Trench effect in the cited gas-burner channel experiments: flames attached above 15° inclination; on the 30° King's Cross escalator, with sidewalls, a fire across the full width lay down in the trench, while a fire across one third of the width rose vertically. Based on Alpert (2008), p. 2-25, and Cox and Kumar (2002), pp. 3-207–3-208.
Trench effect in the cited gas-burner channel experiments: flames attached above 15° inclination; on the 30° King's Cross escalator, with sidewalls, a fire across the full width lay down in the trench, while a fire across one third of the width rose vertically.


Original illustration for [[Escalator fire protection]].
Original illustration for [[Escalator fire protection]].

Latest revision as of 08:53, 13 November 2026

Summary

Trench effect in the cited gas-burner channel experiments: flames attached above 15° inclination; on the 30° King's Cross escalator, with sidewalls, a fire across the full width lay down in the trench, while a fire across one third of the width rose vertically.

Original illustration for Escalator fire protection.

  • Alt text: Diagram of flames detached on a flat surface but attached along a 30 degree walled escalator trench, as at King's Cross