An '''organic peroxide''' is an organic compound that contains two oxygen atoms bonded to each other in the bivalent –O–O– structure. It can be regarded as a derivative of hydrogen peroxide in which one or both hydrogen atoms have been replaced by organic radicals.<ref name="Wri-13-120">C. J. Wright (2008a), p. 13-120.</ref> | An '''organic peroxide''' is an organic compound that contains two oxygen atoms bonded to each other in the bivalent –O–O– structure. It can be regarded as a derivative of hydrogen peroxide in which one or both hydrogen atoms have been replaced by organic radicals.<ref name="Wri-13-120">C. J. Wright (2008a), p. 13-120.</ref> In plastics compounding, peroxides are characterised by a specific half-life or decomposition rate. Organic peroxides are used to start polymerisation reactions in the plastics industry, to bleach flour and as catalysts in the chemical and drug industries.<ref name="Ou-9-56">Ouellette (2008), p. 9-56.</ref><ref name="Dav-7-49">Davenport (2008), p. 7-49.</ref> | ||
All organic peroxides are combustible and increase the intensity of a fire. Many can be decomposed by heat, shock or friction, and some, such as methyl ethyl ketone peroxide, can detonate.<ref name="Dav-7-49" /> Certain organic peroxides are so unstable that they are stored under refrigeration, because their decomposition is exothermic and a batch kept too warm can heat itself until the reaction runs away.<ref name="YN-2-91">Yu and Newman (2008), p. 2-91.</ref><ref name="Gray-2-212">Gray (2002), p. 2-212.</ref> In the international transport classes described by C. J. Wright (2008a), organic peroxides form Division 5.2, next to the oxidisers in Division 5.1.<ref name="Wri-13-119">C. J. Wright (2008a), p. 13-119.</ref> In the United States, their storage is covered by NFPA 432, ''Code for the Storage of Organic Peroxide Formulations'', as described in the 2008 edition of the ''Fire Protection Handbook''.<ref name="Dav-7-50">Davenport (2008), p. 7-50.</ref> | All organic peroxides are combustible and increase the intensity of a fire. Many can be decomposed by heat, shock or friction, and some, such as methyl ethyl ketone peroxide, can detonate.<ref name="Dav-7-49" /> Certain organic peroxides are so unstable that they are stored under refrigeration, because their decomposition is exothermic and a batch kept too warm can heat itself until the reaction runs away.<ref name="YN-2-91">Yu and Newman (2008), p. 2-91.</ref><ref name="Gray-2-212">Gray (2002), p. 2-212.</ref> In the international transport classes described by C. J. Wright (2008a), organic peroxides form Division 5.2, next to the oxidisers in Division 5.1.<ref name="Wri-13-119">C. J. Wright (2008a), p. 13-119.</ref> In the United States, their storage is covered by NFPA 432, ''Code for the Storage of Organic Peroxide Formulations'', as described in the 2008 edition of the ''Fire Protection Handbook''.<ref name="Dav-7-50">Davenport (2008), p. 7-50.</ref> | ||
| Line 5: | Line 5: | ||
== Definition and chemistry == | == Definition and chemistry == | ||
C. J. Wright (2008a) reproduces the transport definition. It calls an organic peroxide "any organic compound containing oxygen (O) in the bivalent -O-O- structure" that may be considered a derivative of hydrogen peroxide, with one or more hydrogen atoms replaced by organic radicals.<ref name="Wri-13-120" /> The glossary of the handbook chapter on the plastics industry adds the property that matters in use. A peroxide is a chemical with a single oxygen-to-oxygen bond and a specific half-life or rate of decomposition; it is added to plastic during compounding to control the flow behaviour of the product.<ref name="Ou-9-56" /> | C. J. Wright (2008a) reproduces the transport definition. It calls an organic peroxide "any organic compound containing oxygen (O) in the bivalent -O-O- structure" that may be considered a derivative of hydrogen peroxide, with one or more hydrogen atoms replaced by organic radicals.<ref name="Wri-13-120" /> The glossary of the handbook chapter on the plastics industry adds the property that matters in use. A peroxide is a chemical with a single oxygen-to-oxygen bond and a specific half-life or rate of decomposition; it is added to plastic during compounding to control the flow behaviour of the product.<ref name="Ou-9-56" /> | ||
[[File:fse-organic-peroxide-v1.svg|thumb|upright=1.5|alt=Three structures side by side: H–O–O–H, R–O–O–H and R–O–O–R′, with the oxygen–oxygen bond highlighted.|An organic peroxide is a derivative of hydrogen peroxide in which one or both hydrogen atoms are replaced by organic radicals (R, R′); the oxygen–oxygen bond is kept.]] | |||
''Introduction to Fire Safety Engineering'' describes combustion as a set of mainly exothermic reactions between a fuel and an oxidiser.<ref name="VR-4.1">Van Rossum (2027), §4.1.</ref> | ''Introduction to Fire Safety Engineering'' describes combustion as a set of mainly exothermic reactions between a fuel and an oxidiser.<ref name="VR-4.1">Van Rossum (2027), §4.1.</ref> Davenport (2008) notes that all organic peroxides are combustible and that, as with the inorganic peroxides, they increase the intensity of a fire.<ref name="Dav-7-49" /> The transport classes place them in Class 5 together with the [[oxidiser|oxidisers]], with the general hazard description that these materials supply oxygen to support combustion and are sensitive to heat, shock, friction and contamination.<ref name="Wri-13-119" /> | ||
The group covers liquids and solids. Davenport (2008) gives tertiary-butyl perbenzoate as an example of a liquid and benzoyl peroxide as an example of a solid, while the transport table names dibenzoyl peroxide as its example for Division 5.2.<ref name="Dav-7-49" /><ref name="Wri-13-119" /> Commercial products | The group covers liquids and solids. Davenport (2008) gives tertiary-butyl perbenzoate as an example of a liquid and benzoyl peroxide as an example of a solid, while the transport table names dibenzoyl peroxide as its example for Division 5.2.<ref name="Dav-7-49" /><ref name="Wri-13-119" /> Commercial products may be supplied as formulations dissolved in flammable or combustible solvents, wetted with water or diluted with stable liquids.<ref name="Dav-7-49" /> Many are diluted to the point where hazardous reactions are impossible, while others still require special precautions.<ref name="Dav-7-49" /> | ||
== Uses == | == Uses == | ||
| Line 27: | Line 28: | ||
== Thermal stability and self-heating == | == Thermal stability and self-heating == | ||
An organic peroxide that decomposes slowly | An organic peroxide that decomposes slowly can release heat inside the mass of material.<ref name="YN-2-91" /> The SFPE Handbook chapter by Gray (2002) develops a general [[self-heating]] model, chiefly for solid materials, in which this can end either in a mild, stable temperature rise or in ignition. The heat release of a reaction rises almost exponentially with temperature, following the Arrhenius law, whereas the heat lost to the surroundings rises only about linearly.<ref name="Gray-2-212" /> In that model, below a critical condition the two balance at a temperature usually 5 to 20 °C above ambient. Above it there is no balance point, so the temperature can rise until ignition occurs.<ref name="Gray-2-214">Gray (2002), p. 2-214.</ref> | ||
[[File:fse-organic-peroxide-v2.svg|thumb|upright=1.5|alt=Convex heat release curve and three parallel heat loss lines: two crossings, one tangent at the critical temperature, and none.|In Gray's general self-heating model, heat release rises almost exponentially with temperature and heat loss only linearly. Below the critical ambient temperature the lines cross at a stable point; at the critical value they just touch; above it heat release exceeds heat loss and the model predicts runaway.]] | |||
Gray (2002) uses the terms runaway reaction and [[thermal runaway]] as synonyms for this supercritical behaviour in a chemical reactor.<ref name="Gray-2-212" /> For a stored body of material, the critical condition is usually stated as a critical ambient temperature for a given size and shape, or as a critical size for a given ambient temperature.<ref name="Gray-2-211">Gray (2002), p. 2-211.</ref> A larger body loses heat more slowly in relation to its volume, so its critical ambient temperature is lower.<ref name="Gray-2-214" /> Two bodies in contact therefore have a considerably lower critical ambient temperature than a single one. Tests on single packages say little about a stack of them unless a theory links the two.<ref name="Gray-2-215">Gray (2002), p. 2-215.</ref> | Gray (2002) uses the terms runaway reaction and [[thermal runaway]] as synonyms for this supercritical behaviour in a chemical reactor.<ref name="Gray-2-212" /> For a stored body of material, the critical condition is usually stated as a critical ambient temperature for a given size and shape, or as a critical size for a given ambient temperature.<ref name="Gray-2-211">Gray (2002), p. 2-211.</ref> A larger body loses heat more slowly in relation to its volume, so its critical ambient temperature is lower.<ref name="Gray-2-214" /> Two bodies in contact therefore have a considerably lower critical ambient temperature than a single one. Tests on single packages say little about a stack of them unless a theory links the two.<ref name="Gray-2-215">Gray (2002), p. 2-215.</ref> | ||
| Line 34: | Line 36: | ||
Packed bodies heat the air around them collectively and produce a "cooperative" critical ambient temperature that can be tens of degrees lower than that of one body. In one comparison, 18 kegs of 14 kg each packed in a steel box had a critical ambient temperature of 54 °C. A single keg in still air had 62.5 °C, so stacking lowered the value by 8.5 K.<ref name="Gray-2-223">Gray (2002), p. 2-223.</ref> The material in this comparison is not named, so the numbers illustrate the principle rather than a property of any peroxide. | Packed bodies heat the air around them collectively and produce a "cooperative" critical ambient temperature that can be tens of degrees lower than that of one body. In one comparison, 18 kegs of 14 kg each packed in a steel box had a critical ambient temperature of 54 °C. A single keg in still air had 62.5 °C, so stacking lowered the value by 8.5 K.<ref name="Gray-2-223">Gray (2002), p. 2-223.</ref> The material in this comparison is not named, so the numbers illustrate the principle rather than a property of any peroxide. | ||
[[File:fse-organic-peroxide-v3.svg|thumb|upright=1.5|alt=Bar chart: critical ambient temperature 62.5 °C for one keg and 54 °C for 18 kegs; 60 °C in stirred air and 55 °C in still air for calcium hypochlorite.|Critical ambient temperatures reported by Gray: stacking 18 kegs of 14 kg lowered the value from 62.5 °C to 54 °C, and still air instead of stirred oven air lowered it from 60 °C to 55 °C for a 0.175 m radius container of hydrated calcium hypochlorite.]] | |||
In line with this, Yu and Newman (2008) note that certain organic peroxides used as polymerisation catalysts are so unstable that they are stored under refrigeration to avoid exothermic heating.<ref name="YN-2-91" /> For process plant, Barry (2002) lists the data needed to identify such hazards. They include shock sensitivity and thermal analysis by differential scanning calorimetry, accelerating rate calorimetry and vent sizing apparatus, together with the effect of contaminants.<ref name="Bar-5-178">Barry (2002), p. 5-178.</ref> Data in material safety data sheets usually refer to atmospheric temperature and pressure, so experimental data for the actual process conditions are sometimes needed.<ref name="Bar-5-178" /> Gray (2002) warns that differential scanning calorimetry and differential thermal analysis give only very general information, although they can show whether an unknown material is capable of an exothermic reaction at all.<ref name="Gray-2-212" /> | In line with this, Yu and Newman (2008) note that certain organic peroxides used as polymerisation catalysts are so unstable that they are stored under refrigeration to avoid exothermic heating.<ref name="YN-2-91" /> For process plant, Barry (2002) lists the data needed to identify such hazards. They include shock sensitivity and thermal analysis by differential scanning calorimetry, accelerating rate calorimetry and vent sizing apparatus, together with the effect of contaminants.<ref name="Bar-5-178">Barry (2002), p. 5-178.</ref> Data in material safety data sheets usually refer to atmospheric temperature and pressure, so experimental data for the actual process conditions are sometimes needed.<ref name="Bar-5-178" /> Gray (2002) warns that differential scanning calorimetry and differential thermal analysis give only very general information, although they can show whether an unknown material is capable of an exothermic reaction at all.<ref name="Gray-2-212" /> | ||
| Line 44: | Line 47: | ||
== Storage and handling == | == Storage and handling == | ||
Davenport (2008) treats organic peroxides as a widely used group of [[Unstable reactive material|unstable chemicals]] that deserves special attention.<ref name="Dav-7-49" /> For all unstable chemicals, the precautions aim both to make a dangerous reaction unlikely and to limit injuries and damage if one occurs. Four points are named: the catalytic effect of containers, other materials in the same storage area that could start a dangerous reaction, the presence of inhibitors, and the effect of direct sunlight or temperature changes.<ref name="Dav-7-49" /> Containers need pressure-relief vents and storage areas need explosion venting, in addition to automatic sprinklers or water spray and the removal of all combustible material. Whenever possible, unstable chemicals are stored in a detached outside location.<ref name="Dav-7-49" /> | Davenport (2008) treats organic peroxides as a widely used group of [[Unstable reactive material|unstable chemicals]] that deserves special attention.<ref name="Dav-7-49" /> For all unstable chemicals, the precautions aim both to make a dangerous reaction unlikely and to limit injuries and damage if one occurs. Four points are named: the catalytic effect of containers, other materials in the same storage area that could start a dangerous reaction, the presence of inhibitors, and the effect of direct sunlight or temperature changes.<ref name="Dav-7-49" /> Containers need pressure-relief vents and storage areas need explosion venting, in addition to automatic sprinklers or water spray and the removal of all combustible material. Whenever possible, unstable chemicals are stored in a detached outside location.<ref name="Dav-7-49" /> | ||
[[File:fse-organic-peroxide-v4.svg|thumb|upright=1.5|alt=Cut-away of a detached store with explosion vent panels, sprinklers, vented containers, no combustibles, and fire fighters at a protected distance.|Storage precautions for unstable chemicals such as organic peroxides as described in the 2008 Fire Protection Handbook: a detached location, explosion venting, automatic sprinklers, vented containers, no combustible material, and manual fire fighting only from a protected distance.]] | |||
In the United States, NFPA 432 gives quantity and arrangement specifications for the various formulations, as described in the 2008 edition of the ''Fire Protection Handbook''. The manufacturer is consulted for specific recommendations.<ref name="Dav-7-50" /> The general principles of chemical storage also apply: segregation from other materials, from processing operations and from incompatible materials, and protection of containers against physical damage.<ref name="Dav-7-44">Davenport (2008), p. 7-44.</ref> The handbook recommends marking storage areas with the [[NFPA 704]] system, whose tables rate the degrees of health, flammability and instability hazard. Where materials with different ratings share an area, the marking shows the most severe hazard present.<ref name="Dav-7-44" /> In the diamond, the yellow right quadrant carries the reactivity rating on a scale from 0 (low) to 4 (high).<ref name="Wri-13-123">C. J. Wright (2008a), p. 13-123.</ref> | In the United States, NFPA 432 gives quantity and arrangement specifications for the various formulations, as described in the 2008 edition of the ''Fire Protection Handbook''. The manufacturer is consulted for specific recommendations.<ref name="Dav-7-50" /> The general principles of chemical storage also apply: segregation from other materials, from processing operations and from incompatible materials, and protection of containers against physical damage.<ref name="Dav-7-44">Davenport (2008), p. 7-44.</ref> The handbook recommends marking storage areas with the [[NFPA 704]] system, whose tables rate the degrees of health, flammability and instability hazard. Where materials with different ratings share an area, the marking shows the most severe hazard present.<ref name="Dav-7-44" /> In the diamond, the yellow right quadrant carries the reactivity rating on a scale from 0 (low) to 4 (high).<ref name="Wri-13-123">C. J. Wright (2008a), p. 13-123.</ref> | ||
| Line 52: | Line 56: | ||
The handbook is not uniform on water. Yu and Newman (2008) point out that, for refrigerated organic peroxides, water at normal room temperature would add heat to the peroxide and promote its exothermic decomposition.<ref name="YN-2-91" /> Frank (2008) gives the general rule that water should not be used on materials that react with water and may release oxygen, flammable gases and heat, and names peroxides, organic and inorganic, among the examples.<ref name="Fra-17-41">Frank (2008), p. 17-41.</ref> These statements are not fully consistent with the chapter on chemicals, which also refers to the manufacturer of the peroxide for specific recommendations.<ref name="Dav-7-50" /> In the SFPE Handbook, Grant (2002) notes that halon is not effective in preventing the combustion or reaction of chemicals capable of autothermal decomposition, such as hydrazine or organic peroxides.<ref name="Gra-4-152">Grant (2002), p. 4-152.</ref> | The handbook is not uniform on water. Yu and Newman (2008) point out that, for refrigerated organic peroxides, water at normal room temperature would add heat to the peroxide and promote its exothermic decomposition.<ref name="YN-2-91" /> Frank (2008) gives the general rule that water should not be used on materials that react with water and may release oxygen, flammable gases and heat, and names peroxides, organic and inorganic, among the examples.<ref name="Fra-17-41">Frank (2008), p. 17-41.</ref> These statements are not fully consistent with the chapter on chemicals, which also refers to the manufacturer of the peroxide for specific recommendations.<ref name="Dav-7-50" /> In the SFPE Handbook, Grant (2002) notes that halon is not effective in preventing the combustion or reaction of chemicals capable of autothermal decomposition, such as hydrazine or organic peroxides.<ref name="Gra-4-152">Grant (2002), p. 4-152.</ref> | ||
The hazardous materials emergency response plan of the Fire Department of the City of New York, dated 30 September 1994, is reproduced in NIST NCSTAR 1-8. It placed organic peroxides in its highest response level, Level Three. The same level | The hazardous materials emergency response plan of the Fire Department of the City of New York, dated 30 September 1994, is reproduced in NIST NCSTAR 1-8. It placed organic peroxides in its highest response level, Level Three. The same level also listed Explosive A/B, chlorine, fluorine, anhydrous ammonia and radioactive materials; an NFPA 704 rating of 3 or 4 in any numbered category also triggered Level Three.<ref name="LV-A">Lawson and Vettori (2005), Appendix A.</ref> Zalosh (2008) summarises the guidance of the Center for Chemical Process Safety of the American Institute of Chemical Engineers for recognising reaction hazards before an incident. It combines reviews of lists of unstable materials, software to identify incompatible chemicals, laboratory screening tests of onset temperatures and sensitivities, and expert review of storage and process conditions.<ref name="Zal-2-102" /> | ||
== See also == | == See also == | ||
Latest revision as of 08:27, 8 November 2026
An organic peroxide is an organic compound that contains two oxygen atoms bonded to each other in the bivalent –O–O– structure. It can be regarded as a derivative of hydrogen peroxide in which one or both hydrogen atoms have been replaced by organic radicals.[1] In plastics compounding, peroxides are characterised by a specific half-life or decomposition rate. Organic peroxides are used to start polymerisation reactions in the plastics industry, to bleach flour and as catalysts in the chemical and drug industries.[2][3]
All organic peroxides are combustible and increase the intensity of a fire. Many can be decomposed by heat, shock or friction, and some, such as methyl ethyl ketone peroxide, can detonate.[3] Certain organic peroxides are so unstable that they are stored under refrigeration, because their decomposition is exothermic and a batch kept too warm can heat itself until the reaction runs away.[4][5] In the international transport classes described by C. J. Wright (2008a), organic peroxides form Division 5.2, next to the oxidisers in Division 5.1.[6] In the United States, their storage is covered by NFPA 432, Code for the Storage of Organic Peroxide Formulations, as described in the 2008 edition of the Fire Protection Handbook.[7]
Definition and chemistry
C. J. Wright (2008a) reproduces the transport definition. It calls an organic peroxide "any organic compound containing oxygen (O) in the bivalent -O-O- structure" that may be considered a derivative of hydrogen peroxide, with one or more hydrogen atoms replaced by organic radicals.[1] The glossary of the handbook chapter on the plastics industry adds the property that matters in use. A peroxide is a chemical with a single oxygen-to-oxygen bond and a specific half-life or rate of decomposition; it is added to plastic during compounding to control the flow behaviour of the product.[2]
Introduction to Fire Safety Engineering describes combustion as a set of mainly exothermic reactions between a fuel and an oxidiser.[8] Davenport (2008) notes that all organic peroxides are combustible and that, as with the inorganic peroxides, they increase the intensity of a fire.[3] The transport classes place them in Class 5 together with the oxidisers, with the general hazard description that these materials supply oxygen to support combustion and are sensitive to heat, shock, friction and contamination.[6]
The group covers liquids and solids. Davenport (2008) gives tertiary-butyl perbenzoate as an example of a liquid and benzoyl peroxide as an example of a solid, while the transport table names dibenzoyl peroxide as its example for Division 5.2.[3][6] Commercial products may be supplied as formulations dissolved in flammable or combustible solvents, wetted with water or diluted with stable liquids.[3] Many are diluted to the point where hazardous reactions are impossible, while others still require special precautions.[3]
Uses
Organic peroxides are an important group of industrial chemicals. In the plastics industry they serve as initiators of polymerisation reactions, in the milling industry as flour bleaches, and in the chemical and drug industries as catalysts.[3] Allyl resins can be polymerised either by raising their temperature or by using peroxide initiators.[9] Unsaturated polyesters, used for reinforced plastics in products from electrical components to large boat hulls, are cured by further polymerisation with initiators such as organic peroxides.[10] In compounding, peroxides with a known decomposition rate are used to control the flow of the molten plastic.[2]
Organic peroxides are therefore handled in plastics processing, flour milling, chemical and drug production, and laboratories.[3] In laboratories, the handbook lists organic peroxides among the hazardous chemicals that are not brought in unless the design, construction and fire protection suit the quantity and the hazard. Quantities are kept to the minimum needed for the work, handling follows the manufacturer's recommendations, and materials sensitive to temperature need special storage.[11] In United States workplace regulation, organic peroxides are one of the examples of a "physical hazard", as described by Hildebrand and Noll (2008). The definition is that of the Occupational Safety and Health Administration (29 CFR 1910).[12]
Decomposition and fire behaviour
The central hazard is decomposition. Many organic peroxides can be decomposed by heat, shock or friction, and the rate of decomposition depends on the particular formulation and on the temperature.[3] The violence of the reaction varies widely.[3]
Zalosh (2008) distinguishes two kinds of explosion. In a deflagration the flame travels well below the speed of sound and the pressure rises almost uniformly. In a detonation the flame propagates at supersonic speed and the pressure rise is carried by a shock wave.[13] Some organic peroxides, such as methyl ethyl ketone peroxide, are detonatable.[3]
Benzoyl peroxide illustrates the range of behaviour. In undiluted form it ignites very readily and burns with great rapidity, similar to an equal amount of black powder. Its thermal decomposition is rapid, and if it is confined while heated, explosive decomposition occurs.[7] Heavy shock or frictional heat can also start decomposition. For this reason most benzoyl peroxide is shipped diluted or wetted with water.[7] Formulation can also create new hazards: in solutions, sensitive crystals can form when the liquid freezes.[3]
Containment changes the outcome. Organic peroxides are shipped in specific containers that are designed not to confine the peroxide under fire conditions, and care is needed if the material is transferred to another container.[3][7] Zalosh (2008) describes the general mechanism of chemical reaction explosions. Uncontrolled decompositions of unstable compounds can produce gaseous products that overpressurise vessels without an adequate relief vent area, and runaway exothermic reactions can heat and pressurise the gases already present. Several of these reactions are autocatalytic, which means that their own products speed up the reaction of the remaining material.[14]
Data on the fire size of stored organic peroxides are scarce. In the SFPE Handbook, Babrauskas (2002b) mentions a study of burning pallet loads, with liquids packed in plastic containers inside cardboard boxes and solids in cardboard drums. Data were available for only a few packaging configurations, which was not enough to generalise heat release rate predictions to other arrangements.[15]
Thermal stability and self-heating
An organic peroxide that decomposes slowly can release heat inside the mass of material.[4] The SFPE Handbook chapter by Gray (2002) develops a general self-heating model, chiefly for solid materials, in which this can end either in a mild, stable temperature rise or in ignition. The heat release of a reaction rises almost exponentially with temperature, following the Arrhenius law, whereas the heat lost to the surroundings rises only about linearly.[5] In that model, below a critical condition the two balance at a temperature usually 5 to 20 °C above ambient. Above it there is no balance point, so the temperature can rise until ignition occurs.[16]
Gray (2002) uses the terms runaway reaction and thermal runaway as synonyms for this supercritical behaviour in a chemical reactor.[5] For a stored body of material, the critical condition is usually stated as a critical ambient temperature for a given size and shape, or as a critical size for a given ambient temperature.[17] A larger body loses heat more slowly in relation to its volume, so its critical ambient temperature is lower.[16] Two bodies in contact therefore have a considerably lower critical ambient temperature than a single one. Tests on single packages say little about a stack of them unless a theory links the two.[18]
The effect is large enough to matter in transport. Gray (2002) criticises an empirical oven test, described in the United Nations manual of tests and criteria for the transport of dangerous goods, that is used to set "safe" shipping conditions for self-heating materials. The test determines critical parameters under vaguely defined forced airflow, whereas packages travel in still air, stacked together inside a container.[19]
Packed bodies heat the air around them collectively and produce a "cooperative" critical ambient temperature that can be tens of degrees lower than that of one body. In one comparison, 18 kegs of 14 kg each packed in a steel box had a critical ambient temperature of 54 °C. A single keg in still air had 62.5 °C, so stacking lowered the value by 8.5 K.[20] The material in this comparison is not named, so the numbers illustrate the principle rather than a property of any peroxide.
In line with this, Yu and Newman (2008) note that certain organic peroxides used as polymerisation catalysts are so unstable that they are stored under refrigeration to avoid exothermic heating.[4] For process plant, Barry (2002) lists the data needed to identify such hazards. They include shock sensitivity and thermal analysis by differential scanning calorimetry, accelerating rate calorimetry and vent sizing apparatus, together with the effect of contaminants.[21] Data in material safety data sheets usually refer to atmospheric temperature and pressure, so experimental data for the actual process conditions are sometimes needed.[21] Gray (2002) warns that differential scanning calorimetry and differential thermal analysis give only very general information, although they can show whether an unknown material is capable of an exothermic reaction at all.[5]
Peroxide-forming ethers
Organic peroxides can also form unintentionally. During storage, practically all ethers form ether peroxides, and when the mixture is heated or concentrated, the peroxide can detonate.[7] With some ethers the quantities formed are too small to matter, but peroxide formation is a hazardous property of diethyl ether, ethyl tertiary-butyl ether, ethyl tertiary-amyl ether and the isopropyl ethers. Isopropyl ether is said to be considerably more susceptible than the others.[7] Pure, dry ether stored in a clear, colourless bottle under laboratory conditions develops detectable amounts of peroxides within one month. Light appears to matter more than heat, although peroxides have formed in amber bottles as well.[7]
According to the 2008 handbook, no means was yet available to eliminate peroxide formation completely. Inhibitors, or copper or iron, combined with storage in metal or opaque amber glass containers, give sufficient stability for practical purposes.[7] Ether should not be distilled to dryness unless peroxides have been proved absent.[7] In process hazard identification, Barry (2002) includes peroxide-forming materials among the miscellaneous properties to be collected.[21]
Storage and handling
Davenport (2008) treats organic peroxides as a widely used group of unstable chemicals that deserves special attention.[3] For all unstable chemicals, the precautions aim both to make a dangerous reaction unlikely and to limit injuries and damage if one occurs. Four points are named: the catalytic effect of containers, other materials in the same storage area that could start a dangerous reaction, the presence of inhibitors, and the effect of direct sunlight or temperature changes.[3] Containers need pressure-relief vents and storage areas need explosion venting, in addition to automatic sprinklers or water spray and the removal of all combustible material. Whenever possible, unstable chemicals are stored in a detached outside location.[3]
In the United States, NFPA 432 gives quantity and arrangement specifications for the various formulations, as described in the 2008 edition of the Fire Protection Handbook. The manufacturer is consulted for specific recommendations.[7] The general principles of chemical storage also apply: segregation from other materials, from processing operations and from incompatible materials, and protection of containers against physical damage.[22] The handbook recommends marking storage areas with the NFPA 704 system, whose tables rate the degrees of health, flammability and instability hazard. Where materials with different ratings share an area, the marking shows the most severe hazard present.[22] In the diamond, the yellow right quadrant carries the reactivity rating on a scale from 0 (low) to 4 (high).[23]
Fire control and emergency response
Davenport (2008) recommends water as the extinguishing agent for fires involving unstable chemicals, including organic peroxides.[7] Automatic sprinklers are described as the best protection, because fires involving such materials can lead to explosions. Manual fire fighting is carried out from a distance at which the fire fighters are protected from an explosion.[7] Fire fighters should be thoroughly briefed in advance on the procedures for a fire involving or exposing a store of unstable chemicals.[3]
The handbook is not uniform on water. Yu and Newman (2008) point out that, for refrigerated organic peroxides, water at normal room temperature would add heat to the peroxide and promote its exothermic decomposition.[4] Frank (2008) gives the general rule that water should not be used on materials that react with water and may release oxygen, flammable gases and heat, and names peroxides, organic and inorganic, among the examples.[24] These statements are not fully consistent with the chapter on chemicals, which also refers to the manufacturer of the peroxide for specific recommendations.[7] In the SFPE Handbook, Grant (2002) notes that halon is not effective in preventing the combustion or reaction of chemicals capable of autothermal decomposition, such as hydrazine or organic peroxides.[25]
The hazardous materials emergency response plan of the Fire Department of the City of New York, dated 30 September 1994, is reproduced in NIST NCSTAR 1-8. It placed organic peroxides in its highest response level, Level Three. The same level also listed Explosive A/B, chlorine, fluorine, anhydrous ammonia and radioactive materials; an NFPA 704 rating of 3 or 4 in any numbered category also triggered Level Three.[26] Zalosh (2008) summarises the guidance of the Center for Chemical Process Safety of the American Institute of Chemical Engineers for recognising reaction hazards before an incident. It combines reviews of lists of unstable materials, software to identify incompatible chemicals, laboratory screening tests of onset temperatures and sensitivities, and expert review of storage and process conditions.[14]
See also
- Chemical incompatibility
- Explosive material
- Hazardous materials placarding
- Safety data sheet
- Water-reactive material
Notes
- ↑ 1.0 1.1 C. J. Wright (2008a), p. 13-120.
- ↑ 2.0 2.1 2.2 Ouellette (2008), p. 9-56.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 Davenport (2008), p. 7-49.
- ↑ 4.0 4.1 4.2 4.3 Yu and Newman (2008), p. 2-91.
- ↑ 5.0 5.1 5.2 5.3 Gray (2002), p. 2-212.
- ↑ 6.0 6.1 6.2 C. J. Wright (2008a), p. 13-119.
- ↑ 7.00 7.01 7.02 7.03 7.04 7.05 7.06 7.07 7.08 7.09 7.10 7.11 7.12 Davenport (2008), p. 7-50.
- ↑ Van Rossum (2027), §4.1.
- ↑ Benedetti and Colonna (2008), p. 6-213.
- ↑ Benedetti and Colonna (2008), p. 6-221.
- ↑ Anderson (2008a), p. 9-165.
- ↑ Hildebrand and Noll (2008), p. 13-82.
- ↑ Zalosh (2008), p. 2-99.
- ↑ 14.0 14.1 Zalosh (2008), p. 2-102.
- ↑ Babrauskas (2002b), p. 3-18.
- ↑ 16.0 16.1 Gray (2002), p. 2-214.
- ↑ Gray (2002), p. 2-211.
- ↑ Gray (2002), p. 2-215.
- ↑ Gray (2002), pp. 2-222–2-223.
- ↑ Gray (2002), p. 2-223.
- ↑ 21.0 21.1 21.2 Barry (2002), p. 5-178.
- ↑ 22.0 22.1 Davenport (2008), p. 7-44.
- ↑ C. J. Wright (2008a), p. 13-123.
- ↑ Frank (2008), p. 17-41.
- ↑ Grant (2002), p. 4-152.
- ↑ Lawson and Vettori (2005), Appendix A.
References
- Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
- Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
- Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-176–5-213). National Fire Protection Association; Society of Fire Protection Engineers.
- Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
- Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
- Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
- Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-149–4-172). National Fire Protection Association; Society of Fire Protection Engineers.
- Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
- Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
- Lawson, J. R., & Vettori, R. L. (2005). The emergency response operations (NIST NCSTAR 1-8). National Institute of Standards and Technology.
- Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
- Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.