New FSE wiki article: Halocarbon clean agent (written by GPT-6) |
Wiki review: corrected 5 errors: markup (3), citation (2) (Claude Opus 5.5) |
||
| (2 intermediate revisions by 2 users not shown) | |||
| Line 1: | Line 1: | ||
A '''halocarbon clean agent''' is a halogen-containing extinguishing medium that meets the clean-agent characteristics relevant to fire protection, including electrical non-conductivity and negligible agent residue after evaporation. The SFPE Handbook distinguishes these compounds from inert-gas agents. Their extinguishing action combines thermal and chemical effects in proportions that depend on the agent.<ref name="G-cbc28f5156">DiNenno (2002), pp. 4-174–4-175.</ref> | A '''halocarbon clean agent''' is a halogen-containing extinguishing medium that meets the clean-agent characteristics relevant to fire protection, including electrical non-conductivity and negligible agent residue after evaporation. The SFPE Handbook distinguishes these compounds from inert-gas agents. Their extinguishing action combines thermal and chemical effects in proportions that depend on the agent.<ref name="G-cbc28f5156">DiNenno (2002), pp. 4-174–4-175.</ref> | ||
[[File:fse-halocarbon-clean-agent-v1.svg|thumb|upright=1.5|alt=Agent identity branches into five separate properties: low residue, electrical non-conductivity, suppression, exposure and decomposition|Equipment properties and human exposure are distinct questions for a halocarbon clean agent; a clean agent is not necessarily harmless.]] | |||
The family includes alternatives developed for applications previously served by [[Halon|halon]]. A [[Gaseous extinguishing system|gaseous extinguishing system]] using such an agent requires appropriate distribution and concentration to achieve [[Flame extinction|flame extinction]]. A favourable small-scale result does not establish complete protection of every enclosure or fuel arrangement.<ref name="F-1f3e33d044">Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-110–17-112.</ref> | The family includes alternatives developed for applications previously served by [[Halon|halon]]. A [[Gaseous extinguishing system|gaseous extinguishing system]] using such an agent requires appropriate distribution and concentration to achieve [[Flame extinction|flame extinction]]. A favourable small-scale result does not establish complete protection of every enclosure or fuel arrangement.<ref name="F-1f3e33d044">Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-110–17-112.</ref> | ||
| Line 19: | Line 20: | ||
Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.<ref name="F-95a10b91d4" /> | Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.<ref name="F-95a10b91d4" /> | ||
Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.<ref name="G-48f9ac6e19">DiNenno (2002), | Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.<ref name="G-48f9ac6e19">DiNenno (2002), p. 4-174.</ref><ref name="F-8cbcab761a">Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.</ref> | ||
Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.<ref name="F-72d0b0d751">Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.</ref><ref name="F-5d55059c9a">Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.</ref> | Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.<ref name="F-72d0b0d751">Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.</ref><ref name="F-5d55059c9a">Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.</ref> | ||
| Line 25: | Line 26: | ||
== Concentration, distribution and discharge == | == Concentration, distribution and discharge == | ||
Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.<ref name="F-72d0b0d751" /> | Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.<ref name="F-72d0b0d751" /> | ||
[[File:fse-halocarbon-clean-agent-v2.svg|thumb|upright=1.5|alt=Stored agent is discharged through the distribution system into the protected volume, where the concentration after delivery must be retained over time|Delivery and time-dependent retention of a halocarbon clean agent in a protected volume.]] | |||
Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.<ref name="F-4d17adc0ab">Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.</ref> | Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.<ref name="F-4d17adc0ab">Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.</ref> | ||
The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.<ref name="G-b3ce0218d6">DiNenno (2002), | The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.<ref name="G-b3ce0218d6">DiNenno (2002), p. 4-175.</ref><ref name="F-4d17adc0ab" /> | ||
Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.<ref name="F-5d55059c9a" /> | Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.<ref name="F-5d55059c9a" /> | ||
| Line 52: | Line 54: | ||
== Laboratory evidence and system verification == | == Laboratory evidence and system verification == | ||
The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.<ref name="G-b3ce0218d6" /><ref name="F-4d17adc0ab" /> | The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.<ref name="G-b3ce0218d6" /><ref name="F-4d17adc0ab" /> | ||
[[File:fse-halocarbon-clean-agent-v3.svg|thumb|upright=1.5|alt=Four types of evidence (laboratory extinction, distribution evidence, enclosure leakage and retention prediction), each with what it shows and what it does not prove, combined into a complete assessment that is reassessed after change|Complementary evidence and its limits in assessing a halocarbon clean-agent system.]] | |||
System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.<ref name="F-4d17adc0ab" /> | System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.<ref name="F-4d17adc0ab" /> | ||
Latest revision as of 00:41, 16 November 2026
A halocarbon clean agent is a halogen-containing extinguishing medium that meets the clean-agent characteristics relevant to fire protection, including electrical non-conductivity and negligible agent residue after evaporation. The SFPE Handbook distinguishes these compounds from inert-gas agents. Their extinguishing action combines thermal and chemical effects in proportions that depend on the agent.[1]
The family includes alternatives developed for applications previously served by halon. A gaseous extinguishing system using such an agent requires appropriate distribution and concentration to achieve flame extinction. A favourable small-scale result does not establish complete protection of every enclosure or fuel arrangement.[2]
NFPA 2001 supplies the clean-agent system framework discussed in the 2008 handbook. NOAEL and LOAEL describe particular toxicological test endpoints, while hydrogen fluoride can be relevant to thermal decomposition of fluorinated agents. These exposure and decomposition questions remain distinct from the low-residue property described by the term clean.[3]
Meaning and engineering application
The agent's chemical identity determines its relevant physical properties and suppression behaviour. Some formulations absorb heat strongly as they vaporise and mix into the flame environment. Chemical inhibition can also contribute, but not identically for every compound. The handbook therefore compares agents individually rather than assigning all halocarbons the same mechanism or concentration requirement.[4]
Clean describes properties of the discharged medium in relation to equipment contamination and conductivity. It does not mean that fire products or thermal decomposition products are absent. The SFPE definition and the handbook's toxicity discussion address different parts of the assessment. Both are needed when interpreting suitability for a sensitive, occupied or enclosed application.[1][5]
The system has to deliver the agent throughout the protected region in the intended time. Nozzle and distribution tests address that requirement, while enclosure retention addresses the period after discharge. A storage-container label cannot demonstrate either condition by itself. The agent quantity, equipment arrangement and enclosure characteristics jointly support the protection claim.[6]
Comparison with halon also requires separate treatment of environmental criteria. Ozone effects, persistence and climate-related characteristics are different properties. The historical handbook records the development and assessment of alternatives, but does not provide a current regulatory approval for an unnamed installation. The technical comparison remains tied to the particular agent, hazard and applicable edition.[7]
Thermal and chemical extinguishing mechanisms
A gaseous extinguishant changes the conditions supporting combustion around the flame. The SFPE treatment distinguishes thermal effects, dilution and chemical inhibition rather than assigning one identical mechanism to all agents. Adding a gas can increase the energy needed to maintain the reacting mixture at flame temperature. Some halogenated agents also interfere with the chemical reactions sustaining the flame.[1]
Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.[4]
Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.[8][9]
Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.[10][11]
Concentration, distribution and discharge
Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.[10]
Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.[12]
The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.[13][12]
Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.[11]
Enclosure leakage and retention
An enclosure is part of a total-flooding system because it influences where the agent travels and how long it remains. Doors, service penetrations, ducts and construction joints can provide leakage paths. The importance of a path depends on its size, position and the pressure conditions across it. A room that appears closed can therefore differ substantially from the enclosure assumed in the design.[11]
Retention is the maintenance of an adequate concentration for the required period. Its purpose depends on the fire, including the possibility of re-ignition from hot material or continuing electrical energy. The handbook discusses different retention needs for different hazards and system arrangements. A single observation immediately after discharge cannot establish that the protective atmosphere persists for the intended duration.[11]
A fan-based integrity assessment uses pressure and airflow measurements to estimate enclosure leakage. A model then relates that leakage to the expected loss of agent under stated assumptions. Leakage distribution and the behaviour of the gas mixture influence the result. The test therefore evaluates an enclosure characteristic and supports a retention prediction; it is not a direct demonstration that the extinguishing nozzles discharge correctly.[11]
Pressure relief and retention must also be considered together. The discharge can change enclosure pressure, while an opening that relieves pressure can allow agent to escape. The design has to account for both functions and their operating states. Later changes to doors, ventilation or penetrations can alter that balance, which connects enclosure assessment with the IFEG requirement to review the assumptions affected by building alterations.[11][14]
Exposure endpoints and occupied spaces
Extinguishing effectiveness and human exposure are separate assessment questions. The concentration that removes a flame does not by itself establish acceptable conditions for people. Relevant effects depend on the agent, concentration, duration and the circumstances of exposure. The handbook therefore treats toxicological information alongside extinguishing performance, rather than using one measurement as a substitute for the other.[5][15]
The no-observed-adverse-effect level, or NOAEL, identifies the highest tested exposure level without the specified adverse effect. The lowest-observed-adverse-effect level, or LOAEL, identifies the lowest tested level at which that effect was observed. These are experimental endpoints with defined test conditions. They do not describe a universal boundary between harmless and harmful exposure for every person and duration.[5]
For halocarbon agents, the handbook discusses cardiac sensitisation testing and the relationship between concentration, uptake and exposure duration. Inert-gas protection raises the separate issue of reduced oxygen concentration. Carbon dioxide adds direct physiological effects and cannot be assessed solely as an oxygen-displacing gas. These differences prevent a common exposure rule from being inferred merely because all three media can extinguish a fire.[5][16]
The fire itself also changes the atmosphere. Combustion products remain relevant, and some agents can form decomposition products when exposed to flame or hot surfaces. Warning, evacuation and the discharge sequence consequently belong within the system assessment. The handbook's historical concentration tables support understanding of the assessment method; they do not establish a current permitted exposure for an unspecified installation or population.[3]
Laboratory evidence and system verification
The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.[13][12]
System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.[12]
The installed enclosure presents a further set of questions. Leakage testing supports assessment of retention, while inspection examines openings and the conditions assumed by the calculation. Neither test demonstrates every part of the release circuit or distribution piping. Commissioning therefore needs to connect the separate evidence for controls, agent delivery and enclosure behaviour with the intended operating sequence.[11][17]
Uncertainty enters through both measurement and representation of the hazard. A laboratory flame has controlled geometry and ventilation, whereas equipment can contain obstructed or concealed burning surfaces. The design concentration and retention requirement must relate to the relevant fire evidence and system conditions. The defensible result is a stated protection claim with identifiable assumptions, rather than a general assertion that any fire will be extinguished.[13][6]
Residue, decomposition and environmental effects
The term clean agent concerns properties relevant to the protected equipment, particularly electrical conductivity and residue after discharge. It does not mean that the agent has no physiological or environmental effects. The SFPE treatment separates these matters when comparing alternatives to halon. An assessment can therefore favour an agent for sensitive equipment while still requiring separate evaluation of exposure and environmental consequences.[1]
Halon replacement followed concern about stratospheric ozone depletion. The handbook describes the development of alternatives and the recovery of halon for particular continuing applications. This is a historical account of the situation discussed in the 2008 edition. The chemistry explaining ozone effects is different from the criteria used to describe persistence or climate effects, so one environmental property cannot stand for all others.[18]
Thermal decomposition is another distinct issue. A halogenated agent exposed to fire can form products with different properties from the original extinguishant. The quantity formed depends on the fire and the conditions during discharge. Early detection and effective suppression can affect the duration of contact between agent and flame. The handbook therefore connects decomposition with system performance, rather than treating it only as a stored-product characteristic.[19]
Comparisons must retain the conditions supporting each claim. A statement about residue, ozone depletion or extinguishing concentration answers a different question from a statement about occupancy or allowable use. The historical handbook provides a technical framework for these comparisons, but not a current inventory of permitted products. Product selection requires the relevant agent identity, performance evidence and governing edition to remain explicit within the assessment.[20]
Protection objectives and limits of performance
Suppression describes an intended change in a fire, but the required outcome needs further definition. Control can limit growth or reduce the rate of heat release without extinguishing every burning item. Extinguishment removes the continuing combustion under the conditions considered. Prevention of renewed burning may require cooling, continued agent retention or removal of an ignition source. These outcomes impose different demands on the protection arrangement.[21][11]
Agent selection follows the fuel and the objective. Water can cool a solid surface, foam can maintain a barrier over a liquid, and a gaseous agent can change the atmosphere surrounding a fire. None of these descriptions establishes universal effectiveness. The protected material, fire geometry, ventilation and available delivery arrangement determine whether the relevant mechanism can operate where it is needed.[22][23]
The assessment also distinguishes successful operation from unsuccessful or delayed operation. An explicit example appears in Australia's Fire Safety Verification Method Standard, 2022 edition. Its structural-stability scenario considers failures of suppression, delayed fire brigade intervention and combinations of failures. That requirement belongs to the Australian method and its stated scenario. It illustrates why the mere presence of equipment is insufficient evidence of the building's performance.[24]
The protection claim consequently includes its conditions of use. These include the hazard, the quantity and distribution of agent, the expected activation sequence and the time for which protection is maintained. Changes to storage, ventilation or operating procedures can alter those conditions. The International Fire Engineering Guidelines connect continued building use and alterations with review of the original engineering assumptions.[25]
See also
- Cup burner test
- Data centre fire protection
- Enclosure integrity test
- Environmental Protection Agency
- Explosion suppression system
- Inert gas agent
Notes
- ↑ 1.0 1.1 1.2 1.3 DiNenno (2002), pp. 4-174–4-175.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-110–17-112.
- ↑ 3.0 3.1 Cote et al. (2008), chapter 17.6, pp. 17-101–17-103, 17-120–17-121.
- ↑ 4.0 4.1 Cote et al. (2008), chapter 17.6, pp. 17-95–17-96, 17-98–17-99.
- ↑ 5.0 5.1 5.2 5.3 Cote et al. (2008), chapter 17.6, pp. 17-101–17-103.
- ↑ 6.0 6.1 Cote et al. (2008), chapter 17.6, pp. 17-110–17-112, 17-119–17-121.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-102–17-103.
- ↑ DiNenno (2002), p. 4-174.
- ↑ Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.
- ↑ 10.0 10.1 Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.
- ↑ 11.0 11.1 11.2 11.3 11.4 11.5 11.6 11.7 Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.
- ↑ 12.0 12.1 12.2 12.3 Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.
- ↑ 13.0 13.1 13.2 DiNenno (2002), p. 4-175.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.8; p. 0.3-7.
- ↑ Cote et al. (2008), chapter 17.7, pp. 17-129–17-130.
- ↑ Cote et al. (2008), chapter 17.1, pp. 17-4–17-5.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.4; p. 0.3-6.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-93–17-94, 17-102–17-103.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-102–17-103, 17-120–17-121.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-101–17-103.
- ↑ Cote et al. (2008), chapter 17.3, pp. 17-32–17-33.
- ↑ Cote et al. (2008), chapter 17.3, pp. 17-32–17-33, 17-36–17-38.
- ↑ Cote et al. (2008), chapter 17.4, pp. 17-45–17-49.
- ↑ Australian Building Codes Board (2022), §2.12.2; p. 19.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.6–0.3.2.8; pp. 0.3-6–0.3-7.
References
- Australian Building Codes Board. (2022). Fire Safety Verification Method Standard 2022.
- Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire Protection Handbook (20th ed.). National Fire Protection Association.
- DiNenno, P. J. (2002). Halon replacement clean agent total flooding systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr., & J. M. Watts, Jr. (Eds.), SFPE Handbook of Fire Protection Engineering (3rd ed., chapter 4-7, pp. 4-173–4-200). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International Fire Engineering Guidelines (2005 ed.). Australian Building Codes Board.