Skip to content

File:Fse-fire-propagation-apparatus-v2.svg: Difference between revisions

From Fire Safety Academy Wiki
Lisa (talk | contribs)
Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
 
Linda (talk | contribs)
Remove bibliographic source lines from image captions and descriptions
 
(One intermediate revision by one other user not shown)
Line 1: Line 1:
== Summary ==
== Summary ==
Ignition data for an XLPO/XLPO communications cable in the fire propagation apparatus. The inverse square root of the ignition time is linear in the heat flux; the slope gives TRP = 537 kW·s½/m² and the intercept the critical heat flux of 19.9 kW/m². Based on Tewarson (2002), pp. 3-84 and 3-93.
Ignition data for an XLPO/XLPO communications cable in the fire propagation apparatus. The inverse square root of the ignition time is linear in the heat flux; the slope gives TRP = 537 kW·s½/m² and the intercept the critical heat flux of 19.9 kW/m².


Original illustration for [[Fire propagation apparatus]].
Original illustration for [[Fire propagation apparatus]].


* Source basis: Tewarson (2002), p. 3-83 (Equation 2), p. 3-84 (TRP as inverse slope), p. 3-93 (Example 4 ignition data)
* Alt text: Scatter plot of four ignition points for an XLPO cable on a straight line crossing zero at 19.9 kW/m², slope giving TRP of 537.
* Alt text: Scatter plot of four ignition points for an XLPO cable on a straight line crossing zero at 19.9 kW/m², slope giving TRP of 537.


== Licensing ==
== Licensing ==
New drawing by Fire Safety Academy. © Fire Safety Academy.
New drawing by Fire Safety Academy. © Fire Safety Academy.

Latest revision as of 08:31, 8 November 2026

Summary

Ignition data for an XLPO/XLPO communications cable in the fire propagation apparatus. The inverse square root of the ignition time is linear in the heat flux; the slope gives TRP = 537 kW·s½/m² and the intercept the critical heat flux of 19.9 kW/m².

Original illustration for Fire propagation apparatus.

  • Alt text: Scatter plot of four ignition points for an XLPO cable on a straight line crossing zero at 19.9 kW/m², slope giving TRP of 537.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current08:28, 8 November 2026Thumbnail for version as of 08:28, 8 November 20261,510 × 965 (13 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
08:15, 8 November 2026Thumbnail for version as of 08:15, 8 November 20261,190 × 879 (12 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata