Skip to content
From Fire Safety Academy Wiki
Lisa (talk | contribs)
Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
 
Mark (talk | contribs)
m Remove source references from file description
 
Line 1: Line 1:
== Summary ==
== Summary ==
Temperature and velocity profile in a ceiling jet: the maximum lies about 1% of the fire-to-ceiling height below the ceiling, the jet is about 10 to 12% of that height deep. Based on Alpert (2002), p. 2-19, and Iqbal and Salley (2004), pp. 10-9 and 10-11.
Temperature and velocity profile in a ceiling jet: the maximum lies about 1% of the fire-to-ceiling height below the ceiling, the jet is about 10 to 12% of that height deep.


Original vector illustration for [[Ceiling jet]], level 2 Intermediate.
Original vector illustration for [[Ceiling jet]], level 2 Intermediate.


* Source basis: Alpert (2002), p. 2-19 (thickness definition 1/e, 10–12% of H, maximum at 1–2% of H, devices outside the jet); Iqbal and Salley (2004), p. 10-9 (5–12% of H, maximum at 1%) and p. 10-11 (temperature rises to a maximum then falls with depth)
* Alt text: Profile below a ceiling: gas temperature and velocity peak just under the ceiling and fall to ambient at about one tenth of the fire-to-ceiling height.
* Alt text: Profile below a ceiling: gas temperature and velocity peak just under the ceiling and fall to ambient at about one tenth of the fire-to-ceiling height.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:44, 13 November 2026

Summary

Temperature and velocity profile in a ceiling jet: the maximum lies about 1% of the fire-to-ceiling height below the ceiling, the jet is about 10 to 12% of that height deep.

Original vector illustration for Ceiling jet, level 2 Intermediate.

  • Alt text: Profile below a ceiling: gas temperature and velocity peak just under the ceiling and fall to ambient at about one tenth of the fire-to-ceiling height.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:04, 2 November 2026Thumbnail for version as of 17:04, 2 November 2026900 × 600 (11 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata