The '''Fire tetrahedron''' is a conceptual model that adds the uninhibited chemical chain reaction to the fuel, oxygen and heat of the [[Fire triangle]]. It represents four conditions that support [[Combustion]] and identifies chemical inhibition as a fourth way to interrupt a fire, alongside fuel removal, oxygen limitation and cooling.<ref name="Grant-4-152">Grant (2002), pp. 4-152–4-153.</ref> | The '''Fire tetrahedron''' is a conceptual model that adds the uninhibited chemical chain reaction to the fuel, oxygen and heat of the [[Fire triangle]]. It represents four conditions that support [[Combustion]] and identifies chemical inhibition as a fourth way to interrupt a fire, alongside fuel removal, oxygen limitation and cooling.<ref name="Grant-4-152">Grant (2002), pp. 4-152–4-153.</ref> | ||
[[File:fse-fire-tetrahedron-v1.svg|thumb|upright=1.5|alt=Tetrahedron labelled fuel, oxygen, heat and uninhibited chemical chain reaction.|The fire tetrahedron adds chain chemistry to fuel, oxygen and heat. Based on Grant (2002), pp. 4-152–4-153.]] | |||
The model developed from the observation that some extinguishing agents do not act primarily by removing fuel, excluding oxygen or absorbing heat. Halogenated agents can instead interfere with reactive chemical species in a flame. When the chain reaction can no longer sustain itself, flaming combustion stops even though the original three elements have not all been removed.<ref name="Grant-4-152" /> | The model developed from the observation that some extinguishing agents do not act primarily by removing fuel, excluding oxygen or absorbing heat. Halogenated agents can instead interfere with reactive chemical species in a flame. When the chain reaction can no longer sustain itself, flaming combustion stops even though the original three elements have not all been removed.<ref name="Grant-4-152" /> | ||
| Line 18: | Line 19: | ||
A chain reaction involves reactive intermediates that are consumed in one step and regenerated in another. Chain-branching steps increase the number of these reactive centres, while chain-termination steps remove them. The balance between production and removal influences whether the reaction accelerates, reaches a steady state or dies out.<ref name="Simmons-1-150" /> | A chain reaction involves reactive intermediates that are consumed in one step and regenerated in another. Chain-branching steps increase the number of these reactive centres, while chain-termination steps remove them. The balance between production and removal influences whether the reaction accelerates, reaches a steady state or dies out.<ref name="Simmons-1-150" /> | ||
One branching step in hydrocarbon flames involves a hydrogen atom reacting with an oxygen molecule to produce a hydroxyl radical and an oxygen atom. A radical is a reactive chemical species that participates in the continuing reaction sequence. In this example, one reactive centre produces two, allowing further reactions to follow. The symbols H, O₂, OH and O represent atomic hydrogen, molecular oxygen, hydroxyl and atomic oxygen respectively:<ref name="Simmons-1-149">Simmons (2002), pp. 1-149–1-150.</ref> | |||
<math display="block">\mathrm{H}+\mathrm{O}_2\rightarrow\mathrm{OH}+\mathrm{O}</math> | |||
Termination has the opposite effect. A hydrogen atom and a hydroxyl radical can combine to form water, removing both reactive centres. Simmons includes this recombination among the processes that limit radical concentrations in the later flame region. Branching and termination operate within the same flame, so their relative rates matter more than the presence of either reaction alone.<ref name="Simmons-1-150" /> | |||
[[File:fse-fire-tetrahedron-v3.svg|thumb|upright=1.5|alt=Reactive centre splitting into more centres or ending through termination.|Chain branching and termination influence whether reaction continues. Based on Simmons (2002), p. 1-150.]] | |||
Simmons describes how chain branching can produce a rapid rise in reactive-centre concentration. Later consumption of reactants and termination processes limit that rise. In a hydrocarbon-air flame, these chemical developments contribute to the luminous reaction zone. The light emitted from parts of a flame can therefore be connected with excited chemical species as well as with hot particles.<ref name="Simmons-1-150" /> | Simmons describes how chain branching can produce a rapid rise in reactive-centre concentration. Later consumption of reactants and termination processes limit that rise. In a hydrocarbon-air flame, these chemical developments contribute to the luminous reaction zone. The light emitted from parts of a flame can therefore be connected with excited chemical species as well as with hot particles.<ref name="Simmons-1-150" /> | ||
| Line 27: | Line 35: | ||
== Chemical inhibition == | == Chemical inhibition == | ||
Chemical inhibition changes the balance within the reaction sequence. An inhibiting agent can remove active species or promote termination so that chain branching no longer sustains the flame. This mechanism differs from adding an inert diluent, which mainly reduces temperature and burning velocity by increasing the amount of material that must be heated.<ref name="Simmons-1- | Chemical inhibition changes the balance within the reaction sequence. An inhibiting agent can remove active species or promote termination so that chain branching no longer sustains the flame. This mechanism differs from adding an inert diluent, which mainly reduces temperature and burning velocity by increasing the amount of material that must be heated.<ref name="Simmons-inhibition">Simmons (2002), pp. 1-150–1-151.</ref> | ||
The SFPE Handbook contrasts nitrogen and bromine-containing additives to illustrate this difference. Nitrogen acts as a diluent and must be present at substantial concentration to prevent propane-air flame propagation in the reported test. Bromine compounds can be much more effective because they participate in chain-termination chemistry. The | The SFPE Handbook contrasts nitrogen and bromine-containing additives to illustrate this difference. Nitrogen acts as a diluent and must be present at substantial concentration to prevent propane-air flame propagation in the reported test. Bromine compounds can be much more effective because they participate in chain-termination chemistry. The comparison belongs to the cited experiments and does not establish an agent concentration for other fuels or configurations.<ref name="Simmons-inhibition" /> | ||
Grant describes the action of Halon 1301 through bromine radicals that interfere with active flame species. The exact extinguishing mechanism was not presented as completely understood, but the chemical interaction was distinct from simple cooling or smothering. This account comes from a 2002 handbook chapter on halon design and should be read in that historical context.<ref name="Grant-4-153">Grant (2002), p. 4-153.</ref> | Grant describes the action of Halon 1301 through bromine radicals that interfere with active flame species. The exact extinguishing mechanism was not presented as completely understood, but the chemical interaction was distinct from simple cooling or smothering. This account comes from a 2002 handbook chapter on halon design and should be read in that historical context.<ref name="Grant-4-153">Grant (2002), p. 4-153.</ref> | ||
| Line 46: | Line 54: | ||
[[Extinguishing mechanisms]] can use more than one route at the same time. A measure may cool the fuel while also reducing oxygen availability, while a separate agent interferes with flame chemistry. The tetrahedron does not require a measure to fit only one category. It provides language for identifying what each part of the intervention changes.<ref name="Grant-4-152" /><ref name="VR-4.3" /> | [[Extinguishing mechanisms]] can use more than one route at the same time. A measure may cool the fuel while also reducing oxygen availability, while a separate agent interferes with flame chemistry. The tetrahedron does not require a measure to fit only one category. It provides language for identifying what each part of the intervention changes.<ref name="Grant-4-152" /><ref name="VR-4.3" /> | ||
[[File:fse-fire-tetrahedron-v2.svg|thumb|upright=1.5|alt=Four routes: remove fuel, limit oxygen, remove heat and inhibit chain reactions.|Four routes for interrupting combustion. Based on Grant (2002), pp. 4-152–4-153.]] | |||
[[Flame extinction]] occurs when the flame can no longer sustain its reaction and heat balance. This can follow reduced burning velocity, excessive heat loss, lack of fuel or oxidiser, or chemical termination of the chain reaction. Extinction of visible flaming does not necessarily end smouldering or remove the possibility of later reignition.<ref name="Drysdale-1-97">Drysdale (2002), p. 1-97.</ref><ref name="Ohlemiller-2-208">Ohlemiller (2002), p. 2-208.</ref> | [[Flame extinction]] occurs when the flame can no longer sustain its reaction and heat balance. This can follow reduced burning velocity, excessive heat loss, lack of fuel or oxidiser, or chemical termination of the chain reaction. Extinction of visible flaming does not necessarily end smouldering or remove the possibility of later reignition.<ref name="Drysdale-1-97">Drysdale (2002), p. 1-97.</ref><ref name="Ohlemiller-2-208">Ohlemiller (2002), p. 2-208.</ref> | ||
| Line 74: | Line 83: | ||
Ignition provides another distinction. The International Fire Engineering Guidelines describe piloted, non-piloted and self-induced routes to ignition. The tetrahedron does not select between these routes or predict their timing. It becomes useful after considering whether the resulting reaction can sustain itself and which mechanism could interrupt that reaction.<ref name="IFEG-2.4-4" /> | Ignition provides another distinction. The International Fire Engineering Guidelines describe piloted, non-piloted and self-induced routes to ignition. The tetrahedron does not select between these routes or predict their timing. It becomes useful after considering whether the resulting reaction can sustain itself and which mechanism could interrupt that reaction.<ref name="IFEG-2.4-4" /> | ||
== Common misunderstandings == | == Common misunderstandings == | ||
| Line 83: | Line 90: | ||
Removing visible flame does not demonstrate removal of all four elements. Hot fuel can remain, oxygen can return and pyrolysis gases can later form a flammable mixture. Smouldering can also continue without visible flame. A stable outcome requires assessment of the fuel condition as well as observation of the flame.<ref name="Ohlemiller-2-206" /><ref name="Ohlemiller-2-208" /> | Removing visible flame does not demonstrate removal of all four elements. Hot fuel can remain, oxygen can return and pyrolysis gases can later form a flammable mixture. Smouldering can also continue without visible flame. A stable outcome requires assessment of the fuel condition as well as observation of the flame.<ref name="Ohlemiller-2-206" /><ref name="Ohlemiller-2-208" /> | ||
The tetrahedron does not imply that every extinguishing agent acts chemically. Fuel removal, smothering and cooling remain distinct mechanisms. Chemical inhibition is relevant when an agent changes the reaction sequence itself. Correct identification matters because delivery, persistence and fuel-specific limitations differ between these routes.<ref name="Grant-4-152" /> | |||
== Notes == | == Notes == | ||
| Line 98: | Line 99: | ||
* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board. | * Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board. | ||
* Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association. | * Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 1-110–1-131). National Fire Protection Association. | ||
* Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association. | * Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 1-90–1-98). National Fire Protection Association. | ||
* Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association. | * Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 4-149–4-172). National Fire Protection Association. | ||
* Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association. | * Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 2-200–2-210). National Fire Protection Association. | ||
* Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association. | * Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 1-144–1-154). National Fire Protection Association. | ||
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy. | * Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy. | ||
[[Category:Combustion]] | [[Category:Combustion]] | ||
Latest revision as of 18:31, 2 November 2026
The Fire tetrahedron is a conceptual model that adds the uninhibited chemical chain reaction to the fuel, oxygen and heat of the Fire triangle. It represents four conditions that support Combustion and identifies chemical inhibition as a fourth way to interrupt a fire, alongside fuel removal, oxygen limitation and cooling.[1]
The model developed from the observation that some extinguishing agents do not act primarily by removing fuel, excluding oxygen or absorbing heat. Halogenated agents can instead interfere with reactive chemical species in a flame. When the chain reaction can no longer sustain itself, flaming combustion stops even though the original three elements have not all been removed.[1]
The tetrahedron is useful for explaining extinction and the chemistry of flames. It is not a calculation method and does not assign numerical thresholds to its four parts. Fire development still depends on material decomposition, mixing, heat transfer and the physical arrangement of fuel and oxygen.[2][3]
From three elements to four
Fuel supplies the substance that reacts, oxygen usually serves as the oxidiser and heat enables ignition and continuing reaction. These elements explain many familiar prevention measures: keep fuel away from an ignition source, stop a fuel supply, cool burning material or restrict oxygen. They also apply to gases, liquids and solids, although liquids and solids generally need to produce vapour or decomposition gases before flaming.[4][5]
The fourth element describes how gas-phase reactions propagate through a flame. A combustion reaction is not necessarily a single direct conversion of fuel and oxygen into final products. Reactive intermediate species take part in sequences of elementary reactions. These sequences can sustain further reaction by producing additional reactive species while final combustion products and heat are formed.[6]
Grant explains the historical extension through the action of halons. Traditional extinguishment involved removing fuel, smothering the fire or quenching it by heat removal. Halons could instead break up the uninhibited chain reaction. The tetrahedron therefore represents a chemical route to extinction that the triangle alone did not express.[1]
The geometric form is a teaching device. It does not imply that the four conditions have equal magnitudes or that a fire has four physical components. It also does not replace the need to describe the actual fuel, the oxidiser concentration or the energy supplied and lost. Its purpose is to show four places where the overall process can be interrupted.[1][7]
Chemical chain reactions
A chain reaction involves reactive intermediates that are consumed in one step and regenerated in another. Chain-branching steps increase the number of these reactive centres, while chain-termination steps remove them. The balance between production and removal influences whether the reaction accelerates, reaches a steady state or dies out.[6]
One branching step in hydrocarbon flames involves a hydrogen atom reacting with an oxygen molecule to produce a hydroxyl radical and an oxygen atom. A radical is a reactive chemical species that participates in the continuing reaction sequence. In this example, one reactive centre produces two, allowing further reactions to follow. The symbols H, O₂, OH and O represent atomic hydrogen, molecular oxygen, hydroxyl and atomic oxygen respectively:[8]
Termination has the opposite effect. A hydrogen atom and a hydroxyl radical can combine to form water, removing both reactive centres. Simmons includes this recombination among the processes that limit radical concentrations in the later flame region. Branching and termination operate within the same flame, so their relative rates matter more than the presence of either reaction alone.[6]
Simmons describes how chain branching can produce a rapid rise in reactive-centre concentration. Later consumption of reactants and termination processes limit that rise. In a hydrocarbon-air flame, these chemical developments contribute to the luminous reaction zone. The light emitted from parts of a flame can therefore be connected with excited chemical species as well as with hot particles.[6]
The chemistry varies through the flame. In a diffusion flame, fuel and oxygen arrive from different sides and react across a region with changing local composition. The fuel-rich side can be dominated by thermal decomposition and carbon formation, while the highest temperature occurs in the main reaction zone on the air side. Local reaction conditions consequently differ even when the overall fuel and oxygen amounts are known.[9]
This chemical interpretation complements the physical description of mixing. In many real diffusion flames, fuel and oxygen transport controls the overall rate rather than the speed of the elementary chemical reactions. A stable flame can nevertheless depend on a small premixed region near its base, where local flow and burning velocity determine whether it remains attached or blows off.[9]
Chemical inhibition
Chemical inhibition changes the balance within the reaction sequence. An inhibiting agent can remove active species or promote termination so that chain branching no longer sustains the flame. This mechanism differs from adding an inert diluent, which mainly reduces temperature and burning velocity by increasing the amount of material that must be heated.[10]
The SFPE Handbook contrasts nitrogen and bromine-containing additives to illustrate this difference. Nitrogen acts as a diluent and must be present at substantial concentration to prevent propane-air flame propagation in the reported test. Bromine compounds can be much more effective because they participate in chain-termination chemistry. The comparison belongs to the cited experiments and does not establish an agent concentration for other fuels or configurations.[10]
Grant describes the action of Halon 1301 through bromine radicals that interfere with active flame species. The exact extinguishing mechanism was not presented as completely understood, but the chemical interaction was distinct from simple cooling or smothering. This account comes from a 2002 handbook chapter on halon design and should be read in that historical context.[11]
An Extinguishing agent that uses chemical inhibition still has to reach the reaction region in sufficient quantity and remain there under the relevant conditions. Agent movement, enclosure geometry and fire location affect this contact. The tetrahedron identifies the mechanism but does not demonstrate that a particular system will deliver the agent successfully.[11]
Some fuels present additional limits. Grant lists reactive metals and substances containing their own oxidising agent among materials for which Halon 1301 was ineffective or not recommended. These examples show that interrupting one conceptual element cannot be assumed to work universally. Fuel chemistry and the location of the oxidiser can defeat an otherwise suitable mechanism.[1]
The four extinguishing routes
Fuel control removes or isolates the material supplying the reaction. In a continuing incident this can involve stopping a fuel flow or preventing additional items from becoming involved. In prevention it can involve reducing combustible inventory or separating fuel from energy sources. The measure acts before or during combustion by limiting what can react.[12]
Oxygen limitation restricts the oxidiser reaching the reaction zone. This can be effective for some enclosed fires, but hot fuel can reignite if oxygen returns before cooling is complete. Smouldering fuels are especially relevant because their porous structure can retain heat while admitting oxygen slowly. Apparent extinction therefore has to be distinguished from a durable end to reaction.[13]
Heat removal lowers the energy available for ignition, decomposition and continuing reaction. Cooling can reduce the production of combustible vapour and weaken the feedback that sustains a flame. For a deep fuel bed, removing enough heat can be difficult because the material insulates the reaction region. The triangle's heat element therefore includes both the fire's feedback and heat losses to the surroundings.[14][13]
Extinguishing mechanisms can use more than one route at the same time. A measure may cool the fuel while also reducing oxygen availability, while a separate agent interferes with flame chemistry. The tetrahedron does not require a measure to fit only one category. It provides language for identifying what each part of the intervention changes.[1][2]
Flame extinction occurs when the flame can no longer sustain its reaction and heat balance. This can follow reduced burning velocity, excessive heat loss, lack of fuel or oxidiser, or chemical termination of the chain reaction. Extinction of visible flaming does not necessarily end smouldering or remove the possibility of later reignition.[15][16]
Flames, heat and the chain reaction
The chemical chain reaction and the fire's heat balance are linked. Reactions release energy, while the temperature influences reaction rates and the stability of chemical species. Heat loss can lower temperature until propagation fails, and inhibitors can reduce reaction until heat production falls below losses. The fourth element therefore interacts with the heat element rather than operating independently.[17]
A theoretical adiabatic flame temperature assumes no heat transfer to the surroundings. Real flames lose radiation and other energy, and high-temperature dissociation absorbs energy through changes in combustion products. These processes reduce actual temperature below a simple theoretical maximum. They also show why the tetrahedron cannot be read as four separate switches with no interaction.[17]
Near a flammability limit, heat production and heat loss become finely balanced. Drysdale explains that radiation losses can exceed production so that a flame cannot sustain itself. Chemical inhibition can shift the same balance by lowering reaction rates. Both routes can lead to loss of flame propagation even though their physical mechanisms differ.[15][6]
The visible boundary of a flame is not a complete map of its chemistry. Fuel-rich and oxygen-rich regions contain different species and reaction rates, and local equilibrium assumptions can fail. Simmons notes that turbulent diffusion flames add further departures from equilibrium. This complexity is one reason the tetrahedron remains a qualitative model rather than a design equation.[3]
Use and limits in fire safety engineering
The tetrahedron can support a systematic review of candidate interventions. Fuel, oxidiser, heat and reaction chemistry are considered separately, so a chemical agent is not incorrectly described as merely smothering a fire. It also encourages evaluation of whether an intervention reaches the relevant region and whether the remaining conditions permit reignition.[11][13]
For a design assessment, the model must be accompanied by the fire scenario. Fuel state, ventilation, enclosure and scale determine how the four conditions develop. A flammable gas cloud, a liquid pool and a porous solid all produce different mixing and heat-transfer problems. Identical conceptual elements do not produce identical fire behaviour.[4][18]
The model is less direct for smouldering than for flaming. Smouldering is sustained by oxidation at the surface of a condensed-phase fuel and does not require a gas-phase flame. Its persistence depends strongly on oxygen transport through the fuel and heat retention. Chemical chain reactions in a flame are therefore not a sufficient description of every form of combustion.[19]
A further limitation is that thermodynamics does not determine reaction rate. Energy values can describe potential heat release, but not how quickly chemical change occurs or how a flame responds to an inhibitor. Engineering analysis combines chemical information with measured burning behaviour, flow and heat transfer rather than treating the tetrahedron as a predictive substitute.[7]
Historical accounts of particular agents also need to be kept within their source context. The SFPE Handbook's halon chapter documents the chemistry and design understanding behind the model in 2002. It does not, by itself, establish current regulatory acceptance or suitability of that agent for a new application. The general lesson concerns interruption of reaction chemistry, not a universal recommendation of one substance.[1]
The fourth element also has to be distinguished from fuel production. Pyrolysis decomposes a heated solid into smaller molecules and combustible gases without requiring oxygen at the decomposition site. Those gases may later burn through a chain reaction, but pyrolysis and combustion are separate processes. A measure can therefore reduce fuel-gas production through cooling without acting as a chemical flame inhibitor.[20]
Ignition provides another distinction. The International Fire Engineering Guidelines describe piloted, non-piloted and self-induced routes to ignition. The tetrahedron does not select between these routes or predict their timing. It becomes useful after considering whether the resulting reaction can sustain itself and which mechanism could interrupt that reaction.[12]
Common misunderstandings
The fourth element is sometimes described as though it were another fuel component. It is instead the continuing sequence of chemical reactions that allows combustion to propagate. Fuel, oxygen and heat create conditions for that sequence, while reactive intermediates carry it forward.[6]
Removing visible flame does not demonstrate removal of all four elements. Hot fuel can remain, oxygen can return and pyrolysis gases can later form a flammable mixture. Smouldering can also continue without visible flame. A stable outcome requires assessment of the fuel condition as well as observation of the flame.[13][16]
The tetrahedron does not imply that every extinguishing agent acts chemically. Fuel removal, smothering and cooling remain distinct mechanisms. Chemical inhibition is relevant when an agent changes the reaction sequence itself. Correct identification matters because delivery, persistence and fuel-specific limitations differ between these routes.[1]
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Grant (2002), pp. 4-152–4-153.
- ↑ 2.0 2.1 Van Rossum (2027), §4.3.
- ↑ 3.0 3.1 Simmons (2002), p. 1-152.
- ↑ 4.0 4.1 Van Rossum (2027), §4.1.
- ↑ Van Rossum (2027), §4.2.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Simmons (2002), p. 1-150.
- ↑ 7.0 7.1 Drysdale (2002), p. 1-90.
- ↑ Simmons (2002), pp. 1-149–1-150.
- ↑ 9.0 9.1 Simmons (2002), pp. 1-151–1-152.
- ↑ 10.0 10.1 Simmons (2002), pp. 1-150–1-151.
- ↑ 11.0 11.1 11.2 Grant (2002), p. 4-153.
- ↑ 12.0 12.1 Australian Building Codes Board et al. (2005), p. 2.4-4.
- ↑ 13.0 13.1 13.2 13.3 Ohlemiller (2002), p. 2-206.
- ↑ Beyler and Hirschler (2002), p. 1-110.
- ↑ 15.0 15.1 Drysdale (2002), p. 1-97.
- ↑ 16.0 16.1 Ohlemiller (2002), p. 2-208.
- ↑ 17.0 17.1 Drysdale (2002), pp. 1-96–1-97.
- ↑ Ohlemiller (2002), pp. 2-201–2-202.
- ↑ Ohlemiller (2002), p. 2-200.
- ↑ Van Rossum (2027), §3.1.
References
- Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association.
- Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-90–1-98). National Fire Protection Association.
- Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-149–4-172). National Fire Protection Association.
- Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association.
- Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.