The handbook states the heating rule precisely: the heat generated in a conductor is in direct proportion to its resistance and to the square of the current.<ref name="Milatovich-8-127" /> Because of the square, a current 1.5 times the design value produces about 2.25 times the heat, and a doubled current produces four times the heat. In symbols: | The handbook states the heating rule precisely: the heat generated in a conductor is in direct proportion to its resistance and to the square of the current.<ref name="Milatovich-8-127" /> Because of the square, a current 1.5 times the design value produces about 2.25 times the heat, and a doubled current produces four times the heat. In symbols: | ||
[[File:fse-overcurrent-protection-v1.svg|thumb|upright=1.5|alt=Line chart of relative heat generation against current as a multiple of design current, rising as a parabola|Relative heat generation in a conductor of constant resistance as a function of current. Doubling the current gives four times the heat | [[File:fse-overcurrent-protection-v1.svg|thumb|upright=1.5|alt=Line chart of relative heat generation against current as a multiple of design current, rising as a parabola|Relative heat generation in a conductor of constant resistance as a function of current. Doubling the current gives four times the heat.]] | ||
<math display="block">\dot{Q} \propto I^2 R</math> | <math display="block">\dot{Q} \propto I^2 R</math> | ||
| Line 35: | Line 35: | ||
[[File:fse-overcurrent-protection-v4.jpg|thumb|upright=1.5|alt=an Edison-base plug fuse, a Type S plug fuse with its adapter, and a cartridge fuse on a neutral background|Edison-base plug fuse (left), Type S fuse with tamper-resistant adapter (centre) and cartridge fuse (right).]] | [[File:fse-overcurrent-protection-v4.jpg|thumb|upright=1.5|alt=an Edison-base plug fuse, a Type S plug fuse with its adapter, and a cartridge fuse on a neutral background|Edison-base plug fuse (left), Type S fuse with tamper-resistant adapter (centre) and cartridge fuse (right).]] | ||
A circuit breaker opens and closes a circuit by hand and opens it automatically on a predetermined overload, without damage to itself within its rating.<ref name="Iqbal-F-14">IEEE Std 100-1988, as cited in Iqbal and Salley (2004), p. F-14.</ref> Adjustable-trip breakers are used mainly in large installations with qualified staff, while nonadjustable breakers come in a | A circuit breaker opens and closes a circuit by hand and opens it automatically on a predetermined overload, without damage to itself within its rating.<ref name="Iqbal-F-14">IEEE Std 100-1988, as cited in Iqbal and Salley (2004), p. F-14.</ref> Adjustable-trip breakers are used mainly in large installations with qualified staff, while nonadjustable breakers come in a moulded case that makes their rating very hard to change. A moulded-case breaker of the inverse-time thermal-magnetic type has an electromagnetic element that trips quickly on a high fault current and a bimetallic element that gives a time delay.<ref name="Milatovich-8-145-146">Milatovich (2008), pp. 8-145–8-146.</ref> Unless the device is thermally compensated, a high ambient temperature lowers the current at which a breaker or fuse trips.<ref name="Milatovich-8-146">Milatovich (2008), p. 8-146.</ref> | ||
Some devices cover only part of the task. Thermal devices protect against comparatively small overloads but not against short circuits, such as a motor overload relay backed by branch-circuit fuses. The thermal protector in a recessed luminaire opens the circuit temporarily when the fitting becomes too hot.<ref name="Milatovich-8-146" /> Some installations where more than 10,000 A is available on a short circuit use current-limiting devices, which keep the fault current well below what the circuit could otherwise deliver.<ref name="Milatovich-8-146" /> On utility networks, protective relays measure currents and voltages and trip breakers that isolate the faulted section, while fuses serve low-voltage distribution.<ref name="McAllister-638">McAllister et al. (2008), pp. 638–639.</ref> | Some devices cover only part of the task. Thermal devices protect against comparatively small overloads but not against short circuits, such as a motor overload relay backed by branch-circuit fuses. The thermal protector in a recessed luminaire opens the circuit temporarily when the fitting becomes too hot.<ref name="Milatovich-8-146" /> Some installations where more than 10,000 A is available on a short circuit use current-limiting devices, which keep the fault current well below what the circuit could otherwise deliver.<ref name="Milatovich-8-146" /> On utility networks, protective relays measure currents and voltages and trip breakers that isolate the faulted section, while fuses serve low-voltage distribution.<ref name="McAllister-638">McAllister et al. (2008), pp. 638–639.</ref> | ||
| Line 70: | Line 70: | ||
Coordination decides which device opens first. A time-current curve plots the tripping time of a fuse, breaker or relay against the current; the larger the current, the faster the device operates.<ref name="Iqbal-F-66">Iqbal and Salley (2004), p. F-66.</ref> Comparing the curves of devices in series shows whether only the device nearest a fault will open. | Coordination decides which device opens first. A time-current curve plots the tripping time of a fuse, breaker or relay against the current; the larger the current, the faster the device operates.<ref name="Iqbal-F-66">Iqbal and Salley (2004), p. F-66.</ref> Comparing the curves of devices in series shows whether only the device nearest a fault will open. | ||
A single low-impedance short normally trips the lowest upstream device. Without coordination, multiple high-impedance faults can trip a higher-level device and de-energise a whole bus.<ref name="Iqbal-A-6" /> NUREG/CR-6850 notes that, based on past experience, 120 V alternating current (ac) and 125 V direct current (dc) plant circuits are generally more prone to such problems than higher-voltage circuits. The reason is that small | A single low-impedance short normally trips the lowest upstream device. Without coordination, multiple high-impedance faults can trip a higher-level device and de-energise a whole bus.<ref name="Iqbal-A-6" /> NUREG/CR-6850 notes that, based on past experience, 120 V alternating current (ac) and 125 V direct current (dc) plant circuits are generally more prone to such problems than higher-voltage circuits. The reason is that small moulded-case breakers, circuit protectors and fuses have overlapping curves.<ref name="Nowlen-3-18">Nowlen et al. (2005b), p. 3-18.</ref> Emergency generators raise a similar issue: their short-circuit current decays, and if it decays too fast, selective tripping may not be possible.<ref name="Chisholm-10-6">Chisholm (2008), p. 10-6.</ref> | ||
[[File:fse-overcurrent-protection-v2.svg|thumb|upright=1.5|alt=One-line diagram from service to panelboard to three branch circuits, with a fault on one branch and only its breaker open|Overcurrent devices are placed where each conductor receives its supply. With coordination, a fault on a branch circuit opens only the branch device | [[File:fse-overcurrent-protection-v2.svg|thumb|upright=1.5|alt=One-line diagram from service to panelboard to three branch circuits, with a fault on one branch and only its breaker open|Overcurrent devices are placed where each conductor receives its supply. With coordination, a fault on a branch circuit opens only the branch device.]] | ||
== Fire pump circuits == | == Fire pump circuits == | ||
| Line 77: | Line 77: | ||
The [[fire pump controller]] contains no motor overload relays, so its own circuit breaker gives the only overload, overcurrent and short-circuit protection for controller, motor and wiring.<ref name="NasbyKovacik-15-115" /> That breaker is rated at 115 % or more of the motor full-load current. Its trip curve is fixed by two points: no trip at 300 % of full-load current, and a trip within 8 to 20 seconds at 600 %.<ref name="NasbyKovacik-15-134">Nasby and Kovacik (2008), p. 15-134.</ref> For the 124 A motor of the worked example, it would hold 372 A indefinitely and open within 8–20 s at about 744 A. Ground-fault protection is prohibited, although ground-fault monitoring is allowed and monitoring of motor current for overload is recommended.<ref name="NasbyKovacik-15-116">Nasby and Kovacik (2008), p. 15-116.</ref> | The [[fire pump controller]] contains no motor overload relays, so its own circuit breaker gives the only overload, overcurrent and short-circuit protection for controller, motor and wiring.<ref name="NasbyKovacik-15-115" /> That breaker is rated at 115 % or more of the motor full-load current. Its trip curve is fixed by two points: no trip at 300 % of full-load current, and a trip within 8 to 20 seconds at 600 %.<ref name="NasbyKovacik-15-134">Nasby and Kovacik (2008), p. 15-134.</ref> For the 124 A motor of the worked example, it would hold 372 A indefinitely and open within 8–20 s at about 744 A. Ground-fault protection is prohibited, although ground-fault monitoring is allowed and monitoring of motor current for overload is recommended.<ref name="NasbyKovacik-15-116">Nasby and Kovacik (2008), p. 15-116.</ref> | ||
[[File:fse-overcurrent-protection-v3.svg|thumb|upright=1.5|alt=Log chart of trip time against current with a no-trip region below 300 percent and a trip window of 8 to 20 seconds at 600 percent|Trip requirements of a fire pump controller breaker: no trip up to 300 % of full-load current and a trip within 8–20 s at 600 % | [[File:fse-overcurrent-protection-v3.svg|thumb|upright=1.5|alt=Log chart of trip time against current with a no-trip region below 300 percent and a trip window of 8 to 20 seconds at 600 percent|Trip requirements of a fire pump controller breaker: no trip up to 300 % of full-load current and a trip within 8–20 s at 600 %.]] | ||
Practice differs between regions. The handbook compares North American equipment built to NFPA 20 with the equipment used in most of Europe under the rules of the Loss Prevention Council (LPC).<ref name="NasbyKovacik-15-106" /> Both prohibit motor overload relays, but they differ in device type and settings. | Practice differs between regions. The handbook compares North American equipment built to NFPA 20 with the equipment used in most of Europe under the rules of the Loss Prevention Council (LPC).<ref name="NasbyKovacik-15-106" /> Both prohibit motor overload relays, but they differ in device type and settings. | ||
Latest revision as of 00:45, 16 November 2026
Overcurrent protection is the use of devices, chiefly fuses and circuit breakers, that open an electrical circuit when the current rises above the value that its conductors or equipment can carry safely.[1][2] Overcurrent can result from an overload, a short circuit or a ground fault;[3] because conductor heating grows with the square of the current, it deteriorates the insulation and may ignite combustibles nearby.[4][5] The correct conductor size, suitable insulation and correctly sized protection together reduce the risk that wiring becomes an ignition source.[5] In the United States the rules are those of NFPA 70, the National Electrical Code (NEC), and the Fire Protection Handbook (2008) states that no feature of an installation deserves more careful attention.[6][1] The devices have limits: they miss low, erratic arcing currents, do not protect extension cords against overload, and are defeated by oversized fuses or pennies in place of fuses.[7][8][9] Electric fire pump circuits are a deliberate exception, protected so loosely that the motor is sacrificed rather than the water supply interrupted.[10]
Definitions and kinds of overcurrent
The glossary of NUREG-1805, quoting IEEE Std 100-1988, defines overcurrent as any current in excess of the rated current of equipment or the rated ampacity of a conductor.[2] Ampacity is the maximum current a conductor can carry without overheating.[4][5] The same glossary defines overcurrent protection as protection that operates when the current exceeds a predetermined value. An overload is an overcurrent that is not large enough to be called a short circuit.[2] The handbook chapter on fire pump controllers uses the same definition and adds that a locked rotor, a motor loaded so heavily that its shaft cannot turn, is also an overload.[3]
A short circuit, also simply called a fault, is usually a high and rapid flow of current that conventional protective devices detect quickly.[7] A ground fault is current that flows from a live conductor to earthed metal. Grounding the exposed metal parts gives this current a low-resistance path back to the source, so that it is large enough to operate the fuse or breaker quickly.[11] A low-impedance short often trips the fuses or breakers, while a high-impedance fault may let power pass from one conductor to another or to ground.[12] An arc fault is different again: an unintentional discharge with a low and erratic current that can ignite combustibles, against which standard breakers give no protection.[7]
How overcurrent leads to fire
NUREG-1805 explains electricity with a water analogy based on NFPA 921. Voltage corresponds to water pressure, current to the flow rate, resistance to pipe friction, and conductor size to pipe diameter.[13] Whenever current flows through a conductor, heat is generated, and the amount depends on the resistance and on the current. A larger conductor has less resistance and can carry more current. Wire sizes are given as American Wire Gauge (AWG) numbers, where a larger number means a thinner conductor.[13]
The handbook states the heating rule precisely: the heat generated in a conductor is in direct proportion to its resistance and to the square of the current.[4] Because of the square, a current 1.5 times the design value produces about 2.25 times the heat, and a doubled current produces four times the heat. In symbols:
| Symbol | Description | Unit |
|---|---|---|
| Rate of heat generation in the conductor | W | |
| Current through the conductor | A | |
| Electrical resistance of the conductor | Ω |
Under design conditions this heating is almost never a fire hazard, because the NEC limits the current to the ampacity of the conductor.[4] Ampacity depends on the conductor size, the ambient temperature, the type of insulation and the way the conductor is installed, for example in a raceway, a cable, the earth or free air. When the current exceeds that value, the heat deteriorates the insulation and may ignite combustibles in contact with or close to the conductor.[5]
Equipment needs protection for a second reason. An electric arc can melt the metal of the conductor, and embers from burning material and splatters of hot metal can fall on combustibles and ignite them.[4] Overcurrent protection limits the effects of a fault inside equipment and so reduces the arcing and the ejection of hot metal.[1] Arcing and overheating are the two basic causes of electrical ignition that all electrical standards try to prevent.[14]
Protective devices
Fuses and circuit breakers are the most common devices for feeders, branch circuits and equipment. Overcurrent and undervoltage relays serve high-voltage, high-current systems, and thermal motor overload devices are not counted as overcurrent protection.[1] A fuse opens when a current-sensitive element melts during a specified overcurrent.[15] Cartridge fuses come in time-delay and non-time-delay types, and as one-time or renewable-link fuses. Renewable links can be doubled or tripled, which defeats their purpose, and can be left with loose connections after replacement.[1]
Plug fuses exist in two basic types. An Edison-base fuseholder accepts an Edison-base fuse of any size up to 30 A, so it does not stop a fuse that is too large for the circuit. Under the 2005 NEC, as summarised in the handbook, Edison-base fuses are allowed only as replacements in existing installations without evidence of tampering. Type S fuses fit adapters that cannot be removed without damaging the fuseholder and that block higher-rated fuses and pennies. Time-delay plug fuses tolerate motor starting surges, so a smaller fuse can be used, yet they open a short circuit as fast as or faster than a non-time-delay fuse.[1]

A circuit breaker opens and closes a circuit by hand and opens it automatically on a predetermined overload, without damage to itself within its rating.[16] Adjustable-trip breakers are used mainly in large installations with qualified staff, while nonadjustable breakers come in a moulded case that makes their rating very hard to change. A moulded-case breaker of the inverse-time thermal-magnetic type has an electromagnetic element that trips quickly on a high fault current and a bimetallic element that gives a time delay.[17] Unless the device is thermally compensated, a high ambient temperature lowers the current at which a breaker or fuse trips.[18]
Some devices cover only part of the task. Thermal devices protect against comparatively small overloads but not against short circuits, such as a motor overload relay backed by branch-circuit fuses. The thermal protector in a recessed luminaire opens the circuit temporarily when the fitting becomes too hot.[18] Some installations where more than 10,000 A is available on a short circuit use current-limiting devices, which keep the fault current well below what the circuit could otherwise deliver.[18] On utility networks, protective relays measure currents and voltages and trip breakers that isolate the faulted section, while fuses serve low-voltage distribution.[19]
Sizing, worked example and coordination
The 2005 NEC, as summarised in the handbook, requires overcurrent devices to be rated or set according to the conductor ampacity tables. A device is placed in each ungrounded conductor of every circuit and feeder, where that conductor receives its supply.[1] A breaker or fuse operates only when the current exceeds its rating.[17] The tables apply to a stated ambient temperature, and a correction factor is used in warmer or cooler spaces.[20] The check is that the corrected ampacity is at least the design current:
For conductors supplying a fire pump motor, and for loads running 3 hours or more such as store lighting, the design current is 125 % of the normal current:[21][22][23]
| Symbol | Description | Unit |
|---|---|---|
| Tabulated allowable ampacity at 30 °C ambient | A | |
| Ambient temperature correction factor from the same table | – | |
| Corrected allowable ampacity | A | |
| Design current that the conductor must carry | A | |
| Full-load current of the motor or normal current of a continuous load | A |
The values used here come from Table 8.13.1 of the handbook, which reproduces the 2005 NEC. That table covers insulated conductors rated 0–2000 V, with no more than three current-carrying conductors in a raceway, cable or the earth, at 30 °C ambient.[20] Other tables apply to conductors in free air or with higher temperature ratings.[5] The 2005 NEC also limits the loads on a 15 A or 20 A branch circuit: one cord-and-plug appliance may not exceed 80 % of the circuit rating. The total rating of fixed appliances may not exceed 50 % when lighting units or other appliances are also supplied.[24]
Worked example. The handbook sizes the supply of a 75 kW (100 hp), 460 V three-phase induction motor driving a fire pump, with a full-load current of 124 A.[21] The conductors must carry 1.25 × 124 A = 155 A. In the 75 °C copper column, a 1/0 AWG conductor carries 150 A, which is too little, so 2/0 AWG at 175 A is the minimum at 30 °C.[20] If the run passed through a space at 36–40 °C, the factor 0.88 would cut the 2/0 rating to 154 A, just below 155 A. The next size, 3/0 AWG at 200 A, gives 176 A after correction and would be chosen.
The supply fuses or breakers must carry the locked-rotor current of 725 A, which leads to the next standard rating of 800 A.[21] Where the voltage drop at the controller during starting exceeds 15 %, still larger conductors are needed, so the thermal check is only the first step.[21]
Coordination decides which device opens first. A time-current curve plots the tripping time of a fuse, breaker or relay against the current; the larger the current, the faster the device operates.[25] Comparing the curves of devices in series shows whether only the device nearest a fault will open.
A single low-impedance short normally trips the lowest upstream device. Without coordination, multiple high-impedance faults can trip a higher-level device and de-energise a whole bus.[12] NUREG/CR-6850 notes that, based on past experience, 120 V alternating current (ac) and 125 V direct current (dc) plant circuits are generally more prone to such problems than higher-voltage circuits. The reason is that small moulded-case breakers, circuit protectors and fuses have overlapping curves.[26] Emergency generators raise a similar issue: their short-circuit current decays, and if it decays too fast, selective tripping may not be possible.[27]
Fire pump circuits
Electric fire pumps reverse the usual priorities. The 2007 edition of NFPA 20, as summarised in the handbook, sets higher limits on overcurrent devices than NFPA 70, so that the motor can free an obstructed or seized pump and keep pumping. Electrical safety and preservation of equipment are secondary, and the pump equipment is treated as sacrificial.[10] NFPA 20 allows a supervised connection with a disconnecting means ahead of the controller. Its overcurrent device must carry indefinitely the sum of the locked-rotor currents of the fire pump and pressure maintenance pump motors and the full-load current of the accessory equipment. The handbook notes that this raises the potential for equipment failure and for an additional ignition source.[28]
The fire pump controller contains no motor overload relays, so its own circuit breaker gives the only overload, overcurrent and short-circuit protection for controller, motor and wiring.[23] That breaker is rated at 115 % or more of the motor full-load current. Its trip curve is fixed by two points: no trip at 300 % of full-load current, and a trip within 8 to 20 seconds at 600 %.[29] For the 124 A motor of the worked example, it would hold 372 A indefinitely and open within 8–20 s at about 744 A. Ground-fault protection is prohibited, although ground-fault monitoring is allowed and monitoring of motor current for overload is recommended.[30]
Practice differs between regions. The handbook compares North American equipment built to NFPA 20 with the equipment used in most of Europe under the rules of the Loss Prevention Council (LPC).[10] Both prohibit motor overload relays, but they differ in device type and settings.
| Attribute | LPC style | NFPA style |
|---|---|---|
| Overcurrent protective device | Fuses | Circuit breaker |
| Overcurrent setting | 200 %, for 5 h minimum | 300 % or less, no trip |
| Locked-rotor protection timing | 75 % of motor burn-out time | 8 to 20 s |
| Overload relays allowed | No | No |
Fire experience and failure modes
In the United States, structure fires coded as caused by electrical failure averaged 81,670 a year in 1994–1998. Of these, 2,520 a year involved a power switch or an overcurrent protection device, against 15,030 for fixed wiring.[32] Special studies by electrical inspectors and the U.S. Consumer Product Safety Commission suggest that these fires involve circuit breakers more often than fuses, both overall and relative to their use. This is notable because fuses are found mainly in much older homes and are more open to tampering.[33] In U.S. electronic equipment rooms outside homes, overcurrent devices were involved in 96 of 944 fires a year in 1994–1998.[34]
Electrical distribution and lighting equipment caused an estimated 32,400 U.S. home fires a year in 1999–2002, or 9 % of the total, with 220 civilian deaths. It ranked second for property damage, at 13 %, because many such fires are in concealed spaces and hard to attack.[35] The handbook names the widespread use and enforcement of the NEC as probably the main reason for this modest share. One study found that 61 % of home electrical fires involved code violations, particularly of the general workmanship provisions.[35]
Human error defeats much of the protection. Overfusing, the use of a fuse with too high an ampere rating, is a typical installation error.[36] In converted board and care homes, fuses may be the wrong size for the circuits they protect.[37] In older residence halls, breakers that trip continually may lead occupants to run extension cords from elsewhere, and power strips with their own breakers do not necessarily protect the circuit.[38] The handbook also warns that devices may fail, and that under some conditions overloaded or partially grounded wiring, for example after flooding, may ignite combustibles without blowing a fuse. It names an improperly sized fuse or circuit breaker as the most common example of failed protection.[39]
Nuclear power plant experience shows the same pattern at higher energies. Two cable fires at San Onofre Unit 1 in 1968 were most probably caused by stressed, undersized cables combined with individual fuses on each phase of three-phase circuits. That arrangement let fault current feed back through the unfaulted phases and worsened the overcurrent.[40]
At San Onofre Unit 3 in 2001, one phase of a 4160 V breaker about 25 years old failed to close completely during a bus transfer. The resulting fire burned for about 3 hours. NUREG-1805 concludes that a stuck or slow breaker on such a supply leaves enough energy to cause an explosion within a few cycles.[41] In nearly all of the 11 high-energy arcing faults at U.S. nuclear power plants in 1979–2001 reviewed in NUREG/CR-6850, the fault began in the feed breaker cubicle, where most of the energy resides. Similar failures can occur in large oil-filled transformers, a hazard treated under transformer fire.[42]
Limits and complementary protection
Fuses and breakers protect the fixed wiring. They let an overload persist for a time set by their inverse-time curve, and they give no overload protection to extension cords.[8] They also miss arcing faults, whose low and erratic current can continue undetected in damaged cords or cables. Arc-fault circuit interrupters fill this gap by recognising the electrical pattern of arcing; the handbook (2008) describes them as available for 125 V branch circuits of 15 A or 20 A.[7] In 1998, fixed wiring in U.S. homes accounted for 13,000 reported structure fires, 96 civilian deaths and 293 civilian injuries.[7]
Protection of people is a separate task. Lighting and receptacle circuits are usually rated 15 A or 20 A, while under certain conditions as little as 20 mA can kill a healthy adult.[18] Ground-fault circuit interrupters therefore trip when line-to-ground current exceeds 5 mA, within about 25 ms once it reaches 6 mA.[43] Ground-fault protection of equipment was first required by the 1971 NEC on services of 1000 A or more at 480Y/277 V, after many burndowns. Under the 2005 NEC its sensors may be set no higher than 1200 A. Faults greater than 3000 A must last no more than 1 second, because arc damage is proportional to burning time.[21]
Engineers rely on these devices in risk analysis. The fire probabilistic risk assessment method of NUREG/CR-6850, written for U.S. nuclear power plants, assumes that properly sized and coordinated devices operate as designed and so prevent secondary fires.[44] Where a device cannot interrupt the available fault current, or is too large to protect a cable, faults on other cables could start a secondary fire in a shared raceway or panel.[45] The acceptance criterion should be that secondary fire, not simply exceeding the continuous or overload rating of the cable, which reflects long-term degradation.[26] In Australia, the Fire Safety Verification Method handbook (2020) takes unreported ignition in a cavity, caused by maintenance work or an electrical fault, as a typical concealed space scenario.[46] After a fire, investigators look for arcs on circuits that were energised, because their locations help to show how the fire progressed.[47]
The same principle applies outside buildings. On U.S. boats, the handbook states that dc conductors except cranking motor leads need overcurrent protection at the source, generally within 178 mm (7 in.). Many marine dc motors lack internal thermal protectors, so branch breakers or fuses must also protect pumps and blowers against a locked rotor.[48] In fuel cell vehicles, the high-voltage system should likewise have fusing or overcurrent protection, so that excessive current from shorts or malfunctions cannot cause overheating and fires.[49]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Milatovich (2008), p. 8-145.
- ↑ 2.0 2.1 2.2 IEEE Std 100-1988, as cited in Iqbal and Salley (2004), p. F-43.
- ↑ 3.0 3.1 Nasby and Kovacik (2008), p. 15-111.
- ↑ 4.0 4.1 4.2 4.3 4.4 Milatovich (2008), p. 8-127.
- ↑ 5.0 5.1 5.2 5.3 5.4 Milatovich (2008), p. 8-131.
- ↑ Milatovich (2008), p. 8-137.
- ↑ 7.0 7.1 7.2 7.3 7.4 Milatovich (2008), p. 8-148.
- ↑ 8.0 8.1 Milatovich (2008), p. 8-149.
- ↑ Lathrop (2008b), p. 20-58.
- ↑ 10.0 10.1 10.2 Nasby and Kovacik (2008), p. 15-106.
- ↑ Milatovich (2008), p. 8-142.
- ↑ 12.0 12.1 Iqbal and Salley (2004), p. A-6.
- ↑ 13.0 13.1 Iqbal and Salley (2004), pp. B-11–B-12.
- ↑ Milatovich (2008), p. 8-134.
- ↑ NEMA Std FU-1 (1986), as cited in Iqbal and Salley (2004), p. F-33.
- ↑ IEEE Std 100-1988, as cited in Iqbal and Salley (2004), p. F-14.
- ↑ 17.0 17.1 Milatovich (2008), pp. 8-145–8-146.
- ↑ 18.0 18.1 18.2 18.3 Milatovich (2008), p. 8-146.
- ↑ McAllister et al. (2008), pp. 638–639.
- ↑ 20.0 20.1 20.2 Milatovich (2008), p. 8-128.
- ↑ 21.0 21.1 21.2 21.3 21.4 Milatovich (2008), p. 8-140.
- ↑ Milatovich (2008), pp. 8-151–8-152.
- ↑ 23.0 23.1 Nasby and Kovacik (2008), p. 15-115.
- ↑ Milatovich (2008), pp. 8-150–8-151.
- ↑ Iqbal and Salley (2004), p. F-66.
- ↑ 26.0 26.1 Nowlen et al. (2005b), p. 3-18.
- ↑ Chisholm (2008), p. 10-6.
- ↑ Nasby and Kovacik (2008), pp. 15-111–15-112.
- ↑ Nasby and Kovacik (2008), p. 15-134.
- ↑ Nasby and Kovacik (2008), p. 15-116.
- ↑ Nasby and Kovacik (2008), p. 15-107.
- ↑ Milatovich (2008), p. 8-136.
- ↑ Milatovich (2008), pp. 8-136–8-137.
- ↑ Rawson (2008), p. 8-60.
- ↑ 35.0 35.1 Hall and Cote (2008), p. 3-15.
- ↑ Milatovich (2008), p. 8-135.
- ↑ Jose (2008), p. 20-18.
- ↑ Berkol et al. (2008), p. 20-33.
- ↑ McDaniel (2008), p. 20-184.
- ↑ Iqbal and Salley (2004), p. H-7.
- ↑ Iqbal and Salley (2004), pp. H-26–H-27.
- ↑ Nowlen et al. (2005b), pp. M-1–M-2.
- ↑ Milatovich (2008), pp. 8-146–8-147.
- ↑ Nowlen et al. (2005b), p. 3-4.
- ↑ Nowlen et al. (2005b), p. 3-17.
- ↑ Australian Building Codes Board (2020b), p. 77.
- ↑ Custer and Sheppard (2008), p. 3-35.
- ↑ Eberly (2008), p. 21-158.
- ↑ Scheffler and Collins (2008), p. 21-83.
References
- Australian Building Codes Board. (2020b). Handbook: Fire Safety Verification Method (Print version 1.1).
- Berkol, A., Briese, B., & Comeau, E. (2008). Hotels and university housing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-23–20-36). National Fire Protection Association.
- Chisholm, D., Sr. (2008). Emergency and standby power supplies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-3–10-8). National Fire Protection Association.
- Custer, R. L. P., & Sheppard, D. T. (2008). Fire loss investigation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-31–3-41). National Fire Protection Association.
- Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
- Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Jose, P. R. (2008). Board and care facilities. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-15–20-21). National Fire Protection Association.
- Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
- McAllister, T. P., Gann, R. G., Averill, J. D., Gross, J. L., Grosshandler, W. L., Lawson, J. R., McGrattan, K. B., Pitts, W. M., Prasad, K. R., Sadek, F. H., & Nelson, H. E. (2008). Structural fire response and probable collapse sequence of World Trade Center Building 7 (NIST NCSTAR 1-9, Vols. 1–2). National Institute of Standards and Technology.
- McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
- Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
- Nasby, J. S., & Kovacik, J. R. (2008). Fire pump controllers and power supply arrangements for motor-driven fire pumps. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 15-105–15-145). National Fire Protection Association.
- Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
- Rawson, B. P. (2008). Protection of electronic equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-57–8-64). National Fire Protection Association.
- Scheffler, G. W., & Collins, W. P. (2008). Fuel cell vehicles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-77–21-89). National Fire Protection Association.