adjoining section at a joint, so such ducts should be bonded and grounded.[20] All machinery and conveyor parts should be bonded and grounded, and belts can be made of conductive material or fitted with a grounded static collector.[21] Where stock moving through a dryer generates static, all conductive parts of the dryer should be bonded and grounded.[22] In plastics plants, static tinsel must be grounded, and people who handle plastic parts must be grounded so that their body voltage does not rise with every touch.[23] For grain bucket elevators, US OSHA rules described by Maness and Sargent (2008) call for belting with a surface resistivity below 100 MΩ.[24]

Grounding the vessel does not ground everything inside it. In Zalosh's silo example, grounding prevents high voltage on the silo, but ungrounded objects inside and a highly resistive powder can still hold charge.[25] Inspection programmes should therefore include checking the continuity of static grounding systems.[26] Snyder (2008) lists adequate grounding and bonding of all equipment that handles flammable liquids among the basic loss prevention measures.[27]

Electrical system grounding

In building wiring, dangerous voltages can be imposed by lightning, accidental contact with a high-voltage primary system, insulation breakdown in transformers, surface leakage due to dirt or moisture, or a loose wire.[2] The National Electrical Code, cited in the handbook from its 2005 edition,[28] deals with this by grounding one conductor of the system and all exposed noncurrent-carrying metal parts.[2] Fault current then has a low-resistance path through the equipment grounding conductor that operates the fuse or circuit breaker.[2] The impedance of that path must be low enough for the overcurrent device to operate quickly.[2] Metal armour of cables, raceways, boxes, cabinets and fittings must be grounded; Article 250 of the code contains the general requirements.[2]

The code, as summarised by Milatovich (2008), also requires grounding of exposed metal parts likely to become energised in two cases.[11] These are where people stand on the ground or on metal, and where equipment runs at more than 150 V to ground.[11] Cord- and plug-connected appliances such as refrigerators, washers and portable motor-operated tools are included, unless double insulation gives equivalent protection.[11] The electrodes available at a building, such as metal water pipe, building steel and concrete-encased electrodes, must be bonded together into one grounding electrode system.[11] A metal underground water pipe may serve if at least 3.0 m (10 ft) is in direct contact with the earth.[11] It must be supplemented by another electrode in case it is later replaced by plastic pipe.[11] Bonding jumpers must bridge insulated joints and equipment likely to be removed for repair.[11]

Schematic of a meter, service panel, neutral bonding point, water pipe electrode and supplemental ground rod
Grounding and bonding at a small 120/240 V service, with a water pipe electrode and a supplemental electrode.

Lightning protection

Lightning potentials have been estimated as high as 15 million volts, and the rapid changes in current induce hazardous charges.[3] NFPA 780, as described by Caloggero (2008), therefore requires bonding of metallic masses as part of any lightning protection system.[3] The bonds keep all conductive components at the same potential and minimise arcing between them.[3] Ground connections are essential, and every effort should be made to provide ample contact with the earth.[9] A down conductor run inside an iron pipe for mechanical protection must be bonded to the pipe at both ends, because the pipe otherwise chokes the conductor and raises its impedance.[9]

Where soil is poor, ground rings and buried networks are used, and for new construction on sandy soil a concrete-encased electrode, made of reinforcing bars in the foundation footing, is recommended.[29] Electrical and lightning bonding meet in some places. Elevator rails may be bonded to a lightning protection down conductor, but the down conductor may not run in the hoistway and the rails may not serve as one.[30]

Limitations

Bonding and grounding control charge mainly on conductors.[8] Charges on the surface of a liquid in a tank cannot be removed by bonding or grounding the tank, and a spark can still jump from the liquid surface to the shell.[14] Such charges are made harmless by inerting, by raising the vapour concentration above the upper flammable limit or by additives that increase conductivity.[14][31] Static can also accumulate on the liquid even when all conductive equipment is properly grounded, for example with high flow velocities or filtration through nonconducting media.[13]

Connections also degrade. Paint, grease, corrosion or spray residue can break the path, which is why tests at 500 V or more and periodic continuity checks are recommended.[6][17][26] Finally, the code editions and practices described here are those cited in the 2008 handbook; the handbook refers to the NFPA catalogue for current editions.[5]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 Scarbrough (2008a), p. 11-62.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Milatovich (2008), p. 8-142.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Caloggero (2008), p. 11-73.
  4. ↑ 4.0 4.1 Iqbal and Salley (2004), p. F-62.
  5. ↑ 5.0 5.1 5.2 5.3 Scarbrough (2008a), p. 11-67.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 Scarbrough (2008a), p. 11-61.
  7. ↑ Zalosh (2002), p. 3-402.
  8. ↑ 8.0 8.1 Scarbrough (2008a), p. 11-60.
  9. ↑ 9.0 9.1 9.2 Caloggero (2008), p. 11-76.
  10. ↑ Zalosh (2002), p. 3-405.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 11.5 11.6 11.7 Milatovich (2008), p. 8-143.
  12. ↑ 12.0 12.1 Milatovich (2008), p. 8-146.
  13. ↑ 13.0 13.1 13.2 13.3 Scarbrough (2008a), p. 11-63.
  14. ↑ 14.00 14.01 14.02 14.03 14.04 14.05 14.06 14.07 14.08 14.09 Scarbrough (2008a), p. 11-64.
  15. ↑ Ordile (2008), p. 7-31.
  16. ↑ 16.0 16.1 16.2 16.3 16.4 16.5 16.6 16.7 16.8 Ordile (2008), p. 7-30.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 Scarbrough (2008b), p. 9-34.
  18. ↑ Scarbrough (2008b), p. 9-28.
  19. ↑ Scarbrough (2008b), p. 9-33.
  20. ↑ Lataille (2008), p. 8-14.
  21. ↑ Bouchard (2008), p. 8-36.
  22. ↑ Ostrowski (2008a), p. 8-91.
  23. ↑ Ouellette (2008), p. 9-62.
  24. ↑ Maness and Sargent (2008), p. 9-98.
  25. ↑ Zalosh (2002), pp. 3-405–3-406.
  26. ↑ 26.0 26.1 Mattern (2008b), p. 11-37.
  27. ↑ Snyder (2008), p. 12-187.
  28. ↑ Milatovich (2008), p. 8-127.
  29. ↑ Caloggero (2008), pp. 11-76–11-77.
  30. ↑ Milatovich (2008), p. 8-161.
  31. ↑ Scarbrough (2008a), p. 11-65.

References

  • Bouchard, J. K. (2008). Materials-Handling equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-31–8-41). National Fire Protection Association.
  • Caloggero, J. M. (2008). Lightning protection systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-69–11-81). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
  • Maness, J. E., & Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-85–9-103). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.