Time to electrical failure of cables exposed to hot gas, as tabulated for US nuclear plant screening. Thermoplastic cables fail at lower temperatures and sooner | Time to electrical failure of cables exposed to hot gas, as tabulated for US nuclear plant screening. Thermoplastic cables fail at lower temperatures and sooner. | ||
Original illustration for [[Cable fire]]. | Original illustration for [[Cable fire]]. | ||
Latest revision as of 08:43, 13 November 2026
Summary
Time to electrical failure of cables exposed to hot gas, as tabulated for US nuclear plant screening. Thermoplastic cables fail at lower temperatures and sooner.
Original illustration for Cable fire.
- Alt text: Line chart of time to cable failure against exposure temperature, thermoplastic from 30 minutes at 205 °C and thermoset from 28 minutes at 330 °C