Line 5: Line 5:
== Fire experience ==
== Fire experience ==
United States statistics show a substantial and fairly steady decline in home fires that begin with upholstered furniture.<ref name="Bab08-6-103" /> Reported fires fell from 36,850 in 1980 to 8,800 in 2002, a drop of about 76 %, and civilian deaths fell from 1,356 to 502.<ref name="Bab08-6-104">Babrauskas (2008b), p. 6-104.</ref> In 1999 to 2002 the annual average was 9,900 home fires, 561 civilian deaths and 1,124 injuries.<ref name="Bab08-6-104" /> These fires were only 3 % of home fire incidents but caused 19 % of home fire deaths. Together with mattresses and bedding, they accounted for nearly 1,000 home fire deaths a year.<ref name="Bab08-6-103" />
United States statistics show a substantial and fairly steady decline in home fires that begin with upholstered furniture.<ref name="Bab08-6-103" /> Reported fires fell from 36,850 in 1980 to 8,800 in 2002, a drop of about 76 %, and civilian deaths fell from 1,356 to 502.<ref name="Bab08-6-104">Babrauskas (2008b), p. 6-104.</ref> In 1999 to 2002 the annual average was 9,900 home fires, 561 civilian deaths and 1,124 injuries.<ref name="Bab08-6-104" /> These fires were only 3 % of home fire incidents but caused 19 % of home fire deaths. Together with mattresses and bedding, they accounted for nearly 1,000 home fire deaths a year.<ref name="Bab08-6-103" />
[[File:fse-upholstered-furniture-fire-v1.svg|thumb|upright=1.5|alt=Two line charts: United States home upholstered furniture fires fell from 36,850 in 1980 to 8,800 in 2002 and deaths from 1,356 to 502.|Reported United States home structure fires that began with upholstered furniture, and the civilian deaths in them, 1980–2002 (national estimates).]]


Cigarettes dominate the heat sources. In 1999 to 2002 they started 34 % of home upholstered furniture fires and caused 49 % of the deaths.<ref name="Bab08-6-106">Babrauskas (2008b), p. 6-106.</ref> Other leading sources were candles, matches and lighters, and radiated heat from equipment such as space heaters.<ref name="Bab08-6-103" /> In the then-small NFIRS 5.0 subset, the most frequent recorded contributing factor was abandoned or discarded material, such as a lit cigarette or a used match. It was cited in 29 % of these fires and 35 % of the deaths; the handbook cautions that the subset may not be representative.<ref name="Bab08-6-108">Babrauskas (2008b), p. 6-108.</ref>
Cigarettes dominate the heat sources. In 1999 to 2002 they started 34 % of home upholstered furniture fires and caused 49 % of the deaths.<ref name="Bab08-6-106">Babrauskas (2008b), p. 6-106.</ref> Other leading sources were candles, matches and lighters, and radiated heat from equipment such as space heaters.<ref name="Bab08-6-103" /> In the then-small NFIRS 5.0 subset, the most frequent recorded contributing factor was abandoned or discarded material, such as a lit cigarette or a used match. It was cited in 29 % of these fires and 35 % of the deaths; the handbook cautions that the subset may not be representative.<ref name="Bab08-6-108">Babrauskas (2008b), p. 6-108.</ref>
Line 12: Line 13:
== Materials and construction ==
== Materials and construction ==
An upholstered chair can contain well over a dozen materials: cover fabric, interliner, several paddings, weltcords, a decking fabric below the seat cushion, frame and springs. During ignition only the cover fabric and the one or two padding layers below it matter, but frame and springs later affect how the burning item collapses.<ref name="Bab08-6-109" /> Most furniture is still hand-built on a wood frame. Polyurethane foam became common in the 1960s and today often carries a "topper" layer of polyester batting.<ref name="Bab08-6-106" />
An upholstered chair can contain well over a dozen materials: cover fabric, interliner, several paddings, weltcords, a decking fabric below the seat cushion, frame and springs. During ignition only the cover fabric and the one or two padding layers below it matter, but frame and springs later affect how the burning item collapses.<ref name="Bab08-6-109" /> Most furniture is still hand-built on a wood frame. Polyurethane foam became common in the 1960s and today often carries a "topper" layer of polyester batting.<ref name="Bab08-6-106" />
[[File:fse-upholstered-furniture-fire-v2.svg|thumb|upright=1.5|alt=Cutaway of an armchair: cover fabric, interliner, polyester batting, foam, decking, springs and frame, with the seat-back crevice marked.|Main materials of an upholstered armchair. The crevice between seat cushion, back and arm is the most vulnerable location for cigarette and small-flame ignition.]]


Statistics published in 1997 by the United States Consumer Product Safety Commission (CPSC) showed polyester batting over polyurethane foam in 76 % of items and foam alone in 17 %. Thermoplastic cover fabrics made up 51 % and cellulosic fabrics, such as cotton, rayon and linen, 31 %.<ref name="Bab08-6-106" /><ref name="Bab08-6-110">Babrauskas (2008b), p. 6-110.</ref> In the United States market of about 2007, fire-retarded furniture was not offered in retail showrooms, only in specialty markets such as hospitals and correctional facilities.<ref name="Bab08-6-106-107">Babrauskas (2008b), pp. 6-106–6-107.</ref>
Statistics published in 1997 by the United States Consumer Product Safety Commission (CPSC) showed polyester batting over polyurethane foam in 76 % of items and foam alone in 17 %. Thermoplastic cover fabrics made up 51 % and cellulosic fabrics, such as cotton, rayon and linen, 31 %.<ref name="Bab08-6-106" /><ref name="Bab08-6-110">Babrauskas (2008b), p. 6-110.</ref> In the United States market of about 2007, fire-retarded furniture was not offered in retail showrooms, only in specialty markets such as hospitals and correctional facilities.<ref name="Bab08-6-106-107">Babrauskas (2008b), pp. 6-106–6-107.</ref>
Line 54: Line 56:


Measured sofas give a check. The measured growth of many real fuel arrays, including upholstered furniture, tends to be faster than the medium curve.<ref name="IS04-B-5">Iqbal and Salley (2004), p. B-5.</ref> A medium-sized sofa can reach 2 to 3 MW only 3 to 5 minutes after ignition.<ref name="Bab08-6-120" /> If this range is idealised as t-squared growth from ignition, it corresponds to α between 2000/300² ≈ 0.022 and 3000/180² ≈ 0.093 kW/s². The whole range lies above the medium value, and its upper part above the fast value of 0.0469 kW/s². At 180 s the medium curve gives only about 380 kW, but the comparison cannot determine time available before flashover because the measured sofa times start at ignition and the design curve at established flaming.
Measured sofas give a check. The measured growth of many real fuel arrays, including upholstered furniture, tends to be faster than the medium curve.<ref name="IS04-B-5">Iqbal and Salley (2004), p. B-5.</ref> A medium-sized sofa can reach 2 to 3 MW only 3 to 5 minutes after ignition.<ref name="Bab08-6-120" /> If this range is idealised as t-squared growth from ignition, it corresponds to α between 2000/300² ≈ 0.022 and 3000/180² ≈ 0.093 kW/s². The whole range lies above the medium value, and its upper part above the fast value of 0.0469 kW/s². At 180 s the medium curve gives only about 380 kW, but the comparison cannot determine time available before flashover because the measured sofa times start at ignition and the design curve at established flaming.
[[File:fse-upholstered-furniture-fire-v3.svg|thumb|upright=1.5|alt=Heat release rate against time: medium, fast and ultrafast t-squared curves, a sofa box at 2-3 MW and 3-5 min, and a flashover band.|Medium, fast and ultrafast t-squared fires compared with the reported growth of a medium-sized sofa (2–3 MW after 3–5 minutes) and with the heat release rate for flashover through one normal-sized door.]]


Regulatory design fires vary. In the Netherlands, the national annex to Eurocode 1 assigns an ultrafast rate to storage of upholstered furniture, but a medium rate to dwellings.<ref name="NB-VR">NEN-EN 1991-1-2/NB, as cited in Van Rossum (2027), §8.6.</ref> In New Zealand, Verification Method C/VM2 (second edition, 2025) prescribes a fast growth of 0.0469''t''² kW for most buildings, with a soot yield of 0.07 kg/kg.<ref name="MBIE25-20">Ministry of Business, Innovation and Employment (2025b), p. 20.</ref> The 2013 commentary on the first edition explains that this soot yield came from a review that relied heavily on the European Combustion Behaviour of Upholstered Furniture (CBUF) study.<ref name="MBIE13-57">Ministry of Business, Innovation and Employment (2013), p. 57.</ref> C/VM2 (2025) also assigns a design fire load energy density of 800 MJ/m² to seating areas with upholstered furniture, against 400 MJ/m² without it.<ref name="MBIE25-22">Ministry of Business, Innovation and Employment (2025b), p. 22.</ref>
Regulatory design fires vary. In the Netherlands, the national annex to Eurocode 1 assigns an ultrafast rate to storage of upholstered furniture, but a medium rate to dwellings.<ref name="NB-VR">NEN-EN 1991-1-2/NB, as cited in Van Rossum (2027), §8.6.</ref> In New Zealand, Verification Method C/VM2 (second edition, 2025) prescribes a fast growth of 0.0469''t''² kW for most buildings, with a soot yield of 0.07 kg/kg.<ref name="MBIE25-20">Ministry of Business, Innovation and Employment (2025b), p. 20.</ref> The 2013 commentary on the first edition explains that this soot yield came from a review that relied heavily on the European Combustion Behaviour of Upholstered Furniture (CBUF) study.<ref name="MBIE13-57">Ministry of Business, Innovation and Employment (2013), p. 57.</ref> C/VM2 (2025) also assigns a design fire load energy density of 800 MJ/m² to seating areas with upholstered furniture, against 400 MJ/m² without it.<ref name="MBIE25-22">Ministry of Business, Innovation and Employment (2025b), p. 22.</ref>
Line 72: Line 75:


The European CBUF research programme, completed in 1995, produced the best-known method.<ref name="Bab08-6-120" /> It first separates propagating items, which burn over most of their surface, from nonpropagating items, which stop burning when the ignition source dies out. Nonpropagating chair fires normally peak at 20 to 100 kW, and a 100 kW fire does not seriously injure occupants unless they are very close. CBUF set the dividing line at a 180 s average cone heat release rate of 65 kW/m².<ref name="Bab08-6-121" /> For propagating items, the peak heat release rate follows from two correlating parameters:
The European CBUF research programme, completed in 1995, produced the best-known method.<ref name="Bab08-6-120" /> It first separates propagating items, which burn over most of their surface, from nonpropagating items, which stop burning when the ignition source dies out. Nonpropagating chair fires normally peak at 20 to 100 kW, and a 100 kW fire does not seriously injure occupants unless they are very close. CBUF set the dividing line at a 180 s average cone heat release rate of 65 kW/m².<ref name="Bab08-6-121" /> For propagating items, the peak heat release rate follows from two correlating parameters:
[[File:fse-upholstered-furniture-fire-v4.svg|thumb|upright=1.5|alt=Flowchart of the CBUF method: cone test of the composite, propagation check at 65 kW/m², then peak heat release from x1 and x2.|Simplified CBUF procedure for predicting the peak heat release rate of upholstered furniture from cone calorimeter tests of the fabric and padding composite at 35 kW/m².]]


<math display="block">x_1 = m_\mathrm{soft}^{1.25}\,A\,\left(\dot{q}''_\mathrm{pk} + \dot{q}''_{300}\right)^{0.7}\left(15 + t_\mathrm{ig}\right)^{-0.7}</math>
<math display="block">x_1 = m_\mathrm{soft}^{1.25}\,A\,\left(\dot{q}''_\mathrm{pk} + \dot{q}''_{300}\right)^{0.7}\left(15 + t_\mathrm{ig}\right)^{-0.7}</math>

Latest revision as of 08:25, 8 November 2026

An upholstered furniture fire is a fire that starts in, or grows mainly through, a padded item of seating such as an armchair, sofa or office chair. Such items combine a cover fabric, padding layers and a frame into a composite that can burn very fast once flames take hold.[1] Upholstered items, including mattresses, were identified many years ago as the class of burnable items behind the largest share of fire deaths in the United States. In 1999 to 2002 upholstered furniture still accounted for 19 % of United States home fire deaths, more than any other burnable item.[2]

Two very different fires can start in the same chair. A dropped cigarette usually causes smouldering, a slow flameless fire that may last for hours before it bursts into flame. A match, lighter or candle causes flaming ignition, after which a sofa padded with polyurethane foam can reach a heat release rate of 2 to 3 MW within 3 to 5 minutes.[1][3] Less than 2 MW is enough for flashover in a room with a normal-sized door.[3] Resistance to cigarettes and resistance to flames are not necessarily achieved by the same means, so each threat is tested separately.[2] Furniture fires serve as a reference for design fire curves, and full-scale tests in the furniture calorimeter underpin United States standards for furniture in high-risk occupancies.[4][5]

Fire experience

United States statistics show a substantial and fairly steady decline in home fires that begin with upholstered furniture.[2] Reported fires fell from 36,850 in 1980 to 8,800 in 2002, a drop of about 76 %, and civilian deaths fell from 1,356 to 502.[6] In 1999 to 2002 the annual average was 9,900 home fires, 561 civilian deaths and 1,124 injuries.[6] These fires were only 3 % of home fire incidents but caused 19 % of home fire deaths. Together with mattresses and bedding, they accounted for nearly 1,000 home fire deaths a year.[2]

Two line charts: United States home upholstered furniture fires fell from 36,850 in 1980 to 8,800 in 2002 and deaths from 1,356 to 502.
Reported United States home structure fires that began with upholstered furniture, and the civilian deaths in them, 1980–2002 (national estimates).

Cigarettes dominate the heat sources. In 1999 to 2002 they started 34 % of home upholstered furniture fires and caused 49 % of the deaths.[7] Other leading sources were candles, matches and lighters, and radiated heat from equipment such as space heaters.[2] In the then-small NFIRS 5.0 subset, the most frequent recorded contributing factor was abandoned or discarded material, such as a lit cigarette or a used match. It was cited in 29 % of these fires and 35 % of the deaths; the handbook cautions that the subset may not be representative.[8]

In the national fire statistics for 1999 to 2002, smoking materials caused more than a quarter of all civilian fire deaths in structures. Most of these fires began with upholstered furniture, mattresses or bedding.[9] Such fires can smoulder for hours before open burning, so many deaths in dwellings occur at night while everyone is asleep.[10] A majority of home fire victims are not in the room where the fire starts. This leaves time and distance for smoke alarms, sprinklers and compartment barriers to act before conditions become fatal.[11]

Materials and construction

An upholstered chair can contain well over a dozen materials: cover fabric, interliner, several paddings, weltcords, a decking fabric below the seat cushion, frame and springs. During ignition only the cover fabric and the one or two padding layers below it matter, but frame and springs later affect how the burning item collapses.[1] Most furniture is still hand-built on a wood frame. Polyurethane foam became common in the 1960s and today often carries a "topper" layer of polyester batting.[7]

Cutaway of an armchair: cover fabric, interliner, polyester batting, foam, decking, springs and frame, with the seat-back crevice marked.
Main materials of an upholstered armchair. The crevice between seat cushion, back and arm is the most vulnerable location for cigarette and small-flame ignition.

Statistics published in 1997 by the United States Consumer Product Safety Commission (CPSC) showed polyester batting over polyurethane foam in 76 % of items and foam alone in 17 %. Thermoplastic cover fabrics made up 51 % and cellulosic fabrics, such as cotton, rayon and linen, 31 %.[7][12] In the United States market of about 2007, fire-retarded furniture was not offered in retail showrooms, only in specialty markets such as hospitals and correctional facilities.[13]

The change from traditional to synthetic materials raised the hazard sharply. Furniture of the 1950s and 1960s typically had steel springs, cotton batting and a natural-fibre fabric. By the 1970s polyurethane foam dominated, and modern furniture showed heat release rates many times those of traditional types.[14] In tests at the National Institute of Standards and Technology (NIST), a chair with polyolefin fabric over foam peaked at about 2 MW. A chair of the same construction with cotton fabric peaked at about 700 kW.[14] Because furniture can stay in use for 30 years or more and may be re-covered several times, a substantial share of it retains the burning characteristics of older products.[15]

Smouldering ignition

A burning cigarette is a familiar example of true smouldering and one of the most common initiators of smouldering in upholstery and bedding.[16] It releases only about 5 W, but it burns for about 1,200 s with a maximum heat flux of 35 to 42 kW/m², depending on its moisture.[17] Crevices, such as the junction of seat cushion, armrest and back, ignite far more readily than flat surfaces.[18] Cellulosic fabrics are the weak point. In small-scale tests only about 39 % of retail items covered in cellulosic fabric resisted cigarette smouldering, against about 95 % of items covered in thermoplastic fabric.[7] A cellulosic fabric over polyurethane foam can smoulder over a much wider range of conditions than the foam alone, because the fabric adds heat to the smoulder zone.[19]

Smouldering upholstery can produce enough smoke and toxic gas to kill, but rarely does so before the fire turns to flaming, goes out or is put out.[1] The smouldering-to-flaming transition does not always happen. In a literature survey by Babrauskas and Krasny, about two-thirds of the chairs and beds tested made it, 22 to 306 minutes after smouldering began.[20] A chimney-like air flow in the crevice between cushions has been suggested as the trigger, but this has not been demonstrated in real furniture.[21] A risk study with the Hazard I model concluded that toxic exposure from a smouldering chair was rarely fatal, and that deaths followed the transition to flaming.[21]

Smouldering furniture is hard to extinguish, because soaking or even immersion in water may not stop it. Babrauskas advises removing the item, tearing it apart and wetting the pieces. Many victims wetted a smouldering chair, went to bed and woke hours later to dense smoke or a full fire.[12] In performance-based design, a cigarette in upholstered furniture in a living room or bedroom is listed as a common smouldering scenario for a single-family house.[22]

Flaming ignition and fire growth

The ignition sources tabulated by Babrauskas (2008b) vary greatly in output: about 80 W for a wood match and 50 kW for a burning polyethylene wastebasket. Their measured maximum heat fluxes are about 18–20 and 35 kW/m², respectively. Babrauskas uses about 35 kW/m² as typical of an incidental flame.[17] As source power rises, the exposed area grows: about 10 by 30 mm for a wood match versus 60 by 700 mm for the wastebasket.[17] Small target areas need higher fluxes to ignite. Many thermoplastic fabrics shrink away from a small flame, yet ignite and burn vigorously under a larger one.[5]

Once flames spread over the seat, fabrics behave very differently. Cotton and rayon char ahead of the flame front until the char bursts into flame. Thermoplastic fabrics shrink back, but the burning bead of melted fabric ignites the foam below, so flames spread faster over thermoplastic-covered mock-ups.[5] At furniture scale, radiation rather than convection dominates flame spread and burning.[5] Melting thermoplastics can also form a burning pool under the item.[23] Studies in England found that in some cases pool burning accounts for about 50 % of the peak heat release rate of an upholstered chair.[24]

Data from NFPA 921 (2004 edition) give 290 to 370 kW for cotton easy chairs of 17.7 to 31.8 kg (39 to 70 lb). Polyurethane easy chairs of 12.2 to 27.7 kg (27 to 61 lb) gave 1,350 to 1,990 kW, and a 51.3 kg (113 lb) polyurethane sofa 3,120 kW.[25] Large or sectional sofas commonly reach about 5 MW.[3] Introduction to Fire Safety Engineering uses 2.5 MW as a guide value for an average living-room sofa and 1,884 MJ as the energy content of a three-seat sofa.[26][27] A curve measured by the Netherlands Institute for Public Safety (NIPV) for one sofa peaks at roughly 3.3 MW after a little over seven minutes. The curve applies only to that sofa, because material, filling, size and ventilation all change the result.[28]

In a room, the hot layer and walls radiate back to the burning item. For upholstered chairs this raises the heat release rate by only about 20 % up to a 1 MW fire. Flashover through a single normal-sized door needs about 1.5 to 1.75 MW.[29] A single upholstered item with a high enough burning rate can therefore cause flashover.[1] In a 1985 Michigan hospice fire that started in an upholstered chair and killed eight people, flashover could have occurred in under 4 minutes.[30]

Design fires

For engineering analysis, flaming furniture fires are often idealised as a t-squared fire, whose heat release rate grows with the square of time. In the scheme described by Hurley and Bukowski, the slow, medium, fast and ultrafast curves reach 1,055 kW (1,000 Btu/s) after 600, 300, 150 and 75 s. The medium curve is typical of upholstered furniture and mattresses, and some older types of furniture are ultrafast.[4] The curves assume a reasonably large flaming source and exclude the incubation period of a small one.[4] The growth equation is:

Q˙=αt2,α=1055 kWtg2

Symbol Description Unit
Q˙ Heat release rate of the design fire kW
α Fire growth coefficient kW/s²
t Time from the start of established flaming s
tg Growth time to reach 1,055 kW (600, 300, 150 or 75 s) s

Worked example

A designer checks whether the medium curve suits a polyurethane sofa in a living room with one normal-sized door. The medium coefficient is α = 1055/300² = 0.01172 kW/s². The curve would reach the lower 1.5 MW flashover estimate after t = (1500/0.01172)1/2 ≈ 358 s, about 6 minutes. With the ultrafast coefficient of 1055/75² = 0.1876 kW/s², it would reach that estimate after about 89 s.[4][29]

Measured sofas give a check. The measured growth of many real fuel arrays, including upholstered furniture, tends to be faster than the medium curve.[31] A medium-sized sofa can reach 2 to 3 MW only 3 to 5 minutes after ignition.[3] If this range is idealised as t-squared growth from ignition, it corresponds to α between 2000/300² ≈ 0.022 and 3000/180² ≈ 0.093 kW/s². The whole range lies above the medium value, and its upper part above the fast value of 0.0469 kW/s². At 180 s the medium curve gives only about 380 kW, but the comparison cannot determine time available before flashover because the measured sofa times start at ignition and the design curve at established flaming.

Heat release rate against time: medium, fast and ultrafast t-squared curves, a sofa box at 2-3 MW and 3-5 min, and a flashover band.
Medium, fast and ultrafast t-squared fires compared with the reported growth of a medium-sized sofa (2–3 MW after 3–5 minutes) and with the heat release rate for flashover through one normal-sized door.

Regulatory design fires vary. In the Netherlands, the national annex to Eurocode 1 assigns an ultrafast rate to storage of upholstered furniture, but a medium rate to dwellings.[32] In New Zealand, Verification Method C/VM2 (second edition, 2025) prescribes a fast growth of 0.0469t² kW for most buildings, with a soot yield of 0.07 kg/kg.[33] The 2013 commentary on the first edition explains that this soot yield came from a review that relied heavily on the European Combustion Behaviour of Upholstered Furniture (CBUF) study.[34] C/VM2 (2025) also assigns a design fire load energy density of 800 MJ/m² to seating areas with upholstered furniture, against 400 MJ/m² without it.[35]

Testing and regulation

In the United States, cigarette resistance has been handled mostly through voluntary programmes. Since the early 1980s, residential furniture has been available with the hangtag of the Upholstered Furniture Action Council (UFAC), which certifies manufacture to UFAC standards.[36] By the mid-1990s, 86 % of upholstered seating on the retail market met all UFAC requirements. CPSC estimated that a cigarette placed on any mid-1990s furniture item had about an 85 % chance of failing to ignite it.[37]

The test cigarette is a filterless 85 mm commercial cigarette, placed in the crevice and covered with sheeting.[37] NFPA 260 classifies components by ignition and char length, and NFPA 261 tests mock-ups with crevices.[38] Regulating the cigarette instead of the furniture led to the fire-safe cigarette.[37]

California made Technical Bulletin 117 (TB 117) mandatory in 1975. Its small-flame part exposed naked foam to a vertical Bunsen burner, a test that a small dose of fire-retardant chemicals passes. CPSC found that furniture meeting TB 117 very often did not resist a small flame, because the flame reaches the fabric first.[39]

In the United Kingdom, regulations of 1988 and 1989 required furniture to resist both cigarettes and small flames. British furniture therefore generally used advanced fire-retardant foams and treated fabrics.[18][39] CPSC drafted a federal small-flame test in 1997 and issued proposals up to 2006, but by 2008 no regulation appeared imminent.[40][24]

For high-risk and public occupancies, full-scale testing is used. California TB 133 burns a real item or full-scale mock-up in a room or under a furniture calorimeter hood. Since its 1990 revision it uses a gas burner and a pass/fail limit of 80 kW.[41] It became mandatory in California in 1992 for certain public occupancies and was adopted as ASTM E1537. Because it is a system test, the same materials can pass in a small chair and fail in a larger one.[41] NFPA 101, the Life Safety Code, refers to TB 133 or similar furniture for health care, detention and other high-risk occupancies, as described in the 2008 edition of the Fire Protection Handbook.[3]

Bench-scale prediction

The furniture calorimeter, developed at NIST in 1982, measures the heat release rate of a whole item burning under a hood. It uses the oxygen consumption principle: about 13.1 × 10³ kJ is released per kilogram of oxygen consumed, within about 5 %.[5] Because full-scale tests are costly, bench-scale methods burn a fabric and padding composite in the cone calorimeter at 35 kW/m², with specimens prepared to ASTM E1474.[3][42][43]

The European CBUF research programme, completed in 1995, produced the best-known method.[3] It first separates propagating items, which burn over most of their surface, from nonpropagating items, which stop burning when the ignition source dies out. Nonpropagating chair fires normally peak at 20 to 100 kW, and a 100 kW fire does not seriously injure occupants unless they are very close. CBUF set the dividing line at a 180 s average cone heat release rate of 65 kW/m².[42] For propagating items, the peak heat release rate follows from two correlating parameters:

Flowchart of the CBUF method: cone test of the composite, propagation check at 65 kW/m², then peak heat release from x1 and x2.
Simplified CBUF procedure for predicting the peak heat release rate of upholstered furniture from cone calorimeter tests of the fabric and padding composite at 35 kW/m².

x1=msoft1.25A(q˙′'pk+q˙′'300)0.7(15+tig)−0.7

x2=880+500msoft0.7A(Δhc,effq′'tot)1.4

If x1 > 115, or q″tot > 70 and x1 > 40, or the item has style code 3 or 4 and x1 > 70, the peak is Q˙=x2. Otherwise it is Q˙=14.4x1 when x1 < 56, and Q˙=600+3.77x1 in the remaining cases.[42] The total heat released, a measure of the item's effective fire load, is estimated as:[44]

Q=0.9msoftΔhc,eff+2.1(mcomb,total−msoft)1.5

Symbol Description Unit
Q˙ Predicted peak heat release rate of the full-scale item kW
x1,x2 Correlating parameters of the CBUF model –
msoft Mass of the soft parts: fabric, filling, interliner, dust cover kg
mcomb,total Total combustible mass, excluding metal and other noncombustible parts kg
A Style factor A (1.0 for an average armchair, 0.8 for a three-seat sofa) –
q˙′'pk Peak cone heat release rate at 35 kW/m² kW/m²
q˙′'300 300 s average cone heat release rate at 35 kW/m² kW/m²
tig Cone ignition time at 35 kW/m² s
Δhc,eff Effective heat of combustion in the cone test MJ/kg
q′'tot Total heat release in the cone test at 35 kW/m² MJ/m²
Q Total heat released by the full-scale item MJ

The style list is not exhaustive but covers the majority of common types.[42] Style factor B, used for the time to peak and to untenable conditions, ranges from 0.75 for a sofa-bed to 2.5 for a wingback chair.[44] For propagating fires, the heat release measured in a test is only a lower bound for a real room, because other items can ignite.[42]

Reducing the hazard

Toxic gases cause far more fire deaths than burns, but the toxicity per gram is very similar for most common furniture materials. The practical way to reduce the toxic hazard is therefore to reduce the heat release rate, the strategy behind TB 133.[45] Wool, modacrylic and fire-retardant-treated fabrics perform well in flaming fires, and Babrauskas recommends avoiding polyolefin fabrics. A pure cellulosic fabric heavier than 440 g/m² (13 oz/yd²) has great difficulty passing cigarette tests. Blends with less than 80 % cellulosic fibre are much more smoulder resistant.[45]

The simplest foam strategy is to use less foam, because the peak heat release rate depends strongly on the mass of upholstery. Ordinary foam can also be replaced by combustion-modified grades.[45][46] Flame retardant chemicals raised toxicological questions in the United States. In 2000 the National Research Council reviewed 16 agents likely to be used on furniture fabrics and found that 8 needed no further study.[40]

Interliners are among the most promising measures. Modern interliners weigh 70 to 170 g/m² and are commonly made of glass fibre or aramid, and an average chair needs about 4 m².[46][24] As the foam melts and retreats, the interliner stays in place as a radiation shield and flame barrier, which slows the melting and lowers the heat release rate. Its main drawback, apart from cost, is a stiffer seat.[46] Panel mounting instead of webbing is a powerful design strategy, and any measure that reduces pool burning lowers the hazard considerably. Gaps wider than 75 mm between cushions help, while loosely sewn cushions and fabric skirts make fires worse.[24]

Limits and common misconceptions

Cigarette resistance and flame resistance are separate properties, and tests or regulations cannot combine the two.[24] A heavy thermoplastic fabric that resists cigarettes may burn readily from a flame. Passing a small-flame test also says little about a larger flame, so Bunsen-burner tests are considered unsuitable for high-risk occupancies such as health care.[5]

Component tests are often misleading, because fabric and padding interact thermally and chemically.[39] Open-burning results have limits too. After flashover, the heat release rate in a room can differ drastically from the open-burn value, mainly because of radiation from the hot layer and walls.[29] Finally, statistics describe the furniture in use, which changes slowly. Changes in cigarettes can reach all users within months, whereas changes in furniture may take decades to work through the stock in homes.[47]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Babrauskas (2008b), p. 6-109.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Babrauskas (2008b), p. 6-103.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Babrauskas (2008b), p. 6-120.
  4. ↑ 4.0 4.1 4.2 4.3 Hurley and Bukowski (2008), p. 3-127.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Babrauskas (2008b), p. 6-119.
  6. ↑ 6.0 6.1 Babrauskas (2008b), p. 6-104.
  7. ↑ 7.0 7.1 7.2 7.3 Babrauskas (2008b), p. 6-106.
  8. ↑ Babrauskas (2008b), p. 6-108.
  9. ↑ Hall and Cote (2008), p. 3-14.
  10. ↑ Lathrop (2008b), p. 20-58.
  11. ↑ Babrauskas (2008b), p. 6-105.
  12. ↑ 12.0 12.1 Babrauskas (2008b), p. 6-110.
  13. ↑ Babrauskas (2008b), pp. 6-106–6-107.
  14. ↑ 14.0 14.1 Babrauskas (2002b), pp. 3-28–3-29.
  15. ↑ Hall (2002b), p. 5-151.
  16. ↑ Ohlemiller (2002), p. 2-200.
  17. ↑ 17.0 17.1 17.2 Babrauskas (2008b), p. 6-118.
  18. ↑ 18.0 18.1 Babrauskas (2008b), p. 6-107.
  19. ↑ Ohlemiller (2002), p. 2-206.
  20. ↑ Babrauskas and Krasny (1997), as cited in Ohlemiller (2002), p. 2-208.
  21. ↑ 21.0 21.1 Ohlemiller (2002), pp. 2-207–2-208.
  22. ↑ Puchovsky and Hurley (2008), p. 3-172.
  23. ↑ Custer (2008), p. 2-50.
  24. ↑ 24.0 24.1 24.2 24.3 24.4 Babrauskas (2008b), p. 6-126.
  25. ↑ NFPA 921 (2004), as cited in Custer (2008), p. 2-50.
  26. ↑ Van Rossum (2027), §4.5.
  27. ↑ Van Rossum (2027), §4.4.
  28. ↑ Van Rossum (2027), §8.6.
  29. ↑ 29.0 29.1 29.2 Babrauskas (2002b), p. 3-1.
  30. ↑ O'Connor (2008), p. 20-144.
  31. ↑ Iqbal and Salley (2004), p. B-5.
  32. ↑ NEN-EN 1991-1-2/NB, as cited in Van Rossum (2027), §8.6.
  33. ↑ Ministry of Business, Innovation and Employment (2025b), p. 20.
  34. ↑ Ministry of Business, Innovation and Employment (2013), p. 57.
  35. ↑ Ministry of Business, Innovation and Employment (2025b), p. 22.
  36. ↑ Babrauskas (2008b), pp. 6-111–6-112.
  37. ↑ 37.0 37.1 37.2 Babrauskas (2008b), p. 6-112.
  38. ↑ Stull and Chines (2008), p. 6-94.
  39. ↑ 39.0 39.1 39.2 Babrauskas (2008b), p. 6-113.
  40. ↑ 40.0 40.1 Babrauskas (2008b), pp. 6-114–6-115.
  41. ↑ 41.0 41.1 Babrauskas (2008b), p. 6-116.
  42. ↑ 42.0 42.1 42.2 42.3 42.4 Babrauskas (2008b), p. 6-121.
  43. ↑ Babrauskas (2002b), p. 3-29.
  44. ↑ 44.0 44.1 Babrauskas (2008b), p. 6-122.
  45. ↑ 45.0 45.1 45.2 Babrauskas (2008b), p. 6-124.
  46. ↑ 46.0 46.1 46.2 Babrauskas (2008b), p. 6-125.
  47. ↑ Ahrens et al. (2008), p. 3-90.

References

  • Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Custer, R. L. P. (2008). Dynamics of compartment fire growth. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-49–2-58). National Fire Protection Association.
  • Hall, J. R., Jr. (2002b). Product fire risk. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-143–5-152). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
  • Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
  • O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.
  • Puchovsky, M. T., & Hurley, M. J. (2008). Performance-Based codes and standards for fire safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-167–3-181). National Fire Protection Association.
  • Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.