The autoignition temperature explains why silane needs no ignition source. In the SFPE Handbook, Kanury describes autoignition as a self-induced initiation of flame in a relatively large volume of reacting gas and air, unlike piloted ignition at a local igniter.<ref name="KA-2-195">Kanury (2002b), p. 2-195.</ref> The NFPA handbook defines the autoignition temperature of a liquid as the temperature of the surroundings that starts combustion without an obvious ignition source such as a spark or flame.<ref name="SL-6-201">Slye (2008), p. 6-201.</ref> ''Introduction to Fire Safety Engineering'' explains combustion with the fire triangle of oxygen, fuel and temperature. A fuel mixed with oxygen cannot ignite unless enough heat is added, and the ignition temperature is the lowest temperature at which ignition occurs.<ref name="VR-4.2">Van Rossum (2027), §4.2.</ref> For silane the tabulated autoignition temperature is 120 K below a normal room temperature of 20 °C, so the heat leg of the triangle is already present wherever the gas meets air.<ref name="IFEG-3.3-3" /><ref name="LE-6-166" /> | The autoignition temperature explains why silane needs no ignition source. In the SFPE Handbook, Kanury describes autoignition as a self-induced initiation of flame in a relatively large volume of reacting gas and air, unlike piloted ignition at a local igniter.<ref name="KA-2-195">Kanury (2002b), p. 2-195.</ref> The NFPA handbook defines the autoignition temperature of a liquid as the temperature of the surroundings that starts combustion without an obvious ignition source such as a spark or flame.<ref name="SL-6-201">Slye (2008), p. 6-201.</ref> ''Introduction to Fire Safety Engineering'' explains combustion with the fire triangle of oxygen, fuel and temperature. A fuel mixed with oxygen cannot ignite unless enough heat is added, and the ignition temperature is the lowest temperature at which ignition occurs.<ref name="VR-4.2">Van Rossum (2027), §4.2.</ref> For silane the tabulated autoignition temperature is 120 K below a normal room temperature of 20 °C, so the heat leg of the triangle is already present wherever the gas meets air.<ref name="IFEG-3.3-3" /><ref name="LE-6-166" /> | ||
[[File:fse-silane-v1.svg|thumb|upright=1.5|alt=Two bar charts: silane burns from 1 to 100 percent in air and autoignites at minus 100 °C, unlike methane, propane, hydrogen and acetylene.|Flammable range in air (left) and autoignition temperature (right) of silane compared with four other flammable gases. Silane is the only one whose autoignition temperature lies below room temperature.]] | |||
This property changes the usual safety logic for gases. The IFEG notes that ignition requires a fuel, an oxidiser and a source of heat, and that the heat source is often external. For gaseous fuels the normal strategy is to keep the concentration well below the LFL, because very weak sources of a few millijoules can ignite a mixture inside the flammable range.<ref name="IFEG-3.3-2">National Research Council of Canada et al. (2005), p. 3.3-2.</ref> For most flammable gases, control of ignition sources is a second line of defence alongside the limiting of gas–air mixtures.<ref name="LE-6-175">Lemoff (2008), p. 6-175.</ref> For a pyrophoric gas, which needs no ignition source, that second line does not exist. The concept of a flash point has no practical meaning either, because a flammable gas is always above its flash point, usually well above it.<ref name="LE-6-166" /> | This property changes the usual safety logic for gases. The IFEG notes that ignition requires a fuel, an oxidiser and a source of heat, and that the heat source is often external. For gaseous fuels the normal strategy is to keep the concentration well below the LFL, because very weak sources of a few millijoules can ignite a mixture inside the flammable range.<ref name="IFEG-3.3-2">National Research Council of Canada et al. (2005), p. 3.3-2.</ref> For most flammable gases, control of ignition sources is a second line of defence alongside the limiting of gas–air mixtures.<ref name="LE-6-175">Lemoff (2008), p. 6-175.</ref> For a pyrophoric gas, which needs no ignition source, that second line does not exist. The concept of a flash point has no practical meaning either, because a flammable gas is always above its flash point, usually well above it.<ref name="LE-6-166" /> | ||
| Line 25: | Line 26: | ||
Silane does not always behave in this way. A release may self-ignite with a visible flame, but it may also escape without ignition or with delayed ignition, possibly resulting in a [[detonation]]. When released into a confined area such as a gas cabinet, silane has been known to detonate.<ref name="DP-9-127" /> A combustion explosion requires a quantity of flammable gas–air mixture to be present in an enclosure.<ref name="LE-6-174">Lemoff (2008), p. 6-174.</ref> | Silane does not always behave in this way. A release may self-ignite with a visible flame, but it may also escape without ignition or with delayed ignition, possibly resulting in a [[detonation]]. When released into a confined area such as a gas cabinet, silane has been known to detonate.<ref name="DP-9-127" /> A combustion explosion requires a quantity of flammable gas–air mixture to be present in an enclosure.<ref name="LE-6-174">Lemoff (2008), p. 6-174.</ref> | ||
[[File:fse-silane-v2.svg|thumb|upright=1.5|alt=Flow diagram: a silane release either self-ignites at once as a flame, or does not ignite at once, accumulates and may detonate in a gas cabinet.|Possible courses of a silane release. Outdoors the gas usually ignites at once and burns like other flammable gases; with no or delayed ignition, a mixture can accumulate and, in a confined space such as a gas cabinet, detonate.]] | |||
A detonation is an explosion in which the flame travels at supersonic speed through the unburned mixture. Its pressure rise is highly nonuniform and almost instantaneous, which rules out protection by explosion venting or explosion suppression.<ref name="ZA-2-99">Zalosh (2008), p. 2-99.</ref> Most accidental explosions are deflagrations. Detonations can occur in very flammable gas mixtures when there is an exceptionally strong ignition source, a long or obstructed geometry or very high turbulence.<ref name="ZA-2-100">Zalosh (2008), p. 2-100.</ref> | A detonation is an explosion in which the flame travels at supersonic speed through the unburned mixture. Its pressure rise is highly nonuniform and almost instantaneous, which rules out protection by explosion venting or explosion suppression.<ref name="ZA-2-99">Zalosh (2008), p. 2-99.</ref> Most accidental explosions are deflagrations. Detonations can occur in very flammable gas mixtures when there is an exceptionally strong ignition source, a long or obstructed geometry or very high turbulence.<ref name="ZA-2-100">Zalosh (2008), p. 2-100.</ref> | ||
| Line 39: | Line 41: | ||
== Gas cabinet ventilation and leak rates == | == Gas cabinet ventilation and leak rates == | ||
NFPA 318 contains performance-based guidance on ventilation rates for silane gas cabinets, based on research testing by FM Global. The handbook reproduces two of its tools: a table of silane flow rates through restricted flow orifices (RFOs) and a chart of average silane concentrations in a ventilated enclosure.<ref name="DP-9-127" /> Limiting orifices are one of the basic safeguards against gas explosions, because they minimise the quantity of gas that can be released.<ref name="LE-6-175" /> The table assumes a source temperature of 25 °C, a downstream pressure of 0 bar and a discharge coefficient of 0.8.<ref name="DP-9-127" /> | NFPA 318 contains performance-based guidance on ventilation rates for silane gas cabinets, based on research testing by FM Global. The handbook reproduces two of its tools: a table of silane flow rates through restricted flow orifices (RFOs) and a chart of average silane concentrations in a ventilated enclosure.<ref name="DP-9-127" /> Limiting orifices are one of the basic safeguards against gas explosions, because they minimise the quantity of gas that can be released.<ref name="LE-6-175" /> The table assumes a source temperature of 25 °C, a downstream pressure of 0 bar and a discharge coefficient of 0.8.<ref name="DP-9-127" /> | ||
[[File:fse-silane-v3.svg|thumb|upright=1.5|alt=Cross-section of a gas cabinet with a silane cylinder, restricted flow orifice, exhaust duct to treatment, gas detector and internal sprinkler.|Main features of a ventilated silane gas cabinet: a restricted flow orifice limits the leak rate, continuous exhaust dilutes and removes the gas to treatment, and the exhaust is monitored.]] | |||
The table does not print its flow unit. In each pair, the first value is about 0.47 times the value in brackets, which is the factor that converts cubic feet per minute into litres per second (1 ft³ = 0.0283 m³). The values are therefore read here as litres per second, with cubic feet per minute in brackets.<ref name="DP-9-127" /><ref name="SFPE-A-13">DiNenno et al. (2002), p. A-13.</ref> | The table does not print its flow unit. In each pair, the first value is about 0.47 times the value in brackets, which is the factor that converts cubic feet per minute into litres per second (1 ft³ = 0.0283 m³). The values are therefore read here as litres per second, with cubic feet per minute in brackets.<ref name="DP-9-127" /><ref name="SFPE-A-13">DiNenno et al. (2002), p. A-13.</ref> | ||
| Line 71: | Line 74: | ||
At an exhaust flow of 142 L/s the average concentration becomes 100 × 1.18 / (1.18 + 142) = 0.82 percent, or 82 percent of the LFL. At 284 L/s it falls to 0.41 percent, and at 708 L/s to 0.17 percent. These results agree with the 103.4 bar curve in the NFPA 318 chart, which shows about 0.8 percent at 142 L/s and about 0.2 percent at 708 L/s.<ref name="DP-9-127" /> | At an exhaust flow of 142 L/s the average concentration becomes 100 × 1.18 / (1.18 + 142) = 0.82 percent, or 82 percent of the LFL. At 284 L/s it falls to 0.41 percent, and at 708 L/s to 0.17 percent. These results agree with the 103.4 bar curve in the NFPA 318 chart, which shows about 0.8 percent at 142 L/s and about 0.2 percent at 708 L/s.<ref name="DP-9-127" /> | ||
[[File:fse-silane-v4.svg|thumb|upright=1.5|alt=Line chart: average silane concentration falls from above 1 percent to 0.17 percent as exhaust flow rises from 50 to 708 L/s; LFL line at 1 percent.|Average silane concentration in a well-mixed, ventilated enclosure for a leak of 1.18 L/s (0.25 mm orifice, 103.4 bar), calculated with the dilution balance, with the lower flammable limit of 1.0 percent and 25 percent of it.]] | |||
Gas detectors usually express a flammable gas reading as a percentage of the LFL.<ref name="CH-14-100" /> For silane, 25 percent of the LFL equals 0.25 percent by volume, or 2,500 parts per million.<ref name="CH-14-100" /> The example also shows the value of the orifice. With a 0.51 mm orifice the leak is 4.72 L/s and the minimum flow rises to 467 L/s. At 142 L/s the average concentration would then be 3.2 percent, well inside the flammable range.<ref name="DP-9-127" /> | Gas detectors usually express a flammable gas reading as a percentage of the LFL.<ref name="CH-14-100" /> For silane, 25 percent of the LFL equals 0.25 percent by volume, or 2,500 parts per million.<ref name="CH-14-100" /> The example also shows the value of the orifice. With a 0.51 mm orifice the leak is 4.72 L/s and the minimum flow rises to 467 L/s. At 142 L/s the average concentration would then be 3.2 percent, well inside the flammable range.<ref name="DP-9-127" /> | ||
| Line 80: | Line 84: | ||
NFPA 55 also requires separation of gas cylinders by hazard class. Pyrophoric gases must be kept 6.1 m (20 ft) from toxic or highly toxic, oxidising and flammable gases. This distance can be reduced without limit by a noncombustible barrier at least 1.5 m (5 ft) high with a fire resistance rating of at least half an hour.<ref name="LR-7-38" /> For laboratories using chemicals, Anderson (2008a) describes special continuously ventilated enclosures for lecture bottle-size cylinders of pyrophoric gases. Larger cylinders need approved continuously ventilated gas cabinets with sprinkler protection inside the cabinet, together with compliance with NFPA 55.<ref name="AN-9-165" /> | NFPA 55 also requires separation of gas cylinders by hazard class. Pyrophoric gases must be kept 6.1 m (20 ft) from toxic or highly toxic, oxidising and flammable gases. This distance can be reduced without limit by a noncombustible barrier at least 1.5 m (5 ft) high with a fire resistance rating of at least half an hour.<ref name="LR-7-38" /> For laboratories using chemicals, Anderson (2008a) describes special continuously ventilated enclosures for lecture bottle-size cylinders of pyrophoric gases. Larger cylinders need approved continuously ventilated gas cabinets with sprinkler protection inside the cabinet, together with compliance with NFPA 55.<ref name="AN-9-165" /> | ||
[[File:fse-silane-v5.svg|thumb|upright=1.5|alt=Plan view: pyrophoric gas cylinders 6.1 m from toxic, oxidising and flammable cylinders, or closer behind a 1.5 m high half-hour barrier.|Separation of pyrophoric gas cylinders from toxic, oxidising and flammable gas cylinders under NFPA 55, as described in the 2008 Fire Protection Handbook: 6.1 m (20 ft), or less behind a noncombustible barrier at least 1.5 m (5 ft) high with half an hour of fire resistance.]] | |||
For bulk systems, the CGA data have been used to set minimum separation distances. The CGA document also covers siting, equipment design, piping, controls, fire protection, gas detection and ventilation. By 2008, P32-2000 had been revised and renamed CGA G-13, ''Storage and Handling of Silane and Silane Mixtures''. Appendix material in NFPA 318 gives guidance on separating bulk silane systems from buildings, based on the system pressure and the size of the pressure relief valve.<ref name="DP-9-127" /> | For bulk systems, the CGA data have been used to set minimum separation distances. The CGA document also covers siting, equipment design, piping, controls, fire protection, gas detection and ventilation. By 2008, P32-2000 had been revised and renamed CGA G-13, ''Storage and Handling of Silane and Silane Mixtures''. Appendix material in NFPA 318 gives guidance on separating bulk silane systems from buildings, based on the system pressure and the size of the pressure relief valve.<ref name="DP-9-127" /> | ||
Latest revision as of 08:27, 8 November 2026
Silane is a gas with the chemical formula SiH4 that belongs to the small group of pyrophoric gases: flammable gases that ignite spontaneously in air, without any source of ignition.[1][2] Pyrophoric gases are not widely used and are most likely to be found in semiconductor manufacturing, where silane serves as a source of silicon and its use has grown greatly.[2][3] Its hazard is unusual because a release can develop in two different ways. The gas may self-ignite at once with a visible flame, or it may escape with no ignition or with delayed ignition, which can end in a detonation. In gas cabinets, silane has been known to detonate.[3]
A compilation of flammability data gives silane a flammable range of 1.0 to 100 percent by volume in air and an autoignition temperature of −100 °C, far below room temperature.[4] For the United States, the 2008 NFPA Fire Protection Handbook describes protection under NFPA 55 and NFPA 318. It relies on small indoor quantities, ventilated gas cabinets, flow-limiting orifices, exhaust treatment, gas detection and separation from other gases.[5][6][7][8][3]
Classification
The handbook chapter on gases uses the categories of NFPA 55, Standard for the Storage, Use, and Handling of Compressed Gases and Cryogenic Fluids in Portable and Stationary Containers, Cylinders, and Tanks. These categories match those used by the United States Department of Transportation (DOT) for labelling gas shipments.[9] NFPA 55 divides physical hazards into flammable, nonflammable, oxidising, pyrophoric and unstable reactive gases. Pyrophoric gases form a class of their own, although they are also flammable gases. The handbook names silane and phosphine as examples and notes that their storage is of special concern because they need no ignition source to burn.[2]
Silane also meets the general definition of a flammable gas. NFPA 55 defines a flammable gas as a material that is a gas at 20 °C (68 °F) or less at an absolute pressure of 101.325 kPa. It must also be ignitable in a mixture of 13 percent or less by volume with air, or have a flammable range in air at least 12 percentage points wide.[9] With a lower limit of 1.0 percent and an upper limit of 100 percent, silane meets both criteria by a wide margin.[4] The DOT definition of Division 2.1 flammable gases uses the same two criteria.[10]
The DOT hazard classes reproduced in the handbook have no separate division for pyrophoric gases. Their definition of a pyrophoric material, in Division 4.2, covers a liquid or solid that can ignite within 5 minutes after contact with air, even in small quantities.[11] In general terms silane is a pyrophoric material: the NUREG-1805 glossary defines pyrophoricity as the spontaneous combustion of a material upon exposure to air, that is, to atmospheric oxygen.[12]
Silane is handled in pressurised compressed gas cylinders and in bulk storage systems.[13] NFPA 55 defines a compressed gas as a material that is a gas at 20 °C or less at 101.325 kPa and has a boiling point of 20 °C or less at that pressure.[14] Silane boils at −112 °C, so it meets the boiling point criterion.[4] The handbook gives the usual upper limit of compressed gas container pressure as 1,800 to 3,600 psi, about 12,400 to 24,800 kPa, set mainly by the economics of container construction.[14] The silane leak data in NFPA 318 cover source pressures up to 103.4 bar (1,500 psi).[3]
Flammability and ignition properties
The table of flammability data in the International Fire Engineering Guidelines (IFEG, 2005) lists silane with a lower flammable limit (LFL) of 1.0 percent by volume and an upper flammable limit (UFL) of 100 percent. The same table gives an autoignition temperature of −100 °C in air and a boiling point of −112 °C; no flash point is given.[4] For comparison, methane in the same table has limits of 5.0 and 15 percent and an autoignition temperature of 640 °C. Silane's flammable range is therefore 99 percentage points wide against 10 for methane, and its autoignition temperature lies 740 K lower.[4] The flammability limits mark the leanest and richest mixtures through which a flame can travel. Below the LFL a flame stays at the ignition source, while above it a flame front propagates through the whole air volume.[15]
The autoignition temperature explains why silane needs no ignition source. In the SFPE Handbook, Kanury describes autoignition as a self-induced initiation of flame in a relatively large volume of reacting gas and air, unlike piloted ignition at a local igniter.[16] The NFPA handbook defines the autoignition temperature of a liquid as the temperature of the surroundings that starts combustion without an obvious ignition source such as a spark or flame.[17] Introduction to Fire Safety Engineering explains combustion with the fire triangle of oxygen, fuel and temperature. A fuel mixed with oxygen cannot ignite unless enough heat is added, and the ignition temperature is the lowest temperature at which ignition occurs.[18] For silane the tabulated autoignition temperature is 120 K below a normal room temperature of 20 °C, so the heat leg of the triangle is already present wherever the gas meets air.[4][2]
This property changes the usual safety logic for gases. The IFEG notes that ignition requires a fuel, an oxidiser and a source of heat, and that the heat source is often external. For gaseous fuels the normal strategy is to keep the concentration well below the LFL, because very weak sources of a few millijoules can ignite a mixture inside the flammable range.[19] For most flammable gases, control of ignition sources is a second line of defence alongside the limiting of gas–air mixtures.[20] For a pyrophoric gas, which needs no ignition source, that second line does not exist. The concept of a flash point has no practical meaning either, because a flammable gas is always above its flash point, usually well above it.[2]
Silane is slightly heavier than air. Its specific density at standard conditions is 1.114, with air at 1.000.[1] The handbook warns that such data must be used with care. Gas leaking from high pressure cools the air into which it flows, and the cooled mixture is denser than the specific density suggests until it warms up again.[1]
Behaviour on release
The burning characteristics of pyrophoric gases such as silane, dichlorosilane, diborane and phosphine are not fully understood. According to DeGiorgio and Peterkin, this is mostly because engineering controls have been so successful in eliminating uncontrolled releases.[8][3] Experience has shown that when a leak occurs in an unconfined area, such as outdoors, pyrophoric gases usually ignite on release. They then burn in a manner similar to other flammable gases.[3]
Silane does not always behave in this way. A release may self-ignite with a visible flame, but it may also escape without ignition or with delayed ignition, possibly resulting in a detonation. When released into a confined area such as a gas cabinet, silane has been known to detonate.[3] A combustion explosion requires a quantity of flammable gas–air mixture to be present in an enclosure.[21]
A detonation is an explosion in which the flame travels at supersonic speed through the unburned mixture. Its pressure rise is highly nonuniform and almost instantaneous, which rules out protection by explosion venting or explosion suppression.[22] Most accidental explosions are deflagrations. Detonations can occur in very flammable gas mixtures when there is an exceptionally strong ignition source, a long or obstructed geometry or very high turbulence.[23]
An enclosure completely filled with a flammable gas–air mixture would have to withstand about 414 to 758 kPa (60 to 110 psi) to remain intact. Conventional structures withstand only 3.45 to 6.89 kPa (0.5 to 1.0 psi). Most combustion explosions in buildings occur with less than 25 percent of the enclosure filled with flammable mixture.[20] Studies by the Compressed Gas Association (CGA) on releases of large quantities of silane led to the publication CGA P32-2000, Safe Storage and Handling of Silane and Silane Mixtures. The minimum separation distances derived from these data recognise both the probability of immediate ignition and that of latent ignition with explosive effects.[3]
Use in semiconductor manufacturing
Integrated circuits are built on silicon wafers in cleanrooms through several hundred process steps. Acids, alkalis, flammable liquids, flammable gases, pyrophoric gases and toxic gases are common in such plants.[24] During wafer preparation a thin surface layer of silicon is grown in an epitaxial reactor in the bipolar process.[25] Later, layers are added by chemical vapour deposition (CVD), in which a thin film forms on the wafer through the chemical reaction of gases.[26] Silane is used in this industry as a source of silicon.[3] The process gases may be pure or mixed with a carrier gas such as hydrogen or nitrogen.[8]
The handbook counts pyrophoric gases among the hazards of a semiconductor fabrication facility that are not widely encountered in other industries.[27] Its recommended practice is to place pyrophoric and toxic gases outside the plant and pipe them to the cleanroom in welded stainless steel tubing. Process equipment using high concentrations of pyrophoric gases such as silane should have exhaust gas conditioning in the exhaust stream. The exhaust systems should carry continuous monitoring devices that warn of abnormal conditions.[8] Exhaust systems serving processes with toxic materials should keep running during a fire or chemical spill, so that fumes can still be removed and treated.[27]
NFPA 318, Standard for the Protection of Semiconductor Fabrication Facilities, was first published in 1992 and was in its 2006 edition when the handbook appeared. It applies to semiconductor facilities that contain a cleanroom or clean zone. Besides construction, sprinklers and ventilation, it pays particular attention to cylinders of hazardous gases and to bulk silane storage systems.[13] The handbook recommends the squib-actuated ultra-high-speed water spray deluge system for special hazards that include silane containment cells.[28] NFPA 15 defines such a system as one that can start discharging water within 100 milliseconds of detection.[29]
Gas cabinet ventilation and leak rates
NFPA 318 contains performance-based guidance on ventilation rates for silane gas cabinets, based on research testing by FM Global. The handbook reproduces two of its tools: a table of silane flow rates through restricted flow orifices (RFOs) and a chart of average silane concentrations in a ventilated enclosure.[3] Limiting orifices are one of the basic safeguards against gas explosions, because they minimise the quantity of gas that can be released.[20] The table assumes a source temperature of 25 °C, a downstream pressure of 0 bar and a discharge coefficient of 0.8.[3]
The table does not print its flow unit. In each pair, the first value is about 0.47 times the value in brackets, which is the factor that converts cubic feet per minute into litres per second (1 ft³ = 0.0283 m³). The values are therefore read here as litres per second, with cubic feet per minute in brackets.[3][30]
For a 0.25 mm (0.010 in.) orifice the flow is 1.18 L/s at 103.4 bar (1,500 psi) and 0.11 L/s at 13.8 bar (200 psi). Source pressure thus changes the leak rate by a factor of about 11. Flows through 0.36 mm and 0.25 mm orifices equal 49 and 25 percent of the flow through a 0.51 mm orifice, which matches the ratio of their opening areas.[3] The chart is drawn for a 0.25 mm orifice, with multipliers of 2.0 for 0.36 mm, 4.0 for 0.51 mm and 0.36 for 0.15 mm.[3]
A simple volume balance links leak rate, ventilation and concentration. The handbook chapter on flammable liquids uses it for solvent vapour. A mixture with more than (100 − LFL)/LFL volumes of air per volume of fuel is too lean to ignite, and the air needed is proportional to the release rate.[31] Applied to a steady leak into a well-mixed cabinet, this gives the minimum ventilation flow and the average concentration:
| Symbol | Description | Unit |
|---|---|---|
| leak rate of silane, for example through a restricted flow orifice | L/s | |
| ventilation (exhaust) flow through the enclosure | L/s | |
| ventilation flow that just holds the average at the lower flammable limit | L/s | |
| lower flammable limit of silane in air, 1.0 | % by volume | |
| average silane concentration in the enclosure | % by volume |
The balance is valid only for a steady leak and a well-mixed enclosure. It gives an average, not the concentration near the leak, and it says nothing about whether the gas ignites. The handbook stresses that in practice a substantial excess of ventilation air is applied as a safety factor.[31][32]
Worked example: cylinder leak through a 0.25 mm orifice
A silane cylinder at 103.4 bar (1,500 psi) is fitted with a 0.25 mm (0.010 in.) RFO, which limits a full release to 1.18 L/s.[3] With an LFL of 1.0 percent, one volume of silane must be mixed with at least (100 − 1.0)/1.0 = 99 volumes of air.[4][31] The minimum ventilation flow is 1.18 × 99 = 116.8 L/s, rounded up to 117 L/s. This value has no safety margin.
At an exhaust flow of 142 L/s the average concentration becomes 100 × 1.18 / (1.18 + 142) = 0.82 percent, or 82 percent of the LFL. At 284 L/s it falls to 0.41 percent, and at 708 L/s to 0.17 percent. These results agree with the 103.4 bar curve in the NFPA 318 chart, which shows about 0.8 percent at 142 L/s and about 0.2 percent at 708 L/s.[3]
Gas detectors usually express a flammable gas reading as a percentage of the LFL.[15] For silane, 25 percent of the LFL equals 0.25 percent by volume, or 2,500 parts per million.[15] The example also shows the value of the orifice. With a 0.51 mm orifice the leak is 4.72 L/s and the minimum flow rises to 467 L/s. At 142 L/s the average concentration would then be 3.2 percent, well inside the flammable range.[3]
Storage and handling requirements in the United States
In the United States, NFPA 55, as described by Lemoff and Rivkin (2008), limits the maximum allowable quantity (MAQ) of each gas class per control area. A control area is a space separated from other areas by a fire barrier. Above these quantities, additional fire protection requirements apply.[6]
The 2005 edition, as reproduced in the handbook, allows no pyrophoric gas at all in unsprinklered areas. In sprinklered areas it allows 1.4 m³ (50 ft³) of nonliquefied or 1.8 kg (4 lb) of liquefied pyrophoric gas without a gas cabinet. With a gas cabinet, gas room or exhausted enclosure, these values double to 2.8 m³ (100 ft³) and 3.6 kg (8 lb).[5] An ordinary nonliquefied flammable gas is allowed 28 m³ (1,000 ft³) in an unsprinklered area without a cabinet.[5]
NFPA 55 also requires separation of gas cylinders by hazard class. Pyrophoric gases must be kept 6.1 m (20 ft) from toxic or highly toxic, oxidising and flammable gases. This distance can be reduced without limit by a noncombustible barrier at least 1.5 m (5 ft) high with a fire resistance rating of at least half an hour.[6] For laboratories using chemicals, Anderson (2008a) describes special continuously ventilated enclosures for lecture bottle-size cylinders of pyrophoric gases. Larger cylinders need approved continuously ventilated gas cabinets with sprinkler protection inside the cabinet, together with compliance with NFPA 55.[7]
For bulk systems, the CGA data have been used to set minimum separation distances. The CGA document also covers siting, equipment design, piping, controls, fire protection, gas detection and ventilation. By 2008, P32-2000 had been revised and renamed CGA G-13, Storage and Handling of Silane and Silane Mixtures. Appendix material in NFPA 318 gives guidance on separating bulk silane systems from buildings, based on the system pressure and the size of the pressure relief valve.[3]
Detection and emergency response
Silane is one of the gases routinely addressed by gas detection, and the handbook lists it among the commonly monitored toxic gases. It adds that most flammable gases are also toxic at some concentration.[15] Fixed gas detection is needed wherever permanent gas hazards exist, and semiconductor fabrication facilities are named among the typical sites.[33] A gas detection system must take gas density into account: in still air, a heavier-than-air gas usually shows its highest concentrations at low points. Sensor placement must also allow for the cooling of gas that leaks from high pressure.[1] In semiconductor plants, continuous monitoring is also fitted to the exhaust systems of process equipment that uses silane.[8]
The handbook's general guidance for gas emergencies distinguishes "no fire" and "fire" situations. Without fire, the aim is to dilute and disperse the gas while stopping the flow if possible. With fire, the aim is to control the heat with water while stopping the flow.[20][34] Actual extinguishment is generally limited to small leaks that would not present a hazard if they reignited. Gas that keeps escaping after the flame is put out can turn a fire into a combustion explosion.[34] Outdoors, a silane leak usually ignites on release and then burns like other flammable gases.[3]
Limits of knowledge and common misconceptions
It would be wrong to assume that a pyrophoric gas always ignites at the moment of release and therefore cannot form an explosive mixture. For silane this is not the case. Releases with no ignition or delayed ignition are recognised hazards, and silane has been known to detonate in gas cabinets.[3] Dilution also offers less margin than for methane. A mixture of only 1.0 percent silane in air is already flammable, against 5.0 percent for methane.[4]
Tabulated ignition data have limits. Kanury shows that the autoignition temperature of a gas mixture is lower in a larger vessel, at higher pressure and for fuels with a larger heat of combustion or molecular weight.[35] A single tabulated value such as −100 °C therefore applies to the conditions under which it was measured. The dilution balance above covers only the average concentration. It cannot predict local pockets of gas, ignition delay or the conditions that turn burning into detonation.[31][23]
The requirements described here are those of United States documents as reproduced in the 2008 handbook: NFPA 55 (2005 edition), NFPA 318 (2006 edition) and CGA P32-2000, by then revised as G-13.[5][13][3] The 2006 edition of NFPA 318 had added a new chapter on quantity limits for hazardous materials, coordinated with NFPA 5000, Building Construction and Safety Code.[13] The handbook itself notes that the burning characteristics of pyrophoric gases are still not fully understood.[8]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 Cholin (2008a), p. 14-107.
- ↑ 2.0 2.1 2.2 2.3 2.4 Lemoff (2008), p. 6-166.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 DeGiorgio and Peterkin (2008), p. 9-127.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Babrauskas (2003), as cited in National Research Council of Canada et al. (2005), p. 3.3-3.
- ↑ 5.0 5.1 5.2 5.3 Lemoff and Rivkin (2008), p. 7-39.
- ↑ 6.0 6.1 6.2 Lemoff and Rivkin (2008), p. 7-38.
- ↑ 7.0 7.1 Anderson (2008a), p. 9-165.
- ↑ 8.0 8.1 8.2 8.3 8.4 8.5 DeGiorgio and Peterkin (2008), p. 9-126.
- ↑ 9.0 9.1 Lemoff (2008), p. 6-165.
- ↑ C. J. Wright (2008a), pp. 13-119–13-120.
- ↑ C. J. Wright (2008a), p. 13-120.
- ↑ Iqbal and Salley (2004), p. F-47.
- ↑ 13.0 13.1 13.2 13.3 DeGiorgio and Peterkin (2008), p. 9-124.
- ↑ 14.0 14.1 Lemoff (2008), p. 6-168.
- ↑ 15.0 15.1 15.2 15.3 Cholin (2008a), p. 14-100.
- ↑ Kanury (2002b), p. 2-195.
- ↑ Slye (2008), p. 6-201.
- ↑ Van Rossum (2027), §4.2.
- ↑ National Research Council of Canada et al. (2005), p. 3.3-2.
- ↑ 20.0 20.1 20.2 20.3 Lemoff (2008), p. 6-175.
- ↑ Lemoff (2008), p. 6-174.
- ↑ Zalosh (2008), p. 2-99.
- ↑ 23.0 23.1 Zalosh (2008), p. 2-100.
- ↑ DeGiorgio and Peterkin (2008), p. 9-119.
- ↑ DeGiorgio and Peterkin (2008), p. 9-120.
- ↑ DeGiorgio and Peterkin (2008), p. 9-122.
- ↑ 27.0 27.1 DeGiorgio and Peterkin (2008), p. 9-125.
- ↑ Gagnon (2008), p. 16-118.
- ↑ Gagnon (2008), p. 16-109.
- ↑ DiNenno et al. (2002), p. A-13.
- ↑ 31.0 31.1 31.2 31.3 Slye (2008), p. 6-202.
- ↑ Slye (2008), p. 6-203.
- ↑ Cholin (2008a), p. 14-106.
- ↑ 34.0 34.1 Lemoff (2008), p. 6-176.
- ↑ Kanury (2002b), p. 2-197.
References
- Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- DeGiorgio, V., & Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-119–9-129). National Fire Protection Association.
- DiNenno, P. J., Drysdale, D., Beyler, C. L., Walton, W. D., Custer, R. L. P., Hall, J. R., Jr., & Watts, J. M., Jr. (Eds.). (2002). SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association; Society of Fire Protection Engineers.
- Gagnon, R. M. (2008). Ultra-High-Speed water spray systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-109–16-133). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.