A '''flammable gas''' is a substance that is a gas at normal temperature and pressure and that burns when mixed with air in the right proportions.<ref name="L-6-165">Lemoff (2008), p. 6-165.</ref> In the United States, the formal definition in NFPA 55 and in the transport regulations of the Department of Transportation (DOT) rests on two tests. The gas must be ignitable in a mixture of 13 % or less by volume with air, or have a flammable range in air at least 12 percentage points wide.<ref name="L-6-165" /><ref name="L-6-166">Lemoff (2008), p. 6-166.</ref> Common examples are natural gas, propane, butane, hydrogen, acetylene and ethylene.<ref name="L-6-174">Lemoff (2008), p. 6-174, Table 6.10.3.</ref>
A '''flammable gas''' is a substance that is a gas at normal temperature and pressure and that burns when mixed with air in the right proportions.<ref name="L-6-165">Lemoff (2008), p. 6-165.</ref> In the United States, the formal definition in NFPA 55 and in the transport regulations of the Department of Transportation (DOT) rests on two tests. The gas must be ignitable in a mixture of 13 % or less by volume with air, or have a flammable range in air at least 12 percentage points wide.<ref name="L-6-165" /><ref name="L-6-166">Lemoff (2008), p. 6-166.</ref> Common examples are natural gas, propane, butane, hydrogen, acetylene and ethylene.<ref name="L-6-174">Lemoff (2008), p. 6-174, Table 6.10.3.</ref>


Unlike a flammable liquid, a flammable gas does not first have to evaporate, so it can always ignite once it is released and mixed with air.<ref name="L-6-166" /> The ''Fire Protection Handbook'' distinguishes two basic hazards of a release: a combustion explosion inside a building or structure, and a fire.<ref name="L-6-174" /> An enclosure that is only partly filled with a flammable mixture can already be destroyed, because ordinary structures withstand only a few kilopascals.<ref name="L-6-175">Lemoff (2008), p. 6-175.</ref> Outdoors, a release can burn as a jet flame, as a flash fire through a drifting cloud, or as a vapour cloud explosion.<ref name="By-3-269">Beyler (2002a), p. 3-269.</ref><ref name="Z08-2-104">Zalosh (2008), p. 2-104.</ref> Protection relies on tight containment, odorisation, ventilation, control of ignition sources, gas detection and water cooling of exposed containers.<ref name="L-6-175" /><ref name="L-6-176">Lemoff (2008), p. 6-176.</ref>
Unlike a flammable liquid, a flammable gas does not first have to evaporate. Once released, it can ignite if it mixes with air within its flammable limits and receives enough ignition energy.<ref name="L-6-166" /> The ''Fire Protection Handbook'' distinguishes two basic hazards of a release: a combustion explosion inside a building or structure, and a fire.<ref name="L-6-174" /> An enclosure that is only partly filled with a flammable mixture can already be destroyed, because ordinary structures withstand only a few kilopascals.<ref name="L-6-175">Lemoff (2008), p. 6-175.</ref> Outdoors, a release can burn as a jet flame, as a flash fire through a drifting cloud, or as a vapour cloud explosion.<ref name="By-3-269">Beyler (2002a), p. 3-269.</ref><ref name="Z08-2-104">Zalosh (2008), p. 2-104.</ref> Protection relies on tight containment, odorisation, ventilation, control of ignition sources, gas detection and water cooling of exposed containers.<ref name="L-6-175" /><ref name="L-6-176">Lemoff (2008), p. 6-176.</ref>


== Definition and classification ==
== Definition and classification ==
The handbook chapter on gases uses the term gas only for substances that are gaseous at normal temperature and pressure (NTP), about 21 °C (70 °F) and 101 kPa.<ref name="L-6-165" /> In the United States, NFPA 55, as described in the 2008 edition of the ''Fire Protection Handbook'', is the standard for the storage, use and handling of compressed gases. It defines a flammable gas as a material that is a gas at 20 °C (68 °F) or less at 101.325 kPa.<ref name="L-6-165" /> It must also be ignitable at that pressure in a mixture of 13 % or less by volume with air, or have a flammable range with air of at least 12 %, regardless of the lower limit.<ref name="L-6-165" /> A flammable liquefied gas is a liquefied compressed gas that is partly liquid at 20 °C in its charged container and that is flammable.<ref name="L-6-166" />
The handbook chapter on gases uses the term gas only for substances that are gaseous at normal temperature and pressure (NTP), about 21 °C (70 °F) and 101 kPa.<ref name="L-6-165" /> In the United States, NFPA 55, as described in the 2008 edition of the ''Fire Protection Handbook'', is the standard for the storage, use and handling of compressed gases. It defines a flammable gas as a material that is a gas at 20 °C (68 °F) or less at 101.325 kPa.<ref name="L-6-165" /> It must also be ignitable at that pressure in a mixture of 13 % or less by volume with air, or have a flammable range with air of at least 12 %, regardless of the lower limit.<ref name="L-6-165" /> A flammable liquefied gas is a liquefied compressed gas that is partly liquid at 20 °C in its charged container and that is flammable.<ref name="L-6-166" />


Lemoff notes that these definitions are the same as those of the DOT regulations, and therefore identical to those used for labelling gases in transport in the United States.<ref name="L-6-166" /> They are also essentially identical to the United Nations protocols for international gas shipments.<ref name="L-6-166" /> In the DOT hazard classes, flammable gases form Division 2.1, with propane, butadiene, acetylene and methyl chloride as examples.<ref name="CJW-13-119">C. J. Wright (2008a), pp. 13-119–13-120.</ref> In the 2007 edition of NFPA 704, the highest flammability rating, 4, covers materials that turn rapidly or completely into vapour at atmospheric pressure and normal ambient temperature and burn readily.<ref name="CJW-13-123">C. J. Wright (2008a), p. 13-123.</ref>
In the 2008 handbook, Lemoff notes that these definitions match those in the DOT regulations then used to label gases for transport in the United States.<ref name="L-6-166" /> They are also described as essentially identical to the United Nations protocols for international gas shipments.<ref name="L-6-166" /> In that account of the DOT hazard classes, flammable gases form Division 2.1, with propane, butadiene, acetylene and methyl chloride as examples.<ref name="CJW-13-119">C. J. Wright (2008a), pp. 13-119–13-120.</ref> In the 2001 edition of NFPA 704, the highest flammability rating, 4, covers materials that turn rapidly or completely into vapour at atmospheric pressure and normal ambient temperature and burn readily.<ref name="CJW-13-123">C. J. Wright (2008a), p. 13-123.</ref>


NFPA 55 places flammable gases among the physical-hazard classes, next to nonflammable, oxidising, pyrophoric and unstable reactive gases.<ref name="L-6-166" /> Pyrophoric gases are flammable gases that ignite spontaneously in air, such as silane and phosphine, and are found mostly in semiconductor manufacturing.<ref name="L-6-166" /> Some gases that can be made to burn are still treated as nonflammable because their range is narrow or their lower limit high. Anhydrous ammonia is the standard example: the DOT classifies it as a nonflammable gas for interstate transport.<ref name="L-6-166" />
The NFPA 55 classification described by Lemoff places flammable gases among the physical-hazard classes, next to nonflammable, oxidising, pyrophoric and unstable reactive gases.<ref name="L-6-166" /> Pyrophoric gases are flammable gases that ignite spontaneously in air, such as silane and phosphine, and are found mostly in semiconductor manufacturing.<ref name="L-6-166" /> Some gases that can be made to burn are still treated as nonflammable because their range is narrow or their lower limit high. Anhydrous ammonia is the handbook's example: DOT classified it as a nonflammable gas for interstate transport at the time.<ref name="L-6-166" />


The flash point, which is central to the classification of flammable liquids, has no practical meaning for flammable gases.<ref name="L-6-166" /> A flammable gas normally exists above its boiling point, even when it is stored as a liquid, and therefore always above its flash point.<ref name="L-6-166" /> By usage, the most widely used fuel gases are natural gas and the liquefied petroleum gases butane and propane.<ref name="L-6-168">Lemoff (2008), p. 6-168.</ref>
The flash point, which is central to the classification of flammable liquids, has no practical meaning for flammable gases.<ref name="L-6-166" /> A flammable gas normally exists above its normal boiling point at atmospheric pressure, even when it is stored as a liquid under pressure, and therefore above its flash point.<ref name="L-6-166" /> By usage, the most widely used fuel gases are natural gas and the liquefied petroleum gases butane and propane.<ref name="L-6-168">Lemoff (2008), p. 6-168.</ref>


== Combustion properties ==
== Combustion properties ==
''Introduction to Fire Safety Engineering'' explains that a flammable gas burns only when it mixes with oxygen in the right proportion and enough energy is available to ignite the mixture.<ref name="VR-3.1">Van Rossum (2027), §3.1.</ref> The ideal proportion is the stoichiometric ratio, and the further a mixture departs from it, the more slowly it burns.<ref name="VR-3.3">Van Rossum (2027), §3.3.</ref> The stoichiometric fuel fraction in air is 0.095 for methane, 0.040 for propane and 0.296 for hydrogen.<ref name="Z08-2-98">Zalosh (2008), p. 2-98.</ref>
''Introduction to Fire Safety Engineering'' explains that a flammable gas burns only when it mixes with oxygen in the right proportion and enough energy is available to ignite the mixture.<ref name="VR-3.1">Van Rossum (2027), §3.1.</ref> The stoichiometric ratio gives the proportions for complete combustion, although the maximum burning velocity can occur on the fuel-rich side of that ratio.<ref name="VR-3.3">Van Rossum (2027), §3.3.</ref><ref name="By-2-179">Beyler (2002b), p. 2-179.</ref> The stoichiometric fuel fraction in air is 0.095 for methane, 0.040 for propane and 0.296 for hydrogen.<ref name="Z08-2-98">Zalosh (2008), p. 2-98.</ref>


Every flammable gas has a lower and an upper flammable limit. A mixture with air ignites only between these [[flammability limits]], and only when at least the [[minimum ignition energy]] is supplied.<ref name="L-6-166" /> The SFPE Handbook defines the limits as the range of compositions within which a premixed flame can propagate, at a specified temperature and pressure.<ref name="By-2-172">Beyler (2002b), p. 2-172.</ref> For most simple hydrocarbons, the limits in air correspond to equivalence ratios of about 0.5 and 3.<ref name="By-2-172" /> Adding oxygen raises the upper limit but hardly changes the lower limit, and both limits widen as the temperature rises.<ref name="By-2-174">Beyler (2002b), pp. 2-173–2-174.</ref> The lower limit is insensitive to pressure except well below atmospheric, while the upper limit rises above atmospheric pressure.<ref name="By-2-174" />
Every flammable gas has a lower and an upper flammable limit. A mixture with air ignites only between these [[flammability limits]], and only when at least the [[minimum ignition energy]] is supplied.<ref name="L-6-166" /> The SFPE Handbook defines the limits as the range of compositions within which a premixed flame can propagate, at a specified temperature and pressure.<ref name="By-2-172">Beyler (2002b), p. 2-172.</ref> For most simple hydrocarbons, the limits in air correspond to equivalence ratios of about 0.5 and 3.<ref name="By-2-172" /> Adding oxygen raises the upper limit but hardly changes the lower limit, and both limits widen as the temperature rises.<ref name="By-2-174">Beyler (2002b), pp. 2-173–2-174.</ref> The lower limit is insensitive to pressure except well below atmospheric, while the upper limit rises above atmospheric pressure.<ref name="By-2-174" />


The table below gives the combustion properties of common flammable gases from the handbook. The specific gravity compares the density of the gas with that of air.<ref name="L-6-174" />
The handbook gives the following properties; specific gravity compares gas density with air.<ref name="L-6-174" />


{| class="wikitable"
{| class="wikitable"
Line 40: Line 40:
|}
|}


Ignition energies differ by orders of magnitude. In dry air at 1 atm and 25 °C, the minimum ignition energy is 0.016 mJ for hydrogen and 0.017 mJ for acetylene. Methane needs 0.21 mJ and propane 0.24 mJ, while ammonia needs 680 mJ.<ref name="Br-17-147">Britton (1999), as cited in Ural and Garzia (2008), p. 17-147.</ref> Hydrogen also has an extremely wide flammable range and the highest burning velocity of any gas, and it burns with a nearly invisible flame.<ref name="L-6-181">Lemoff (2008), pp. 6-181–6-182.</ref> Ethylene combines a wide flammable range with a high burning velocity.<ref name="L-6-180">Lemoff (2008), pp. 6-180–6-181.</ref> Ammonia, by contrast, owes its limited flammability to its high lower limit and low heat of combustion.<ref name="L-6-178">Lemoff (2008), pp. 6-178–6-179.</ref>
Ignition energies differ by orders of magnitude. In dry air at 1 atm and 25 °C, the minimum ignition energy is 0.016 mJ for hydrogen and 0.017 mJ for acetylene. Methane needs 0.21 mJ and propane 0.24 mJ, while ammonia needs 680 mJ.<ref name="Br-17-147">Britton (1999), as cited in Ural and Garzia (2008), p. 17-147.</ref> Hydrogen also has an extremely wide flammable range, a high burning velocity in air, and a nearly invisible flame.<ref name="L-6-181">Lemoff (2008), pp. 6-181–6-182.</ref> Ethylene combines a wide flammable range with a high burning velocity.<ref name="L-6-180">Lemoff (2008), pp. 6-180–6-181.</ref> Ammonia, by contrast, owes its limited flammability to its high lower limit and low heat of combustion.<ref name="L-6-178">Lemoff (2008), pp. 6-178–6-179.</ref>


Gas concentrations are usually expressed as a percentage of the lower flammable limit (% LFL). For a gas with a lower limit of 4.0 %, a reading of 25 % LFL means 1 % gas by volume in the sample.<ref name="C-14-100">Cholin (2008a), p. 14-100.</ref> The older terms lower and upper explosive limit (LEL and UEL) are still found in the literature for the same concentrations.<ref name="C-14-100" /> NUREG-1805 states that the terms explosive limits and flammable limits are used interchangeably.<ref name="IS-B-25">Iqbal and Salley (2004), p. B-25.</ref> Lemoff, however, notes that hydrogen has a recognised explosive range that is narrower than its flammable range. He recommends that the term explosive range be used only for hydrogen.<ref name="L-6-166" />
Gas concentrations can be expressed as a percentage of the lower flammable limit (% LFL). If the limit is 4.0 %, a reading of 25 % LFL means 1 % gas by volume.<ref name="C-14-100">Cholin (2008a), p. 14-100.</ref> Older literature also uses lower and upper explosive limit (LEL and UEL).<ref name="C-14-100" /> NUREG-1805 states that the terms explosive limits and flammable limits are used interchangeably.<ref name="IS-B-25">Iqbal and Salley (2004), p. B-25.</ref> Lemoff, however, notes that hydrogen has a recognised explosive range that is narrower than its flammable range. He recommends that the term explosive range be used only for hydrogen.<ref name="L-6-166" />


== Hazards in containers ==
== Hazards in containers ==
Gases expand when heated, so a fire raises the container pressure. This can open a pressure-relief valve or cause the container to fail, and a heated container can also lose its strength.<ref name="L-6-168" /> Container failure releases the energy stored by compression or liquefaction, often extremely rapidly and violently.<ref name="L-6-169">Lemoff (2008), p. 6-169.</ref> Failures of compressed gas containers are marked mainly by flying fragments. Liquefied gas containers hold far more gas and can release larger quantities.<ref name="L-6-169" />
A fire raises gas pressure and can weaken a container, opening its relief valve or causing failure.<ref name="L-6-168" /> Failure can violently release stored compression or liquefaction energy and throw fragments.<ref name="L-6-169">Lemoff (2008), p. 6-169.</ref> Liquefied gas containers hold more gas and can release larger quantities.<ref name="L-6-169" />


Liquefied flammable gases such as [[liquefied petroleum gas]] add the hazard of the boiling liquid expanding vapour explosion (BLEVE). When such a container fails, about one-third of the liquid can turn to vapour at normal temperatures, and often more than half in a fire.<ref name="L-6-170">Lemoff (2008), pp. 6-170–6-171.</ref> Container pieces can be thrown up to about 0.8 km, and fatal burns have occurred up to 76 m from larger containers.<ref name="L-6-172">Lemoff (2008), p. 6-172.</ref> In the LP-gas disaster near Mexico City on 19 November 1984, about 15 BLEVEs were recorded, and some 500 deaths were reported.<ref name="L-6-172" />
Liquefied flammable gases such as [[liquefied petroleum gas]] add the hazard of the boiling liquid expanding vapour explosion (BLEVE). When such a container fails, about one-third of the liquid can turn to vapour at normal temperatures, and often more than half in a fire.<ref name="L-6-170">Lemoff (2008), pp. 6-170–6-171.</ref> Container pieces can be thrown up to about 0.8 km (½ mile), and fatal burns have occurred up to 76 m from larger containers.<ref name="L-6-172">Lemoff (2008), p. 6-172.</ref> In the LP-gas disaster near Mexico City on 19 November 1984, about 15 BLEVEs were recorded, and some 500 deaths were reported.<ref name="L-6-172" />


A flammable gas can also burn inside a container. Gas–air or gas–oxygen mixtures are seldom made in containers on purpose but can form by accident, for example in piping that carries both oxygen and a fuel gas for cutting and welding. Oxygen–fuel gas cutting systems therefore have special backflow prevention devices.<ref name="L-6-173">Lemoff (2008), p. 6-173.</ref>
A flammable gas can also burn inside a container. Gas–air or gas–oxygen mixtures are seldom made in containers on purpose but can form by accident, for example in piping that carries both oxygen and a fuel gas for cutting and welding. Oxygen–fuel gas cutting systems therefore have special backflow prevention devices.<ref name="L-6-173">Lemoff (2008), p. 6-173.</ref>


== Hazards after release ==
== Hazards after release ==
The handbook describes a combustion explosion as a sequence of events. The gas escapes, mixes with air and forms an ignitable mixture within its flammable range. Once ignited, the mixture burns rapidly and heats the surrounding air, which expands.<ref name="L-6-174" /> If the air is confined in a room, the pressure rises until some part of the structure gives way.<ref name="L-6-174" /> The handbook also calls this a room explosion or vapour–air explosion, but notes that these names are less accurate.<ref name="L-6-174" />
In a combustion explosion, escaped gas mixes with air within its flammable range. Ignition rapidly heats the mixture and surrounding air; in a room, pressure rises until part of the structure gives way.<ref name="L-6-174" /> The handbook also uses the less accurate terms room explosion and vapour–air explosion.<ref name="L-6-174" />


The vulnerability of buildings follows from two numbers. An enclosure completely filled with a flammable gas–air mixture would have to withstand about 400 to 750 kPa (60 to 110 psi) to stay intact.<ref name="L-6-175" /> Conventional structures withstand only about 3.5 to 7.0 kPa (0.5 to 1.0 psi).<ref name="L-6-175" /> Most combustion explosions in conventional structures therefore occur with less than 25 % of the enclosure occupied by the flammable mixture.<ref name="L-6-175" /> Because most flammable mixtures are about 90 % air, whether the gas is lighter or heavier than air matters less inside structures than might be expected.<ref name="L-6-175" />
The vulnerability of buildings follows from two numbers. An enclosure completely filled with a flammable gas–air mixture would have to withstand about 414 to 758 kPa (60 to 110 psi) to stay intact.<ref name="L-6-175" /> Conventional structures withstand only about 3.45 to 6.89 kPa (0.5 to 1.0 psi).<ref name="L-6-175" /> Most combustion explosions in conventional structures therefore occur with less than 25 % of the enclosure occupied by the flammable mixture.<ref name="L-6-175" /> Because most flammable mixtures are about 90 % air, whether the gas is lighter or heavier than air matters less inside structures than might be expected.<ref name="L-6-175" />
[[File:fse-flammable-gas-v3.svg|thumb|upright=1.5|alt=Two bars on a logarithmic pressure scale: 414 to 758 kPa for a room full of gas mixture, 3.45 to 6.89 kPa for conventional structures.|Pressure that an enclosure full of a flammable gas–air mixture would have to withstand, compared with the strength of conventional structures. Most combustion explosions occur with less than 25 % of the room filled.]]


Lemoff describes a gas fire as an aborted combustion explosion. The mixture ignites before an explosive quantity can accumulate, or there is no structure to confine it.<ref name="L-6-175" /> Outdoors, fires are therefore more likely than explosions. After a massive release, however, the surrounding air or buildings can provide enough confinement for an open-air explosion.<ref name="L-6-175" /> Liquefied noncryogenic gases, hydrogen, ethylene and some reactive gases with a high flame speed are subject to this.<ref name="L-6-175" />
Lemoff describes a gas fire as an aborted combustion explosion. The mixture ignites before an explosive quantity can accumulate, or there is no structure to confine it.<ref name="L-6-175" /> Outdoors, fires are therefore more likely than explosions. After a massive release, however, the surrounding air or buildings can provide enough confinement for an open-air explosion.<ref name="L-6-175" /> Liquefied noncryogenic gases, hydrogen, ethylene and some reactive gases with a high flame speed are subject to this.<ref name="L-6-175" />
Line 61: Line 62:


If the release is not ignited at once, a cloud forms and drifts downwind. A remote ignition source can then ignite it, producing a vapour cloud fire, or [[flash fire]], that burns back towards the release point.<ref name="By-3-269" /> The burning cloud can then start a steady jet flame or pool fire at the source.<ref name="By-3-269" /> Where the cloud is large and the flame accelerates, a [[vapour cloud explosion]] can follow. Turbulent jet releases, partial confinement, congested equipment and ignition delays all promote the rapid flame speeds involved.<ref name="Z08-2-104" /> Damaging overpressures in a virtually unconfined cloud need flame speeds of the order of 100 m/s.<ref name="Z08-2-104" /> Propane, propylene, ethylene and aromatic hydrocarbons have been involved in many such explosions.<ref name="Z08-2-104" />
If the release is not ignited at once, a cloud forms and drifts downwind. A remote ignition source can then ignite it, producing a vapour cloud fire, or [[flash fire]], that burns back towards the release point.<ref name="By-3-269" /> The burning cloud can then start a steady jet flame or pool fire at the source.<ref name="By-3-269" /> Where the cloud is large and the flame accelerates, a [[vapour cloud explosion]] can follow. Turbulent jet releases, partial confinement, congested equipment and ignition delays all promote the rapid flame speeds involved.<ref name="Z08-2-104" /> Damaging overpressures in a virtually unconfined cloud need flame speeds of the order of 100 m/s.<ref name="Z08-2-104" /> Propane, propylene, ethylene and aromatic hydrocarbons have been involved in many such explosions.<ref name="Z08-2-104" />
[[File:fse-flammable-gas-v2.svg|thumb|upright=1.5|alt=Gas-release event tree: prompt ignition gives a jet fire, delayed ignition a flash fire or explosion; unignited gas may disperse or accumulate.|Possible outcomes of a flammable gas release. Immediate ignition gives a jet fire; delayed ignition of a drifting cloud gives a flash fire that can burn back to a jet fire, or an explosion where confinement and congestion are present.]]


Flammable gases also arise from processes. In nuclear power plants the most common is hydrogen, used to cool generators and released in battery rooms.<ref name="IS-1-8">Iqbal and Salley (2004), p. 1-8.</ref> In electric vehicles, a battery in thermal runaway can release flammable gases. Ignited, they can cause a flare fire or a gas cloud explosion.<ref name="VdG-22">Van der Graaf et al. (2021/2023), p. 22.</ref> If they are not ignited at once, they can accumulate in a confined or poorly ventilated car park and explode once the lower explosion limit is reached.<ref name="VdG-27">Van der Graaf et al. (2021/2023), p. 27.</ref>
Flammable gases also arise from processes. In nuclear power plants the most common is hydrogen, used to cool generators and released in battery rooms.<ref name="IS-1-8">Iqbal and Salley (2004), p. 1-8.</ref> In electric vehicles, a battery in thermal runaway can release flammable gases. Ignited, they can cause a flare fire or a gas cloud explosion.<ref name="VdG-22">Van der Graaf et al. (2021/2023), p. 22.</ref> If they are not ignited at once, they can accumulate in a confined or poorly ventilated car park and explode once the lower explosion limit is reached.<ref name="VdG-27">Van der Graaf et al. (2021/2023), p. 27.</ref>


== Prevention and protection ==
== Prevention and protection ==
The basic safeguards against a combustion explosion limit the formation of a flammable mixture in a structure. They include rugged containers and equipment, emergency flow-control devices and limiting orifices.<ref name="L-6-175" /> Burners are often fitted with flame-failure devices that shut off the gas if the flame goes out.<ref name="L-6-175" /> Many gases are colourless and odourless. Codes, standards and regulations therefore require natural gas and LP-gas to be odorised, so that people with a normal sense of smell can detect them at one-fifth of the lower limit.<ref name="L-6-175" /> Odorisation has limits: nobody may be present, the sense of smell tires and varies, and some soils scrub the odorant from leaking underground gas.<ref name="L-6-175" />
The basic safeguards against a combustion explosion limit the formation of a flammable mixture in a structure. They include rugged containers and equipment, emergency flow-control devices and limiting orifices.<ref name="L-6-175" /> Burners are often fitted with flame-failure devices that shut off the gas if the flame goes out.<ref name="L-6-175" /> Many gases are colourless and odourless. The 2008 handbook says natural gas and LP-gas must be odorised so that people with a normal sense of smell detect them at or below one-fifth of their lower limit.<ref name="L-6-175" /> Odorisation has limits: nobody may be present, the sense of smell tires and varies, and some soils scrub the odorant from leaking underground gas.<ref name="L-6-175" />


Control of ignition sources is the second line of defence, but it is practical mainly in industrial operations.<ref name="L-6-175" /> In the United States, flammable gas storage areas without filling operations are generally classified as Division 2 locations for electrical equipment.<ref name="LR-7-41">Lemoff and Rivkin (2008), p. 7-41.</ref> Gases are assigned to groups by testing the gap through which a flame can pass, and most flammable gases fall in Groups C and D.<ref name="LR-7-41" /> Acetylene is the only Group A gas and hydrogen is Group B.<ref name="LR-7-41" /> NUREG-1805 lists ethylene as a Group C and propane as a Group D example.<ref name="IS-B-24">Iqbal and Salley (2004), p. B-24.</ref> A gas leak can also create its own ignition source. Gases such as natural gas, methane, ethane and propane are dielectrics, and flow from a high-pressure leak can build up static charges that discharge as sparks.<ref name="C-14-109">Cholin (2008a), p. 14-109.</ref>
Control of ignition sources is the second line of defence, but it is practical mainly in industrial operations.<ref name="L-6-175" /> For United States electrical equipment, the 2008 handbook generally classifies flammable gas storage areas without filling operations as Division 2 locations.<ref name="LR-7-41">Lemoff and Rivkin (2008), p. 7-41.</ref> Gases are assigned to groups by testing the gap through which a flame can pass, and most flammable gases fall in Groups C and D.<ref name="LR-7-41" /> Acetylene is the only Group A gas and hydrogen is Group B.<ref name="LR-7-41" /> NUREG-1805 lists ethylene as a Group C and propane as a Group D example.<ref name="IS-B-24">Iqbal and Salley (2004), p. B-24.</ref> A gas leak can also create its own ignition source. Gases such as natural gas, methane, ethane and propane are dielectrics, and flow from a high-pressure leak can build up static charges that discharge as sparks.<ref name="C-14-109">Cholin (2008a), p. 14-109.</ref>


A [[gas detection system]] provides warning before a mixture becomes flammable. The handbook notes that, apart from NFPA 720 for carbon monoxide, no NFPA standard covered the design of flammable gas detection in commercial or industrial occupancies.<ref name="C-14-99">Cholin (2008a), p. 14-99.</ref> Common sensors use a catalytic bead on which the gas burns, giving a signal in proportion to its concentration.<ref name="C-14-103">Cholin (2008a), p. 14-103.</ref> Such systems usually need monthly calibration with a test gas, typically at 50 % LFL.<ref name="C-14-109" />
A [[gas detection system]] can warn of a leak below the lower flammable limit if its sensors are suitably placed, maintained and set to respond in time.<ref name="C-14-107">Cholin (2008a), p. 14-107.</ref><ref name="C-14-108">Cholin (2008a), p. 14-108.</ref> In the 2008 handbook, Cholin notes that, apart from the then-existing NFPA 720 for carbon monoxide, no NFPA standard covered the design of combustible-gas detection in commercial or industrial occupancies.<ref name="C-14-99">Cholin (2008a), p. 14-99.</ref> Common sensors use a catalytic bead on which the gas burns, giving a signal in proportion to its concentration.<ref name="C-14-103">Cholin (2008a), p. 14-103.</ref> The handbook says most catalytic-bead systems need monthly calibration, usually with a test gas at 50 % LFL; the specific system instructions govern maintenance.<ref name="C-14-109" />


In storage, containers of flammable gases should not be kept with oxidising gases such as oxygen and nitrous oxide. These increase the speed of burning and allow explosions of fuel–oxidant mixtures.<ref name="LR-7-38">Lemoff and Rivkin (2008), p. 7-38.</ref> In the United States, NFPA 55, as described by Lemoff and Rivkin (2008), requires separation of flammable, oxidising, toxic, pyrophoric and unstable reactive gases.<ref name="LR-7-38" /> Indoor storage of more than about 71 m³ (2500 standard cubic feet) of flammable gas needs separation into groups or sprinkler protection.<ref name="LR-7-40">Lemoff and Rivkin (2008), p. 7-40.</ref> For large containers of liquefied flammable gas, NFPA 15 requires water spray at more than 10 (L/min)/m² of container surface to prevent failure.<ref name="LR-7-40" /> Deflagration venting according to [[NFPA 68]] can limit explosion damage, but is applied to industrial structures rather than ordinary buildings.<ref name="L-6-175" />
[[File:fse-flammable-gas-v5.jpg|thumb|upright=1.5|alt=Fixed gas detector head with a metal sensor housing mounted on a wall near gas piping.|Fixed flammable gas detector. In an ordinary gas-air atmosphere, a sintered-metal flame arrester around a catalytic sensor prevents flame from propagating outside the detector; oxygen-enriched atmospheres may require a special arrester.]]
 
In storage, containers of flammable gases should not be kept with oxidising gases such as oxygen and nitrous oxide. These increase the speed of burning and allow explosions of fuel–oxidant mixtures.<ref name="LR-7-38">Lemoff and Rivkin (2008), p. 7-38.</ref> In the United States, NFPA 55 as described by Lemoff and Rivkin (2008) requires separation of relevant flammable, oxidising, corrosive, toxic, pyrophoric and unstable reactive gas classes.<ref name="LR-7-38" /> In the 2008 handbook account, indoor storage of more than about 70.8 m³ (2500 standard cubic feet) of flammable gas requires separation into groups of cylinders or sprinkler protection.<ref name="LR-7-40">Lemoff and Rivkin (2008), p. 7-40.</ref> For larger containers of liquefied flammable gas that is not chemically self-reactive, the 2008 handbook cites NFPA 15 water-spray protection against failure. It gives a density in excess of 0.25 gpm/ft² (about 10.2 L/(min·m²)) over the container surface.<ref name="LR-7-40" /> Deflagration venting according to [[NFPA 68]] can limit explosion damage, but is applied to industrial structures rather than ordinary buildings.<ref name="L-6-175" />


== Emergency control ==
== Emergency control ==
Line 79: Line 83:


== Calculation examples ==
== Calculation examples ==
Two simple checks follow from the definitions and data above. The first applies the two tests of the NFPA 55 and DOT definition to the gases in the table. Natural gas, propane and butane meet the first test, with lower limits below 13 %, but their ranges are only 6.6 to 10.3 percentage points wide.<ref name="L-6-174" /> Hydrogen, acetylene, ethylene and carbon monoxide pass both tests.<ref name="L-6-174" /> Blast furnace gas, with a lower limit of 33.2 %, passes only through its range of 38 points.<ref name="L-6-174" /> Anhydrous ammonia fails both: its lower limit of 16 % exceeds 13 %, and its range of 9 points is less than 12. This explains why the DOT lists it as a nonflammable gas in Division 2.2.<ref name="L-6-166" /><ref name="CJW-13-119" />
Two simple checks follow from the definitions and data above. The first applies the two tests of the NFPA 55 and DOT definition to the gases in the table. Natural gas, propane and butane meet the first test, with lower limits below 13 %, but their ranges are only 6.6 to 10.3 percentage points wide.<ref name="L-6-174" /> Hydrogen, acetylene, ethylene and carbon monoxide pass both tests.<ref name="L-6-174" /> Blast furnace gas, with a lower limit of 33.2 %, passes only through its range of 38 points.<ref name="L-6-174" /> Anhydrous ammonia fails both: its lower limit of 16 % exceeds 13 %, and its range of 9 points is less than 12. This explains the Division 2.2 nonflammable transport classification reported by the 2008 handbook.<ref name="L-6-166" /><ref name="CJW-13-119" />
[[File:fse-flammable-gas-v1.svg|thumb|upright=1.5|alt=Horizontal bars from lower to upper flammable limit for eight gases, with a vertical line at 13 percent by volume.|Flammable ranges of eight gases in air. Under the US criteria, a gas meets the flammable-gas definition if its lower limit is at most 13 % or its range is at least 12 percentage points wide; anhydrous ammonia meets neither.]]


The second check estimates how a steady leak builds up in a ventilated room. NUREG-1805 gives the method of NFPA 69 for a constant gas source in an enclosed volume.<ref name="IS-16-9">Iqbal and Salley (2004), p. 16-9.</ref> The concentration approaches the ratio of the gas release rate to the ventilation rate, at a speed set by the number of air changes:<ref name="IS-16-9" />
The second check estimates how a steady leak builds up in a ventilated room. NUREG-1805 gives the method of NFPA 69 for a constant gas source in an enclosed volume.<ref name="IS-16-9">Iqbal and Salley (2004), p. 16-9.</ref> The concentration approaches the ratio of the gas release rate to the ventilation rate, at a speed set by the number of air changes:<ref name="IS-16-9" />
Line 88: Line 93:
! Symbol !! Description !! Unit
! Symbol !! Description !! Unit
|-
|-
| <math>C</math> || average gas concentration by volume || –
| <math>C</math> || modelled room gas concentration by volume || –
|-
|-
| <math>G</math> || gas release rate || m³/min
| <math>G</math> || gas release rate || m³/min
Line 103: Line 108:
|}
|}


The mixing factor ranges from 0.2 for rooms ventilated only by infiltration through cracks to 0.9 for a perforated ceiling supply with several exhausts.<ref name="IS-16-10">Iqbal and Salley (2004), p. 16-10.</ref> As an assumed example, a room of 4 m × 4 m × 3 m (48 m³) has two air changes per hour, or 1.6 m³/min. A natural gas leak of 0.02 m³/min then gives a long-term average concentration of 0.02/1.6 = 1.25 %. That is 27 % of the lower limit of 4.7 %, so a perfectly mixed room never becomes flammable.<ref name="L-6-174" /> The concentration reaches one-fifth of the lower limit, 0.94 %, when 1 − e<sup>−''KN''</sup> = 0.75. With perfect mixing (''K'' = 1) this takes 1.39 air changes, or about 41 minutes.
The mixing factor ranges from 0.2 for rooms ventilated only by infiltration through cracks to 0.9 for a perforated ceiling supply with several exhausts.<ref name="IS-16-10">Iqbal and Salley (2004), p. 16-10.</ref> As an assumed example, a room of 4 m × 4 m × 3 m (48 m³) has two air changes per hour, or 1.6 m³/min. A natural gas leak of 0.02 m³/min then gives a long-term modelled room concentration of 0.02/1.6 = 1.25 %. That is about 27 % of the lower limit of 4.7 %, so the calculated room concentration stays below that limit.<ref name="L-6-174" /> The concentration reaches one-fifth of the lower limit, 0.94 %, when 1 − e<sup>−''KN''</sup> = 0.94/1.25 = 0.752. With perfect mixing (''K'' = 1) this takes 1.39 air changes, or about 42 minutes.
[[File:fse-flammable-gas-v4.svg|thumb|upright=1.5|alt=Two rising curves of gas concentration against time levelling off at 1.25 percent, with a dashed line at 0.94 percent.|Modelled concentration in a 48 m³ room with two air changes per hour after a natural gas leak of 0.02 m³/min starts, for perfect mixing (K = 1) and K = 0.2, with the NFPA 69 method.]]


The same leak of propane would reach 58 % of its lower limit of 2.15 %.<ref name="L-6-174" /> In this room, a propane leak of about 0.034 m³/min, or 3.7 kg/h, would bring the average concentration to the lower limit. Real rooms are not perfectly mixed, and the handbook warns that practical ventilation systems can handle only rather nominal release rates.<ref name="L-6-175" /> A layer or pocket near the leak can therefore be flammable long before the average is.
The same leak of propane would reach 58 % of its lower limit of 2.15 %.<ref name="L-6-174" /> In this room, a propane leak of about 0.034 m³/min would bring the modelled room concentration to the lower limit; at 21 °C and 101 kPa this is roughly 3.8 kg/h. Real rooms are not perfectly mixed, and the handbook warns that practical ventilation systems can handle only rather nominal release rates.<ref name="L-6-175" /> A layer or pocket near the leak can therefore be flammable even while the modelled room concentration remains below the lower limit.


The SFPE Handbook gives a simple estimate of what such a pocket can do. The pressure rise in a closed enclosure is the closed-vessel pressure multiplied by the fraction of the total mass that burns:<ref name="Z02-408">Zalosh (2002), p. 3-408.</ref>
The SFPE Handbook gives a simple estimate of what such a pocket can do. The pressure rise in a closed enclosure is the closed-vessel pressure multiplied by the fraction of the total mass that burns:<ref name="Z02-408">Zalosh (2002), p. 3-408.</ref>
Line 111: Line 117:
<math display="block">\frac{P - P_0}{P_\mathrm{m} - P_0} = \frac{m_\mathrm{b}}{m_0}</math>
<math display="block">\frac{P - P_0}{P_\mathrm{m} - P_0} = \frac{m_\mathrm{b}}{m_0}</math>


Here ''P'' − ''P''<sub>0</sub> is the pressure rise, ''P''<sub>m</sub> − ''P''<sub>0</sub> the closed-vessel deflagration pressure, ''m''<sub>b</sub> the burned mass and ''m''<sub>0</sub> the total mass in the enclosure. For propane–air, ''P''<sub>m</sub> − ''P''<sub>0</sub> is 7.9 bar.<ref name="Z02-407">Zalosh (2002), p. 3-407.</ref> A stoichiometric mixture has almost the density of air, so the mass fraction is close to the volume fraction of the room that the mixture fills.<ref name="Z02-410">Zalosh (2002), p. 3-410.</ref> A pocket filling only 1 % of the room would then raise the pressure by about 7.9 kPa if no venting occurred. That exceeds the 3.5 to 7.0 kPa that conventional structures withstand, which agrees with the handbook statement on partly filled rooms.<ref name="L-6-175" />
Here ''P'' − ''P''<sub>0</sub> is the pressure rise, ''P''<sub>m</sub> − ''P''<sub>0</sub> the closed-vessel deflagration pressure, ''m''<sub>b</sub> the burned mass and ''m''<sub>0</sub> the total mass in the enclosure. For propane–air, ''P''<sub>m</sub> − ''P''<sub>0</sub> is 7.9 bar.<ref name="Z02-407">Zalosh (2002), p. 3-407.</ref> A stoichiometric mixture has almost the density of air, so the mass fraction is close to the volume fraction of the room that the mixture fills.<ref name="Z02-410">Zalosh (2002), p. 3-410.</ref> A pocket filling only 1 % of the room would then raise the pressure by about 7.9 kPa if no venting occurred. That exceeds the 3.45 to 6.89 kPa that conventional structures withstand, which agrees with the handbook statement on partly filled rooms.<ref name="L-6-175" />


== Limitations and uncertainty ==
== Limitations and uncertainty ==
Line 118: Line 124:
Tabulated limits depend on the test method. Beyler gives 5 % and 15 % by volume for methane in air, while the handbook table gives 4.7 % and 15.0 % for high-methane natural gas.<ref name="By-2-172" /><ref name="L-6-174" /> The standard Bureau of Mines method uses a vertical tube 1.5 m long and 0.05 m wide, and limits for downward propagation are narrower than for upward propagation.<ref name="By-2-172" /><ref name="By-2-174" /> Commercial propane and butane are mixtures, and natural gas compositions vary, so the limits of a real gas can differ from those in a table.<ref name="L-6-174" /> Limits also widen with temperature and, for the upper limit, with pressure and oxygen content.<ref name="By-2-174" />
Tabulated limits depend on the test method. Beyler gives 5 % and 15 % by volume for methane in air, while the handbook table gives 4.7 % and 15.0 % for high-methane natural gas.<ref name="By-2-172" /><ref name="L-6-174" /> The standard Bureau of Mines method uses a vertical tube 1.5 m long and 0.05 m wide, and limits for downward propagation are narrower than for upward propagation.<ref name="By-2-172" /><ref name="By-2-174" /> Commercial propane and butane are mixtures, and natural gas compositions vary, so the limits of a real gas can differ from those in a table.<ref name="L-6-174" /> Limits also widen with temperature and, for the upper limit, with pressure and oxygen content.<ref name="By-2-174" />


The calculation methods above are first-order approximations. The NFPA 69 buildup equation gives an average concentration and assumes a constant leak and a fixed mixing factor.<ref name="IS-16-9" /><ref name="IS-16-10" /> The partial-volume estimate ignores venting through windows and doors and assumes that the burned mixture is stoichiometric.<ref name="Z02-408" />
The calculation methods above are first-order approximations. The NFPA 69 buildup equation gives a modelled room concentration and assumes a constant leak and a fixed mixing factor; it does not resolve local gas pockets.<ref name="IS-16-9" /><ref name="IS-16-10" /> The partial-volume estimate ignores venting through windows and doors and assumes that the burned mixture is stoichiometric.<ref name="Z02-408" />


== See also ==
== See also ==

Latest revision as of 00:37, 16 November 2026

A flammable gas is a substance that is a gas at normal temperature and pressure and that burns when mixed with air in the right proportions.[1] In the United States, the formal definition in NFPA 55 and in the transport regulations of the Department of Transportation (DOT) rests on two tests. The gas must be ignitable in a mixture of 13 % or less by volume with air, or have a flammable range in air at least 12 percentage points wide.[1][2] Common examples are natural gas, propane, butane, hydrogen, acetylene and ethylene.[3]

Unlike a flammable liquid, a flammable gas does not first have to evaporate. Once released, it can ignite if it mixes with air within its flammable limits and receives enough ignition energy.[2] The Fire Protection Handbook distinguishes two basic hazards of a release: a combustion explosion inside a building or structure, and a fire.[3] An enclosure that is only partly filled with a flammable mixture can already be destroyed, because ordinary structures withstand only a few kilopascals.[4] Outdoors, a release can burn as a jet flame, as a flash fire through a drifting cloud, or as a vapour cloud explosion.[5][6] Protection relies on tight containment, odorisation, ventilation, control of ignition sources, gas detection and water cooling of exposed containers.[4][7]

Definition and classification

The handbook chapter on gases uses the term gas only for substances that are gaseous at normal temperature and pressure (NTP), about 21 °C (70 °F) and 101 kPa.[1] In the United States, NFPA 55, as described in the 2008 edition of the Fire Protection Handbook, is the standard for the storage, use and handling of compressed gases. It defines a flammable gas as a material that is a gas at 20 °C (68 °F) or less at 101.325 kPa.[1] It must also be ignitable at that pressure in a mixture of 13 % or less by volume with air, or have a flammable range with air of at least 12 %, regardless of the lower limit.[1] A flammable liquefied gas is a liquefied compressed gas that is partly liquid at 20 °C in its charged container and that is flammable.[2]

In the 2008 handbook, Lemoff notes that these definitions match those in the DOT regulations then used to label gases for transport in the United States.[2] They are also described as essentially identical to the United Nations protocols for international gas shipments.[2] In that account of the DOT hazard classes, flammable gases form Division 2.1, with propane, butadiene, acetylene and methyl chloride as examples.[8] In the 2001 edition of NFPA 704, the highest flammability rating, 4, covers materials that turn rapidly or completely into vapour at atmospheric pressure and normal ambient temperature and burn readily.[9]

The NFPA 55 classification described by Lemoff places flammable gases among the physical-hazard classes, next to nonflammable, oxidising, pyrophoric and unstable reactive gases.[2] Pyrophoric gases are flammable gases that ignite spontaneously in air, such as silane and phosphine, and are found mostly in semiconductor manufacturing.[2] Some gases that can be made to burn are still treated as nonflammable because their range is narrow or their lower limit high. Anhydrous ammonia is the handbook's example: DOT classified it as a nonflammable gas for interstate transport at the time.[2]

The flash point, which is central to the classification of flammable liquids, has no practical meaning for flammable gases.[2] A flammable gas normally exists above its normal boiling point at atmospheric pressure, even when it is stored as a liquid under pressure, and therefore above its flash point.[2] By usage, the most widely used fuel gases are natural gas and the liquefied petroleum gases butane and propane.[10]

Combustion properties

Introduction to Fire Safety Engineering explains that a flammable gas burns only when it mixes with oxygen in the right proportion and enough energy is available to ignite the mixture.[11] The stoichiometric ratio gives the proportions for complete combustion, although the maximum burning velocity can occur on the fuel-rich side of that ratio.[12][13] The stoichiometric fuel fraction in air is 0.095 for methane, 0.040 for propane and 0.296 for hydrogen.[14]

Every flammable gas has a lower and an upper flammable limit. A mixture with air ignites only between these flammability limits, and only when at least the minimum ignition energy is supplied.[2] The SFPE Handbook defines the limits as the range of compositions within which a premixed flame can propagate, at a specified temperature and pressure.[15] For most simple hydrocarbons, the limits in air correspond to equivalence ratios of about 0.5 and 3.[15] Adding oxygen raises the upper limit but hardly changes the lower limit, and both limits widen as the temperature rises.[16] The lower limit is insensitive to pressure except well below atmospheric, while the upper limit rises above atmospheric pressure.[16]

The handbook gives the following properties; specific gravity compares gas density with air.[3]

Combustion properties of common flammable gases[3]
Gas Lower limit (vol %) Upper limit (vol %) Specific gravity (air = 1) Ignition temperature (°C)
Natural gas (high methane type) 4.7 15.0 0.590–0.614 482–632
Propane (commercial) 2.15 9.6 1.52 493–604
Butane (commercial) 1.9 8.5 2.0 482–538
Acetylene 2.5 81.0 0.91 305
Hydrogen 4.0 75.0 0.07 500
Ethylene 2.7 36.0 0.98 490
Carbon monoxide 12.5 74.0 0.97 609
Anhydrous ammonia 16.0 25.0 0.60 651

Ignition energies differ by orders of magnitude. In dry air at 1 atm and 25 °C, the minimum ignition energy is 0.016 mJ for hydrogen and 0.017 mJ for acetylene. Methane needs 0.21 mJ and propane 0.24 mJ, while ammonia needs 680 mJ.[17] Hydrogen also has an extremely wide flammable range, a high burning velocity in air, and a nearly invisible flame.[18] Ethylene combines a wide flammable range with a high burning velocity.[19] Ammonia, by contrast, owes its limited flammability to its high lower limit and low heat of combustion.[20]

Gas concentrations can be expressed as a percentage of the lower flammable limit (% LFL). If the limit is 4.0 %, a reading of 25 % LFL means 1 % gas by volume.[21] Older literature also uses lower and upper explosive limit (LEL and UEL).[21] NUREG-1805 states that the terms explosive limits and flammable limits are used interchangeably.[22] Lemoff, however, notes that hydrogen has a recognised explosive range that is narrower than its flammable range. He recommends that the term explosive range be used only for hydrogen.[2]

Hazards in containers

A fire raises gas pressure and can weaken a container, opening its relief valve or causing failure.[10] Failure can violently release stored compression or liquefaction energy and throw fragments.[23] Liquefied gas containers hold more gas and can release larger quantities.[23]

Liquefied flammable gases such as liquefied petroleum gas add the hazard of the boiling liquid expanding vapour explosion (BLEVE). When such a container fails, about one-third of the liquid can turn to vapour at normal temperatures, and often more than half in a fire.[24] Container pieces can be thrown up to about 0.8 km (½ mile), and fatal burns have occurred up to 76 m from larger containers.[25] In the LP-gas disaster near Mexico City on 19 November 1984, about 15 BLEVEs were recorded, and some 500 deaths were reported.[25]

A flammable gas can also burn inside a container. Gas–air or gas–oxygen mixtures are seldom made in containers on purpose but can form by accident, for example in piping that carries both oxygen and a fuel gas for cutting and welding. Oxygen–fuel gas cutting systems therefore have special backflow prevention devices.[26]

Hazards after release

In a combustion explosion, escaped gas mixes with air within its flammable range. Ignition rapidly heats the mixture and surrounding air; in a room, pressure rises until part of the structure gives way.[3] The handbook also uses the less accurate terms room explosion and vapour–air explosion.[3]

The vulnerability of buildings follows from two numbers. An enclosure completely filled with a flammable gas–air mixture would have to withstand about 414 to 758 kPa (60 to 110 psi) to stay intact.[4] Conventional structures withstand only about 3.45 to 6.89 kPa (0.5 to 1.0 psi).[4] Most combustion explosions in conventional structures therefore occur with less than 25 % of the enclosure occupied by the flammable mixture.[4] Because most flammable mixtures are about 90 % air, whether the gas is lighter or heavier than air matters less inside structures than might be expected.[4]

Two bars on a logarithmic pressure scale: 414 to 758 kPa for a room full of gas mixture, 3.45 to 6.89 kPa for conventional structures.
Pressure that an enclosure full of a flammable gas–air mixture would have to withstand, compared with the strength of conventional structures. Most combustion explosions occur with less than 25 % of the room filled.

Lemoff describes a gas fire as an aborted combustion explosion. The mixture ignites before an explosive quantity can accumulate, or there is no structure to confine it.[4] Outdoors, fires are therefore more likely than explosions. After a massive release, however, the surrounding air or buildings can provide enough confinement for an open-air explosion.[4] Liquefied noncryogenic gases, hydrogen, ethylene and some reactive gases with a high flame speed are subject to this.[4]

A leak from a pressurised pipe or hose can form a gas jet that is easily ignited into a large turbulent flame.[27] The fuel flow of such a jet fire is set by the leak orifice rather than by heat transfer from the flame.[27] Near or within the flames, its radiation can reach 120 to 160 kW/m².[28] Where jet flames engulf a target, the SFPE Handbook reports heat fluxes of up to 250 kW/m² for two-phase LPG jets and 300 kW/m² for sonic natural gas jets.[29]

If the release is not ignited at once, a cloud forms and drifts downwind. A remote ignition source can then ignite it, producing a vapour cloud fire, or flash fire, that burns back towards the release point.[5] The burning cloud can then start a steady jet flame or pool fire at the source.[5] Where the cloud is large and the flame accelerates, a vapour cloud explosion can follow. Turbulent jet releases, partial confinement, congested equipment and ignition delays all promote the rapid flame speeds involved.[6] Damaging overpressures in a virtually unconfined cloud need flame speeds of the order of 100 m/s.[6] Propane, propylene, ethylene and aromatic hydrocarbons have been involved in many such explosions.[6]

Gas-release event tree: prompt ignition gives a jet fire, delayed ignition a flash fire or explosion; unignited gas may disperse or accumulate.
Possible outcomes of a flammable gas release. Immediate ignition gives a jet fire; delayed ignition of a drifting cloud gives a flash fire that can burn back to a jet fire, or an explosion where confinement and congestion are present.

Flammable gases also arise from processes. In nuclear power plants the most common is hydrogen, used to cool generators and released in battery rooms.[30] In electric vehicles, a battery in thermal runaway can release flammable gases. Ignited, they can cause a flare fire or a gas cloud explosion.[31] If they are not ignited at once, they can accumulate in a confined or poorly ventilated car park and explode once the lower explosion limit is reached.[32]

Prevention and protection

The basic safeguards against a combustion explosion limit the formation of a flammable mixture in a structure. They include rugged containers and equipment, emergency flow-control devices and limiting orifices.[4] Burners are often fitted with flame-failure devices that shut off the gas if the flame goes out.[4] Many gases are colourless and odourless. The 2008 handbook says natural gas and LP-gas must be odorised so that people with a normal sense of smell detect them at or below one-fifth of their lower limit.[4] Odorisation has limits: nobody may be present, the sense of smell tires and varies, and some soils scrub the odorant from leaking underground gas.[4]

Control of ignition sources is the second line of defence, but it is practical mainly in industrial operations.[4] For United States electrical equipment, the 2008 handbook generally classifies flammable gas storage areas without filling operations as Division 2 locations.[33] Gases are assigned to groups by testing the gap through which a flame can pass, and most flammable gases fall in Groups C and D.[33] Acetylene is the only Group A gas and hydrogen is Group B.[33] NUREG-1805 lists ethylene as a Group C and propane as a Group D example.[34] A gas leak can also create its own ignition source. Gases such as natural gas, methane, ethane and propane are dielectrics, and flow from a high-pressure leak can build up static charges that discharge as sparks.[35]

A gas detection system can warn of a leak below the lower flammable limit if its sensors are suitably placed, maintained and set to respond in time.[36][37] In the 2008 handbook, Cholin notes that, apart from the then-existing NFPA 720 for carbon monoxide, no NFPA standard covered the design of combustible-gas detection in commercial or industrial occupancies.[38] Common sensors use a catalytic bead on which the gas burns, giving a signal in proportion to its concentration.[39] The handbook says most catalytic-bead systems need monthly calibration, usually with a test gas at 50 % LFL; the specific system instructions govern maintenance.[35]

Fixed gas detector head with a metal sensor housing mounted on a wall near gas piping.
Fixed flammable gas detector. In an ordinary gas-air atmosphere, a sintered-metal flame arrester around a catalytic sensor prevents flame from propagating outside the detector; oxygen-enriched atmospheres may require a special arrester.

In storage, containers of flammable gases should not be kept with oxidising gases such as oxygen and nitrous oxide. These increase the speed of burning and allow explosions of fuel–oxidant mixtures.[40] In the United States, NFPA 55 as described by Lemoff and Rivkin (2008) requires separation of relevant flammable, oxidising, corrosive, toxic, pyrophoric and unstable reactive gas classes.[40] In the 2008 handbook account, indoor storage of more than about 70.8 m³ (2500 standard cubic feet) of flammable gas requires separation into groups of cylinders or sprinkler protection.[41] For larger containers of liquefied flammable gas that is not chemically self-reactive, the 2008 handbook cites NFPA 15 water-spray protection against failure. It gives a density in excess of 0.25 gpm/ft² (about 10.2 L/(min·m²)) over the container surface.[41] Deflagration venting according to NFPA 68 can limit explosion damage, but is applied to industrial structures rather than ordinary buildings.[4]

Emergency control

The handbook separates "no fire" and "fire" emergencies.[4] In a no-fire emergency the gas is directed, diluted and dispersed with a carrier fluid, while the flow is stopped where possible.[7] Liquefied gases are visible as a fog of condensed water vapour, but ignitable mixtures often extend some distance beyond it.[7]

In a fire emergency, water is applied to control the heat while the gas flow is stopped if possible.[7] Many gas fires can be put out with carbon dioxide, dry chemical or halogenated agents. If gas keeps escaping after extinguishment, however, the fire can turn into a combustion explosion. Accepted practice is therefore to extinguish only small leaks that would be harmless if they reignited.[7]

Calculation examples

Two simple checks follow from the definitions and data above. The first applies the two tests of the NFPA 55 and DOT definition to the gases in the table. Natural gas, propane and butane meet the first test, with lower limits below 13 %, but their ranges are only 6.6 to 10.3 percentage points wide.[3] Hydrogen, acetylene, ethylene and carbon monoxide pass both tests.[3] Blast furnace gas, with a lower limit of 33.2 %, passes only through its range of 38 points.[3] Anhydrous ammonia fails both: its lower limit of 16 % exceeds 13 %, and its range of 9 points is less than 12. This explains the Division 2.2 nonflammable transport classification reported by the 2008 handbook.[2][8]

Horizontal bars from lower to upper flammable limit for eight gases, with a vertical line at 13 percent by volume.
Flammable ranges of eight gases in air. Under the US criteria, a gas meets the flammable-gas definition if its lower limit is at most 13 % or its range is at least 12 percentage points wide; anhydrous ammonia meets neither.

The second check estimates how a steady leak builds up in a ventilated room. NUREG-1805 gives the method of NFPA 69 for a constant gas source in an enclosed volume.[42] The concentration approaches the ratio of the gas release rate to the ventilation rate, at a speed set by the number of air changes:[42]

C=GQ(1−e−KN),N=QtV

Symbol Description Unit
C modelled room gas concentration by volume –
G gas release rate m³/min
Q ventilation air flow rate m³/min
K mixing efficiency factor (1.0 for perfect mixing) –
N number of theoretical air changes –
t time since the start of the leak min
V room volume m³

The mixing factor ranges from 0.2 for rooms ventilated only by infiltration through cracks to 0.9 for a perforated ceiling supply with several exhausts.[43] As an assumed example, a room of 4 m × 4 m × 3 m (48 m³) has two air changes per hour, or 1.6 m³/min. A natural gas leak of 0.02 m³/min then gives a long-term modelled room concentration of 0.02/1.6 = 1.25 %. That is about 27 % of the lower limit of 4.7 %, so the calculated room concentration stays below that limit.[3] The concentration reaches one-fifth of the lower limit, 0.94 %, when 1 − e−KN = 0.94/1.25 = 0.752. With perfect mixing (K = 1) this takes 1.39 air changes, or about 42 minutes.

Two rising curves of gas concentration against time levelling off at 1.25 percent, with a dashed line at 0.94 percent.
Modelled concentration in a 48 m³ room with two air changes per hour after a natural gas leak of 0.02 m³/min starts, for perfect mixing (K = 1) and K = 0.2, with the NFPA 69 method.

The same leak of propane would reach 58 % of its lower limit of 2.15 %.[3] In this room, a propane leak of about 0.034 m³/min would bring the modelled room concentration to the lower limit; at 21 °C and 101 kPa this is roughly 3.8 kg/h. Real rooms are not perfectly mixed, and the handbook warns that practical ventilation systems can handle only rather nominal release rates.[4] A layer or pocket near the leak can therefore be flammable even while the modelled room concentration remains below the lower limit.

The SFPE Handbook gives a simple estimate of what such a pocket can do. The pressure rise in a closed enclosure is the closed-vessel pressure multiplied by the fraction of the total mass that burns:[44]

P−P0Pm−P0=mbm0

Here P − P0 is the pressure rise, Pm − P0 the closed-vessel deflagration pressure, mb the burned mass and m0 the total mass in the enclosure. For propane–air, Pm − P0 is 7.9 bar.[45] A stoichiometric mixture has almost the density of air, so the mass fraction is close to the volume fraction of the room that the mixture fills.[46] A pocket filling only 1 % of the room would then raise the pressure by about 7.9 kPa if no venting occurred. That exceeds the 3.45 to 6.89 kPa that conventional structures withstand, which agrees with the handbook statement on partly filled rooms.[4]

Limitations and uncertainty

The definitions in this article are American and international transport definitions as described in the 2008 Fire Protection Handbook.[1][2] Other codes and regulations use somewhat different descriptions of related terms such as compressed gas and liquefied gas.[47] The handbook itself notes that a gas such as ammonia can burn and yet be classified as nonflammable for transport.[2] A classification is therefore a regulatory label, and it does not mean that a gas cannot burn or explode in an enclosure.[48]

Tabulated limits depend on the test method. Beyler gives 5 % and 15 % by volume for methane in air, while the handbook table gives 4.7 % and 15.0 % for high-methane natural gas.[15][3] The standard Bureau of Mines method uses a vertical tube 1.5 m long and 0.05 m wide, and limits for downward propagation are narrower than for upward propagation.[15][16] Commercial propane and butane are mixtures, and natural gas compositions vary, so the limits of a real gas can differ from those in a table.[3] Limits also widen with temperature and, for the upper limit, with pressure and oxygen content.[16]

The calculation methods above are first-order approximations. The NFPA 69 buildup equation gives a modelled room concentration and assumes a constant leak and a fixed mixing factor; it does not resolve local gas pockets.[42][43] The partial-volume estimate ignores venting through windows and doors and assumes that the burned mixture is stoichiometric.[44]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Lemoff (2008), p. 6-165.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 Lemoff (2008), p. 6-166.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 Lemoff (2008), p. 6-174, Table 6.10.3.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 Lemoff (2008), p. 6-175.
  5. ↑ 5.0 5.1 5.2 Beyler (2002a), p. 3-269.
  6. ↑ 6.0 6.1 6.2 6.3 Zalosh (2008), p. 2-104.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 Lemoff (2008), p. 6-176.
  8. ↑ 8.0 8.1 C. J. Wright (2008a), pp. 13-119–13-120.
  9. ↑ C. J. Wright (2008a), p. 13-123.
  10. ↑ 10.0 10.1 Lemoff (2008), p. 6-168.
  11. ↑ Van Rossum (2027), §3.1.
  12. ↑ Van Rossum (2027), §3.3.
  13. ↑ Beyler (2002b), p. 2-179.
  14. ↑ Zalosh (2008), p. 2-98.
  15. ↑ 15.0 15.1 15.2 15.3 Beyler (2002b), p. 2-172.
  16. ↑ 16.0 16.1 16.2 16.3 Beyler (2002b), pp. 2-173–2-174.
  17. ↑ Britton (1999), as cited in Ural and Garzia (2008), p. 17-147.
  18. ↑ Lemoff (2008), pp. 6-181–6-182.
  19. ↑ Lemoff (2008), pp. 6-180–6-181.
  20. ↑ Lemoff (2008), pp. 6-178–6-179.
  21. ↑ 21.0 21.1 Cholin (2008a), p. 14-100.
  22. ↑ Iqbal and Salley (2004), p. B-25.
  23. ↑ 23.0 23.1 Lemoff (2008), p. 6-169.
  24. ↑ Lemoff (2008), pp. 6-170–6-171.
  25. ↑ 25.0 25.1 Lemoff (2008), p. 6-172.
  26. ↑ Lemoff (2008), p. 6-173.
  27. ↑ 27.0 27.1 Alpert (2008), p. 2-21.
  28. ↑ Alpert (2008), p. 2-22.
  29. ↑ Cowley and Prichard (1990), as cited in Beyler (2002a), p. 3-302.
  30. ↑ Iqbal and Salley (2004), p. 1-8.
  31. ↑ Van der Graaf et al. (2021/2023), p. 22.
  32. ↑ Van der Graaf et al. (2021/2023), p. 27.
  33. ↑ 33.0 33.1 33.2 Lemoff and Rivkin (2008), p. 7-41.
  34. ↑ Iqbal and Salley (2004), p. B-24.
  35. ↑ 35.0 35.1 Cholin (2008a), p. 14-109.
  36. ↑ Cholin (2008a), p. 14-107.
  37. ↑ Cholin (2008a), p. 14-108.
  38. ↑ Cholin (2008a), p. 14-99.
  39. ↑ Cholin (2008a), p. 14-103.
  40. ↑ 40.0 40.1 Lemoff and Rivkin (2008), p. 7-38.
  41. ↑ 41.0 41.1 Lemoff and Rivkin (2008), p. 7-40.
  42. ↑ 42.0 42.1 42.2 Iqbal and Salley (2004), p. 16-9.
  43. ↑ 43.0 43.1 Iqbal and Salley (2004), p. 16-10.
  44. ↑ 44.0 44.1 Zalosh (2002), p. 3-408.
  45. ↑ Zalosh (2002), p. 3-407.
  46. ↑ Zalosh (2002), p. 3-410.
  47. ↑ Lemoff (2008), p. 6-167.
  48. ↑ Lemoff (2008), p. 6-179.

References

  • Alpert, R. L. (2008). Physics of fire configuration. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-21–2-29). National Fire Protection Association.
  • Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
  • Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
  • Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.