Line 42: Line 42:


Ignition temperature data scatter more widely. The service station table gives about 441 °C (825 °F), and Beyler (2002b) gives 440 °C for grade 100/130 and 470 °C for grade 115/145. Kanury (2002b) gives an estimate of 644 K, about 371 °C.<ref name="Rivkin-21-32" /><ref name="Beyler-2-176" /><ref name="Kanury-2-193" /> For AVGAS, Boucher (2008) lists an autoignition range of 825 to 960 °F (441 to 516 °C).<ref name="Boucher-21-137" /> In pure oxygen the minimum ignition temperature of gasoline grade 100/130 drops from 440 °C to 316 °C (600 °F).<ref name="RS-9-229">Rosales and Stoltzfus (2008), p. 9-229.</ref>
Ignition temperature data scatter more widely. The service station table gives about 441 °C (825 °F), and Beyler (2002b) gives 440 °C for grade 100/130 and 470 °C for grade 115/145. Kanury (2002b) gives an estimate of 644 K, about 371 °C.<ref name="Rivkin-21-32" /><ref name="Beyler-2-176" /><ref name="Kanury-2-193" /> For AVGAS, Boucher (2008) lists an autoignition range of 825 to 960 °F (441 to 516 °C).<ref name="Boucher-21-137" /> In pure oxygen the minimum ignition temperature of gasoline grade 100/130 drops from 440 °C to 316 °C (600 °F).<ref name="RS-9-229">Rosales and Stoltzfus (2008), p. 9-229.</ref>
[[File:fse-gasoline-v2.svg|thumb|upright=1.5|alt=Dot and range chart of gasoline flash points near minus 45 degrees and ignition temperatures between 316 and 516 degrees from several sources|Flash point and minimum ignition temperature of gasoline as tabulated in different sources.]]


The density depends on the grade and the temperature. Babrauskas (2002b) uses 740 kg/m³ in pool fire data, whereas an SFPE appendix table lists 680.3 kg/m³ at 20 °C, and an SFPE foam example uses a specific gravity of 0.72.<ref name="Babrauskas-3-26" /><ref name="DiNenno-A-26">DiNenno et al. (2002), p. A-26.</ref><ref name="SH-4-130">Scheffey and Hickey (2002), p. 4-130.</ref> Per unit volume, Van der Graaf et al. (2021/2023) give an energy content of about 32 MJ per litre for petrol, against about 36 MJ per litre for diesel.<ref name="VdG-25" /> This agrees with the heat of combustion and density above: 43.7 MJ/kg × 0.74 kg/L gives about 32 MJ/L.
The density depends on the grade and the temperature. Babrauskas (2002b) uses 740 kg/m³ in pool fire data, whereas an SFPE appendix table lists 680.3 kg/m³ at 20 °C, and an SFPE foam example uses a specific gravity of 0.72.<ref name="Babrauskas-3-26" /><ref name="DiNenno-A-26">DiNenno et al. (2002), p. A-26.</ref><ref name="SH-4-130">Scheffey and Hickey (2002), p. 4-130.</ref> Per unit volume, Van der Graaf et al. (2021/2023) give an energy content of about 32 MJ per litre for petrol, against about 36 MJ per litre for diesel.<ref name="VdG-25" /> This agrees with the heat of combustion and density above: 43.7 MJ/kg × 0.74 kg/L gives about 32 MJ/L.
Line 61: Line 62:


At 20 °C, gasoline has a vapour pressure of 55.2 kPa.<ref name="DiNenno-A-26" /> The equation then gives a vapour concentration close to the surface of about 55.2/101.325 = 0.545, or 54.5 percent by volume. This is about seven times the upper flammability limit of 7.6 percent, so the vapour layer directly above warm gasoline is too rich to burn.<ref name="Slye-6-197" /> Kanury (2002b) describes how, with time, the belt of mixture between the lean and rich limits moves away from the surface as the vapour diffuses into the air.<ref name="Kanury-2-194" /> The same reasoning explains why the vapour space of a closed gasoline tank is normally above the upper limit.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref>
At 20 °C, gasoline has a vapour pressure of 55.2 kPa.<ref name="DiNenno-A-26" /> The equation then gives a vapour concentration close to the surface of about 55.2/101.325 = 0.545, or 54.5 percent by volume. This is about seven times the upper flammability limit of 7.6 percent, so the vapour layer directly above warm gasoline is too rich to burn.<ref name="Slye-6-197" /> Kanury (2002b) describes how, with time, the belt of mixture between the lean and rich limits moves away from the surface as the vapour diffuses into the air.<ref name="Kanury-2-194" /> The same reasoning explains why the vapour space of a closed gasoline tank is normally above the upper limit.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref>
[[File:fse-gasoline-v1.svg|thumb|upright=1.5|alt=Logarithmic bar chart comparing the 54.5 percent vapour concentration above gasoline at 20 degrees with its flammable range of 1.4 to 7.6 percent|Vapour concentration just above gasoline at 20 °C compared with its flammable range in air.]]


Ordile (2008) states that tanks of liquids with vapour pressures above 28 kPa (4 psia), such as gasoline, normally have a vapour space too rich to burn. If the liquid is between about −23 and −46 °C (−10 and −50 °F), the vapour space might be within the flammable range.<ref name="Ordile-7-16" /> Air drawn in during off-loading, or sudden cooling by a rainstorm on a hot day, can also make part of the vapour space flammable. Because the vapours stratify, this can last hours or even days.<ref name="Ordile-7-16" />
Ordile (2008) states that tanks of liquids with vapour pressures above 28 kPa (4 psia), such as gasoline, normally have a vapour space too rich to burn. If the liquid is between about −23 and −46 °C (−10 and −50 °F), the vapour space might be within the flammable range.<ref name="Ordile-7-16" /> Air drawn in during off-loading, or sudden cooling by a rainstorm on a hot day, can also make part of the vapour space flammable. Because the vapours stratify, this can last hours or even days.<ref name="Ordile-7-16" />


Because gasoline vapour is heavier than air, it settles on floors and in pits. Slye (2008) states that such vapour can flow along the floor or ground for long distances, be ignited at a remote point and flash back. Removing it at floor level is usually the proper method of ventilation.<ref name="Slye-6-207" /> Wastewater treatment plants list gasoline among heavier-than-air gases and vapours, with storage tank leaks and tank truck spills as sources.<ref name="Wheeler-9-150">Wheeler (2008), p. 9-150.</ref> For the same reason, US rules described by Rivkin (2008a) place heat-producing appliances in repair garages in a separate room or at least 8 ft (2.4 m) above the floor.<ref name="Rivkin-21-33">Rivkin (2008a), p. 21-33.</ref>
Because gasoline vapour is heavier than air, it settles on floors and in pits. Slye (2008) states that such vapour can flow along the floor or ground for long distances, be ignited at a remote point and flash back. Removing it at floor level is usually the proper method of ventilation.<ref name="Slye-6-207" /> Wastewater treatment plants list gasoline among heavier-than-air gases and vapours, with storage tank leaks and tank truck spills as sources.<ref name="Wheeler-9-150">Wheeler (2008), p. 9-150.</ref> For the same reason, US rules described by Rivkin (2008a) place heat-producing appliances in repair garages in a separate room or at least 8 ft (2.4 m) above the floor.<ref name="Rivkin-21-33">Rivkin (2008a), p. 21-33.</ref>
[[File:fse-gasoline-v3.svg|thumb|upright=1.5|alt=Cross-section of a garage floor with a gasoline spill, vapour flowing along the floor into a pit and towards a heater, and an exhaust at floor level|Heavier-than-air gasoline vapour flowing along a floor to a remote ignition source, with floor-level extraction and an elevated heater.]]


Mixing gasoline with a less flammable liquid does not make it safe for long. Slye (2008) describes a mixture of gasoline and carbon tetrachloride that has no flash point when fresh. In an open container the carbon tetrachloride evaporates faster, so the residue shows a progressively lower flash point, approaching that of the heavier gasoline fractions.<ref name="Slye-6-205">Slye (2008), p. 6-205.</ref>
Mixing gasoline with a less flammable liquid does not make it safe for long. Slye (2008) describes a mixture of gasoline and carbon tetrachloride that has no flash point when fresh. In an open container the carbon tetrachloride evaporates faster, so the residue shows a progressively lower flash point, approaching that of the heavier gasoline fractions.<ref name="Slye-6-205">Slye (2008), p. 6-205.</ref>
Line 98: Line 101:


As a worked example, take a gasoline pool 2 m in diameter, with an area of 3.14 m². The factor in brackets is 1 − e<sup>−4.2</sup> = 0.985, so the heat release rate is 0.055 × 43,700 × 3.14 × 0.985, about 7.4 MW. The regression rate is 0.055/740 = 7.4 × 10<sup>−5</sup> m/s, or about 270 mm per hour, which lies inside the range of 150 to 300 mm per hour given by Slye (2008).<ref name="Slye-6-206" /> At this rate a layer 12.7 mm deep burns out in about 2.9 minutes, within Slye's 2½ to 5 minutes. If 50 L of gasoline formed this pool, it would be about 16 mm deep and burn for about 3.6 minutes.
As a worked example, take a gasoline pool 2 m in diameter, with an area of 3.14 m². The factor in brackets is 1 − e<sup>−4.2</sup> = 0.985, so the heat release rate is 0.055 × 43,700 × 3.14 × 0.985, about 7.4 MW. The regression rate is 0.055/740 = 7.4 × 10<sup>−5</sup> m/s, or about 270 mm per hour, which lies inside the range of 150 to 300 mm per hour given by Slye (2008).<ref name="Slye-6-206" /> At this rate a layer 12.7 mm deep burns out in about 2.9 minutes, within Slye's 2½ to 5 minutes. If 50 L of gasoline formed this pool, it would be about 16 mm deep and burn for about 3.6 minutes.
[[File:fse-gasoline-v4.svg|thumb|upright=1.5|alt=Line chart of gasoline pool fire heat release rate rising from about 0.3 MW at 0.5 m diameter to about 189 MW at 10 m|Heat release rate of a gasoline pool fire against pool diameter, from large-pool burning data.]]


An unconfined spill behaves differently. Small gasoline spills of 0.25 to 1 L on wood parquet and vinyl tile spread to depths of only 0.5 to 0.7 mm.<ref name="GW-2-299">Gottuk and White (2002), p. 2-299.</ref> On non-absorbing floors, such spills burned at about one fifth of the maximum pool burning rate.<ref name="GW-2-312">Gottuk and White (2002), p. 2-312.</ref> For a ruptured 208 L drum of gasoline, Gottuk and White (2002) estimate a burning area of 116 m², a peak of 56 MW and a burning time of only about 2 minutes.<ref name="GW-2-314">Gottuk and White (2002), p. 2-314.</ref>
An unconfined spill behaves differently. Small gasoline spills of 0.25 to 1 L on wood parquet and vinyl tile spread to depths of only 0.5 to 0.7 mm.<ref name="GW-2-299">Gottuk and White (2002), p. 2-299.</ref> On non-absorbing floors, such spills burned at about one fifth of the maximum pool burning rate.<ref name="GW-2-312">Gottuk and White (2002), p. 2-312.</ref> For a ruptured 208 L drum of gasoline, Gottuk and White (2002) estimate a burning area of 116 m², a peak of 56 MW and a burning time of only about 2 minutes.<ref name="GW-2-314">Gottuk and White (2002), p. 2-314.</ref>
Line 118: Line 122:


The dispensing equipment is designed to limit releases. Hoses carrying gasoline should have a breakaway device that retains the fuel in the hose, and nozzles must close automatically when released.<ref name="Rivkin-21-35">Rivkin (2008a), p. 21-35.</ref> Gasoline should only be put into a portable container approved for it.<ref name="Rivkin-21-39">Rivkin (2008a), p. 21-39.</ref>
The dispensing equipment is designed to limit releases. Hoses carrying gasoline should have a breakaway device that retains the fuel in the hose, and nozzles must close automatically when released.<ref name="Rivkin-21-35">Rivkin (2008a), p. 21-35.</ref> Gasoline should only be put into a portable container approved for it.<ref name="Rivkin-21-39">Rivkin (2008a), p. 21-39.</ref>
[[File:fse-gasoline-v5.jpg|thumb|upright=1.5|alt=a fuel dispenser with hose, breakaway coupling and nozzle on a concrete island|Gasoline dispenser with breakaway hose coupling and automatic-closing nozzle on a protective island.]]


Case histories in the handbook show why these rules exist. In Saint John, New Brunswick, in 1974, an emergency shutoff valve failed when a vehicle knocked over a dispenser. The released fuel ran into a warehouse below, exploded and killed five people.<ref name="Rivkin-21-35" /> Cleaning floors with gasoline is described as a common unsafe practice that can lead to fires and explosions.<ref name="Rivkin-21-33" /> Ordile (2008) adds that tanks that held leaded gasoline must be lead-free before they can be entered without breathing apparatus and protective clothing.<ref name="Ordile-7-27">Ordile (2008), p. 7-27.</ref>
Case histories in the handbook show why these rules exist. In Saint John, New Brunswick, in 1974, an emergency shutoff valve failed when a vehicle knocked over a dispenser. The released fuel ran into a warehouse below, exploded and killed five people.<ref name="Rivkin-21-35" /> Cleaning floors with gasoline is described as a common unsafe practice that can lead to fires and explosions.<ref name="Rivkin-21-33" /> Ordile (2008) adds that tanks that held leaded gasoline must be lead-free before they can be entered without breathing apparatus and protective clothing.<ref name="Ordile-7-27">Ordile (2008), p. 7-27.</ref>

Latest revision as of 08:29, 9 November 2026

Gasoline, also called petrol, is a volatile liquid motor fuel made of a mixture of light and heavy hydrocarbon fractions, and the most widely used flammable liquid.[1][2][3] In the United States classification of NFPA 30, as reported in the Fire Protection Handbook (2008), it is a Class IB flammable liquid. Its flash point is about −40 to −46 °C (−40 to −50 °F), and it boils over a range of about 38 to 204 °C.[4]

Gasoline gives off flammable vapour at ambient temperatures.[1] Only in severe cold does it fail to form an ignitable mixture above its surface.[5] The vapour is heavier than air, collects in pits and low places, and can travel along the ground to a distant ignition source and flash back.[6] Once ignited, a gasoline pool fire burns at about 0.055 kg/(m²·s) and releases about 43.7 MJ for every kilogram burned.[7] Gasoline is the first material ignited in many fatal vehicle fires and the most hazardous liquid commonly found at service stations.[8][5] Most of the requirements described here are US practice as summarised in the 2008 handbook.

Composition and grades

Gasoline is not a single compound. Slye (2008) describes it as "a compound of light and heavy fractions": the lighter fractions evaporate and burn first, and the heavier fractions later burn at a rate close to that of kerosene.[2] The boiling range of about 38 to 204 °C (100 to 400 °F) given for service station gasoline reflects this mixture.[4] Kanury (2002b) marks the gasoline entry in his property table as an approximate line, and Boucher (2008) notes that figures vary for some values.[9][10]

Motor gasoline is often blended with other components. US fuel statistics in the handbook note that the remaining part of the 85 percent ethanol fuel (E85) is gasoline, and that gasoline consumption includes the ethanol in gasohol and the ether MTBE.[11] Aviation gasoline (AVGAS) is listed separately in aviation fuel tables, and flammability tables give separate values for gasoline grades such as 100/130 and 115/145.[10][12] Boucher (2008) stresses that the octane rating of a fuel has no relation to the degree of its fire hazard.[10]

In the NFPA 30 system, a liquid is classed by its flash point and boiling point, the subject of flammable and combustible liquid classification. The service station table of Rivkin (2008a) places gasoline in Class IB, and diesel fuel no. 1, with a flash point of 38 °C (100 °F), in Class II.[4] Rivkin (2008a) states that the flash point of gasoline is about 83 °C (150 °F) lower than that of diesel fuel no. 1, which explains why gasoline is the more hazardous of the liquids found at service stations.[5]

Fire properties

The main fire properties of gasoline, as tabulated in the sources, are summarised below. The values differ between sources because gasoline is a mixture whose grade, season and test method vary.

Property Value Source
Flash point (closed cup) −40 to −46 °C (−40 to −50 °F) Rivkin (2008a), p. 21-32
Flash point (closed cup) −45 °C (228 K) Kanury (2002b), p. 2-193
Boiling range 38 to 204 °C (100 to 400 °F) Rivkin (2008a), p. 21-32
Lower and upper flammability limits in air about 1.4 and 7.6 % by volume Slye (2008), p. 6-197
Flammability limits, grade 100/130 1.3 and 7.1 % by volume Beyler (2002b), p. 2-176
Minimum ignition temperature in air about 441 °C (825 °F) Rivkin (2008a), p. 21-32
Density 740 kg/m³ Babrauskas (2002b), p. 3-26
Density at 20 °C 680.3 kg/m³ DiNenno et al. (2002), p. A-26
Vapour pressure at 20 °C 55.2 kPa DiNenno et al. (2002), p. A-26
Heat of combustion 43.7 MJ/kg Babrauskas (2002b), p. 3-26
Mass burning rate, large pool 0.055 kg/(m²·s) Babrauskas (2002b), p. 3-26

The flammability limits bound the range of vapour concentrations in air that can burn. For gasoline, Slye (2008) gives about 1.4 to 7.6 percent by volume, a narrow range at low concentration.[13] Beyler (2002b) gives 1.3 to 7.1 percent for grade 100/130 and 1.2 to 7.1 percent for grade 115/145.[12] The lower limit falls as the temperature rises. In a table for industrial ovens, Slye (2008) lists the lower limit of gasoline vapour as 1.07 percent at room temperature, 0.94 percent at 100 °C and 0.77 percent at 200 °C.[14]

Ignition temperature data scatter more widely. The service station table gives about 441 °C (825 °F), and Beyler (2002b) gives 440 °C for grade 100/130 and 470 °C for grade 115/145. Kanury (2002b) gives an estimate of 644 K, about 371 °C.[4][12][9] For AVGAS, Boucher (2008) lists an autoignition range of 825 to 960 °F (441 to 516 °C).[10] In pure oxygen the minimum ignition temperature of gasoline grade 100/130 drops from 440 °C to 316 °C (600 °F).[15]

Dot and range chart of gasoline flash points near minus 45 degrees and ignition temperatures between 316 and 516 degrees from several sources
Flash point and minimum ignition temperature of gasoline as tabulated in different sources.

The density depends on the grade and the temperature. Babrauskas (2002b) uses 740 kg/m³ in pool fire data, whereas an SFPE appendix table lists 680.3 kg/m³ at 20 °C, and an SFPE foam example uses a specific gravity of 0.72.[7][16][17] Per unit volume, Van der Graaf et al. (2021/2023) give an energy content of about 32 MJ per litre for petrol, against about 36 MJ per litre for diesel.[3] This agrees with the heat of combustion and density above: 43.7 MJ/kg × 0.74 kg/L gives about 32 MJ/L.

Vapour behaviour

The fire hazard of a flammable liquid comes from its vapour rather than from the liquid itself.[13] Kanury (2002b) explains that the partial pressure of the vapour just above a liquid surface is about equal to the saturation vapour pressure of the liquid at the surface temperature.[18] For an ideal gas mixture, this partial pressure divided by the total pressure gives the vapour concentration by volume:

Xv≈pvpatm

Symbol Description Unit
Xv vapour concentration (volume fraction) just above the liquid –
pv saturation vapour pressure at the liquid temperature kPa
patm total (atmospheric) pressure, 101.325 kPa at sea level kPa

At 20 °C, gasoline has a vapour pressure of 55.2 kPa.[16] The equation then gives a vapour concentration close to the surface of about 55.2/101.325 = 0.545, or 54.5 percent by volume. This is about seven times the upper flammability limit of 7.6 percent, so the vapour layer directly above warm gasoline is too rich to burn.[13] Kanury (2002b) describes how, with time, the belt of mixture between the lean and rich limits moves away from the surface as the vapour diffuses into the air.[18] The same reasoning explains why the vapour space of a closed gasoline tank is normally above the upper limit.[19]

Logarithmic bar chart comparing the 54.5 percent vapour concentration above gasoline at 20 degrees with its flammable range of 1.4 to 7.6 percent
Vapour concentration just above gasoline at 20 °C compared with its flammable range in air.

Ordile (2008) states that tanks of liquids with vapour pressures above 28 kPa (4 psia), such as gasoline, normally have a vapour space too rich to burn. If the liquid is between about −23 and −46 °C (−10 and −50 °F), the vapour space might be within the flammable range.[19] Air drawn in during off-loading, or sudden cooling by a rainstorm on a hot day, can also make part of the vapour space flammable. Because the vapours stratify, this can last hours or even days.[19]

Because gasoline vapour is heavier than air, it settles on floors and in pits. Slye (2008) states that such vapour can flow along the floor or ground for long distances, be ignited at a remote point and flash back. Removing it at floor level is usually the proper method of ventilation.[6] Wastewater treatment plants list gasoline among heavier-than-air gases and vapours, with storage tank leaks and tank truck spills as sources.[20] For the same reason, US rules described by Rivkin (2008a) place heat-producing appliances in repair garages in a separate room or at least 8 ft (2.4 m) above the floor.[21]

Cross-section of a garage floor with a gasoline spill, vapour flowing along the floor into a pit and towards a heater, and an exhaust at floor level
Heavier-than-air gasoline vapour flowing along a floor to a remote ignition source, with floor-level extraction and an elevated heater.

Mixing gasoline with a less flammable liquid does not make it safe for long. Slye (2008) describes a mixture of gasoline and carbon tetrachloride that has no flash point when fresh. In an open container the carbon tetrachloride evaporates faster, so the residue shows a progressively lower flash point, approaching that of the heavier gasoline fractions.[22]

Burning behaviour

Gasoline burns as a pool fire when it collects in a confined area, and as a thin spill fire when it spreads freely over a floor.[23] Slye (2008) gives a burning rate of 150 to 300 mm (6 to 12 in.) of liquid depth per hour. A pool 12.7 mm (½ in.) deep is expected to burn out in 2½ to 5 minutes.[2] The lighter fractions burn first and faster, and the burning rate later approaches that of kerosene, which Slye gives as 130 to 200 mm per hour.[2]

The heat release rate of a large pool follows from the mass burning rate per unit area, the heat of combustion and the area. The NRC Fire Dynamics Tools write it with an empirical factor that reduces the burning rate of small pools:[24]

Q˙=m˙″ΔHcA(1−e−kβD)ν=m˙″ρ

Symbol Description Unit
Q˙ heat release rate kW
m˙″ mass burning rate per unit area of a large pool kg/(m²·s)
ΔHc heat of combustion kJ/kg
A pool area m²
kβ empirical constant m⁻¹
D pool diameter m
ν regression rate (fall of the liquid surface) m/s
ρ liquid density kg/m³

The regression rate equation is the second relation in the same source.[25] For gasoline, Babrauskas (2002b) gives m˙″ = 0.055 kg/(m²·s), ΔHc = 43.7 MJ/kg, ρ = 740 kg/m³ and kβ = 2.1 m⁻¹.[7] The method assumes a fire burning in the open with the whole surface involved at once.[24]

As a worked example, take a gasoline pool 2 m in diameter, with an area of 3.14 m². The factor in brackets is 1 − e−4.2 = 0.985, so the heat release rate is 0.055 × 43,700 × 3.14 × 0.985, about 7.4 MW. The regression rate is 0.055/740 = 7.4 × 10−5 m/s, or about 270 mm per hour, which lies inside the range of 150 to 300 mm per hour given by Slye (2008).[2] At this rate a layer 12.7 mm deep burns out in about 2.9 minutes, within Slye's 2½ to 5 minutes. If 50 L of gasoline formed this pool, it would be about 16 mm deep and burn for about 3.6 minutes.

Line chart of gasoline pool fire heat release rate rising from about 0.3 MW at 0.5 m diameter to about 189 MW at 10 m
Heat release rate of a gasoline pool fire against pool diameter, from large-pool burning data.

An unconfined spill behaves differently. Small gasoline spills of 0.25 to 1 L on wood parquet and vinyl tile spread to depths of only 0.5 to 0.7 mm.[26] On non-absorbing floors, such spills burned at about one fifth of the maximum pool burning rate.[27] For a ruptured 208 L drum of gasoline, Gottuk and White (2002) estimate a burning area of 116 m², a peak of 56 MW and a burning time of only about 2 minutes.[28]

For their warehouse-spill example, Gottuk and White (2002) assume a gas-phase flame spread speed of 2 m/s. At 20 °C, gasoline is far above its flash point, so the whole spill becomes involved within seconds.[28][29] For AVGAS, Boucher (2008) lists a pool rate of flame spread of 700 to 800 ft/min (about 210 to 240 m/min).[10]

A continuous leak reaches a balance in which the fire burns the liquid as fast as it is released. Slye (2008) states that at a burning rate of 0.3 m per hour, a leak of 3.8 L/min (1 gal/min) reaches an equilibrium burning area of about 0.74 m² (8 ft²). A leak of 38 L/min reaches about 7.4 m².[2] With the regression rate of gasoline calculated above, a leak of 3.8 L/min gives about 0.85 m².

The smoke of gasoline fires is complex. Drysdale (2008) notes that with fuels such as propane and gasoline the variety of intermediate combustion products is very large, with a considerable potential to generate noxious gases.[30] For oxygen demand, the stoichiometric constant of hydrocarbon fuels such as gasoline and diesel is about 3.46 kg of oxygen per kilogram of fuel.[31]

Ignition sources and static electricity

Gasoline vapour can be ignited by flames, sparks, hot surfaces and static electricity. Ordile (2008) lists gasoline, jet fuels, toluene and light fuel oil among liquids that can build up dangerous static charges on their surface. Excessive turbulence, pumping two dissimilar materials, free fall of liquid through the vapour space and very fine filters are among the most likely causes of static ignition in tanks and tank vehicles.[32] The handbook recommends slowing the delivery rate until the fill pipe is covered, allowing at least 30 seconds of relaxation time downstream of a filter, and bonding the fill pipe to the tank vehicle.[33]

Static can also ignite gasoline during refuelling. At unattended US service stations, as described by Rivkin (2008a), customers must stay outside the vehicle while refuelling. A person who re-enters the vehicle can build up a charge on the seat and ignite residual vapour when removing the nozzle.[34] Hot surfaces are a second common source. In commercial vehicles, carburettor flooding or an electric fuel pump that does not shut down can spill gasoline onto a hot surface. Routhier (2008) notes that this is less critical with diesel fuel because of its higher flash point.[35]

Electrical equipment near dispensing is controlled for the same reason. The US code described by Rivkin (2008a) requires special electrical equipment up to 18 in. (0.5 m) above grade within a 20 ft (6.1 m) radius of refuelling areas. In 1976 near Gadsden, Alabama, a pump with a missing junction box cover ignited vapour during a tank truck delivery, and three responding fire fighters died when the truck exploded.[34]

Storage, dispensing and fire protection

Gasoline reaches the public through the motor fuel dispensing facility, whose US design requirements described in the 2008 handbook are based on NFPA 30A.[5] Rivkin (2008a) reports about 210,000 retail outlets selling motor fuel in 2000, and that 62 percent of fires at public service stations from 1994 to 1998 were vehicle fires.[36] Containers at service stations may not exceed 60 gal (227 L). Vent pipes of underground tanks storing Class I liquids such as gasoline must discharge at least 12 ft (3.7 m) above ground.[21] Gasoline tanks in vaults need ventilation and vapour detection that alarms at 25 percent of the lower flammable limit.[37]

The dispensing equipment is designed to limit releases. Hoses carrying gasoline should have a breakaway device that retains the fuel in the hose, and nozzles must close automatically when released.[38] Gasoline should only be put into a portable container approved for it.[39]

a fuel dispenser with hose, breakaway coupling and nozzle on a concrete island
Gasoline dispenser with breakaway hose coupling and automatic-closing nozzle on a protective island.

Case histories in the handbook show why these rules exist. In Saint John, New Brunswick, in 1974, an emergency shutoff valve failed when a vehicle knocked over a dispenser. The released fuel ran into a warehouse below, exploded and killed five people.[38] Cleaning floors with gasoline is described as a common unsafe practice that can lead to fires and explosions.[21] Ordile (2008) adds that tanks that held leaded gasoline must be lead-free before they can be entered without breathing apparatus and protective clothing.[40]

Foam agents are tested and specified on gasoline fires. In US practice described by Scheffey (2002), foam concentrates for hydrocarbon fuels are approved in a 9.29 m² (100 ft²) fire test similar to UL 162. The fixed-nozzle gasoline test has an extinguishment application density of 12.2 L/m² (0.30 gal/ft²).[41] For a cone roof gasoline tank protected by Type II foam chambers, an SFPE design example cites the NFPA 11 requirement of 55 minutes of continuous foam solution discharge.[42]

Vehicle fires

Gasoline is the first material ignited in many fatal vehicle fires. Long et al. (2008) identify two main categories of post-collision passenger vehicle fires: fuel-fed gasoline pool fires and engine compartment fires. About 60 percent of post-collision passenger vehicle fire fatalities in US data result from fires in which gasoline was the first material ignited.[8] Such fuel-fed fires generally occur when collision damage causes a gasoline leak and this fuel is the first material ignited.[8] Under US federal rules for commercial vehicles in interstate commerce, fuel tanks must pass drop, rupture, vent and spillage tests. These requirements were limited to gasoline tanks until 1973, when they were extended to diesel fuel tanks.[35]

See also

Notes

  1. ↑ 1.0 1.1 Slye (2008), p. 6-198.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 Slye (2008), p. 6-206.
  3. ↑ 3.0 3.1 Van der Graaf et al. (2021/2023), p. 25.
  4. ↑ 4.0 4.1 4.2 4.3 Rivkin (2008a), p. 21-32.
  5. ↑ 5.0 5.1 5.2 5.3 Rivkin (2008a), p. 21-30.
  6. ↑ 6.0 6.1 Slye (2008), p. 6-207.
  7. ↑ 7.0 7.1 7.2 Babrauskas (2002b), p. 3-26.
  8. ↑ 8.0 8.1 8.2 Long et al. (2008), p. 21-6.
  9. ↑ 9.0 9.1 Kanury (2002b), p. 2-193.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 Boucher (2008), p. 21-137.
  11. ↑ Rivkin (2008b), p. 21-51.
  12. ↑ 12.0 12.1 12.2 Beyler (2002b), p. 2-176.
  13. ↑ 13.0 13.1 13.2 Slye (2008), p. 6-197.
  14. ↑ Slye (2008), p. 6-203.
  15. ↑ Rosales and Stoltzfus (2008), p. 9-229.
  16. ↑ 16.0 16.1 DiNenno et al. (2002), p. A-26.
  17. ↑ Scheffey and Hickey (2002), p. 4-130.
  18. ↑ 18.0 18.1 Kanury (2002b), p. 2-194.
  19. ↑ 19.0 19.1 19.2 Ordile (2008), p. 7-16.
  20. ↑ Wheeler (2008), p. 9-150.
  21. ↑ 21.0 21.1 21.2 Rivkin (2008a), p. 21-33.
  22. ↑ Slye (2008), p. 6-205.
  23. ↑ Gottuk and White (2002), p. 2-298.
  24. ↑ 24.0 24.1 Iqbal and Salley (2004), p. 3-3.
  25. ↑ Iqbal and Salley (2004), p. 3-8.
  26. ↑ Gottuk and White (2002), p. 2-299.
  27. ↑ Gottuk and White (2002), p. 2-312.
  28. ↑ 28.0 28.1 Gottuk and White (2002), p. 2-314.
  29. ↑ Gottuk and White (2002), p. 2-315.
  30. ↑ Drysdale (2008), p. 2-19.
  31. ↑ Van Rossum (2027), §3.3.
  32. ↑ Ordile (2008), p. 7-29.
  33. ↑ Ordile (2008), p. 7-30.
  34. ↑ 34.0 34.1 Rivkin (2008a), p. 21-36.
  35. ↑ 35.0 35.1 Routhier (2008), p. 21-21.
  36. ↑ Rivkin (2008a), p. 21-29.
  37. ↑ Rivkin (2008a), p. 21-34.
  38. ↑ 38.0 38.1 Rivkin (2008a), p. 21-35.
  39. ↑ Rivkin (2008a), p. 21-39.
  40. ↑ Ordile (2008), p. 7-27.
  41. ↑ Scheffey (2002), p. 4-113.
  42. ↑ Scheffey and Hickey (2002), p. 4-131.

References

  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Boucher, B. (2008). Aviation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-135–21-149). National Fire Protection Association.
  • DiNenno, P. J., Drysdale, D., Beyler, C. L., Walton, W. D., Custer, R. L. P., Hall, J. R., Jr., & Watts, J. M., Jr. (Eds.). (2002). SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association; Society of Fire Protection Engineers.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Long, R. T., Jr., Colwell, J. D., Ray, R., Grossman, H. L., Thomas, B., & Strassburger, R. (2008). Passenger vehicle fires. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-3–21-14). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Rivkin, C. H. (2008a). Automotive and marine service station operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-29–21-40). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Routhier, B. (2008). Fire safety in commercial vehicles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-15–21-27). National Fire Protection Association.
  • Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-88–4-122). National Fire Protection Association; Society of Fire Protection Engineers.
  • Scheffey, J. L., & Hickey, H. E. (2002). Foam system calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-123–4-148). National Fire Protection Association; Society of Fire Protection Engineers.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.