Kandola describes vapour pressure in molecular terms. As the temperature of a liquid rises, the activity of its molecules increases and some of them escape from the surface. The pressure exerted by these escaped molecules just above the surface is the vapour pressure of the liquid.<ref name="Kandola-1-2" /> Evaporation is a physical change of state and does not alter the chemical nature of the substance. It also takes energy from the surroundings.<ref name="VR-3.5">Van Rossum (2027), §3.5.</ref>
Kandola describes vapour pressure in molecular terms. As the temperature of a liquid rises, the activity of its molecules increases and some of them escape from the surface. The pressure exerted by these escaped molecules just above the surface is the vapour pressure of the liquid.<ref name="Kandola-1-2" /> Evaporation is a physical change of state and does not alter the chemical nature of the substance. It also takes energy from the surroundings.<ref name="VR-3.5">Van Rossum (2027), §3.5.</ref>


A true vapour pressure exists only at equilibrium. Slye points out that equilibrium can only be reached in a closed system, such as a tank, pipe or process vessel. In the open air, an evaporating liquid simply goes on evaporating until it is used up.<ref name="Slye-6-203">Slye (2008), p. 6-203.</ref> For a flammable liquid, the liquid evaporates at the rate needed to maintain the equilibrium vapour pressure above its surface. Solid polymers are more complex, because they break down into fragments that each have their own equilibrium vapour pressure.<ref name="Beyler-Hirschler-1-110">Beyler and Hirschler (2002), p. 1-110.</ref>
The vapour pressure used here is an equilibrium property. Slye points out that equilibrium over the whole liquid can be reached in a closed system, such as a tank, pipe or process vessel. In the open air, an evaporating liquid keeps losing vapour until it is used up.<ref name="Slye-6-203">Slye (2008), p. 6-203.</ref> For a flammable liquid, the liquid evaporates at the rate needed to maintain the equilibrium vapour pressure above its surface. Solid polymers are more complex, because they break down into fragments that each have their own equilibrium vapour pressure.<ref name="Beyler-Hirschler-1-110">Beyler and Hirschler (2002), p. 1-110.</ref>
[[File:fse-vapour-pressure-v2.svg|thumb|upright=1.5|alt=Left: closed vessel of acetone with 52 percent vapour in the space above. Right: open dish where vapour keeps leaving.|In a closed vessel, net evaporation stops when the vapour reaches its equilibrium pressure; for acetone at 37.8 °C the space then holds about 52 percent vapour. In the open, the liquid keeps evaporating.]]


The boiling point follows directly from vapour pressure. It is the temperature at which the equilibrium vapour pressure of a liquid equals the total pressure on its surface. The normal boiling point is the boiling temperature at 1 atm, or 101 kPa.<ref name="Slye-6-202" /> A higher total pressure raises the boiling point, and any liquid can in principle be made to boil at any temperature by changing the pressure.<ref name="Slye-6-202" /> Above its critical temperature a substance can only exist as a gas, whatever the pressure.<ref name="Slye-6-199" /> ''Introduction to Fire Safety Engineering'' describes the same limit as the critical point, above which liquid and gas can no longer be told apart.<ref name="VR-3.5" />
The boiling point follows directly from vapour pressure. It is the temperature at which the equilibrium vapour pressure of a liquid equals the total pressure on its surface. The normal boiling point is the boiling temperature at 1 atm, or 101 kPa.<ref name="Slye-6-202" /> A higher total pressure raises the boiling point, and any liquid can in principle be made to boil at any temperature by changing the pressure.<ref name="Slye-6-202" /> Above its critical temperature, increasing the pressure cannot restore a distinct liquid phase.<ref name="Slye-6-199" /> ''Introduction to Fire Safety Engineering'' describes the critical point, beyond which liquid and gas can no longer be told apart and the substance is called supercritical.<ref name="VR-3.5" />


A liquid with a high vapour pressure at a given temperature, a low boiling point and a low latent heat is called highly volatile.<ref name="Kanury-2-189">Kanury (2002b), p. 2-189.</ref> Benedetti notes that the most hazardous combustible liquids are those with a high vapour pressure, because burning takes place in the vapour phase.<ref name="Benedetti-6-6">Benedetti (2008), p. 6-6.</ref> As the boiling point decreases, the vapour pressure and the evaporation rate generally increase.<ref name="Slye-6-200">Slye (2008), p. 6-200.</ref>
A liquid with a high vapour pressure at a given temperature, a low boiling point and a low latent heat is called highly volatile.<ref name="Kanury-2-189">Kanury (2002b), p. 2-189.</ref> Benedetti notes that the most hazardous combustible liquids are those with a high vapour pressure, because burning takes place in the vapour phase.<ref name="Benedetti-6-6">Benedetti (2008), p. 6-6.</ref> As the boiling point decreases, the vapour pressure and the evaporation rate generally increase.<ref name="Slye-6-200">Slye (2008), p. 6-200.</ref>
Line 55: Line 56:
|}
|}


Water gives an everyday sense of the numbers. Stewart lists its vapour pressure as 1.8 kPa at 16 °C, 3.6 kPa at 27 °C, 6.6 kPa at 38 °C and 11.7 kPa at 49 °C.<ref name="Stewart-13-25">Stewart (2008), p. 13-25.</ref> Above about 177 °C (350 °F) the vapour pressure of water rises so fast that heat transfer systems need expensive high-pressure equipment.<ref name="LeBlanc-8-65">LeBlanc (2008), p. 8-65.</ref>
Water gives an everyday sense of the numbers. Wieder lists its vapour pressure as 1.8 kPa at 16 °C, 3.6 kPa at 27 °C, 6.6 kPa at 38 °C and 11.7 kPa at 49 °C.<ref name="Wieder-13-25">Wieder (2008), p. 13-25.</ref> Above about 177 °C (350 °F) the vapour pressure of water rises so fast that heat transfer systems need expensive high-pressure equipment.<ref name="LeBlanc-8-65">LeBlanc (2008), p. 8-65.</ref>
[[File:fse-vapour-pressure-v1.svg|thumb|upright=1.5|alt=Log-scale chart of vapour pressure against temperature for water, acetone, butane and propane, with a line at atmospheric pressure.|Vapour pressure data for water, acetone, butane and propane at the indicated temperatures. Where a curve crosses the atmospheric line, the liquid boils; butane and propane lie above it and are stored as liquefied gases.]]


== Vapour pressure and flammability ==
== Vapour pressure and flammability ==
Line 67: Line 69:


Storage tanks show the practical effect. Ordile explains that the vapour space of a tank holding a liquid with a vapour pressure above about 28 kPa (4 psia), such as petrol, is normally too rich to burn.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref> The vapour space above a liquid below about 14 kPa (2 psia), such as kerosene, is normally too lean.<ref name="Ordile-7-16" /> Ethyl and methyl alcohol and JP-4 jet fuel, at about 14 kPa to 28 kPa at 38 °C, present an unusual hazard, because their vapour spaces are normally within the flammable range.<ref name="Ordile-7-16" /> Petrol cooled to between about −23 °C and −46 °C can also have a flammable vapour space.<ref name="Ordile-7-16" /> It is the temperature of the liquid, not of the air in the tank, that controls the mixture.<ref name="Ordile-7-16" />
Storage tanks show the practical effect. Ordile explains that the vapour space of a tank holding a liquid with a vapour pressure above about 28 kPa (4 psia), such as petrol, is normally too rich to burn.<ref name="Ordile-7-16">Ordile (2008), p. 7-16.</ref> The vapour space above a liquid below about 14 kPa (2 psia), such as kerosene, is normally too lean.<ref name="Ordile-7-16" /> Ethyl and methyl alcohol and JP-4 jet fuel, at about 14 kPa to 28 kPa at 38 °C, present an unusual hazard, because their vapour spaces are normally within the flammable range.<ref name="Ordile-7-16" /> Petrol cooled to between about −23 °C and −46 °C can also have a flammable vapour space.<ref name="Ordile-7-16" /> It is the temperature of the liquid, not of the air in the tank, that controls the mixture.<ref name="Ordile-7-16" />
[[File:fse-vapour-pressure-v3.svg|thumb|upright=1.5|alt=Horizontal scale of vapour pressure with three bands: too lean below 14 kPa, flammable 14 to 28 kPa, too rich above 28 kPa, with fuels marked.|The vapour space of a storage tank is normally too lean below about 14 kPa, flammable between about 14 and 28 kPa and too rich above 28 kPa.]]


Aviation fuels follow the same pattern. Boucher lists Reid vapour pressures of 0.1 psi (0.69 kPa) for kerosene-type Jet A and 2.0 psi to 3.0 psi (13.8 kPa to 20.7 kPa) for JP-4, a blend of petrol and kerosene.<ref name="Boucher-21-137">Boucher (2008), p. 21-137.</ref> Aviation petrol reaches 5.5 psi to 7.0 psi (37.9 kPa to 48.3 kPa).<ref name="Boucher-21-137" /> The corresponding temperature ranges for flammable vapour are about 35 °C to 74 °C for the kerosene grades, −23 °C to 38 °C for JP-4 and −46 °C to −1 °C for aviation petrol.<ref name="Boucher-21-137" />
Aviation fuels follow the same pattern. Boucher lists Reid vapour pressures of 0.1 psi (0.69 kPa) for kerosene-type Jet A and 2.0 psi to 3.0 psi (13.8 kPa to 20.7 kPa) for JP-4, a blend of petrol and kerosene.<ref name="Boucher-21-137">Boucher (2008), p. 21-137.</ref> Aviation petrol reaches 5.5 psi to 7.0 psi (37.9 kPa to 48.3 kPa).<ref name="Boucher-21-137" /> The corresponding temperature ranges for flammable vapour are about 35 °C to 74 °C for the kerosene grades, −23 °C to 38 °C for JP-4 and −46 °C to −1 °C for aviation petrol.<ref name="Boucher-21-137" />
Line 77: Line 80:
The same data can be used the other way round to estimate the flash point. The lean limit of acetone is 2.6 percent by volume.<ref name="Kanury-2-193" /> By Slye's relation, the vapour pressure at the flash point must then be about 1.01 × 2.6, or 2.63 kPa.<ref name="Slye-6-200" /> Solving the Clausius–Clapeyron equation for this vapour pressure gives a surface temperature of about 247 K, or −26 °C.<ref name="Kanury-2-194" /> The measured closed-cup flash point in Kanury's table is 255 K (−18 °C), and the open-cup value is 264 K (−9 °C).<ref name="Kanury-2-193" />
The same data can be used the other way round to estimate the flash point. The lean limit of acetone is 2.6 percent by volume.<ref name="Kanury-2-193" /> By Slye's relation, the vapour pressure at the flash point must then be about 1.01 × 2.6, or 2.63 kPa.<ref name="Slye-6-200" /> Solving the Clausius–Clapeyron equation for this vapour pressure gives a surface temperature of about 247 K, or −26 °C.<ref name="Kanury-2-194" /> The measured closed-cup flash point in Kanury's table is 255 K (−18 °C), and the open-cup value is 264 K (−9 °C).<ref name="Kanury-2-193" />


The estimate is thus about 8 K too low for the closed cup. Kanury explains the gap: the vapour concentration at the pilot flame is lower than at the surface, because the vapour must first diffuse upward.<ref name="Kanury-2-194" /> His fit of many fuels puts this dilution factor between about 0.07 and 0.25.<ref name="Kanury-2-195" /> An equilibrium estimate therefore gives only a lower bound for the flash point. Kanury considers the use of such relations as a predictive tool premature.<ref name="Kanury-2-195" />
The estimate is thus about 8 K too low for the closed cup. Kanury explains the direction of the gap: the vapour concentration at the pilot flame is lower than at the surface, because the vapour must first diffuse upward.<ref name="Kanury-2-194" /> His fit across many fuels puts this dilution factor between about 0.07 and 0.25.<ref name="Kanury-2-195" /> For this acetone example, matching the measured closed-cup temperature would require a factor of about 0.64, outside that fitted range. The equilibrium estimate is therefore only a lower bound, not a quantitative prediction of acetone's flash point. Kanury considers predictive use of such relations premature.<ref name="Kanury-2-195" />


== Measurement and data ==
== Measurement and data ==
For petroleum liquids, vapour pressure is usually measured by the Reid method of ASTM D323. This test gives the vapour pressure at 37.8 °C (100 °F), which differs slightly from the true vapour pressure.<ref name="Slye-6-199" /> Values for many other substances can be found in chemical handbooks.<ref name="Slye-6-199" /> Eberly notes that the Reid vapour pressure of a petroleum cargo expresses the rate at which its flammable gases are given off.<ref name="Eberly-21-168">Eberly (2008), p. 21-168.</ref> Planning for hazardous materials incidents also lists vapour pressure among the properties to consider for a stored chemical.<ref name="Wright-13-134">C. J. Wright (2008a), p. 13-134.</ref>
For petroleum liquids, vapour pressure is usually measured by the Reid method of ASTM D323. This test gives the vapour pressure at 37.8 °C (100 °F), which differs slightly from the true vapour pressure.<ref name="Slye-6-199" /> Values for many other substances can be found in chemical handbooks.<ref name="Slye-6-199" /> Eberly notes that the Reid vapour pressure of a petroleum cargo expresses the rate at which its flammable gases are given off.<ref name="Eberly-21-168">Eberly (2008), p. 21-168.</ref> Planning for hazardous materials incidents also lists vapour pressure among the properties to consider for a stored chemical.<ref name="Wright-13-134">C. J. Wright (2008a), p. 13-134.</ref>


Vapour pressure also defines classes in the United States. NFPA 30, as described by Slye, defines liquids as fluids with a vapour pressure not exceeding 276 kPa (40 psia) at 37.8 °C (100 °F). Anything above that is treated as a gas.<ref name="Slye-6-198" /> Anderson adds that a Class I liquid must have a closed-cup flash point below 37.8 °C and a Reid vapour pressure not above the same limit.<ref name="Anderson-9-163">Anderson (2008a), p. 9-163.</ref> The further split of flammable liquids is explained under [[flammable and combustible liquid classification]].<ref name="Slye-6-198" />
Vapour pressure also affects the United States classification described by Slye (2008). In that account of NFPA 30, liquids have a vapour pressure not exceeding 276 kPa (40 psia) at 37.8 °C (100 °F). A fluid above that pressure is treated as a gas in this classification.<ref name="Slye-6-198" /> Anderson (2008a) adds that a Class I liquid must have a closed-cup flash point below 37.8 °C and a Reid vapour pressure not above the same limit.<ref name="Anderson-9-163">Anderson (2008a), p. 9-163.</ref> The further split of flammable liquids is explained under [[flammable and combustible liquid classification]].<ref name="Slye-6-198" />


The boiling point of mixtures is defined differently in two sources. The handbook uses the 10 percent point of an ASTM D86 distillation as the boiling point in most NFPA standards.<ref name="Slye-6-202" /> NUREG-1805, a fire hazard toolkit of the U.S. Nuclear Regulatory Commission, uses the 20 percent evaporated point of the same test.<ref name="Iqbal-B-21">Iqbal and Salley (2004), p. B-21.</ref> Both sources agree that the boiling point is the temperature at which the vapour pressure equals atmospheric pressure.<ref name="Iqbal-B-21" /><ref name="Slye-6-202" />
The boiling point of mixtures is defined differently in two sources. The handbook uses the 10 percent point of an ASTM D86 distillation as the boiling point in most NFPA standards.<ref name="Slye-6-202" /> NUREG-1805, a fire hazard toolkit of the U.S. Nuclear Regulatory Commission, uses the 20 percent evaporated point of the same test.<ref name="Iqbal-B-21">Iqbal and Salley (2004), p. B-21.</ref> Both sources agree that the boiling point is the temperature at which the vapour pressure equals atmospheric pressure.<ref name="Iqbal-B-21" /><ref name="Slye-6-202" />
Line 89: Line 92:
A liquefied gas is a gas that exists partly as liquid and partly as vapour inside its closed container at 20 °C. It stays under pressure as long as some liquid remains, and that pressure depends on the temperature of the liquid.<ref name="Lemoff-6-168">Lemoff (2008), p. 6-168.</ref> Propane is a gas at room temperature but is liquefied by storing it under a pressure equal to its vapour pressure.<ref name="Rivkin-21-55">Rivkin (2008b), p. 21-55.</ref> Lemoff gives approximate vapour pressures for commercial propane of 895 kPa at 20 °C and 1,482 kPa at 40 °C. For commercial butane the values are 103 kPa and 285 kPa. The same table gives the psi values as gauge pressures, that is, above atmospheric pressure.<ref name="Lemoff-6-183">Lemoff (2008), p. 6-183.</ref>
A liquefied gas is a gas that exists partly as liquid and partly as vapour inside its closed container at 20 °C. It stays under pressure as long as some liquid remains, and that pressure depends on the temperature of the liquid.<ref name="Lemoff-6-168">Lemoff (2008), p. 6-168.</ref> Propane is a gas at room temperature but is liquefied by storing it under a pressure equal to its vapour pressure.<ref name="Rivkin-21-55">Rivkin (2008b), p. 21-55.</ref> Lemoff gives approximate vapour pressures for commercial propane of 895 kPa at 20 °C and 1,482 kPa at 40 °C. For commercial butane the values are 103 kPa and 285 kPa. The same table gives the psi values as gauge pressures, that is, above atmospheric pressure.<ref name="Lemoff-6-183">Lemoff (2008), p. 6-183.</ref>


These numbers drive container design. In the United States, NFPA 58 and the ASME code, as described by Rivkin, set a minimum design pressure of 1,724 kPa (250 psig) for LP-gas vessels. This value is based on gases with a vapour pressure of 1,482 kPa (215 psig) at 38 °C.<ref name="Rivkin-21-72">Rivkin (2008b), p. 21-72.</ref> Aerosol propellants are even named after their vapour pressure at 21 °C. A-31 is isobutane at 214 kPa gauge and A-108 is propane at 745 kPa gauge.<ref name="Fredrickson-6-258">Fredrickson (2008), p. 6-258.</ref>
These numbers inform container design. In his 2008 chapter on vehicle fuels, Rivkin gives 1,724 kPa (250 psig) as the normal minimum design pressure for LP-gas vessels under NFPA 58 and the ASME code. This is based on gases with a vapour pressure of 1,482 kPa (215 psig) at 38 °C. For a vessel installed on a motor vehicle, he gives the higher minimum of 2,154 kPa (312.5 psig).<ref name="Rivkin-21-72">Rivkin (2008b), p. 21-72.</ref> Aerosol propellants are even named after their vapour pressure at 21 °C. A-31 is isobutane at 214 kPa gauge and A-108 is propane at 745 kPa gauge.<ref name="Fredrickson-6-258">Fredrickson (2008), p. 6-258.</ref>


When a liquefied gas container is heated, three effects combine. The vapour is compressed, the liquid expands, and the vapour pressure of the liquid rises with its temperature.<ref name="Lemoff-6-169">Lemoff (2008), p. 6-169.</ref> If the liquid expands until the container is full, a little more heating causes a very large rise in pressure. Codes therefore limit the filling density so that a vapour space always remains.<ref name="Lemoff-6-169" /> Wright warns that a rail tank car exposed to fire can build up vapour pressure until its relief device operates or the tank ruptures.<ref name="Wright-21-110">C. J. Wright (2008b), p. 21-110.</ref>
When a liquefied gas container is heated, three effects combine. The vapour is compressed, the liquid expands, and the vapour pressure of the liquid rises with its temperature.<ref name="Lemoff-6-169">Lemoff (2008), p. 6-169.</ref> If the liquid expands until the container is full, a little more heating causes a very large rise in pressure. Codes therefore limit the filling density so that a vapour space always remains.<ref name="Lemoff-6-169" /> Wright warns that a rail tank car exposed to fire can build up vapour pressure until its relief device operates or the tank ruptures.<ref name="Wright-21-110">C. J. Wright (2008b), p. 21-110.</ref>
[[File:fse-vapour-pressure-v4.svg|thumb|upright=1.5|alt=Three sketches of a horizontal propane tank: normal storage, heated by fire with relief valve open, and failure with liquid flashing to vapour.|A liquefied gas is kept liquid only by its own vapour pressure. Fire raises the liquid temperature and pressure; if the shell fails, part of the liquid flashes to vapour.]]


The failure of such a container is a [[BLEVE]], or boiling liquid expanding vapour explosion. All liquefied gases are stored above their normal boiling points and stay liquid only while the container is closed.<ref name="Lemoff-6-170" /> Lemoff stresses that a BLEVE is what happens after the container fails, not how it fails.<ref name="Lemoff-6-171" />
The failure of such a container is a [[BLEVE]], or boiling liquid expanding vapour explosion. All liquefied gases are stored above their normal boiling points and stay liquid only while the container is closed.<ref name="Lemoff-6-170" /> Lemoff stresses that a BLEVE is what happens after the container fails, not how it fails.<ref name="Lemoff-6-171" />
Line 101: Line 105:
<math display="block">E = 235\,P_{v}^{0.39}</math>
<math display="block">E = 235\,P_{v}^{0.39}</math>


For propane at 20 °C, the vapour pressure of 895 kPa, taken as gauge, corresponds to about 1.0 MPa absolute.<ref name="Lemoff-6-183" /> The correlation then gives an emissive power of about 235 kW/m². This lies within the measured range of 100 kW/m² to 450 kW/m².<ref name="Beyler-3-308" /> A related correlation by Roberts gives the radiative fraction as 0.27 times the storage pressure in MPa to the power 0.32. It was fitted to data between 0.2 MPa and 1.4 MPa, and for propane at 20 °C it gives about 0.27.<ref name="Beyler-3-307">Beyler (2002a), p. 3-307.</ref>
For propane at 20 °C, the vapour pressure of 895 kPa, taken as gauge, corresponds to about 1.0 MPa absolute.<ref name="Lemoff-6-183" /> If the correlation uses absolute pressure, it gives an illustrative emissive power of about 235 kW/m², within the measured range of 100 kW/m² to 450 kW/m².<ref name="Beyler-3-308" /> A related correlation by Roberts gives the radiative fraction as 0.27 times the storage pressure in MPa to the power 0.32. It was fitted to data between 0.2 MPa and 1.4 MPa; with the same pressure assumption, propane at 20 °C gives about 0.27.<ref name="Beyler-3-307">Beyler (2002a), p. 3-307.</ref> Beyler does not state whether either correlation expects absolute or gauge pressure.


Extinguishing agents are stored the same way. Liquid carbon dioxide can exist between its triple point at −57 °C and its critical temperature of 31 °C. At 21 °C its vapour pressure of 58 atm, about 5.9 MPa, expels the agent from the cylinder.<ref name="Yu-2-87">Yu and Newman (2008), p. 2-87.</ref> At 20 °C, Halon 1301 has a vapour pressure of 14.5 atm, Halon 1211 2.5 atm and Halon 2402 only 0.46 atm. Halons can be pressurised with nitrogen where the agent must be expelled faster than its own vapour pressure allows, especially outdoors in winter.<ref name="Yu-2-88">Yu and Newman (2008), p. 2-88.</ref>
Extinguishing agents are stored the same way. Liquid carbon dioxide can exist between its triple point at −57 °C and its critical temperature of 31 °C. At 21 °C its vapour pressure of 58 atm, about 5.9 MPa, expels the agent from the cylinder.<ref name="Yu-2-87">Yu and Newman (2008), p. 2-87.</ref> At 20 °C, Halon 1301 has a vapour pressure of 14.5 atm, Halon 1211 2.5 atm and Halon 2402 only 0.46 atm. Halons can be pressurised with nitrogen where the agent must be expelled faster than its own vapour pressure allows, especially outdoors in winter.<ref name="Yu-2-88">Yu and Newman (2008), p. 2-88.</ref>
Line 113: Line 117:
Vapour pressure explains several extinguishing mechanisms. Foam blocks radiant heat, and if the fire point of the liquid is above the temperature of the foam, the liquid is cooled and its vapour pressure falls. For water-soluble liquids such as alcohols, dilution with water from the foam also reduces the vapour pressure.<ref name="Yu-2-79">Yu and Newman (2008), p. 2-79.</ref> Mawhinney reports that water mist extinguished a diesel pool fire within 60 seconds in tests at the National Research Council of Canada. A heptane fire under the same spray kept burning, because the low flash point of heptane (−4 °C) and its high vapour pressure make it hard to dilute below the lean limit.<ref name="Mawhinney-16-146">Mawhinney (2008), p. 16-146.</ref>
Vapour pressure explains several extinguishing mechanisms. Foam blocks radiant heat, and if the fire point of the liquid is above the temperature of the foam, the liquid is cooled and its vapour pressure falls. For water-soluble liquids such as alcohols, dilution with water from the foam also reduces the vapour pressure.<ref name="Yu-2-79">Yu and Newman (2008), p. 2-79.</ref> Mawhinney reports that water mist extinguished a diesel pool fire within 60 seconds in tests at the National Research Council of Canada. A heptane fire under the same spray kept burning, because the low flash point of heptane (−4 °C) and its high vapour pressure make it hard to dilute below the lean limit.<ref name="Mawhinney-16-146">Mawhinney (2008), p. 16-146.</ref>


The same property limits water supplies. When fire service pumps draft water, the vapour pressure of the water reduces the vacuum that can be achieved and therefore the possible lift.<ref name="Stewart-13-24">Stewart (2008), p. 13-24.</ref> Warmer water has a higher vapour pressure and so gives less lift.<ref name="Stewart-13-25" />
The same property limits water supplies. When fire service pumps draft water, the vapour pressure of the water reduces the vacuum that can be achieved and therefore the possible lift.<ref name="Wieder-13-24">Wieder (2008), p. 13-24.</ref> Warmer water has a higher vapour pressure and so gives less lift.<ref name="Wieder-13-25" />


Several limits apply to the use of vapour pressure. The Clausius–Clapeyron equation assumes a constant heat of vaporisation and ideal-gas vapour, so it is an estimate.<ref name="Kanury-2-194" /> Vapour pressure describes equilibrium, which exists only in closed systems and may take time to develop.<ref name="Slye-6-203" /><ref name="Slye-6-204" /> The Reid value differs slightly from the true vapour pressure.<ref name="Slye-6-199" /> Away from the surface, the vapour concentration is lower than the equilibrium value, because the vapour diffuses into the air above.<ref name="Kanury-2-194" /><ref name="Drysdale-2-17" />
Several limits apply to the use of vapour pressure. The Clausius–Clapeyron equation assumes a constant heat of vaporisation and ideal-gas vapour, so it is an estimate.<ref name="Kanury-2-194" /> Full equilibrium develops slowly in a closed system; an open liquid surface can still have approximately saturated vapour while evaporation continues.<ref name="Slye-6-203" /><ref name="Slye-6-204" /><ref name="Kanury-2-194" /> The Reid value differs slightly from the true vapour pressure.<ref name="Slye-6-199" /> Away from the surface, the vapour concentration is lower than the equilibrium value, because the vapour diffuses into the air above.<ref name="Kanury-2-194" /><ref name="Drysdale-2-17" />


A common misconception is that a liquid with a high flash point cannot form flammable vapour. A liquid that is heated to its flash point or above will do so, whatever its flash point at room temperature.<ref name="Slye-6-203" /> Heavy vapours can also travel along floors to remote ignition sources, a behaviour governed by [[vapour density]] rather than by vapour pressure.<ref name="Slye-6-199" />
A liquid with a high flash point can still form flammable vapour when heated to its flash point.<ref name="Slye-6-203" /> Heavy vapours can also travel along floors to remote ignition sources, a behaviour governed by [[vapour density]] rather than by vapour pressure.<ref name="Slye-6-199" />


== See also ==
== See also ==
Line 149: Line 153:
* Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
* Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
* Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 6-197–6-208). National Fire Protection Association.
* Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 6-197–6-208). National Fire Protection Association.
* Stewart, L. J. (2008). Alternate water supplies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 13-37–13-52). National Fire Protection Association.
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy.
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy.
* Wieder, M. A. (2008). Fire streams. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 13-23–13-35). National Fire Protection Association.
* Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 13-117–13-144). National Fire Protection Association.
* Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 13-117–13-144). National Fire Protection Association.
* Wright, C. J. (2008b). Rail transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 21-109–21-134). National Fire Protection Association.
* Wright, C. J. (2008b). Rail transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), ''Fire protection handbook'' (20th ed., pp. 21-109–21-134). National Fire Protection Association.

Latest revision as of 08:25, 8 November 2026

Vapour pressure is the pressure exerted by the vapour of a liquid in the space just above its surface when vapour and liquid are in equilibrium.[1] It rises steeply with temperature, and a liquid boils when its vapour pressure equals the total pressure above it.[1][2] In fire protection, vapour pressure matters because flammable and combustible liquids burn as vapour, not as liquid.[3] The vapour pressure sets how much vapour can mix with the air above a liquid. The Fire Protection Handbook (20th edition, 2008) therefore lists it among the basic physical characteristics of flammable and combustible liquids.[4]

The share of vapour in a closed container equals the vapour pressure divided by the total pressure. Acetone at 37.8 °C, for example, has a vapour pressure of 52 kPa, so its vapour makes up about 52 percent of the space above it at atmospheric pressure.[4] This link explains the flash point, the temperature at which the vapour pressure is just high enough to reach the lower flammability limit.[5] It also explains why liquefied gases such as propane stay under pressure in their containers and why their containers can fail violently in a fire.[6] In the United States, NFPA 30, as described in the 2008 edition of the handbook, also uses vapour pressure to separate liquids from gases.[7]

Definition and physical basis

Kandola describes vapour pressure in molecular terms. As the temperature of a liquid rises, the activity of its molecules increases and some of them escape from the surface. The pressure exerted by these escaped molecules just above the surface is the vapour pressure of the liquid.[1] Evaporation is a physical change of state and does not alter the chemical nature of the substance. It also takes energy from the surroundings.[8]

The vapour pressure used here is an equilibrium property. Slye points out that equilibrium over the whole liquid can be reached in a closed system, such as a tank, pipe or process vessel. In the open air, an evaporating liquid keeps losing vapour until it is used up.[9] For a flammable liquid, the liquid evaporates at the rate needed to maintain the equilibrium vapour pressure above its surface. Solid polymers are more complex, because they break down into fragments that each have their own equilibrium vapour pressure.[10]

Left: closed vessel of acetone with 52 percent vapour in the space above. Right: open dish where vapour keeps leaving.
In a closed vessel, net evaporation stops when the vapour reaches its equilibrium pressure; for acetone at 37.8 °C the space then holds about 52 percent vapour. In the open, the liquid keeps evaporating.

The boiling point follows directly from vapour pressure. It is the temperature at which the equilibrium vapour pressure of a liquid equals the total pressure on its surface. The normal boiling point is the boiling temperature at 1 atm, or 101 kPa.[2] A higher total pressure raises the boiling point, and any liquid can in principle be made to boil at any temperature by changing the pressure.[2] Above its critical temperature, increasing the pressure cannot restore a distinct liquid phase.[4] Introduction to Fire Safety Engineering describes the critical point, beyond which liquid and gas can no longer be told apart and the substance is called supercritical.[8]

A liquid with a high vapour pressure at a given temperature, a low boiling point and a low latent heat is called highly volatile.[11] Benedetti notes that the most hazardous combustible liquids are those with a high vapour pressure, because burning takes place in the vapour phase.[12] As the boiling point decreases, the vapour pressure and the evaporation rate generally increase.[13]

Temperature dependence: the Clausius–Clapeyron equation

The vapour pressure of a liquid grows roughly exponentially with its temperature.[11] Kanury gives this dependence with the integrated Clausius–Clapeyron equation. In words, the ratio of the vapour pressure at the surface temperature to a reference pressure depends on the heat of vaporisation and on how far the temperature lies from the reference temperature.[14] If the reference is taken at the normal boiling point, the reference pressure is simply atmospheric pressure:[14]

PvP∘=exp⁡[(hfgRTb)(1−TbTs)]

The equation rests on three assumptions. The heat of vaporisation does not change with temperature, the vapour occupies far more volume than the liquid, and the vapour behaves nearly as an ideal gas.[14] For many nonpolar liquids, the group in the first bracket is close to a constant, a relation known as Trouton's rule:[14]

hfgRTb≈10.18

Trouton's constant is larger than 10.18 for alcohols and smaller for acids.[14] With the rule, the vapour pressure curve of a liquid can be estimated from its normal boiling point alone. Kanury refers to the CRC Handbook of Physics and Chemistry for measured vapour pressure tables of hundreds of liquids.[14]

When the liquid surface is in equilibrium with the gas above it, the mole fraction, or volume fraction, of fuel vapour at the surface is the vapour pressure divided by the total pressure:[14][4]

Xv=PvP

At an atmospheric pressure of about 101 kPa, a vapour pressure in kPa is therefore numerically close to the vapour concentration in percent by volume.[13] The volume fraction away from the surface is lower, because the vapour must diffuse into the air above.[14] The surface value is therefore the highest concentration that the liquid can produce at that temperature.[14]

Symbol Description Unit
Pv vapour pressure of the liquid at its surface temperature kPa
P∘ reference pressure; atmospheric pressure when the reference temperature is the normal boiling point kPa
P total (ambient) pressure kPa
hfg heat (enthalpy) of vaporisation kJ/kg
R gas constant of the vapour, 8.314 kJ/(kmol·K) divided by the molar mass kJ/(kg·K)
Tb normal boiling point K
Ts temperature of the liquid surface K
Xv mole fraction (volume fraction) of vapour –
LFL lower flammable limit vol. %
V vapour pressure at the closed-cup flash point kPa
E surface emissive power of a fireball kW/m²

Water gives an everyday sense of the numbers. Wieder lists its vapour pressure as 1.8 kPa at 16 °C, 3.6 kPa at 27 °C, 6.6 kPa at 38 °C and 11.7 kPa at 49 °C.[15] Above about 177 °C (350 °F) the vapour pressure of water rises so fast that heat transfer systems need expensive high-pressure equipment.[16]

Log-scale chart of vapour pressure against temperature for water, acetone, butane and propane, with a line at atmospheric pressure.
Vapour pressure data for water, acetone, butane and propane at the indicated temperatures. Where a curve crosses the atmospheric line, the liquid boils; butane and propane lie above it and are stored as liquefied gases.

Vapour pressure and flammability

Because vapour pressure fixes the vapour concentration over a liquid in a closed space, it decides whether that space can burn.[4] At low temperatures the mixture is too lean. At the temperature where the vapour pressure at the surface reaches the lower flammable limit, the mixture becomes ignitable. Beyler identifies that temperature with the flash point.[17] At a still higher temperature the vapour exceeds the upper flammable limit. Beyler notes that this typically occurs in an automobile petrol tank.[17]

Slye turns this relation into a simple estimate. It is the same proportionality between vapour pressure and vapour concentration, applied at the flash point. If the closed-cup flash point of a liquid and its vapour pressure at that temperature are known, the lower flammable limit in percent by volume follows from:[13]

LFL=100VP

At normal atmospheric pressure this reduces to LFL=V/1.01 with V in kPa.[13] The flash point itself corresponds only roughly to the temperature at which the vapour pressure produces a mixture at the lower flammable limit.[13] The fire point, at which burning can continue, lies somewhat higher still.[18]

Storage tanks show the practical effect. Ordile explains that the vapour space of a tank holding a liquid with a vapour pressure above about 28 kPa (4 psia), such as petrol, is normally too rich to burn.[19] The vapour space above a liquid below about 14 kPa (2 psia), such as kerosene, is normally too lean.[19] Ethyl and methyl alcohol and JP-4 jet fuel, at about 14 kPa to 28 kPa at 38 °C, present an unusual hazard, because their vapour spaces are normally within the flammable range.[19] Petrol cooled to between about −23 °C and −46 °C can also have a flammable vapour space.[19] It is the temperature of the liquid, not of the air in the tank, that controls the mixture.[19]

Horizontal scale of vapour pressure with three bands: too lean below 14 kPa, flammable 14 to 28 kPa, too rich above 28 kPa, with fuels marked.
The vapour space of a storage tank is normally too lean below about 14 kPa, flammable between about 14 and 28 kPa and too rich above 28 kPa.

Aviation fuels follow the same pattern. Boucher lists Reid vapour pressures of 0.1 psi (0.69 kPa) for kerosene-type Jet A and 2.0 psi to 3.0 psi (13.8 kPa to 20.7 kPa) for JP-4, a blend of petrol and kerosene.[20] Aviation petrol reaches 5.5 psi to 7.0 psi (37.9 kPa to 48.3 kPa).[20] The corresponding temperature ranges for flammable vapour are about 35 °C to 74 °C for the kerosene grades, −23 °C to 38 °C for JP-4 and −46 °C to −1 °C for aviation petrol.[20]

Pressure acts in the opposite direction to temperature. A liquid releases more vapour when the pressure above it is lowered and less when it is raised.[9] A flammable mixture can therefore exist far below the stated flash point when the pressure is much less than 1 atm.[21] Kanury adds that the flash point rises with total pressure in the same way as the boiling point.[22] Slye warns that published charts of these effects assume equilibrium. Before equilibrium is reached, a vessel expected to be too rich can pass through the flammable range.[23]

Worked example: acetone

Kanury lists acetone with a molar mass of 58 kg/kmol, a normal boiling point of 329 K and a heat of vaporisation of 521 kJ/kg. Its Trouton ratio is 11.05.[24] At 37.8 °C, or 310.95 K, the exponent of the Clausius–Clapeyron equation is 11.05 × (1 − 329/310.95), which is −0.641. The vapour pressure is then 101.3 kPa × e−0.641, or about 53 kPa.[14] Slye gives a measured value of 7.6 psia (52 kPa), so the simple equation agrees within about 3 percent.[4] The vapour then forms about 52 percent of an equilibrium mixture at atmospheric pressure, as Slye states.[4]

The same data can be used the other way round to estimate the flash point. The lean limit of acetone is 2.6 percent by volume.[24] By Slye's relation, the vapour pressure at the flash point must then be about 1.01 × 2.6, or 2.63 kPa.[13] Solving the Clausius–Clapeyron equation for this vapour pressure gives a surface temperature of about 247 K, or −26 °C.[14] The measured closed-cup flash point in Kanury's table is 255 K (−18 °C), and the open-cup value is 264 K (−9 °C).[24]

The estimate is thus about 8 K too low for the closed cup. Kanury explains the direction of the gap: the vapour concentration at the pilot flame is lower than at the surface, because the vapour must first diffuse upward.[14] His fit across many fuels puts this dilution factor between about 0.07 and 0.25.[22] For this acetone example, matching the measured closed-cup temperature would require a factor of about 0.64, outside that fitted range. The equilibrium estimate is therefore only a lower bound, not a quantitative prediction of acetone's flash point. Kanury considers predictive use of such relations premature.[22]

Measurement and data

For petroleum liquids, vapour pressure is usually measured by the Reid method of ASTM D323. This test gives the vapour pressure at 37.8 °C (100 °F), which differs slightly from the true vapour pressure.[4] Values for many other substances can be found in chemical handbooks.[4] Eberly notes that the Reid vapour pressure of a petroleum cargo expresses the rate at which its flammable gases are given off.[25] Planning for hazardous materials incidents also lists vapour pressure among the properties to consider for a stored chemical.[26]

Vapour pressure also affects the United States classification described by Slye (2008). In that account of NFPA 30, liquids have a vapour pressure not exceeding 276 kPa (40 psia) at 37.8 °C (100 °F). A fluid above that pressure is treated as a gas in this classification.[7] Anderson (2008a) adds that a Class I liquid must have a closed-cup flash point below 37.8 °C and a Reid vapour pressure not above the same limit.[27] The further split of flammable liquids is explained under flammable and combustible liquid classification.[7]

The boiling point of mixtures is defined differently in two sources. The handbook uses the 10 percent point of an ASTM D86 distillation as the boiling point in most NFPA standards.[2] NUREG-1805, a fire hazard toolkit of the U.S. Nuclear Regulatory Commission, uses the 20 percent evaporated point of the same test.[28] Both sources agree that the boiling point is the temperature at which the vapour pressure equals atmospheric pressure.[28][2]

Liquefied gases and the BLEVE

A liquefied gas is a gas that exists partly as liquid and partly as vapour inside its closed container at 20 °C. It stays under pressure as long as some liquid remains, and that pressure depends on the temperature of the liquid.[29] Propane is a gas at room temperature but is liquefied by storing it under a pressure equal to its vapour pressure.[30] Lemoff gives approximate vapour pressures for commercial propane of 895 kPa at 20 °C and 1,482 kPa at 40 °C. For commercial butane the values are 103 kPa and 285 kPa. The same table gives the psi values as gauge pressures, that is, above atmospheric pressure.[31]

These numbers inform container design. In his 2008 chapter on vehicle fuels, Rivkin gives 1,724 kPa (250 psig) as the normal minimum design pressure for LP-gas vessels under NFPA 58 and the ASME code. This is based on gases with a vapour pressure of 1,482 kPa (215 psig) at 38 °C. For a vessel installed on a motor vehicle, he gives the higher minimum of 2,154 kPa (312.5 psig).[32] Aerosol propellants are even named after their vapour pressure at 21 °C. A-31 is isobutane at 214 kPa gauge and A-108 is propane at 745 kPa gauge.[33]

When a liquefied gas container is heated, three effects combine. The vapour is compressed, the liquid expands, and the vapour pressure of the liquid rises with its temperature.[34] If the liquid expands until the container is full, a little more heating causes a very large rise in pressure. Codes therefore limit the filling density so that a vapour space always remains.[34] Wright warns that a rail tank car exposed to fire can build up vapour pressure until its relief device operates or the tank ruptures.[35]

Three sketches of a horizontal propane tank: normal storage, heated by fire with relief valve open, and failure with liquid flashing to vapour.
A liquefied gas is kept liquid only by its own vapour pressure. Fire raises the liquid temperature and pressure; if the shell fails, part of the liquid flashes to vapour.

The failure of such a container is a BLEVE, or boiling liquid expanding vapour explosion. All liquefied gases are stored above their normal boiling points and stay liquid only while the container is closed.[6] Lemoff stresses that a BLEVE is what happens after the container fails, not how it fails.[36]

When the container fails, the heat stored in the liquid makes part of it flash into vapour. The fraction is proportional to the difference between the liquid temperature and the normal boiling point. For many flammable liquefied gases at normal temperatures it is about one-third.[6] Propane at the highest relief valve setting of 1,896 kPa (275 psig) gauge boils at about 57 °C, far above its atmospheric boiling point of about −40 °C.[6][31] In a fire with the relief valve operating, more than half of the liquid can therefore vaporise when the container fails.[36]

Vapour pressure also appears in the correlations for the resulting fireball. Fireballs form when volatile hydrocarbons are released and rapidly ignited, as when the vapour from a failed container meets the fire that caused the failure.[37][36] Beyler reports the correlation of Pape et al. for the surface emissive power of hydrocarbon fireballs as a function of the vapour pressure in MPa:[38]

E=235Pv0.39

For propane at 20 °C, the vapour pressure of 895 kPa, taken as gauge, corresponds to about 1.0 MPa absolute.[31] If the correlation uses absolute pressure, it gives an illustrative emissive power of about 235 kW/m², within the measured range of 100 kW/m² to 450 kW/m².[38] A related correlation by Roberts gives the radiative fraction as 0.27 times the storage pressure in MPa to the power 0.32. It was fitted to data between 0.2 MPa and 1.4 MPa; with the same pressure assumption, propane at 20 °C gives about 0.27.[39] Beyler does not state whether either correlation expects absolute or gauge pressure.

Extinguishing agents are stored the same way. Liquid carbon dioxide can exist between its triple point at −57 °C and its critical temperature of 31 °C. At 21 °C its vapour pressure of 58 atm, about 5.9 MPa, expels the agent from the cylinder.[40] At 20 °C, Halon 1301 has a vapour pressure of 14.5 atm, Halon 1211 2.5 atm and Halon 2402 only 0.46 atm. Halons can be pressurised with nitrogen where the agent must be expelled faster than its own vapour pressure allows, especially outdoors in winter.[41]

Mixtures of liquids

For mixtures, the vapour pressure depends on whether the components dissolve in each other. Completely miscible liquids lower each other's vapour pressures.[13] For nearly immiscible liquids, the vapour pressure of the mixture is the sum of the partial pressures of each liquid layer, following Dalton's law of partial pressures. Partly miscible liquids behave in a more complex way.[13]

Differences in vapour pressure between components can change the hazard over time. Slye describes a mixture of petrol with enough carbon tetrachloride to have no flash point at all. In an open container, the carbon tetrachloride evaporates faster than the petrol, so the remaining liquid shows a falling flash point.[42] The last 10 percent finally approaches the flash point of the heavier petrol fractions. Fractional evaporation tests at 10, 20, 40, 60 and 90 percent evaporated can reveal such behaviour.[42] Gottuk and White note that defining a vapour pressure for each component of a multicomponent fuel is tedious at best and often impossible.[43]

Use in fire protection and limits

Vapour pressure explains several extinguishing mechanisms. Foam blocks radiant heat, and if the fire point of the liquid is above the temperature of the foam, the liquid is cooled and its vapour pressure falls. For water-soluble liquids such as alcohols, dilution with water from the foam also reduces the vapour pressure.[44] Mawhinney reports that water mist extinguished a diesel pool fire within 60 seconds in tests at the National Research Council of Canada. A heptane fire under the same spray kept burning, because the low flash point of heptane (−4 °C) and its high vapour pressure make it hard to dilute below the lean limit.[45]

The same property limits water supplies. When fire service pumps draft water, the vapour pressure of the water reduces the vacuum that can be achieved and therefore the possible lift.[46] Warmer water has a higher vapour pressure and so gives less lift.[15]

Several limits apply to the use of vapour pressure. The Clausius–Clapeyron equation assumes a constant heat of vaporisation and ideal-gas vapour, so it is an estimate.[14] Full equilibrium develops slowly in a closed system; an open liquid surface can still have approximately saturated vapour while evaporation continues.[9][23][14] The Reid value differs slightly from the true vapour pressure.[4] Away from the surface, the vapour concentration is lower than the equilibrium value, because the vapour diffuses into the air above.[14][5]

A liquid with a high flash point can still form flammable vapour when heated to its flash point.[9] Heavy vapours can also travel along floors to remote ignition sources, a behaviour governed by vapour density rather than by vapour pressure.[4]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Kandola (2002), p. 1-2.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Slye (2008), p. 6-202.
  3. ↑ Slye (2008), p. 6-197.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 Slye (2008), p. 6-199.
  5. ↑ 5.0 5.1 Drysdale (2008), p. 2-17.
  6. ↑ 6.0 6.1 6.2 6.3 Lemoff (2008), p. 6-170.
  7. ↑ 7.0 7.1 7.2 Slye (2008), p. 6-198.
  8. ↑ 8.0 8.1 Van Rossum (2027), §3.5.
  9. ↑ 9.0 9.1 9.2 9.3 Slye (2008), p. 6-203.
  10. ↑ Beyler and Hirschler (2002), p. 1-110.
  11. ↑ 11.0 11.1 Kanury (2002b), p. 2-189.
  12. ↑ Benedetti (2008), p. 6-6.
  13. ↑ 13.0 13.1 13.2 13.3 13.4 13.5 13.6 13.7 Slye (2008), p. 6-200.
  14. ↑ 14.00 14.01 14.02 14.03 14.04 14.05 14.06 14.07 14.08 14.09 14.10 14.11 14.12 14.13 14.14 Kanury (2002b), p. 2-194.
  15. ↑ 15.0 15.1 Wieder (2008), p. 13-25.
  16. ↑ LeBlanc (2008), p. 8-65.
  17. ↑ 17.0 17.1 Beyler (2002b), p. 2-174.
  18. ↑ Simmons (2002), p. 1-147.
  19. ↑ 19.0 19.1 19.2 19.3 19.4 Ordile (2008), p. 7-16.
  20. ↑ 20.0 20.1 20.2 Boucher (2008), p. 21-137.
  21. ↑ Slye (2008), p. 6-201.
  22. ↑ 22.0 22.1 22.2 Kanury (2002b), p. 2-195.
  23. ↑ 23.0 23.1 Slye (2008), p. 6-204.
  24. ↑ 24.0 24.1 24.2 Kanury (2002b), p. 2-193.
  25. ↑ Eberly (2008), p. 21-168.
  26. ↑ C. J. Wright (2008a), p. 13-134.
  27. ↑ Anderson (2008a), p. 9-163.
  28. ↑ 28.0 28.1 Iqbal and Salley (2004), p. B-21.
  29. ↑ Lemoff (2008), p. 6-168.
  30. ↑ Rivkin (2008b), p. 21-55.
  31. ↑ 31.0 31.1 31.2 Lemoff (2008), p. 6-183.
  32. ↑ Rivkin (2008b), p. 21-72.
  33. ↑ Fredrickson (2008), p. 6-258.
  34. ↑ 34.0 34.1 Lemoff (2008), p. 6-169.
  35. ↑ C. J. Wright (2008b), p. 21-110.
  36. ↑ 36.0 36.1 36.2 Lemoff (2008), p. 6-171.
  37. ↑ Beyler (2002a), p. 3-306.
  38. ↑ 38.0 38.1 Beyler (2002a), p. 3-308.
  39. ↑ Beyler (2002a), p. 3-307.
  40. ↑ Yu and Newman (2008), p. 2-87.
  41. ↑ Yu and Newman (2008), p. 2-88.
  42. ↑ 42.0 42.1 Slye (2008), p. 6-205.
  43. ↑ Gottuk and White (2002), p. 2-301.
  44. ↑ Yu and Newman (2008), p. 2-79.
  45. ↑ Mawhinney (2008), p. 16-146.
  46. ↑ Wieder (2008), p. 13-24.

References

  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
  • Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
  • Boucher, B. (2008). Aviation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-135–21-149). National Fire Protection Association.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
  • Fredrickson, D. L. (2008). Manufacture and storage of aerosol products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-257–6-267). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kandola, B. S. (2002). Introduction to mechanics of fluids. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-1–1-26). National Fire Protection Association; Society of Fire Protection Engineers.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • LeBlanc, J. A. (2008). Heat transfer systems and fluids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-65–8-70). National Fire Protection Association.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Mawhinney, J. R. (2008). Water mist fire suppression systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-135–16-180). National Fire Protection Association.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wieder, M. A. (2008). Fire streams. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-23–13-35). National Fire Protection Association.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
  • Wright, C. J. (2008b). Rail transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-109–21-134). National Fire Protection Association.
  • Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.