== Principle of operation == | == Principle of operation == | ||
In the proton-conducting design shown in the handbook, hydrogen passes over the anode and splits into protons and electrons. The electrons flow through an external circuit, while protons cross the electrolyte. At the cathode, they combine with oxygen to form water and heat.<ref name="Big-8-108" /><ref name="SC-21-81" /> Because the fuel is oxidised electrochemically rather than burned, fuel cells are not constrained by the efficiency limits that apply to engines.<ref name="Big-8-105" /> This sets them apart from a [[stationary combustion engine]], in which combustion generates the energy.<ref name="Big-8-111">Biggins (2008), p. 8-111.</ref> | In the proton-conducting design shown in the handbook, hydrogen passes over the anode and splits into protons and electrons. The electrons flow through an external circuit, while protons cross the electrolyte. At the cathode, they combine with oxygen to form water and heat.<ref name="Big-8-108" /><ref name="SC-21-81" /> Because the fuel is oxidised electrochemically rather than burned, fuel cells are not constrained by the efficiency limits that apply to engines.<ref name="Big-8-105" /> This sets them apart from a [[stationary combustion engine]], in which combustion generates the energy.<ref name="Big-8-111">Biggins (2008), p. 8-111.</ref> | ||
[[File:fse-fuel-cell-v1.svg|thumb|upright=1.5|alt=Fuel cell cross-section: hydrogen enters at the anode, protons cross the electrolyte, electrons flow through an external load, water leaves at the cathode|Operation of a hydrogen fuel cell with a proton-conducting electrolyte.]] | |||
The most efficient fuel cells use hydrogen and oxygen directly. In conventional fuel cells, a carbon-rich fuel is first reformed into hydrogen. In many designs this happens inside the cell, at very high temperatures of 750 to 900 °C (1,382 to 1,652 °F).<ref name="Big-8-108" /> A stationary fuel cell power system therefore contains more than the cell stack. NFPA 853 describes a fuel-processing system, an oxidant-processing system, the fuel cell module, thermal management, power conditioning, water treatment, ventilation and automatic controls. Besides electrical power, the system delivers usable heat, waste heat, condensate and exhaust gases.<ref name="She-9-184">Sheridan (2008), p. 9-184.</ref> | The most efficient fuel cells use hydrogen and oxygen directly. In conventional fuel cells, a carbon-rich fuel is first reformed into hydrogen. In many designs this happens inside the cell, at very high temperatures of 750 to 900 °C (1,382 to 1,652 °F).<ref name="Big-8-108" /> A stationary fuel cell power system therefore contains more than the cell stack. NFPA 853 describes a fuel-processing system, an oxidant-processing system, the fuel cell module, thermal management, power conditioning, water treatment, ventilation and automatic controls. Besides electrical power, the system delivers usable heat, waste heat, condensate and exhaust gases.<ref name="She-9-184">Sheridan (2008), p. 9-184.</ref> | ||
[[File:fse-fuel-cell-v2.svg|thumb|upright=1.5|alt=Block diagram of a stationary fuel cell power system with fuel processing, fuel cell module, thermal management and power conditioning inside a cabinet|Main modules of a stationary fuel cell power system as described in NFPA 853.]] | |||
The principle is old. In 1839 the British scientist William Robert Grove found that hydrogen and oxygen could be combined to produce water and an electric current.<ref name="SC-21-81">Scheffler and Collins (2008), p. 21-81.</ref> A design developed by Francis Bacon's team in the late 1950s powered the Apollo and Skylab programmes, and fuel cells also supplied power on board the space shuttle.<ref name="SC-21-81" /> Industrial use long remained limited, because the technology is demanding and cheaper alternatives dominated the market.<ref name="Big-8-108" /> | The principle is old. In 1839 the British scientist William Robert Grove found that hydrogen and oxygen could be combined to produce water and an electric current.<ref name="SC-21-81">Scheffler and Collins (2008), p. 21-81.</ref> A design developed by Francis Bacon's team in the late 1950s powered the Apollo and Skylab programmes, and fuel cells also supplied power on board the space shuttle.<ref name="SC-21-81" /> Industrial use long remained limited, because the technology is demanding and cheaper alternatives dominated the market.<ref name="Big-8-108" /> | ||
| Line 31: | Line 33: | ||
The use of hydrogen as a fuel presents special concerns, the subject of [[hydrogen safety]].<ref name="Big-8-110" /> The [[flammability limits]] of a gas are the limits of composition over which a self-sustaining flame can propagate.<ref name="Sim-1-146">Simmons (2002), p. 1-146.</ref> For hydrogen in air, the SFPE Handbook lists limits of 4.0 and 75 percent by volume, against 5.0 and 15.0 percent for methane, the main component of [[natural gas]].<ref name="Bey-2-176">Beyler (2002b), p. 2-176.</ref> The maximum burning velocity of hydrogen–air mixtures is 320 cm/s, compared with 41 cm/s for propane–air.<ref name="Sim-1-146" /> The deflagration index ''K''<sub>G</sub> of hydrogen is 550 bar·m/s, ten times the 55 bar·m/s of methane.<ref name="Zal-3-407">Zalosh (2002), p. 3-407.</ref> | The use of hydrogen as a fuel presents special concerns, the subject of [[hydrogen safety]].<ref name="Big-8-110" /> The [[flammability limits]] of a gas are the limits of composition over which a self-sustaining flame can propagate.<ref name="Sim-1-146">Simmons (2002), p. 1-146.</ref> For hydrogen in air, the SFPE Handbook lists limits of 4.0 and 75 percent by volume, against 5.0 and 15.0 percent for methane, the main component of [[natural gas]].<ref name="Bey-2-176">Beyler (2002b), p. 2-176.</ref> The maximum burning velocity of hydrogen–air mixtures is 320 cm/s, compared with 41 cm/s for propane–air.<ref name="Sim-1-146" /> The deflagration index ''K''<sub>G</sub> of hydrogen is 550 bar·m/s, ten times the 55 bar·m/s of methane.<ref name="Zal-3-407">Zalosh (2002), p. 3-407.</ref> | ||
[[File:fse-fuel-cell-v3.svg|thumb|upright=1.5|alt=Range bars of flammability limits for hydrogen, natural gas and propane, alongside burning velocities for hydrogen and propane|Flammability limits in air for three gases, with maximum laminar burning velocities for hydrogen and propane.]] | |||
The US Nuclear Regulatory Commission's fire dynamics tools report adds that hydrogen needs only a very weak spark of about 10<sup>−4</sup> J to ignite. It burns with a nonluminous flame that is often invisible in daylight.<ref name="IS-16-2">Iqbal and Salley (2004), p. 16-2.</ref><ref name="IS-16-4">Iqbal and Salley (2004), p. 16-4.</ref> Its lower limit depends on the direction of flame propagation: 4.1 percent upwards, 6.0 percent horizontally and 9.0 percent downwards.<ref name="IS-16-2" /> | The US Nuclear Regulatory Commission's fire dynamics tools report adds that hydrogen needs only a very weak spark of about 10<sup>−4</sup> J to ignite. It burns with a nonluminous flame that is often invisible in daylight.<ref name="IS-16-2">Iqbal and Salley (2004), p. 16-2.</ref><ref name="IS-16-4">Iqbal and Salley (2004), p. 16-4.</ref> Its lower limit depends on the direction of flame propagation: 4.1 percent upwards, 6.0 percent horizontally and 9.0 percent downwards.<ref name="IS-16-2" /> | ||
The handbook’s stationary-fuel-cell chapter rounds hydrogen’s vapour density relative to air to 0.1, while its vehicle-fuel chapter gives 0.07. Both describe rapid dispersal after an outdoor release.<ref name="Big-8-110" /><ref name="Riv-21-55">Rivkin (2008b), p. 21-55.</ref> | The handbook’s stationary-fuel-cell chapter rounds hydrogen’s vapour density relative to air to 0.1, while its vehicle-fuel chapter gives 0.07. Both describe rapid dispersal after an outdoor release.<ref name="Big-8-110" /><ref name="Riv-21-55">Rivkin (2008b), p. 21-55.</ref> Hydrogen is normally not odorised, because odorants would contaminate the fuel cell catalysts.<ref name="Riv-21-60">Rivkin (2008b), p. 21-60.</ref> When hydrogen is the fuel, the handbook recommends vapour detection devices.<ref name="Big-8-110" /> | ||
Tests on lean mixtures show that the 4 percent limit is not the whole story. In deflagration tests, the fraction of hydrogen burned rose from zero at 4 percent to complete combustion at about 8 percent.<ref name="Zal-3-407" /> The lower flammability limit (LFL) is measured in a uniform, quiescent mixture, and tests cited in the fuel cell vehicle chapter found that concentrations above 8 percent are typically required to ignite a dispersing discharge.<ref name="SC-21-86">Scheffler and Collins (2008), p. 21-86.</ref> A mixture is potentially flammable only when it contains more than 4 percent hydrogen and more than 5 percent oxygen. A discharge diluted with inert gas to 5 percent hydrogen therefore stays nonflammable as it mixes with air.<ref name="SC-21-86" /> | Tests on lean mixtures show that the 4 percent limit is not the whole story. In deflagration tests, the fraction of hydrogen burned rose from zero at 4 percent to complete combustion at about 8 percent.<ref name="Zal-3-407" /> The lower flammability limit (LFL) is measured in a uniform, quiescent mixture, and tests cited in the fuel cell vehicle chapter found that concentrations above 8 percent are typically required to ignite a dispersing discharge.<ref name="SC-21-86">Scheffler and Collins (2008), p. 21-86.</ref> A mixture is potentially flammable only when it contains more than 4 percent hydrogen and more than 5 percent oxygen. A discharge diluted with inert gas to 5 percent hydrogen therefore stays nonflammable as it mixes with air.<ref name="SC-21-86" /> | ||
| Line 44: | Line 47: | ||
Ventilation and gas detection are the main safeguards indoors. The room should be kept at negative or neutral pressure, with its own mechanical ventilation unless natural ventilation is shown to be sufficient.<ref name="Big-8-110" /> Vents of pressure tanks, regulators and relief valves should discharge to a safe location outside. If exhaust is mechanical, an interlock should shut down the unit when ventilation fails.<ref name="Big-8-110" /> An exhaust rate of at least 1 cfm per square foot of floor area, and not less than 150 cfm for the room, is typically considered effective:<ref name="Big-8-110" /> | Ventilation and gas detection are the main safeguards indoors. The room should be kept at negative or neutral pressure, with its own mechanical ventilation unless natural ventilation is shown to be sufficient.<ref name="Big-8-110" /> Vents of pressure tanks, regulators and relief valves should discharge to a safe location outside. If exhaust is mechanical, an interlock should shut down the unit when ventilation fails.<ref name="Big-8-110" /> An exhaust rate of at least 1 cfm per square foot of floor area, and not less than 150 cfm for the room, is typically considered effective:<ref name="Big-8-110" /> | ||
[[File:fse-fuel-cell-v4.svg|thumb|upright=1.5|alt=Section through a separated fuel cell room with exhaust fan, gas detector, fuel shutoff valve, fire detector and sprinklers|Fire safety provisions for an indoor stationary fuel cell room under the US practice summarised in 2008.]] | |||
<math display="block">\dot V_\mathrm{ex} = \max\left(q\,A;\ \dot V_\mathrm{min}\right)</math> | <math display="block">\dot V_\mathrm{ex} = \max\left(q\,A;\ \dot V_\mathrm{min}\right)</math> | ||
A combustible gas detection system in the enclosure, the exhaust or the room should alarm at 25 percent of the lower flammable limit (LEL). It should be interlocked to shut off the fuel at 60 percent, using the lowest LEL of the gases present:<ref name="Big-8-110" /><ref name="Big-8-111" /> | A combustible gas detection system in the enclosure, the exhaust or the room should alarm at 25 percent of the lower flammable limit (LEL). It should be interlocked to shut off the fuel at 60 percent, using the lowest LEL of the gases present:<ref name="Big-8-110" /><ref name="Big-8-111" /> | ||
| Line 70: | Line 74: | ||
== Fuel cell vehicles == | == Fuel cell vehicles == | ||
In a [[fuel cell vehicle]], the fuel cell supplies the electric traction motors and typically also the auxiliary systems. A separate auxiliary power unit typically rates 3 to 10 kW.<ref name="SC-21-78" /> Fuel cell vehicles ranged in 2008 from 12.2 m (40 ft) transit buses to motor scooters and fork-lift trucks. The California Fuel Cell Partnership expected about 300 fuel cell cars and buses in demonstrations in that state by 2007.<ref name="SC-21-78" /><ref name="SC-21-77">Scheffler and Collins (2008), p. 21-77.</ref> Many use a hybrid layout in which batteries or ultracapacitors store energy recovered by regenerative braking.<ref name="SC-21-78" /> | In a [[fuel cell vehicle]], the fuel cell supplies the electric traction motors and typically also the auxiliary systems. A separate auxiliary power unit typically rates 3 to 10 kW.<ref name="SC-21-78" /> Fuel cell vehicles ranged in 2008 from 12.2 m (40 ft) transit buses to motor scooters and fork-lift trucks. The California Fuel Cell Partnership expected about 300 fuel cell cars and buses in demonstrations in that state by 2007.<ref name="SC-21-78" /><ref name="SC-21-77">Scheffler and Collins (2008), p. 21-77.</ref> Many use a hybrid layout in which batteries or ultracapacitors store energy recovered by regenerative braking.<ref name="SC-21-78" /> | ||
[[File:fse-fuel-cell-v5.jpg|thumb|upright=1.5|alt=Hydrogen fuel cell transit bus with roof-mounted equipment at a bus stop|Fuel cell transit bus; transit buses were seen as an early market for fuel cell vehicles.]] | |||
Most fuel cell vehicles store compressed hydrogen gas.<ref name="SC-21-78" /> A typical vehicle needs about 6 kg of hydrogen, and storage pressures were rising from 350 to 700 bar (5,000 to 10,000 psig).<ref name="SC-21-84">Scheffler and Collins (2008), p. 21-84.</ref> With a calorific value of 120 MJ/kg, 6 kg of hydrogen holds about 720 MJ, the energy of about 16 kg of petrol at 44 MJ/kg.<ref name="NRC-3.3-5">National Research Council of Canada et al. (2005), p. 3.3-5.</ref> Hydrogen fuelling stations usually store their fuel on site, often as a cryogenic liquid. They work at up to about 690 bar (10,000 psi), against 207 to 276 bar (3,000 to 4,000 psi) for natural gas, because hydrogen gas has such a low density.<ref name="Riv-21-74">Rivkin (2008b), p. 21-74.</ref> A release of liquid hydrogen boils off rapidly and can condense oxygen out of the air, which adds a further hazard.<ref name="Riv-21-55" /> | Most fuel cell vehicles store compressed hydrogen gas.<ref name="SC-21-78" /> A typical vehicle needs about 6 kg of hydrogen, and storage pressures were rising from 350 to 700 bar (5,000 to 10,000 psig).<ref name="SC-21-84">Scheffler and Collins (2008), p. 21-84.</ref> With a calorific value of 120 MJ/kg, 6 kg of hydrogen holds about 720 MJ, the energy of about 16 kg of petrol at 44 MJ/kg.<ref name="NRC-3.3-5">National Research Council of Canada et al. (2005), p. 3.3-5.</ref> Hydrogen fuelling stations usually store their fuel on site, often as a cryogenic liquid. They work at up to about 690 bar (10,000 psi), against 207 to 276 bar (3,000 to 4,000 psi) for natural gas, because hydrogen gas has such a low density.<ref name="Riv-21-74">Rivkin (2008b), p. 21-74.</ref> A release of liquid hydrogen boils off rapidly and can condense oxygen out of the air, which adds a further hazard.<ref name="Riv-21-55" /> | ||
Latest revision as of 00:49, 16 November 2026
A fuel cell is an electrochemical device that converts the energy of a reaction between a hydrogen-based fuel and an oxidant, usually oxygen, directly into direct-current electricity and heat, without combustion.[1][2] Like a battery, it has two electrodes separated by an electrolyte. Unlike a battery, it stores its fuel and oxidant outside the cell, so it keeps operating as long as they are supplied.[2] Cells are combined into stacks to obtain usable power and voltage.[1] According to the 20th edition of the Fire Protection Handbook (2008), fuel cells serve stationary power plants and vehicles. A fuel cell vehicle can achieve an energy efficiency of over 50 percent, whereas a petrol engine converts only about 16 percent of the fuel energy into motion.[3]
The fire hazards of fuel cells come mainly from two sources. Several types operate at temperatures high enough to ignite nearby combustible materials, and the fuel is often a flammable gas or liquid.[4] Hydrogen, on which the cell reaction is based, is colourless, odourless and flammable between 4 and 75 percent by volume in air.[5] In the United States, stationary installations of 50 kW or more are covered by NFPA 853, Standard for the Installation of Stationary Fuel Cell Power Systems, first developed in 2000.[4]
Principle of operation
In the proton-conducting design shown in the handbook, hydrogen passes over the anode and splits into protons and electrons. The electrons flow through an external circuit, while protons cross the electrolyte. At the cathode, they combine with oxygen to form water and heat.[2][6] Because the fuel is oxidised electrochemically rather than burned, fuel cells are not constrained by the efficiency limits that apply to engines.[1] This sets them apart from a stationary combustion engine, in which combustion generates the energy.[7]
The most efficient fuel cells use hydrogen and oxygen directly. In conventional fuel cells, a carbon-rich fuel is first reformed into hydrogen. In many designs this happens inside the cell, at very high temperatures of 750 to 900 °C (1,382 to 1,652 °F).[2] A stationary fuel cell power system therefore contains more than the cell stack. NFPA 853 describes a fuel-processing system, an oxidant-processing system, the fuel cell module, thermal management, power conditioning, water treatment, ventilation and automatic controls. Besides electrical power, the system delivers usable heat, waste heat, condensate and exhaust gases.[8]
The principle is old. In 1839 the British scientist William Robert Grove found that hydrogen and oxygen could be combined to produce water and an electric current.[6] A design developed by Francis Bacon's team in the late 1950s powered the Apollo and Skylab programmes, and fuel cells also supplied power on board the space shuttle.[6] Industrial use long remained limited, because the technology is demanding and cheaper alternatives dominated the market.[2]
Types of fuel cell
Fuel cells are named after their electrolyte, and the types operate at different temperatures and supply different amounts of heat.[4] The handbook chapter on stationary engines and fuel cells describes four common types. Their operating temperatures range from ambient to about 1,000 °C, which matters for the clearance to combustible materials.[4]
| Type | Electrolyte | Operating temperature | Notes |
|---|---|---|---|
| Phosphoric acid | phosphoric acid | about 200 °C (393 °F) | oldest and most readily available commercial type; reforms methane to a hydrogen-rich gas |
| Solid oxide | typically zirconia | about 1,000 °C (1,832 °F) | runs on hydrogen, methane or carbon monoxide; waste heat suits cogeneration |
| Polymer electrolyte | layer of solid polymer that transmits protons | about 154 °C (309 °F) | used mainly for mobile applications |
| Alkaline | potassium or lithium hydroxide solution | ambient | best developed type, used in spacecraft |
The handbook chapter on fuel cell vehicles notes that almost all prototype fuel cell cars and buses use proton exchange membrane (PEM) cells, the polymer electrolyte type.[6] Each PEM cell is a thin wafer with a catalyst-coated membrane between conducting graphite or metal plates. Hydrogen is fed to one side and air to the other, and protons cross the membrane to combine with oxygen and electrons into water.[6] Stacks of 50 to 150 kW powered prototype cars, minivans, sport utility vehicles and transit buses in 2008.[6]
Fire and explosion hazards
The temperature of the cell is the first hazard. Several types operate hot enough to ignite combustible materials nearby, so the distance to combustible walls and ceilings is one of the factors in the choice of location.[4] The second hazard is the fuel. Fuel cells have been designed for natural gas, compressed natural gas (CNG), liquefied petroleum gas, biogas and hydrogen, and for liquid fuels such as diesel, JP-4, JP-5, ethanol, methanol and naphtha.[5] Fuel cells typically need on-site fuel storage for reliability, so the hazards of storing these fuels come with the installation.[5] The handbook chapter on emergency and standby power supplies refers to the fuel cell chapter for these safeguards.[9]
The use of hydrogen as a fuel presents special concerns, the subject of hydrogen safety.[5] The flammability limits of a gas are the limits of composition over which a self-sustaining flame can propagate.[10] For hydrogen in air, the SFPE Handbook lists limits of 4.0 and 75 percent by volume, against 5.0 and 15.0 percent for methane, the main component of natural gas.[11] The maximum burning velocity of hydrogen–air mixtures is 320 cm/s, compared with 41 cm/s for propane–air.[10] The deflagration index KG of hydrogen is 550 bar·m/s, ten times the 55 bar·m/s of methane.[12]
The US Nuclear Regulatory Commission's fire dynamics tools report adds that hydrogen needs only a very weak spark of about 10−4 J to ignite. It burns with a nonluminous flame that is often invisible in daylight.[13][14] Its lower limit depends on the direction of flame propagation: 4.1 percent upwards, 6.0 percent horizontally and 9.0 percent downwards.[13]
The handbook’s stationary-fuel-cell chapter rounds hydrogen’s vapour density relative to air to 0.1, while its vehicle-fuel chapter gives 0.07. Both describe rapid dispersal after an outdoor release.[5][15] Hydrogen is normally not odorised, because odorants would contaminate the fuel cell catalysts.[16] When hydrogen is the fuel, the handbook recommends vapour detection devices.[5]
Tests on lean mixtures show that the 4 percent limit is not the whole story. In deflagration tests, the fraction of hydrogen burned rose from zero at 4 percent to complete combustion at about 8 percent.[12] The lower flammability limit (LFL) is measured in a uniform, quiescent mixture, and tests cited in the fuel cell vehicle chapter found that concentrations above 8 percent are typically required to ignite a dispersing discharge.[17] A mixture is potentially flammable only when it contains more than 4 percent hydrogen and more than 5 percent oxygen. A discharge diluted with inert gas to 5 percent hydrogen therefore stays nonflammable as it mixes with air.[17]
Installation of stationary fuel cells
Local building codes gave limited information on fuel cell installations in 2008, and NFPA 853 sets minimum requirements for power plants rated 50 kW or more.[4] A fuel cell should stand on a firm foundation above the base flood elevation. It should be anchored and protected against rain, snow, ice, freezing, wind, earthquakes and lightning.[4] It should be protected against access by unauthorised persons while keeping fire department access, and it should not affect the required exits.[4] Fuel cells should be located outside hazardous atmospheres as defined by the NEC, unless listed for them, and away from combustible materials, hazardous chemicals and high-piled stock.[4]
Indoor installations outside industrial areas belong in a room separated from the rest of the building by construction approved by the authority having jurisdiction.[5] On a roof, the roofing below the unit and within 0.3 m (1 ft) of it should be noncombustible or have a Class A rating. Outdoor units must be designed for that use, and their exhausts should not be directed onto walkways.[5] Liquid fuel storage needs level alarms, a high-level automatic shutoff for tanks filled by pumps, and diking or other spill containment.[5]
Ventilation and gas detection are the main safeguards indoors. The room should be kept at negative or neutral pressure, with its own mechanical ventilation unless natural ventilation is shown to be sufficient.[5] Vents of pressure tanks, regulators and relief valves should discharge to a safe location outside. If exhaust is mechanical, an interlock should shut down the unit when ventilation fails.[5] An exhaust rate of at least 1 cfm per square foot of floor area, and not less than 150 cfm for the room, is typically considered effective:[5]
A combustible gas detection system in the enclosure, the exhaust or the room should alarm at 25 percent of the lower flammable limit (LEL). It should be interlocked to shut off the fuel at 60 percent, using the lowest LEL of the gases present:[5][7]
| Symbol | Description | Unit |
|---|---|---|
| required exhaust air flow from the fuel cell room | m³/min | |
| q | exhaust rate per unit floor area, 1 cfm/ft² = 0.305 m³/(min·m²) | m³/(min·m²) |
| A | floor area of the room | m² |
| minimum exhaust for the room, 150 cfm = 4.25 m³/min | m³/min | |
| Calarm, Cshut | gas concentrations for alarm and for fuel shutoff | vol % |
| LFLmin | lowest lower flammability limit of the gases present | vol % |
The handbook prints the minimum as 45 m³/min, but 150 cfm converts to 4.25 m³/min. As a worked example, the two exhaust criteria are equal when 0.305 A = 4.25, that is for a floor area of 13.9 m² (150 ft²). Smaller rooms need the fixed minimum of 4.25 m³/min, while a room of 20 m² needs 0.305 × 20 = 6.1 m³/min. For a unit supplied with natural gas that is reformed into hydrogen, the lowest LFL is that of hydrogen, 4.0 percent.[11] The detectors should then alarm at 0.25 × 4.0 = 1.0 percent and shut off the fuel at 0.60 × 4.0 = 2.4 percent. Methane alone (LFL 5.0 percent) would give 1.25 and 3.0 percent.
The enclosure should also have automatic fire detection that reports to a constantly attended location, and the room an automatic fire suppression system.[7] Indoor liquid fuel pumping should be protected by wet pipe sprinklers to NFPA 13, with an automatic valve that shuts off the fuel when the sprinklers operate.[7] Each installation needs a written emergency plan covering alarms, evacuation, admission of the fire department, the use of fire water on operating equipment and the location of emergency controls.[7]
Fuel cell vehicles
In a fuel cell vehicle, the fuel cell supplies the electric traction motors and typically also the auxiliary systems. A separate auxiliary power unit typically rates 3 to 10 kW.[3] Fuel cell vehicles ranged in 2008 from 12.2 m (40 ft) transit buses to motor scooters and fork-lift trucks. The California Fuel Cell Partnership expected about 300 fuel cell cars and buses in demonstrations in that state by 2007.[3][18] Many use a hybrid layout in which batteries or ultracapacitors store energy recovered by regenerative braking.[3]

Most fuel cell vehicles store compressed hydrogen gas.[3] A typical vehicle needs about 6 kg of hydrogen, and storage pressures were rising from 350 to 700 bar (5,000 to 10,000 psig).[19] With a calorific value of 120 MJ/kg, 6 kg of hydrogen holds about 720 MJ, the energy of about 16 kg of petrol at 44 MJ/kg.[20] Hydrogen fuelling stations usually store their fuel on site, often as a cryogenic liquid. They work at up to about 690 bar (10,000 psi), against 207 to 276 bar (3,000 to 4,000 psi) for natural gas, because hydrogen gas has such a low density.[21] A release of liquid hydrogen boils off rapidly and can condense oxygen out of the air, which adds a further hazard.[15]
In the 2008 vehicle chapter, a design objective was that foreseeable single-point hardware or software failures during normal and anticipated operation should not create an unreasonable safety risk. Designs therefore separate hazards and are fail-safe: electrical disconnects open and fuel shutoffs close when they lose power.[22] Where an automatic shutdown could itself create a hazard while driving, a staged warning and shutdown is used instead.[22] When crash sensors detect a collision, the fuel is shut off and the electrical system disconnected.[6]
The drive system runs at 300 to 600 V. It is isolated from the chassis, so that a high-voltage circuit can be touched at any single point without an electric shock.[23][24] Its cables are coloured orange, and hazardous-voltage compartments carry a black-on-yellow high-voltage symbol.[24][19] After a crash, high-voltage circuits are to be discharged or isolated, and the hydrogen must stay contained.[25] Pressure relief devices release hydrogen in a fire to prevent the container from bursting. The SAE recommended a blue diamond label, similar to that of CNG vehicles, to identify the hydrogen fuel to emergency responders.[26]
The cited SAE approach aims to keep the local mixing region unignitable and the surrounding atmosphere unclassified under NEC Article 500. If this is demonstrated, the chapter says fuel cell vehicles can be used and stored like petrol vehicles without changes to building codes.[26][17] At fuelling stations, relief valves protect the vehicle storage at 1.38 times the nominal working pressure, about 483 bar for a 350 bar system and 966 bar for a 700 bar system.[25] Repair garages built to NFPA 30A are considered adequate as long as no work is done on the hydrogen storage system.[25]
For the vehicles discussed in 2008, the industry was considering a hydrogen quality target of less than 1,000 ppm impurities.[17] Odorising hydrogen, as is done with natural gas, does not suit fuel cells. The odorant either damages the cell components or passes through and is concentrated up to 500 times in the exhaust, where its smell would mask a leak.[27] In liquid hydrogen, odorants separate out as solids, so a leaking gas would not carry them. The fuel cell vehicles discussed in the handbook were designed for odorant-free hydrogen.[27]
Limits and uncertainty
The handbook describes the technology of 2008, when fuel cells were still moving from aerospace into industry and vehicles were largely demonstration models.[7][18] Members of the US Fuel Cell Council, the industry association, contributed to the vehicle chapter.[18] That chapter states that hydrogen is as safe as, if not safer than, conventional fuels, citing a 1997 study for the US Department of Energy and a Norwegian study of 2002.[26] Neither handbook chapter gives fire incident statistics for fuel cells.
The property data also differ between sources. The lower flammability limit of hydrogen is given as 4.0 percent in the SFPE Handbook and as 4.1 percent in the alternative-fuel chapter of the NFPA handbook.[11][28] Its autoignition temperature is given as 400 °C, 500 °C and 566 to 582 °C (1,050 to 1,080 °F) in three documents.[11][13][28] Values measured in quiescent laboratory mixtures do not describe dispersing discharges well, as the vehicle tests show.[17]
Practice in other countries is not covered by these US documents. A 2021 Dutch study of indoor car parks by the Netherlands Institute for Public Safety left hydrogen vehicles out of scope because they were still rare. It noted, however, that their incident response risks can be as complex as those of electric vehicles.[29] The US requirements in this article are those of NFPA 853 and related standards as summarised in the 2008 handbook.
See also
Notes
- ↑ 1.0 1.1 1.2 Biggins (2008), p. 8-105.
- ↑ 2.0 2.1 2.2 2.3 2.4 Biggins (2008), p. 8-108.
- ↑ 3.0 3.1 3.2 3.3 3.4 Scheffler and Collins (2008), p. 21-78.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 Biggins (2008), p. 8-109.
- ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 5.12 Biggins (2008), p. 8-110.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 Scheffler and Collins (2008), p. 21-81.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Biggins (2008), p. 8-111.
- ↑ Sheridan (2008), p. 9-184.
- ↑ Chisholm (2008), p. 10-3.
- ↑ 10.0 10.1 Simmons (2002), p. 1-146.
- ↑ 11.0 11.1 11.2 11.3 Beyler (2002b), p. 2-176.
- ↑ 12.0 12.1 Zalosh (2002), p. 3-407.
- ↑ 13.0 13.1 13.2 Iqbal and Salley (2004), p. 16-2.
- ↑ Iqbal and Salley (2004), p. 16-4.
- ↑ 15.0 15.1 Rivkin (2008b), p. 21-55.
- ↑ Rivkin (2008b), p. 21-60.
- ↑ 17.0 17.1 17.2 17.3 17.4 Scheffler and Collins (2008), p. 21-86.
- ↑ 18.0 18.1 18.2 Scheffler and Collins (2008), p. 21-77.
- ↑ 19.0 19.1 Scheffler and Collins (2008), p. 21-84.
- ↑ National Research Council of Canada et al. (2005), p. 3.3-5.
- ↑ Rivkin (2008b), p. 21-74.
- ↑ 22.0 22.1 Scheffler and Collins (2008), p. 21-80.
- ↑ Scheffler and Collins (2008), p. 21-82.
- ↑ 24.0 24.1 Scheffler and Collins (2008), p. 21-83.
- ↑ 25.0 25.1 25.2 Scheffler and Collins (2008), p. 21-88.
- ↑ 26.0 26.1 26.2 Scheffler and Collins (2008), p. 21-85.
- ↑ 27.0 27.1 Scheffler and Collins (2008), p. 21-87.
- ↑ 28.0 28.1 Rivkin (2008b), p. 21-56.
- ↑ Van der Graaf et al. (2021/2023), p. 19.
References
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
- Chisholm, D., Sr. (2008). Emergency and standby power supplies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-3–10-8). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
- Scheffler, G. W., & Collins, W. P. (2008). Fuel cell vehicles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-77–21-89). National Fire Protection Association.
- Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
- Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
- Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.