Probability of losing sprinkler protection for one and two systems, with independent failures and with a shared water supply | Probability of losing sprinkler protection for one and two systems, with independent failures and with a shared water supply. | ||
Original illustration for [[Common cause failure]], level 4 Expert. | Original illustration for [[Common cause failure]], level 4 Expert. | ||
* Alt text: Log-scale bar chart: one system 0.02 or 0.029 with shared supply; two systems 0.0004 if independent, 0.0095 with shared supply. | * Alt text: Log-scale bar chart: one system 0.02 or 0.029 with shared supply; two systems 0.0004 if independent, 0.0095 with shared supply. | ||
== Licensing == | == Licensing == | ||
New drawing by Fire Safety Academy. © Fire Safety Academy. | New drawing by Fire Safety Academy. © Fire Safety Academy. | ||
Latest revision as of 08:46, 13 November 2026
Summary
Probability of losing sprinkler protection for one and two systems, with independent failures and with a shared water supply.
Original illustration for Common cause failure, level 4 Expert.
- Alt text: Log-scale bar chart: one system 0.02 or 0.029 with shared supply; two systems 0.0004 if independent, 0.0095 with shared supply.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.