Summary
Separation of pyrophoric gas cylinders from toxic, oxidising and flammable gas cylinders under NFPA 55, as described in the 2008 Fire Protection Handbook: 6.1 m (20 ft), or less behind a noncombustible barrier at least 1.5 m (5 ft) high with half an hour of fire resistance.
Original illustration for Silane.
- Alt text: Plan view: pyrophoric gas cylinders 6.1 m from toxic, oxidising and flammable cylinders, or closer behind a 1.5 m high half-hour barrier.
Licensing