Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
m Remove source references from file description |
||
| Line 1: | Line 1: | ||
== Summary == | == Summary == | ||
A 30.5 m atrium and its 1/8 scale model. Heat release rate and fan flow shrink with the length ratio to the power 5/2, time with its square root; temperatures stay the same | A 30.5 m atrium and its 1/8 scale model. Heat release rate and fan flow shrink with the length ratio to the power 5/2, time with its square root; temperatures stay the same. | ||
Original illustration for [[Froude scaling]], level 4 Expert. | Original illustration for [[Froude scaling]], level 4 Expert. | ||
* Alt text: A tall atrium with a 5 MW fire next to a model one eighth its height with a 28 kW fire, with the scaled values listed. | * Alt text: A tall atrium with a 5 MW fire next to a model one eighth its height with a 28 kW fire, with the scaled values listed. | ||
== Licensing == | == Licensing == | ||
New drawing by Fire Safety Academy. © Fire Safety Academy. | New drawing by Fire Safety Academy. © Fire Safety Academy. | ||
Latest revision as of 09:06, 13 November 2026
Summary
A 30.5 m atrium and its 1/8 scale model. Heat release rate and fan flow shrink with the length ratio to the power 5/2, time with its square root; temperatures stay the same.
Original illustration for Froude scaling, level 4 Expert.
- Alt text: A tall atrium with a 5 MW fire next to a model one eighth its height with a 28 kW fire, with the scaled values listed.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:36, 2 November 2026 | 900 × 600 (9 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: