Skip to content

File:Fse-fuel-controlled-fire-v3.svg: Difference between revisions

From Fire Safety Academy Wiki
Lisa (talk | contribs)
Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
 
Mark (talk | contribs)
m Remove source references from file description
 
Line 1: Line 1:
== Summary ==
== Summary ==
Equivalence ratio φ against heat release rate for a room with a door of 1.08 m² and 1.8 m high: fuel controlled below φ = 1. Based on Walton and Thomas (2002), pp. 3-181, 3-184 and 3-185.
Equivalence ratio φ against heat release rate for a room with a door of 1.08 m² and 1.8 m high: fuel controlled below φ = 1.


Original vector illustration for [[Fuel-controlled fire]], level 2 Intermediate.
Original vector illustration for [[Fuel-controlled fire]], level 2 Intermediate.


* Source basis: Walton and Thomas (2002), p. 3-181 (equivalence ratio, fuel lean below 1), p. 3-184 (stoichiometric heat release rate 1,500 A0√H0) and p. 3-185 (example room; Babrauskas flashover at 750 A0√H0)
* Alt text: Straight line of equivalence ratio against heat release rate for a room with a 1.08 m² door; markers at 500 kW, at flashover (1,087 kW) and at φ = 1 (2,173 kW).
* Alt text: Straight line of equivalence ratio against heat release rate for a room with a 1.08 m² door; markers at 500 kW, at flashover (1,087 kW) and at φ = 1 (2,173 kW).


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 09:06, 13 November 2026

Summary

Equivalence ratio φ against heat release rate for a room with a door of 1.08 m² and 1.8 m high: fuel controlled below φ = 1.

Original vector illustration for Fuel-controlled fire, level 2 Intermediate.

  • Alt text: Straight line of equivalence ratio against heat release rate for a room with a 1.08 m² door; markers at 500 kW, at flashover (1,087 kW) and at φ = 1 (2,173 kW).

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.