A '''[[Carbon dioxide|carbon dioxide]] extinguishing system''' stores and discharges carbon dioxide to establish extinguishing conditions around a protected fire. It is a [[Gaseous extinguishing system|gaseous extinguishing system]] whose performance depends on concentration, distribution and duration. The Fire Protection Handbook describes both total flooding of enclosures and direct application to defined hazards.<ref name="F-4fdea27425">Cote et al. (2008), chapter 17.1, pp. 17-3–17-8.</ref> | A '''[[Carbon dioxide|carbon dioxide]] extinguishing system''' stores and discharges carbon dioxide to establish extinguishing conditions around a protected fire. It is a [[Gaseous extinguishing system|gaseous extinguishing system]] whose performance depends on concentration, distribution and duration. The Fire Protection Handbook describes both total flooding of enclosures and direct application to defined hazards.<ref name="F-4fdea27425">Cote et al. (2008), chapter 17.1, pp. 17-3–17-8.</ref> | ||
[[File:fse-carbon-dioxide-extinguishing-system-v1.svg|thumb|upright=1.5|alt= | [[File:fse-carbon-dioxide-extinguishing-system-v1.svg|thumb|upright=1.5|alt=Agent storage feeds, through distribution, either total flooding of an enclosed volume (retention) or local application by a local nozzle onto a defined surface (coverage); a warning notes that carbon dioxide extinguishing concentrations are hazardous|Total flooding and local application: two carbon dioxide protection arrangements with different boundaries. Extinguishing concentrations are hazardous to people.]] | ||
The agent is electrically non-conductive and leaves no solid agent residue, but extinguishing concentrations create serious physiological hazards. [[Oxygen depletion]] is only part of that problem because carbon dioxide also has direct effects on the body. It is therefore distinct from the inert-gas clean agents described in the SFPE Handbook.<ref name="F-8cbcab761a">Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.</ref><ref name="G-48f9ac6e19">DiNenno (2002), | The agent is electrically non-conductive and leaves no solid agent residue, but extinguishing concentrations create serious physiological hazards. [[Oxygen depletion]] is only part of that problem because carbon dioxide also has direct effects on the body. It is therefore distinct from the inert-gas clean agents described in the SFPE Handbook.<ref name="F-8cbcab761a">Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.</ref><ref name="G-48f9ac6e19">DiNenno (2002), p. 4-174.</ref> | ||
A [[Local application system|local application system]] can protect a defined surface such as a [[Dip tank|dip tank]] without flooding the whole room. For total flooding, enclosure leakage and retention become central questions, and an [[Enclosure integrity test|enclosure integrity test]] can support their assessment. These arrangements require different evidence about how the agent reaches and remains around the hazard.<ref name="F-72d0b0d751">Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.</ref><ref name="F-5d55059c9a">Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.</ref> | A [[Local application system|local application system]] can protect a defined surface such as a [[Dip tank|dip tank]] without flooding the whole room. For total flooding, enclosure leakage and retention become central questions, and an [[Enclosure integrity test|enclosure integrity test]] can support their assessment. These arrangements require different evidence about how the agent reaches and remains around the hazard.<ref name="F-72d0b0d751">Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.</ref><ref name="F-5d55059c9a">Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.</ref> | ||
| Line 26: | Line 26: | ||
== Concentration, distribution and discharge == | == Concentration, distribution and discharge == | ||
Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.<ref name="F-72d0b0d751" /> | Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.<ref name="F-72d0b0d751" /> | ||
[[File:fse-carbon-dioxide-extinguishing-system-v2.svg|thumb|upright=1.5|alt= | [[File:fse-carbon-dioxide-extinguishing-system-v2.svg|thumb|upright=1.5|alt=Storage and distribution lead to total flooding, where the agent is retained in an enclosed volume, or to local application, where a nozzle covers a defined surface; carbon dioxide extinguishing concentrations are hazardous|Protection boundaries of a carbon dioxide system: retention in an enclosed volume for total flooding, coverage of a defined surface for local application. The diagram specifies no nozzle layout or concentration.]] | ||
Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.<ref name="F-4d17adc0ab">Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.</ref> | Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.<ref name="F-4d17adc0ab">Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.</ref> | ||
The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.<ref name="G-b3ce0218d6">DiNenno (2002), | The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.<ref name="G-b3ce0218d6">DiNenno (2002), p. 4-175.</ref><ref name="F-4d17adc0ab" /> | ||
Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.<ref name="F-5d55059c9a" /> | Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.<ref name="F-5d55059c9a" /> | ||
| Line 72: | Line 72: | ||
== Commissioning, maintenance and change == | == Commissioning, maintenance and change == | ||
An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.<ref name="I-f73f312240">National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.</ref> | An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.<ref name="I-f73f312240">National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.</ref> | ||
[[File:fse-carbon-dioxide-extinguishing-system-v3.svg|thumb|upright=1.5|alt= | [[File:fse-carbon-dioxide-extinguishing-system-v3.svg|thumb|upright=1.5|alt=Physical inspection, functional test, integrated response and recorded conditions, each with what it shows and what it does not prove, combine into a performance assessment that is reassessed after any change|Complementary evidence for a carbon dioxide extinguishing system and its limits; a change leads to reassessment.]] | ||
Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook's foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.<ref name="F-2ef4d8b6a4">Cote et al. (2008), chapter 17.4, | Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook's foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.<ref name="F-2ef4d8b6a4">Cote et al. (2008), chapter 17.4, p. 17-68.</ref> | ||
Records connect observations with the installation's intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.<ref name="F-739a9f298d">Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.</ref> | Records connect observations with the installation's intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.<ref name="F-739a9f298d">Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.</ref> | ||
Latest revision as of 00:40, 16 November 2026
A carbon dioxide extinguishing system stores and discharges carbon dioxide to establish extinguishing conditions around a protected fire. It is a gaseous extinguishing system whose performance depends on concentration, distribution and duration. The Fire Protection Handbook describes both total flooding of enclosures and direct application to defined hazards.[1]
The agent is electrically non-conductive and leaves no solid agent residue, but extinguishing concentrations create serious physiological hazards. Oxygen depletion is only part of that problem because carbon dioxide also has direct effects on the body. It is therefore distinct from the inert-gas clean agents described in the SFPE Handbook.[2][3]
A local application system can protect a defined surface such as a dip tank without flooding the whole room. For total flooding, enclosure leakage and retention become central questions, and an enclosure integrity test can support their assessment. These arrangements require different evidence about how the agent reaches and remains around the hazard.[4][5]
Carbon dioxide behaviour and application
Carbon dioxide is stored in a liquid-containing arrangement and changes phase as it is released. The handbook describes cooling and snow formation during discharge, but distinguishes these effects from water's sustained cooling of a fuel surface. Extinguishment mainly depends on changing the atmosphere and thermal conditions around the reacting fire. The delivered concentration and its duration therefore remain central.[2]
Surface fires and deep-seated hazards require different treatment. A surface flame may disappear while a hot mass remains capable of renewed burning. The handbook discusses retention and extended discharge in relation to these conditions. It also identifies materials for which carbon dioxide is unsuitable, preventing its non-conductive and residue-free characteristics from being interpreted as universal extinguishing suitability.[4]
Local application depends on nozzle coverage, discharge rate and the immediate surroundings of the hazard. Air movement can disperse agent and adjacent surfaces can affect the application. Total flooding instead relies on an enclosure capable of supporting the required concentration. The protection boundary must therefore be defined before the stored quantity or discharge arrangement can be interpreted.[6]
Occupancy and migration require separate attention. Agent can move into connected spaces, and concentrations appropriate for extinguishment can be dangerous to people. The handbook's dedicated carbon dioxide chapter explicitly addresses this hazard. Electrical non-conductivity and absence of solid residue do not remove this physiological hazard.[7]
Thermal and chemical extinguishing mechanisms
A gaseous extinguishant changes the conditions supporting combustion around the flame. The SFPE treatment distinguishes thermal effects, dilution and chemical inhibition rather than assigning one identical mechanism to all agents. Adding a gas can increase the energy needed to maintain the reacting mixture at flame temperature. Some halogenated agents also interfere with the chemical reactions sustaining the flame.[8]
Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.[9]
Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.[3][2]
Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.[4][5]
Concentration, distribution and discharge
Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.[4]
Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.[10]
The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.[11][10]
Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.[5]
Local coverage and process interfaces
Local application directs agent at a defined hazard rather than establishing a uniform extinguishing atmosphere throughout an entire room. The handbook's carbon dioxide examples include exposed equipment and liquid surfaces, while its chemical-system examples include protected cooking appliances. In each case, the arrangement depends on the dimensions and position of the hazard. The protection boundary is therefore part of the system definition.[6][12]
Nozzle position and discharge characteristics determine whether the agent reaches that boundary. Obstruction, air movement and movement of equipment can change the result. A nozzle arrangement proven for one appliance configuration does not automatically cover a relocated or different appliance. The handbook's discussion of proprietary cooking systems connects tested nozzle arrangements with the particular equipment and associated exhaust components being protected.[12]
The operating sequence can include shutdown of a continuing heat or fuel source. This matters because rapid flame removal can otherwise be followed by renewed burning. For cooking protection, the residual heat of oil and equipment remains relevant after the initial discharge. The protective sequence consequently joins agent delivery with the controls that remove continuing energy input. Assessing only the extinguishing container leaves part of that sequence unexamined.[12]
Changes to the process require review of the protection relationship. A moved appliance, altered duct or newly installed obstruction can affect coverage without changing any electrical indication. Commissioning establishes the original configuration, while management and maintenance keep its assumptions visible during use. The IFEG lifecycle framework provides the broader connection between the engineering assessment, operational responsibilities and subsequent alterations.[13]
Enclosure leakage and retention
An enclosure is part of a total-flooding system because it influences where the agent travels and how long it remains. Doors, service penetrations, ducts and construction joints can provide leakage paths. The importance of a path depends on its size, position and the pressure conditions across it. A room that appears closed can therefore differ substantially from the enclosure assumed in the design.[5]
Retention is the maintenance of an adequate concentration for the required period. Its purpose depends on the fire, including the possibility of re-ignition from hot material or continuing electrical energy. The handbook discusses different retention needs for different hazards and system arrangements. A single observation immediately after discharge cannot establish that the protective atmosphere persists for the intended duration.[5]
A fan-based integrity assessment uses pressure and airflow measurements to estimate enclosure leakage. A model then relates that leakage to the expected loss of agent under stated assumptions. Leakage distribution and the behaviour of the gas mixture influence the result. The test therefore evaluates an enclosure characteristic and supports a retention prediction; it is not a direct demonstration that the extinguishing nozzles discharge correctly.[5]
Pressure relief and retention must also be considered together. The discharge can change enclosure pressure, while an opening that relieves pressure can allow agent to escape. The design has to account for both functions and their operating states. Later changes to doors, ventilation or penetrations can alter that balance, which connects enclosure assessment with the IFEG requirement to review the assumptions affected by building alterations.[5][14]
Exposure endpoints and occupied spaces
Extinguishing effectiveness and human exposure are separate assessment questions. The concentration that removes a flame does not by itself establish acceptable conditions for people. Relevant effects depend on the agent, concentration, duration and the circumstances of exposure. The handbook therefore treats toxicological information alongside extinguishing performance, rather than using one measurement as a substitute for the other.[15][16]
The no-observed-adverse-effect level, or NOAEL, identifies the highest tested exposure level without the specified adverse effect. The lowest-observed-adverse-effect level, or LOAEL, identifies the lowest tested level at which that effect was observed. These are experimental endpoints with defined test conditions. They do not describe a universal boundary between harmless and harmful exposure for every person and duration.[15]
For halocarbon agents, the handbook discusses cardiac sensitisation testing and the relationship between concentration, uptake and exposure duration. Inert-gas protection raises the separate issue of reduced oxygen concentration. Carbon dioxide adds direct physiological effects and cannot be assessed solely as an oxygen-displacing gas. These differences prevent a common exposure rule from being inferred merely because all three media can extinguish a fire.[15][7]
The fire itself also changes the atmosphere. Combustion products remain relevant, and some agents can form decomposition products when exposed to flame or hot surfaces. Warning, evacuation and the discharge sequence consequently belong within the system assessment. The handbook's historical concentration tables support understanding of the assessment method; they do not establish a current permitted exposure for an unspecified installation or population.[17]
Matching the agent to the hazard
The first selection question concerns the material that is burning. Ordinary solid combustibles, flammable liquids, cooking fats and combustible metals do not respond identically to the same agent. The Fire Protection Handbook consequently relates extinguisher selection to fire classification and to the specific hazard within that classification. A familiar agent name is not sufficient evidence of suitability for every material in a broad group.[18]
Electrical equipment adds another selection question. Conductivity concerns the possibility of an electrical path through the applied agent, while residue concerns contamination after discharge. These characteristics are distinct from extinguishing effectiveness. An agent can be electrically non-conductive yet leave deposits that are undesirable around sensitive equipment. Conversely, a water-based formulation does not become electrically non-conductive merely because an additive improves its wetting or foaming behaviour.[19][20]
The physical arrangement of the fire also matters. A surface flame, a concealed hot mass and a continuing release of burning liquid present different delivery and re-ignition problems. Rapid flame removal does not necessarily cool the underlying material sufficiently. Protection of a process can therefore include isolation of its fuel or heat source as well as application of the selected extinguishing medium.[4][12]
Compatibility extends to the equipment carrying the agent. Concentrate, powder formulation, seals, valves and discharge devices form a specified combination. The handbook identifies both incompatible dry chemicals and foam systems requiring matched proportioning and discharge equipment. Substitution based only on a similar generic description can change flow or extinguishing performance. The applicable product information and test evidence describe the combination being assessed.[19][21]
Commissioning, maintenance and change
An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.[22]
Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook's foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.[23]
Records connect observations with the installation's intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.[24]
Continuing performance also depends on management of change. A modified appliance, altered storage arrangement or new partition may change the hazard while leaving the protection equipment apparently intact. Maintenance alone cannot restore a design assumption that no longer describes the site. The IFEG lifecycle approach consequently connects alterations, operational responsibilities and maintenance with the original fire engineering assessment and its documented conditions.[25]
See also
Notes
- ↑ Cote et al. (2008), chapter 17.1, pp. 17-3–17-8.
- ↑ 2.0 2.1 2.2 Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.
- ↑ 3.0 3.1 DiNenno (2002), p. 4-174.
- ↑ 4.0 4.1 4.2 4.3 4.4 Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.
- ↑ 6.0 6.1 Cote et al. (2008), chapter 17.1, pp. 17-6–17-8.
- ↑ 7.0 7.1 Cote et al. (2008), chapter 17.1, pp. 17-4–17-5.
- ↑ DiNenno (2002), pp. 4-174–4-175.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-95–17-96, 17-98–17-99.
- ↑ 10.0 10.1 Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.
- ↑ DiNenno (2002), p. 4-175.
- ↑ 12.0 12.1 12.2 12.3 Cote et al. (2008), chapter 17.2, pp. 17-24–17-26.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.8; pp. 0.3-6–0.3-7.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.8; p. 0.3-7.
- ↑ 15.0 15.1 15.2 Cote et al. (2008), chapter 17.6, pp. 17-101–17-103.
- ↑ Cote et al. (2008), chapter 17.7, pp. 17-129–17-130.
- ↑ Cote et al. (2008), chapter 17.6, pp. 17-101–17-103, 17-120–17-121.
- ↑ Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-81–17-82.
- ↑ 19.0 19.1 Cote et al. (2008), chapter 17.2, pp. 17-18–17-20.
- ↑ Cote et al. (2008), chapter 17.3, pp. 17-36–17-38.
- ↑ Cote et al. (2008), chapter 17.4, pp. 17-50–17-52, 17-64.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.
- ↑ Cote et al. (2008), chapter 17.4, p. 17-68.
- ↑ Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.
- ↑ National Research Council of Canada et al. (2005), §0.3.2.6–0.3.2.8; pp. 0.3-6–0.3-7.
References
- Cote, A. E., Grant, C. C., Hall, J. R., Jr., & Solomon, R. E. (Eds.). (2008). Fire Protection Handbook (20th ed.). National Fire Protection Association.
- DiNenno, P. J. (2002). Halon replacement clean agent total flooding systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr., & J. M. Watts, Jr. (Eds.), SFPE Handbook of Fire Protection Engineering (3rd ed., chapter 4-7, pp. 4-173–4-200). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International Fire Engineering Guidelines (2005 ed.). Australian Building Codes Board.