'''Seismic bracing''' is the system of restraints that transfers earthquake-induced forces from fire protection piping to suitable structural supports. <ref name="F_4-84_4-85">Fleming (2002), ch. 4-3, pp. 4-84–4-85.</ref><ref name="H_16_4_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-65–16-67.</ref> It works with flexibility and clearance provisions that accommodate relative movement. Brace placement, assigned load, component capacity and building attachment form a continuous design problem. Preserving the water route also requires attention to sources and connections beyond the braced pipe segment. <ref name="H_16_4_16-55_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-55,16-65–16-67.</ref>
'''Seismic bracing''' is the system of restraints that transfers earthquake-induced forces from fire protection piping to suitable structural supports. <ref name="F_4-84_4-85">Fleming (2002), ch. 4-3, pp. 4-84–4-85.</ref><ref name="H_16_4_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-65–16-67.</ref> It works with flexibility and clearance provisions that accommodate relative movement. Brace placement, assigned load, component capacity and building attachment form a continuous design problem. Preserving the water route also requires attention to sources and connections beyond the braced pipe segment. <ref name="H_16_4_16-55_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-55,16-65–16-67.</ref>


The structural assessment follows forces through every component to the supporting building. The hydraulic assessment follows water through the corresponding distribution route. Both functions must remain intact for the installed system to deliver its intended protection. Changes in pipe material, geometry, supports or nearby construction can therefore require more than a check of the nominal water pressure. <ref name="H_16_4_16-55_16-58_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-55,16-58,16-65–16-67.</ref><ref name="F_4-84_4-85" /> Connections can govern capacity before the brace member does. <ref name="H_16_4_16-67">Cote (2008), ch. 16.4, pp. 16-67.</ref>
The structural assessment follows forces through every component to the supporting building. The hydraulic assessment follows water through the corresponding distribution route. Both functions must remain intact for the installed system to deliver its intended protection. Changes in pipe material, geometry, supports or nearby construction can therefore require more than a check of the nominal water pressure. <ref name="H_16_4_16-55_16-58_16-65_16-67">Cote (2008), ch. 16.4, pp. 16-55,16-58,16-65–16-67.</ref><ref name="F_4-84_4-85" /> Connections can govern capacity before the brace member does. <ref name="H_16_4_16-67">Cote (2008), ch. 16.4, p. 16-67.</ref>


== Restraint, flexibility and post-earthquake service ==
== Restraint, flexibility and post-earthquake service ==
Line 39: Line 39:
[[File:fse-seismic-bracing-v3.svg|thumb|upright=1.5|alt=The support load path. Mechanism and application limits are distinguished.|The support load path. Schematic explanation; dimensions are not installation instructions.]]
[[File:fse-seismic-bracing-v3.svg|thumb|upright=1.5|alt=The support load path. Mechanism and application limits are distinguished.|The support load path. Schematic explanation; dimensions are not installation instructions.]]


A trapeze hanger introduces a spanning member between available support points; it is useful where the pipe route does not coincide with the building's structural members. The member carries bending as well as transferring load to its end connections. Its span, section and load position therefore influence its behaviour. <ref name="H_16_4_16-58">Cote (2008), ch. 16.4, pp. 16-58.</ref><ref name="F_4-84">Fleming (2002), ch. 4-3, pp. 4-84.</ref>
A trapeze hanger introduces a spanning member between available support points; it is useful where the pipe route does not coincide with the building's structural members. The member carries bending as well as transferring load to its end connections. Its span, section and load position therefore influence its behaviour. <ref name="H_16_4_16-58">Cote (2008), ch. 16.4, p. 16-58.</ref><ref name="F_4-84">Fleming (2002), ch. 4-3, p. 4-84.</ref>


The historical NFPA 13 provisions discussed by the handbook distinguish hanger requirements from the capacity required of the supporting structure. This prevents a single component factor from being applied indiscriminately to every part of the assembly. The source describes trapezes as an extension of the building support arrangement. The engineering assessment follows the actual load path and the relevant design basis. <ref name="H_16_4_16-58" />
The historical NFPA 13 provisions discussed by the handbook distinguish hanger requirements from the capacity required of the supporting structure. This prevents a single component factor from being applied indiscriminately to every part of the assembly. The source describes trapezes as an extension of the building support arrangement. The engineering assessment follows the actual load path and the relevant design basis. <ref name="H_16_4_16-58" />
Line 59: Line 59:
The hydraulic route and the structural route intersect but answer different questions; pipe diameter and material influence both water resistance and supported weight. A hydraulically adequate pipe still needs appropriate support and attachment. Conversely, a strong support system does not establish that the internal bore or available pressure meets the discharge demand. <ref name="H_16_3_16-41_16-42">Cote (2008), ch. 16.3, pp. 16-41–16-42.</ref><ref name="H_16_4_16-55_16-58" /><ref name="F_4-75_4-85">Fleming (2002), ch. 4-3, pp. 4-75–4-85.</ref>
The hydraulic route and the structural route intersect but answer different questions; pipe diameter and material influence both water resistance and supported weight. A hydraulically adequate pipe still needs appropriate support and attachment. Conversely, a strong support system does not establish that the internal bore or available pressure meets the discharge demand. <ref name="H_16_3_16-41_16-42">Cote (2008), ch. 16.3, pp. 16-41–16-42.</ref><ref name="H_16_4_16-55_16-58" /><ref name="F_4-75_4-85">Fleming (2002), ch. 4-3, pp. 4-75–4-85.</ref>


Changes around the pipework can compromise the intended support; the handbook's inspection discussion includes loose hangers and inappropriate additional loads applied to sprinkler piping. Attachment to a different structural member also changes the load path. These conditions belong to the installed system assessment, rather than being resolved by an unchanged hydraulic calculation. <ref name="H_16_11_16-210">Cote (2008), ch. 16.11, pp. 16-210.</ref><ref name="I_1_7-8">National Research Council of Canada et al. (2005), pp. 1.7-8.</ref>
Changes around the pipework can compromise the intended support; the handbook's inspection discussion includes loose hangers and inappropriate additional loads applied to sprinkler piping. Attachment to a different structural member also changes the load path. These conditions belong to the installed system assessment, rather than being resolved by an unchanged hydraulic calculation. <ref name="H_16_11_16-210">Cote (2008), ch. 16.11, p. 16-210.</ref><ref name="I_1_7-8">National Research Council of Canada et al. (2005), p. 1.7-8.</ref>


== Availability and common dependencies ==
== Availability and common dependencies ==
Line 102: Line 102:
Inspection, testing and maintenance provide different forms of evidence; visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation's intended state. <ref name="H_16_11_16-205_16-212">Cote (2008), ch. 16.11, pp. 16-205–16-212.</ref>
Inspection, testing and maintenance provide different forms of evidence; visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation's intended state. <ref name="H_16_11_16-205_16-212">Cote (2008), ch. 16.11, pp. 16-205–16-212.</ref>


The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance; a system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. <ref name="H_16_11_16-205">Cote (2008), ch. 16.11, pp. 16-205.</ref>
The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance; a system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. <ref name="H_16_11_16-205">Cote (2008), ch. 16.11, p. 16-205.</ref>


An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position; neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. <ref name="H_16_3_16-42_16-43">Cote (2008), ch. 16.3, pp. 16-42–16-43.</ref><ref name="H_16_11_16-209_16-210">Cote (2008), ch. 16.11, pp. 16-209–16-210.</ref>
An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position; neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. <ref name="H_16_3_16-42_16-43">Cote (2008), ch. 16.3, pp. 16-42–16-43.</ref><ref name="H_16_11_16-209_16-210">Cote (2008), ch. 16.11, pp. 16-209–16-210.</ref>
Line 119: Line 119:
Temporary measures depend on the unavailable function and the activities taking place; the handbook discusses temporary water arrangements, fire watch and control of hazardous activities among possible responses. These measures have their own limitations and do not automatically reproduce an automatic sprinkler system. Their role must be understood in relation to the actual interruption. <ref name="H_16_11_16-208_16-209_16-221" />
Temporary measures depend on the unavailable function and the activities taking place; the handbook discusses temporary water arrangements, fire watch and control of hazardous activities among possible responses. These measures have their own limitations and do not automatically reproduce an automatic sprinkler system. Their role must be understood in relation to the actual interruption. <ref name="H_16_11_16-208_16-209_16-221" />


Identification prevents a closed valve or disconnected interface from becoming an unnoticed permanent condition; the handbook describes tags and documented isolation arrangements, including equipment that must remain safe during work. The record identifies the responsible person and the component affected. Emergency impairments need this same controlled return to service, even when advance preparation was impossible. <ref name="H_16_11_16-221">Cote (2008), ch. 16.11, pp. 16-221.</ref>
Identification prevents a closed valve or disconnected interface from becoming an unnoticed permanent condition; the handbook describes tags and documented isolation arrangements, including equipment that must remain safe during work. The record identifies the responsible person and the component affected. Emergency impairments need this same controlled return to service, even when advance preparation was impossible. <ref name="H_16_11_16-221">Cote (2008), ch. 16.11, p. 16-221.</ref>


Restoration involves more than declaring that a repair is complete; valves return to their normal operating positions, relevant tests verify the restored functions, and temporarily bypassed alarm interfaces are reconnected. Tags and records are reconciled with the actual installation. Notifications then communicate the restored condition to parties that were relying on the impairment information. <ref name="H_14_4_14-43">Cote (2008), ch. 14.4, pp. 14-43.</ref><ref name="H_16_11_16-208_16-211_16-221">Cote (2008), ch. 16.11, pp. 16-208–16-211,16-221.</ref>
Restoration involves more than declaring that a repair is complete; valves return to their normal operating positions, relevant tests verify the restored functions, and temporarily bypassed alarm interfaces are reconnected. Tags and records are reconciled with the actual installation. Notifications then communicate the restored condition to parties that were relying on the impairment information. <ref name="H_14_4_14-43">Cote (2008), ch. 14.4, p. 14-43.</ref><ref name="H_16_11_16-208_16-211_16-221">Cote (2008), ch. 16.11, pp. 16-208–16-211,16-221.</ref>


The sequence matters because maintenance itself can introduce a hidden loss of protection; a mechanically repaired pipe still lacks water if its supply remains closed. A functioning sprinkler may fail to summon assistance if its signalling path remains disabled after testing. The IFEG's management framework therefore connects physical work, commissioning evidence and the maintained operating state. <ref name="H_14_4_14-43" /><ref name="I_1_7-8" />
The sequence matters because maintenance itself can introduce a hidden loss of protection; a mechanically repaired pipe still lacks water if its supply remains closed. A functioning sprinkler may fail to summon assistance if its signalling path remains disabled after testing. The IFEG's management framework therefore connects physical work, commissioning evidence and the maintained operating state. <ref name="H_14_4_14-43" /><ref name="I_1_7-8" />

Latest revision as of 00:42, 16 November 2026

Seismic bracing is the system of restraints that transfers earthquake-induced forces from fire protection piping to suitable structural supports. [1][2] It works with flexibility and clearance provisions that accommodate relative movement. Brace placement, assigned load, component capacity and building attachment form a continuous design problem. Preserving the water route also requires attention to sources and connections beyond the braced pipe segment. [3]

The structural assessment follows forces through every component to the supporting building. The hydraulic assessment follows water through the corresponding distribution route. Both functions must remain intact for the installed system to deliver its intended protection. Changes in pipe material, geometry, supports or nearby construction can therefore require more than a check of the nominal water pressure. [4][1] Connections can govern capacity before the brace member does. [5]

Restraint, flexibility and post-earthquake service

A sprinkler system may be needed during a fire following earthquake; pipe hangers carry ordinary gravity loads, while seismic restraints address additional movement and inertia. The distinction matters because a vertically supported pipe can still move into another component or overstress a joint. Bracing and movement accommodation therefore form complementary parts of the arrangement. [3][1]

Seismic bracing: functional relationships. Mechanism and application limits are distinguished.
Seismic bracing: functional relationships. Schematic explanation; dimensions are not installation instructions.

The fire water storage tank and its outlet connections can experience movement as well; bracing the distribution pipe does not by itself establish the tank's anchorage or continued availability. Reliability of fire protection systems depends on the complete route remaining usable. A protected pipe segment downstream of an unavailable source cannot deliver its intended flow. [6][7]

The handbook's United States NFPA 13 (2007) account uses seismic coefficients and zones of influence to determine brace loads; it also identifies the limiting role of fittings and fasteners. The brace member alone is therefore not the complete assembly. Its structural attachment must carry the applied load without tying together building parts expected to move differently. [2]

Earthquake movement and restraint

Earthquake protection of piping combines restraint with accommodation of movement; braces limit displacement by transferring inertia forces to suitable structural members. Flexible connections and clearance address relative movement where rigid restraint would create damaging interaction. Treating every part as either completely rigid or completely free misses this combined function. [3][1]

Complete brace assembly. Mechanism and application limits are distinguished.
Complete brace assembly. Schematic explanation; dimensions are not installation instructions.

Lateral bracing resists movement across the pipe direction, while longitudinal bracing resists movement along it; a four-way arrangement addresses both horizontal directions. The supported piping assigned to a brace is described through its zone of influence. That allocation includes the relevant water-filled pipework and associated load allowances in the stated design method. [2]

The handbook expresses the horizontal design force as a coefficient multiplied by the assigned weight; the coefficient represents the seismic design basis, rather than a property of the pipe material. Its value cannot be selected from pipe diameter alone. The resulting force then has to pass through the brace, its fittings, its fastener and the building structure. [2]

Fp=CpWp

Symbol Description Unit
Fp Horizontal design force N
Cp Seismic coefficient for the stated method dimensionless
Wp Assigned piping weight including applicable allowances N

The United States NFPA 13 (2007) table reproduced in the handbook gives a coefficient of 0.52 for its stated mapped-acceleration input of 1.00. A normalised example with an assigned weight of 1.00 kN therefore produces 0.52 kN of horizontal force. This shows the arithmetic, not a site-specific seismic selection. The table's assumptions and the actual building conditions remain separate design inputs. [2]

The weakest component limits the brace assembly; inclination changes the forces carried by the brace and its connections. Slender compression members can buckle, while tension-only cables need arrangements that resist movement in opposing directions. The capacity of the receiving structural member must also be established, so an adequate pipe clamp alone does not complete the load path. [5][1]

Structural support and load transfer

Water-based piping needs a continuous path by which its weight reaches the building structure; the supported load includes the pipe and its contained water. Hangers, attachments and the structural members receiving those attachments all participate in that path. Checking a hanger rod alone cannot establish the capacity of the whole support arrangement. [8][1]

The support load path. Mechanism and application limits are distinguished.
The support load path. Schematic explanation; dimensions are not installation instructions.

A trapeze hanger introduces a spanning member between available support points; it is useful where the pipe route does not coincide with the building's structural members. The member carries bending as well as transferring load to its end connections. Its span, section and load position therefore influence its behaviour. [9][10]

The historical NFPA 13 provisions discussed by the handbook distinguish hanger requirements from the capacity required of the supporting structure. This prevents a single component factor from being applied indiscriminately to every part of the assembly. The source describes trapezes as an extension of the building support arrangement. The engineering assessment follows the actual load path and the relevant design basis. [9]

Fleming gives an equivalent-span method for a single off-centre load on a trapeze. The relation compares the bending effect with a centred load on an equivalent span. [10]

Le=4aba+b

Symbol Description Unit
Le Equivalent centred span m
a,b Distances from the load to the respective supports m

The source illustrates the relation using unequal support distances. If the distances to the end supports are 0.457 m and 2.591 m, the equivalent centred span is approximately 1.55 m. This example illustrates how load position affects bending. It does not establish the capacity of a member, connection or supporting building component. [10]

The hydraulic route and the structural route intersect but answer different questions; pipe diameter and material influence both water resistance and supported weight. A hydraulically adequate pipe still needs appropriate support and attachment. Conversely, a strong support system does not establish that the internal bore or available pressure meets the discharge demand. [11][8][12]

Changes around the pipework can compromise the intended support; the handbook's inspection discussion includes loose hangers and inappropriate additional loads applied to sprinkler piping. Attachment to a different structural member also changes the load path. These conditions belong to the installed system assessment, rather than being resolved by an unchanged hydraulic calculation. [13][14]

Availability and common dependencies

Two components do not necessarily provide two independent supplies; a pair of pumps may share the same tank, intake, electrical route or vulnerable connecting main. A looped network may still depend on one source connection. The relevant question is whether the required water path remains available after the particular failure being considered. [15][7]

The NIST investigation of the World Trade Center's 2001 fire suppression systems provides a specific illustration; its review identified vulnerabilities associated with floor-feed arrangements and with the limits of some hydraulic calculation paths. It also considered the dependence of manually operated equipment on personnel access and action. These findings describe that complex and that investigation; they are not failure probabilities for all buildings. [7]

The case also shows why upstream duplication alone is insufficient; alternative water sources may converge on a single downstream segment. Damage or isolation at that segment can interrupt the route to the affected area despite apparently generous upstream equipment. Conversely, a reserve serving another pressure zone does not automatically become a usable alternative without an available connection. [7]

Automatic and manual supply functions need separate treatment; a fire department connection depends on responding apparatus, water, personnel and access. A stored or pumped automatic supply can begin serving a demand without those same preliminary actions, provided its own operating chain remains intact. Calling both arrangements a water supply does not make their activation times or dependencies equivalent. [16][17]

Duration introduces further common dependencies; refill may rely on the same utility that a reserve is intended to supplement. Fuel and cooling water can constrain a driver even when the pump itself is mechanically sound. Seasonal source variation can affect both the initial reserve and its replenishment. Such dependencies belong in the description of the actual arrangement. [18][19][20]

Availability also changes during maintenance; sectional isolation can limit the area affected by work, while unclear valve identification can enlarge it. The handbook links planned shutdowns to preparation, notification and verified restoration. Records of the normal configuration make these operational controls meaningful rather than relying on an assumed open water path. [21]

Flow, pressure and duration

A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed; these characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. [22][23]

Demand must identify which outlets operate together; sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. [24][25]

The supply location also matters; a pressure measured in a street main is not automatically available at a building riser. Connecting pipework, backflow assemblies and changes in elevation affect the transfer. The assessment follows the supply through these elements to the same reference point used for the calculated demand. [16][26]

Storage introduces a time dimension that a pressure-flow curve alone does not show; usable water is the quantity that the outlet or pump can actually draw while meeting its operating conditions. Water below the effective intake, or reserved for another purpose, cannot simply be counted as fire reserve. Replenishment contributes only through an identified source and a delivery arrangement that remains available. [18][27]

A constant-flow volume calculation multiplies flow by duration. In the following form, flow is in litres per minute and usable volume is in cubic metres. The factor converts litres to cubic metres. [27]

Vu=Qt1000

Symbol Description Unit
Vu Usable water volume m³
Q,t Constant discharge and duration L/min; min

A worked example separates usable water from gross capacity. Using Fleming's example of 530 L/min for 30 minutes gives 15,900 L, or 15.9 m³, of usable water. This arithmetic does not select a design duration or establish the gross tank volume. The example is a historical worked calculation, with tank configuration and unavailable volume assessed separately. [27]

Public supplies can change with domestic use, industrial demand, maintenance and seasonal conditions; tank levels and pump operation can change during a fire as well. The design record therefore needs the conditions represented by the available supply, including relevant adverse conditions. A favourable isolated reading does not establish availability throughout the required incident duration. [22][28]

Inspection and evidence of readiness

Inspection, testing and maintenance provide different forms of evidence; visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation's intended state. [29]

The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance; a system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. [30]

An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position; neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. [31][32]

Deposits on a sprinkler can interfere with heating or mechanical release; corrosion can affect both the operating mechanism and water passage. Inside pipes, scale or foreign material can migrate to smaller fittings and outlets. These mechanisms explain why an apparently pressurised system may still have reduced effective protection. [33]

The purpose of a test determines its interpretation; an alarm test can establish signalling without demonstrating the full water demand. A main-drain comparison can reveal a changed supply condition without reproducing every operating sprinkler. A pump start test exercises starting functions, while a flow test examines delivery capability over selected operating points. [34][35]

The International Fire Engineering Guidelines (IFEG) links commissioning to the performance assumed in a fire engineering evaluation; it also links subsequent management and maintenance to keeping those assumptions valid. This provides a useful framework for reading test records: the observation must answer the performance question being claimed. Successful operation of one component is evidence about that component and the functions actually exercised. [14]

Isolation and restoration of protection

An impairment occurs when some intended fire protection function is unavailable; planned maintenance, an emergency leak and replacement after a fire can all create that condition. The affected area may be wider than the location of the work if an upstream valve serves several systems. Defining the scope of isolation is therefore part of describing the impairment itself. [21]

The handbook describes an impairment coordinator who follows the work from shutdown through restoration; preparation includes identifying the system, the work, the necessary people and equipment, and the parties that need notification. Having materials available before isolation reduces avoidable downtime. Sectional isolation can preserve protection elsewhere where the installed arrangement permits it. [36]

Temporary measures depend on the unavailable function and the activities taking place; the handbook discusses temporary water arrangements, fire watch and control of hazardous activities among possible responses. These measures have their own limitations and do not automatically reproduce an automatic sprinkler system. Their role must be understood in relation to the actual interruption. [21]

Identification prevents a closed valve or disconnected interface from becoming an unnoticed permanent condition; the handbook describes tags and documented isolation arrangements, including equipment that must remain safe during work. The record identifies the responsible person and the component affected. Emergency impairments need this same controlled return to service, even when advance preparation was impossible. [37]

Restoration involves more than declaring that a repair is complete; valves return to their normal operating positions, relevant tests verify the restored functions, and temporarily bypassed alarm interfaces are reconnected. Tags and records are reconciled with the actual installation. Notifications then communicate the restored condition to parties that were relying on the impairment information. [38][39]

The sequence matters because maintenance itself can introduce a hidden loss of protection; a mechanically repaired pipe still lacks water if its supply remains closed. A functioning sprinkler may fail to summon assistance if its signalling path remains disabled after testing. The IFEG's management framework therefore connects physical work, commissioning evidence and the maintained operating state. [38][14]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Fleming (2002), ch. 4-3, pp. 4-84–4-85.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Cote (2008), ch. 16.4, pp. 16-65–16-67.
  3. ↑ 3.0 3.1 3.2 Cote (2008), ch. 16.4, pp. 16-55,16-65–16-67.
  4. ↑ Cote (2008), ch. 16.4, pp. 16-55,16-58,16-65–16-67.
  5. ↑ 5.0 5.1 Cote (2008), ch. 16.4, p. 16-67.
  6. ↑ Cote (2008), ch. 15.1, pp. 15-4–15-5.
  7. ↑ 7.0 7.1 7.2 7.3 Hopkins et al. (2005), pp. xxxvii–xlii.
  8. ↑ 8.0 8.1 Cote (2008), ch. 16.4, pp. 16-55,16-58.
  9. ↑ 9.0 9.1 Cote (2008), ch. 16.4, p. 16-58.
  10. ↑ 10.0 10.1 10.2 Fleming (2002), ch. 4-3, p. 4-84.
  11. ↑ Cote (2008), ch. 16.3, pp. 16-41–16-42.
  12. ↑ Fleming (2002), ch. 4-3, pp. 4-75–4-85.
  13. ↑ Cote (2008), ch. 16.11, p. 16-210.
  14. ↑ 14.0 14.1 14.2 National Research Council of Canada et al. (2005), p. 1.7-8.
  15. ↑ Cote (2008), ch. 15.2, pp. 15-27–15-30.
  16. ↑ 16.0 16.1 Cote (2008), ch. 15.4, pp. 15-63–15-65.
  17. ↑ Cote (2008), ch. 16.10, pp. 16-200–16-201.
  18. ↑ 18.0 18.1 Cote (2008), ch. 15.1, pp. 15-3–15-5.
  19. ↑ Cote (2008), ch. 15.6, pp. 15-98–15-99.
  20. ↑ Cote (2008), ch. 13.4, pp. 13-40–13-44.
  21. ↑ 21.0 21.1 21.2 Cote (2008), ch. 16.11, pp. 16-208–16-209,16-221.
  22. ↑ 22.0 22.1 Cote (2008), ch. 15.2, pp. 15-23–15-24.
  23. ↑ Cote (2008), ch. 15.4, pp. 15-63–15-67.
  24. ↑ Cote (2008), ch. 15.2, pp. 15-23–15-29.
  25. ↑ Fleming (2002), ch. 4-3, pp. 4-74–4-81.
  26. ↑ Fleming (2002), ch. 4-3, pp. 4-81–4-83.
  27. ↑ 27.0 27.1 27.2 Fleming (2002), ch. 4-3, pp. 4-83–4-84.
  28. ↑ Cote (2008), ch. 15.4, pp. 15-63–15-64.
  29. ↑ Cote (2008), ch. 16.11, pp. 16-205–16-212.
  30. ↑ Cote (2008), ch. 16.11, p. 16-205.
  31. ↑ Cote (2008), ch. 16.3, pp. 16-42–16-43.
  32. ↑ Cote (2008), ch. 16.11, pp. 16-209–16-210.
  33. ↑ Cote (2008), ch. 16.11, pp. 16-207–16-212.
  34. ↑ Cote (2008), ch. 14.4, pp. 14-42–14-43.
  35. ↑ Cote (2008), ch. 16.11, pp. 16-210–16-211,16-220.
  36. ↑ Cote (2008), ch. 16.11, pp. 16-208,16-221.
  37. ↑ Cote (2008), ch. 16.11, p. 16-221.
  38. ↑ 38.0 38.1 Cote (2008), ch. 14.4, p. 14-43.
  39. ↑ Cote (2008), ch. 16.11, pp. 16-208–16-211,16-221.

References

  • Cote, A. E. (Ed.). (2008). Fire protection handbook (20th ed.). National Fire Protection Association.
  • Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-72–4-87). National Fire Protection Association.
  • Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines. Australian Building Codes Board.