'''Fire risk''' is the potential for unwanted consequences to human life, health, property or the environment as a result of fire. It involves both the likelihood of events and the losses they may cause. A hazard describes a condition with potential for harm, while risk also requires attention to exposure and probability.<ref name="Watts-5-3">Watts and Hall (2002b), pp. 5-2–5-4.</ref><ref name="Watts-5-155">Watts and Hall (2002a), pp. 5-154–5-156.</ref>
'''Fire risk''' is the potential for a fire to cause unwanted, adverse consequences to human life, health, property or the environment.<ref name="WH-5-3">Watts and Hall (2002), p. 5-3.</ref> It brings together three questions: what could happen, how bad it would be, and how likely it is.<ref name="WH-5-1">Watts and Hall (2002), pp. 5-1–5-2.</ref> A fire risk therefore depends both on the consequences of possible fires and on the likelihood that they occur. It describes the uncertainty of a loss, not a loss that is certain to happen.<ref name="WH-5-1" /> Every decision related to fire safety is in effect a fire risk decision, whether or not it is treated as one.<ref name="WH-5-1" />
[[File:fse-fire-risk-v1.svg|thumb|upright=1.5|alt=What could happen, how likely and how severe lead to a risk evaluation.|Fire risk combines event scenarios, likelihood and consequences. Based on Watts and Hall (2002), pp. 5-1–5-3 and Meacham (2002), pp. 5-154–5-156.]]


Fire risk cannot be described completely by fire size or by the number of past fires. The assessment must ask what could happen, how severe the consequences would be and how likely those consequences are. The answers depend on the building, occupants, systems and evidence being considered.<ref name="Watts-5-1">Watts and Hall (2002b), pp. 5-1–5-3.</ref><ref name="Hall-5-65">Hall and Ahrens (2002), pp. 5-65–5-67.</ref>
Zero risk is not an achievable goal, because no technology is completely reliable and natural events such as lightning and earthquakes can also cause fires.<ref name="WH-5-4">Watts and Hall (2002), p. 5-4.</ref> The practical questions are how large the remaining risk is and whether it is acceptable. Accepting a level of risk requires a value judgement, and people make such judgements in different ways.<ref name="WH-5-1" /> Fire risk is estimated from [[Fire statistics|fire statistics]], usage data and laboratory tests, and the result is then judged for its acceptability.<ref name="HallAhrens-5-65">Hall and Ahrens (2002), p. 5-65.</ref><ref name="WH-5-3" />


Zero risk is not an achievable goal. Fire safety work instead evaluates and reduces risks under stated conditions, then considers whether the remaining risk is acceptable. Acceptability involves values and stakeholder decisions as well as technical calculations.<ref name="Watts-5-4">Watts and Hall (2002b), pp. 5-3–5-4.</ref><ref name="IFEG-0-2-8">Australian Building Codes Board et al. (2005), pp. 0.2-7–0.2-8.</ref>
== Hazard, consequence and probability ==


== Hazard, exposure and consequence ==
A hazard is a chemical or physical condition that has the potential to cause damage to people, property or the environment.<ref name="WH-5-3" /> An analysis of what could happen and how bad it would be, without considering how likely it is, is called a fire hazard analysis. A fire risk analysis adds the likelihood. A sequence of events that ends in a fire loss is called a scenario.<ref name="WH-5-1" /> For a whole building, the fire risk is the full spread of possible events and their consequences, not the outcome of one scenario.<ref name="WH-5-3" />


A hazard is a chemical or physical condition that can cause injury or damage. Fuel, an ignition source and an impaired barrier can each form part of a hazardous condition. Their presence identifies potential, but does not quantify how likely or severe an event will be.<ref name="Watts-5-3" />
Consequences describe how bad a fire would be if it happened. They range from deaths and damage to property to intangible losses such as business interruption, environmental damage and the destruction of cultural objects. A consequence can be direct, such as damaged property, or indirect, such as a company that is out of business for several days. It can also be objective, such as a replacement cost, or subjective, such as the pain and suffering of an injury.<ref name="WH-5-1" /> In building fire risk analysis, the main things of value are life safety, property, business continuity, the environment and heritage.<ref name="Meacham-5-153">Meacham (2002), pp. 5-153–5-154.</ref>


A scenario is a sequence of events leading to a fire loss. It can include ignition, development, system responses, exposure and final consequences. Evaluating only one link would omit the causal path that determines the outcome.<ref name="Watts-5-2">Watts and Hall (2002b), pp. 5-1–5-2.</ref><ref name="Watts-5-157">Watts and Hall (2002a), pp. 5-157–5-158.</ref>
Risk is usually estimated by combining the probability that an event occurs with the consequence of the event if it does occur.<ref name="WH-5-3" /> The terminology is not consistent: a committee of the Society for Risk Analysis found 17 different definitions of risk.<ref name="WH-5-3" /> The SFPE Handbook also describes fire risk as the possibility of an unwanted outcome in an uncertain situation, where fire may cause loss or harm to something that is valued.<ref name="Meacham-5-153" /> A related term is the fire safety level, which the Australian Fire Safety Verification Method handbook (2020) calls the reciprocal of fire risk: when the risk to occupants falls, the safety level rises.<ref name="ABCB-140">Australian Building Codes Board (2020b), p. 140.</ref>


Exposure concerns who or what can experience harm. Occupants, firefighters, a building, its contents and neighbouring property can have different exposures. The same fire can therefore create several different risk problems.<ref name="Watts-5-155" /><ref name="IFEG-1-2-7">Australian Building Codes Board et al. (2005), pp. 1.2-7–1.2-8.</ref>
== Frequency and probability ==


Consequences describe the effects if the event occurs. They can include injury, death, property damage, business interruption, environmental harm or loss of heritage. Some consequences are measured directly, while others require explicit valuation and assumptions.<ref name="Watts-5-2" /><ref name="Watts-5-155" />
A frequency states how often an event occurs in a period, such as the number of fires per year. On its own it is not a probability, because the number of possible occurrences is also needed.<ref name="Meacham-5-159">Meacham (2002), p. 5-159.</ref> In a hypothetical example, 20 fires a year in toasters that are switched on 20 million times a year give a probability of one in a million per start.<ref name="Meacham-5-159" /> Fire incident data therefore have to be combined with usage or exposure data, such as the number of appliances in use or the floor area of a type of building.<ref name="HallAhrens-5-65" />


Fire risk analysis must connect these elements. A severe consequence with low likelihood and a frequent event with limited consequences present different decisions. Neither consequence nor frequency alone supplies the full comparison.<ref name="Watts-5-2" /><ref name="Watts-5-4" />
There are two views of probability. In the frequency view, probability is the proportion of the time that an event occurs in the long run. In the subjective view, it measures how strongly a person believes that an event will occur.<ref name="WH-5-3" /> Fires are relatively rare, and buildings and their contents change over time, so past losses are a limited guide to future ones. This is a strong argument for using subjective probabilities, based on current knowledge and judgement, in building fire risk analysis.<ref name="Meacham-5-159" />


== Likelihood, frequency and probability ==
The amount of available data differs widely. For US homes there are very many recorded fires with limited detail, while for US nuclear power plants there are far fewer fires but much more detail on each. For a single existing building there are very few fires at all. In fire safety engineering, risk analysis is therefore mostly used for an application or a class of facility with a considerable fire loss history.<ref name="WH-5-3" />


Frequency describes how often an event occurs within a period. Probability is the proportion of relevant opportunities or time in which the event occurs in a frequency interpretation. A count of fires alone does not provide the opportunities needed to form such a proportion.<ref name="Watts-5-3" /><ref name="Watts-5-159">Watts and Hall (2002a), p. 5-159.</ref>
== Typical values ==


For example, a rate per building-year requires both the number of incidents and the relevant building exposure. Without that denominator, a larger incident count may simply reflect more buildings or better reporting. The rate's meaning depends on its defined exposure measure.<ref name="Hall-5-65" />
The frequency of fire depends strongly on the use of a building. In British Standards Institution data from 2001, quoted in the International Fire Engineering Guidelines (2005), a dwelling had about 0.003 fire starts per year and an office about 0.006. Schools and industrial buildings had about 0.04, entertainment venues about 0.12 and hospitals about 0.3 fire starts per building per year. The guidelines warn that such values may have changed with new technologies and materials.<ref name="IFEG-3-2-2">National Research Council of Canada et al. (2005), p. 3.2-2.</ref> Finnish data show that the number of fires per square metre falls as buildings get larger, while the number per building generally rises with floor area.<ref name="IFEG-3-2-3">National Research Council of Canada et al. (2005), p. 3.2-3.</ref>


Probability can also represent a degree of belief based on knowledge and judgement. This subjective interpretation can be useful where events are rare or the future differs from the recorded past. It requires transparent treatment of the knowledge and assumptions used.<ref name="Watts-5-3" /><ref name="Watts-5-159" />
Risk studies often sort frequencies into broad classes. One example in the SFPE Handbook calls events anticipated if they occur more often than once in 100 years. Events are unlikely between once in 100 and once in 10,000 years, and extremely unlikely between once in 10,000 and once in a million years. Rarer events are beyond extremely unlikely. Frequencies should be counted for a given loss rather than for a single scenario: 30 scenarios that each occur once in 10 million years together occur three times in a million years.<ref name="Meacham-5-166">Meacham (2002), pp. 5-166–5-167.</ref>


Changing buildings and contents complicate future estimates. Past data may describe another fuel arrangement, occupancy or protection system. A statistical frequency is therefore not automatically a prediction of future risk in the altered setting.<ref name="Watts-5-159" /><ref name="Hall-5-70">Hall and Ahrens (2002), pp. 5-69–5-71.</ref>
Reliability values are typical inputs as well. In reported US home fires, roughly one-third of smoke alarms were not working, but a general study of home installations found only one-fifth not working. Data from unreported fires suggest that the main reason is that working alarms keep many fires so small that the fire service is never called. Reported US fires suggest that sprinklers do not operate in one-sixth to one-fifth of the fires large enough to activate them, yet their real reliability could be well over 90 %.<ref name="HallAhrens-5-72">Hall and Ahrens (2002), p. 5-72.</ref>


The distinction between likelihood and consequence must be retained in every scenario. High reliability can reduce the chance of failure but not prove that a failure would be harmless. Likewise, a severe scenario can be credible without being probable enough to dominate a risk decision.<ref name="Watts-5-4" /><ref name="Notarianni-5-43">Notarianni (2002), pp. 5-43–5-44.</ref>
== Individual and societal risk ==


== Individual and societal measures ==
Risk to people is often expressed in two complementary ways. [[Individual risk]] is the probability of injury or death to a person at a specified location relative to a fire or explosion source. It can be drawn as contour lines that connect points of equal risk, regardless of whether anyone is actually present there.<ref name="Barry-5-210">Barry (2002), p. 5-210.</ref> In the Australian Fire Safety Verification Method handbook (2020), individual risk is the frequency at which a person may be expected to suffer a given level of harm from a fire in the building.<ref name="ABCB-22">Australian Building Codes Board (2020b), p. 22.</ref>


[[Individual risk]] concerns the probability of injury or death to a person at a specified location relative to a defined source. Barry's description uses location within the fire or explosion effect zone. It can be shown as a profile or as contours of equal potential risk.<ref name="Barry-5-210">Barry (2002), pp. 5-210–5-211.</ref>
[[Societal risk]] takes into account the likelihood of fires or explosions that cause multiple casualties. It is often shown as an F-N curve, which plots the frequency of events that exceed a given number of fatalities, N, against that number.<ref name="Barry-5-210" /> Such a curve requires the population at risk, the likelihood that people are present and the reliability of measures such as evacuation to be defined.<ref name="Barry-5-211">Barry (2002), p. 5-211.</ref> Barry (2002) describes these measures for the chemical process industries, where most calculations of risk to people are based on fatalities.<ref name="Barry-5-211" />
[[File:fse-fire-risk-v2.svg|thumb|upright=1.5|alt=Location-based individual contours contrast with cumulative frequency for multiple casualties.|Individual and societal risk answer different questions. Based on Barry (2002), pp. 5-210–5-211.]]


Individual-risk contours describe geographical variation of that potential harm. The cited definition does not require a person to be present for the location-based contour to be drawn. Actual exposure and the presence of people must still be addressed when interpreting the result.<ref name="Barry-5-210" />
The two measures answer different questions. Individual risk shows how the risk to one person varies from place to place, while societal risk shows how often losses of many lives can occur.<ref name="Barry-5-210" /> Single-value risk indices, such as an annual predicted fatality rate, are easy to understand and useful for comparing design options. A ranking of the events that contribute most to the total helps to focus risk reduction.<ref name="Barry-5-211" /> In Australia, the Fire Safety Verification Method Standard 2022 accepts the deemed-to-satisfy provisions of the National Construction Code as reflecting societal expectations, including on individual and societal risk.<ref name="ABCB2022-7">Australian Building Codes Board (2022), p. 7.</ref>


[[Societal risk]] considers the likelihood of multiple casualties resulting from fire or explosion. It therefore addresses population outcomes rather than only a single person's location. The population at risk and the likelihood of presence must be defined.<ref name="Barry-5-211">Barry (2002), pp. 5-211–5-212.</ref>
== Acceptable risk ==


One presentation is a cumulative frequency plot of events exceeding different fatality numbers. Such a curve shows how the frequency changes with consequence severity. It relies on assumptions about exposed populations, mitigation and the reliability of those assumptions.<ref name="Barry-5-211" />
Acceptable risk is a value judgement applied to a chosen scale for measuring risk. It needs two prior decisions: how risk is measured, and whose views on acceptability count. For a practising engineer, acceptable risk is usually the risk acceptable to the client, while for an authority it is meant to be acceptable to society or to a particular community. A universally acceptable level of fire risk does not exist, because it depends on the problem and on the person judging it.<ref name="WH-5-4" />


Individual and societal measures answer different questions and are not interchangeable. A location with high individual risk need not describe the total population consequence. A low expected total can also conceal a high consequence event with small frequency.<ref name="Barry-5-211" /><ref name="Watts-5-2" />
People judge the same risk in different ways. Experts mainly weigh the calculated reduction in fire risk, while ordinary people also weigh costs and other needs. Enforcers act on behalf of society, and managers such as builders are most directly affected by the costs.<ref name="WH-5-1" /> The reduced fire risk of a home sprinkler system, for example, appears to be valued less by the average citizen than the benefit of a new car.<ref name="WH-5-1" /> Risks that are objectively equal are also perceived differently: people prefer certain over uncertain, familiar over unfamiliar, voluntary over involuntary and ordinary over dramatic risks.<ref name="WH-5-3" /> Dying in a fire is perceived as worse than dying in a car accident, and most people who die in fires die at home.<ref name="VR-7">Van Rossum (2027), §7.</ref>


== Fire statistics as evidence ==
Reducing fire risk may even increase other risks, as with the potential damage to the ozone layer from halon extinguishing agents. The goal that comes closest to zero risk is risk as low as is technically possible. In fire protection engineering, this may mean accepting the residual risk after all identified risk reduction measures have been adopted. A complication is that this residual risk may then be perceived as zero, although a non-zero risk remains.<ref name="WH-5-4" /> In Australia, workplace health and safety legislation also requires safe design, which a code of practice defines as eliminating risks to health and safety or, if this is not reasonably practicable, minimising them.<ref name="ABCB-25">Australian Building Codes Board (2020b), p. 25.</ref>


[[Fire statistics]] supply incident, exposure and loss data for estimating parts of a risk problem. They can inform ignition frequencies, consequence distributions and the effectiveness of protective measures. Their definitions and collection methods must be compatible with the analysis question.<ref name="Hall-5-65" /><ref name="Hall-5-67">Hall and Ahrens (2002), pp. 5-67–5-69.</ref>
Building regulations rarely state an acceptable risk in numbers. The Australian Fire Safety Verification Method Standard 2022 notes that the National Construction Code contains no specific safety targets. A design assessed with this method must therefore be at least equivalent to the deemed-to-satisfy provisions.<ref name="ABCB2022-7" /> It adds that a full quantitative probabilistic risk assessment would ideally be used, but the tools and data for it are not included. The method instead permits a simple deterministic comparison of available and required escape times, with additional checks.<ref name="ABCB2022-18">Australian Building Codes Board (2022), p. 18.</ref>


Incident records provide observed cases, but not every fire is reported. Small fires may be handled by occupants or private brigades and never enter municipal records. National estimates consequently require careful treatment of missing populations and reporting practices.<ref name="Hall-5-70" />
In the Netherlands, where no risk-based limit values exist, the residual risk can be expressed as an acceptable probability of failure. One way to set it is by comparison with a reference situation that follows the rules.<ref name="VR-1-2">Van Rossum (2027), §1.2.</ref><ref name="VR-1-4">Van Rossum (2027), §1.4.</ref> In performance-based design, deciding which consequences matter is often described as setting fire safety goals, [[Fire safety objectives|fire safety objectives]] and criteria.<ref name="Meacham-5-155">Meacham (2002), p. 5-155.</ref>


Laboratory data provide controlled measurements of ignition, fire growth, material response or system activation. Field observations provide evidence of degradation, impairment and actual use. These sources complement incident statistics rather than competing with them.<ref name="Hall-5-65" /><ref name="Hall-5-72">Hall and Ahrens (2002), pp. 5-71–5-73.</ref>
== Fire statistics as evidence ==
 
Unknown or unreported characteristics can distort patterns. If unknown causes are ignored, every known category can appear to grow even when the total number of incidents is unchanged. Allocation methods make assumptions about those unknown records explicit.<ref name="Hall-5-68">Hall and Ahrens (2002), pp. 5-67–5-69.</ref>
 
Anecdotes can show the diversity of possible events but cannot estimate incident rates or probabilities. Opportunity samples may overrepresent severe or unusual fires. A larger and more detailed database is not automatically representative of the target population.<ref name="Hall-5-70" />


== Objectives and acceptability ==
Fire incident data show how often fires start and how severe they are. In the United States, the national fire incident reporting system collects roughly a million fires a year, but only about half of the fires reported to fire departments. A separate survey of fire departments is therefore used to scale the data up to national estimates. Fires with an unknown cause must be allocated over the known causes. If they are ignored while the share of unknowns falls, every known cause can appear to grow although the total number of fires stays the same.<ref name="HallAhrens-5-67">Hall and Ahrens (2002), pp. 5-67–5-68.</ref>


[[Fire safety objectives]] define the outcomes being pursued and the people or assets to be protected. They determine which consequences must be characterised and which criteria will be used. Risk analysis without those objectives can produce numbers without a clear decision.<ref name="IFEG-1-2-7" /><ref name="Watts-5-155" />
Not every fire appears in these statistics. Fires handled by the occupants or by private fire brigades are not reported, and fires in buildings with sprinklers or good detection are more likely to be controlled on site. Anecdotes show the range of fires that can happen but cannot be used to estimate rates or probabilities. Detailed databases that are not statistically representative can also mislead, so analysts should not give up statistical validity for detail.<ref name="HallAhrens-5-69">Hall and Ahrens (2002), pp. 5-69–5-70.</ref>


Acceptable risk is a value judgement applied to a particular measure of risk. It requires a decision about both the measurement scale and the person or community whose acceptance matters. Technical experts, enforcers, managers and the public can weigh costs and benefits differently.<ref name="Watts-5-4" /><ref name="Watts-5-2" />
Data on the reliability of fire protection systems are scarce.<ref name="HallAhrens-5-69" /> Expert estimates tend to rate reliable systems even higher and unreliable systems even lower than they really are. Inspection and testing records usually come from well-maintained properties, so they show better reliability than typical buildings achieve. They can also miss short-lived failures, such as a door blocked open.<ref name="HallAhrens-5-71">Hall and Ahrens (2002), p. 5-71.</ref>


Zero risk is not a realistic acceptance criterion. IFEG repeats that position in its regulatory discussion, while Watts and Hall emphasise that no technology is completely reliable or immune to misuse. Reducing fire risk can also change other risks and must be evaluated in context.<ref name="Watts-5-4" /><ref name="IFEG-0-2-8" />
== Assessing and reducing fire risk ==


Stakeholder involvement can clarify the values behind a decision. The Fire Engineering Brief provides a structure for agreeing on objectives, criteria and scenarios. It does not eliminate disagreement, but it makes those choices visible for review.<ref name="IFEG-0-2-8" /><ref name="IFEG-1-2-2">Australian Building Codes Board et al. (2005), pp. 1.2-2–1.2-3.</ref>
Fire risk analysis is a structured approach to decision making under uncertainty. A general procedure identifies the fire hazards, estimates their consequences and probabilities, identifies options to control them, estimates how each option changes the risk, and selects the protection.<ref name="WH-5-4" /> Methods of [[Fire risk assessment|fire risk assessment]] range from checklists and written recommendations through risk indexing to probabilistic methods.<ref name="WH-5-4" /> Checklists and written recommendations do not quantify risk: a design passes if it follows them, and the residual risk is never evaluated.<ref name="WH-5-5">Watts and Hall (2002), p. 5-5.</ref>


[[ALARP]] is a named concept in the term metadata for this topic, but it is not defined in the supplied source documents. No universal ALARP criterion or numerical threshold is therefore stated in this article. The sources instead support evaluation of residual risk, technically possible reduction and stakeholder acceptability.<ref name="Watts-5-4" /><ref name="IFEG-0-2-8" />
A risk matrix sorts hazards by classes of consequence and likelihood, and each cell can record whether such risks are acceptable or how they should be reduced. Probabilistic methods are the most informative, because their results can be traced back through explicit assumptions, data and relationships. Common tools are event trees, which follow the possible outcomes after an initiating event in time order, and fault trees, which show the combinations of system states that lead to an outcome.<ref name="WH-5-5" />


== Risk reduction and system performance ==
Risk can be reduced at several points in the chain from cause to consequence. The SFPE Handbook describes a causal sequence from an initiating event through its outcome and the exposure of people or property to the final consequences. The sequence can be interrupted at each of these points, by blocking the event, the outcome, the exposure or the consequence.<ref name="Meacham-5-157">Meacham (2002), p. 5-157.</ref> In the chemical process industries, some measures reduce how often incidents occur, such as preventive maintenance, control of ignition sources and operator training. Others reduce how severe they are, such as gas and fire detection, fireproofing of steel and water sprays.<ref name="Barry-5-211" />
[[File:fse-fire-risk-v3.svg|thumb|upright=1.5|alt=Ignition, fire development, exposure and consequences offer different intervention points.|Risk reduction can act at several points in the fire scenario. Based on Meacham (2002), pp. 5-157–5-159 and Barry (2002), p. 5-211.]]


Risk reduction can address the frequency of initiating events, the severity of outcomes or exposure to them. Prevention, suppression, compartmentation, evacuation and management affect different stages. The selection should follow the causal structure rather than relying on one preferred measure.<ref name="Watts-5-157" /><ref name="Barry-5-211" />
Measures only reduce risk if they work when they are needed. Typical reliability questions are whether the battery in a smoke alarm works, whether a sprinkler valve is open and whether a fire door is blocked open.<ref name="WH-5-6">Watts and Hall (2002), p. 5-6.</ref> A US Nuclear Regulatory Commission guide lists causes of sprinkler failure. Examples are a closed water supply valve, an empty tank and a fire pump that fails to start, for instance after a power failure.<ref name="NUREG-10-2">Iqbal and Salley (2004), p. 10-2.</ref> Failures can also share a common cause, as when a failure of the fire detection system stops a smoke control system from working as intended.<ref name="ABCBDS-C4">Australian Building Codes Board (2020a), Data Sheet C4, p. 131.</ref>
 
The fire safety concepts tree distinguishes preventing ignition from managing fire impact. This supports a systematic review of possible measures without assuming every ignition can be prevented. Residual events still require attention to their consequences.<ref name="Watts-5-158">Watts and Hall (2002a), pp. 5-158–5-159.</ref>
 
Protective-system reliability influences risk. A sprinkler, alarm or smoke-control system can be effective when operational but unavailable because of power, supply, detection or maintenance failures. Common dependencies must be represented when several measures are credited.<ref name="NUREG-10-2">U.S. Nuclear Regulatory Commission (2005), p. 10-2.</ref><ref name="ABCB-131">Australian Building Codes Board (2020), p. 131.</ref>
 
Reliability data also have limitations. Inspection programmes can miss transient impairments and can overrepresent well-maintained properties. Laboratory and field evidence should be combined to understand both tested performance and actual availability.<ref name="Hall-5-72" /><ref name="Hall-5-71">Hall and Ahrens (2002), pp. 5-71–5-72.</ref>
 
Reducing risk in one area can introduce other effects. Suppression agents, altered routes and new technologies can create secondary hazards or operational demands. The evaluation should include those effects rather than assuming every protective measure is beneficial in every respect.<ref name="Watts-5-4" /><ref name="NUREG-B57">U.S. Nuclear Regulatory Commission (2005), p. B-57.</ref>


== Uncertainty and variability ==
== Uncertainty and variability ==


Uncertainty includes incomplete knowledge about models, data, inputs and future conditions. Variability describes real differences among people, buildings and events. Treating all variation as one distribution can hide the different meaning of those limitations.<ref name="Watts-5-159" /><ref name="Notarianni-5-43" />
Fire risk estimates are always uncertain. Unwanted combustion is perhaps the least predictable common physical phenomenon, and uncertainty analysis should underpin the choice of safety factors and safety margins. This concerns the uncertainty of the engineer about how large a risk is, not the uncertainty of a potential victim about whether a fire loss will occur.<ref name="WH-5-6" /> A totally objective way to measure fire risk does not exist, because defining the problem, collecting data and combining information all involve subjective judgements.<ref name="WH-5-3" />
 
Model uncertainty arises when physical processes are omitted, simplified or represented by empirical correlations. Input uncertainty arises from inaccurate or incomplete values. Both can change a result even when the calculation is implemented correctly.<ref name="Notarianni-5-43" /><ref name="Watts-5-160">Watts and Hall (2002a), p. 5-160.</ref>
 
Human behaviour introduces both uncertainty and variability. Occupants may not begin moving immediately, may need assistance or may choose familiar routes. Those differences can alter risk to different groups and should not be replaced by a single idealised occupant.<ref name="Notarianni-5-43" /><ref name="Proulx-3-342">Proulx (2002), pp. 3-342–3-344.</ref>
 
Sensitivity analysis examines whether reasonable changes in inputs alter the decision. Notarianni calls a change in acceptability switchover and links it to criteria, scenarios, models and behavioural assumptions. It is a decision-level concern, not only a numerical variation.<ref name="Notarianni-5-43" />
 
The analysis record should distinguish measured data from expert judgement. Where evidence is missing or unrepresentative, that limitation should be documented. More decimal places cannot resolve those underlying weaknesses.<ref name="Watts-5-160" /><ref name="Hall-5-70" />
 
== Interpretation and communication ==
 
Risk results should be presented in a form that matches the decision. Profiles can show spatial variation, cumulative curves can show multiple-casualty outcomes, and option comparisons can show risk reduction. The chosen format must not hide important uncertainty.<ref name="Barry-5-209">Barry (2002), pp. 5-209–5-212.</ref>
 
Single-value indices can simplify communication but can also conceal the distribution of events. A severe, low-frequency event and a frequent small loss may produce similar aggregate values while requiring different actions. Contributors to the total should remain visible.<ref name="Barry-5-211" /><ref name="Watts-5-2" />
 
[[Fire risk assessment]] uses these inputs to identify, evaluate and manage risk in a structured way. It can include hazard identification, consequence and likelihood estimation, control options and evaluation of their effects. The scope and depth should suit the decision.<ref name="Watts-5-4" /><ref name="Watts-5-155" />
 
A completed assessment should not be treated as permanent. Changes to fuel, occupants, building systems or operations can alter the scenarios and evidence. Re-evaluation is needed when those changes affect the safety basis.<ref name="IFEG-0-3-8">Australian Building Codes Board et al. (2005), p. 0.3-8.</ref>
 
The useful outcome is an informed decision, not a claim of perfect prediction. The record should identify objectives, scenarios, data, assumptions, uncertainty and remaining risk. This allows stakeholders to judge both the technical result and whether it is acceptable to them.<ref name="Watts-5-4" /><ref name="Watts-5-160" />
 
The scope of a risk study can be retrospective or prospective. A retrospective study examines what happened and infers patterns from incidents, while a prospective study evaluates how a proposed change may alter future outcomes. Both require relevant data and explicit treatment of differences between past and proposed conditions.<ref name="Watts-5-3" />
 
Fire hazard analysis and fire risk analysis are related but not identical. Hazard analysis examines what can happen and how bad it can be without necessarily assessing likelihood. Risk analysis adds likelihood and evaluates how control options change the resulting risks.<ref name="Watts-5-2" /><ref name="Watts-5-4" />
 
Different stakeholders can interpret the same risk reduction differently. A technical assessment may emphasise predicted loss reduction, while a manager considers cost and operations and a community considers fairness and other needs. The engineering report should make the evaluation criteria visible so those perspectives can be discussed.<ref name="Watts-5-2" />
 
Data should be chosen for the particular level of analysis. A national occupancy estimate, a product assessment and a specific building evaluation require different exposure definitions and detail. Evidence that is suitable for one level may be too aggregated or unrepresentative for another.<ref name="Hall-5-65" /><ref name="Watts-5-3" />


Protective options should be compared by their effects on the complete scenario. A measure can reduce ignition probability, limit spread, reduce exposure or change the consequence, and those effects need not be equal. Comparing only equipment efficiency would miss the resulting change in overall risk.<ref name="Watts-5-157" /><ref name="Barry-5-211" />
Uncertainty and variability are different things. It may not be known how many people will be exposed, which is uncertainty, while the people who are exposed differ from each other, which is variability.<ref name="Meacham-5-159" /> Scientific uncertainties come from theories and models, from data and inputs, from limits of the calculation, from the level of detail and from how well a model represents reality. Further uncertainty lies in human behaviour, in perceptions of risk and values, and in decision making itself.<ref name="Meacham-5-160">Meacham (2002), p. 5-160.</ref>


Residual risk should be stated after the selected measures are evaluated. This includes hazards that remain, uncertainties that could change the outcome and any new effects introduced by the protection. Such a statement gives decision-makers a more accurate basis than describing only the expected benefit.<ref name="Watts-5-4" /><ref name="Watts-5-160" />
Calculations can hide much of this uncertainty. Fire models give single values, such as a detector activation time of 121 s, although the real time may be longer or shorter. One widely used egress model assumes that all occupants are readily mobile and start leaving as soon as they hear an alarm, which experience shows is often not the case. In a full uncertainty analysis, only the inputs that could change the decision on whether a design is acceptable, a change called switchover, need detailed quantitative treatment.<ref name="Notarianni-5-43">Notarianni (2002), pp. 5-43–5-44.</ref>


Where the evidence cannot distinguish between plausible outcomes, that limitation should remain visible in the conclusion. It may be necessary to obtain better data, evaluate another scenario or change the design rather than select one outcome arbitrarily. Recording this uncertainty preserves the difference between a demonstrated result and an unresolved risk question.<ref name="Watts-5-160" /><ref name="Notarianni-5-43" />
Design practice also handles variability and uncertainty in simpler ways. The Dutch national annex to Eurocode 1 (NEN-EN 1991-1-2/NB), for example, gives both average fire loads and 80 % fractiles for a more conservative approach. An 80 % fractile is a value that the actual fire load does not exceed in 80 % of cases.<ref name="VR-8-5">Van Rossum (2027), §8.5.</ref> An escape time analysis keeps a safety margin between the available and the required escape time, because many of the inputs are uncertain. The more reliable the inputs are, the smaller the margin needs to be.<ref name="VR-7-1">Van Rossum (2027), §7.1.</ref>


== See also ==
== See also ==


* [[Fire risk assessment]]
* [[Event tree analysis]]
* [[Fire statistics]]
* [[Fault tree analysis]]
* [[Individual risk]]
* [[Quantitative risk assessment]]
* [[Reliability of fire protection systems]]
* [[Uncertainty analysis]]
* [[Fire safety concepts tree]]


== Notes ==
== Notes ==
Line 127: Line 93:
== References ==
== References ==


* Australian Building Codes Board. (2020). ''Fire safety verification method data sheets'' (Version 1.1). Author.
* Australian Building Codes Board. (2020a). ''Data sheets: Fire Safety Verification Method'' (Handbook annex, Print version 1.1).
* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board.
* Australian Building Codes Board. (2020b). ''Handbook: Fire Safety Verification Method'' (Print version 1.1).
* Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Australian Building Codes Board. (2022). ''Fire Safety Verification Method Standard 2022''.
* Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 5-176–5-213). National Fire Protection Association; Society of Fire Protection Engineers.
* Notarianni, K. A. (2002). Uncertainty. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
* Proulx, G. (2002). Movement of people: The evacuation timing. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Iqbal, N., & Salley, M. H. (2004). ''Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program'' (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
* U.S. Nuclear Regulatory Commission. (2005). ''Fire dynamics tools: Quantitative fire hazard analysis methods for the U.S. nuclear regulatory commission fire protection inspection program'' (NUREG-1805). Author.
* Meacham, B. J. (2002). Building fire risk analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 5-153–5-175). National Fire Protection Association; Society of Fire Protection Engineers.
* National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board.
* Notarianni, K. A. (2002). Uncertainty. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 5-40–5-64). National Fire Protection Association; Society of Fire Protection Engineers.
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy.
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy.
* Watts, J. M., Jr., & Hall, J. R., Jr. (2002a). Building fire risk analysis. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Watts, J. M., Jr., & Hall, J. R., Jr. (2002). Introduction to fire risk analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 5-1–5-7). National Fire Protection Association; Society of Fire Protection Engineers.
* Watts, J. M., Jr., & Hall, J. R., Jr. (2002b). Introduction to fire risk analysis. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.


[[Category:Fire Risk Analysis]]
[[Category:Fire Risk Analysis]]

Latest revision as of 22:32, 2 November 2026

Fire risk is the potential for a fire to cause unwanted, adverse consequences to human life, health, property or the environment.[1] It brings together three questions: what could happen, how bad it would be, and how likely it is.[2] A fire risk therefore depends both on the consequences of possible fires and on the likelihood that they occur. It describes the uncertainty of a loss, not a loss that is certain to happen.[2] Every decision related to fire safety is in effect a fire risk decision, whether or not it is treated as one.[2]

What could happen, how likely and how severe lead to a risk evaluation.
Fire risk combines event scenarios, likelihood and consequences. Based on Watts and Hall (2002), pp. 5-1–5-3 and Meacham (2002), pp. 5-154–5-156.

Zero risk is not an achievable goal, because no technology is completely reliable and natural events such as lightning and earthquakes can also cause fires.[3] The practical questions are how large the remaining risk is and whether it is acceptable. Accepting a level of risk requires a value judgement, and people make such judgements in different ways.[2] Fire risk is estimated from fire statistics, usage data and laboratory tests, and the result is then judged for its acceptability.[4][1]

Hazard, consequence and probability

A hazard is a chemical or physical condition that has the potential to cause damage to people, property or the environment.[1] An analysis of what could happen and how bad it would be, without considering how likely it is, is called a fire hazard analysis. A fire risk analysis adds the likelihood. A sequence of events that ends in a fire loss is called a scenario.[2] For a whole building, the fire risk is the full spread of possible events and their consequences, not the outcome of one scenario.[1]

Consequences describe how bad a fire would be if it happened. They range from deaths and damage to property to intangible losses such as business interruption, environmental damage and the destruction of cultural objects. A consequence can be direct, such as damaged property, or indirect, such as a company that is out of business for several days. It can also be objective, such as a replacement cost, or subjective, such as the pain and suffering of an injury.[2] In building fire risk analysis, the main things of value are life safety, property, business continuity, the environment and heritage.[5]

Risk is usually estimated by combining the probability that an event occurs with the consequence of the event if it does occur.[1] The terminology is not consistent: a committee of the Society for Risk Analysis found 17 different definitions of risk.[1] The SFPE Handbook also describes fire risk as the possibility of an unwanted outcome in an uncertain situation, where fire may cause loss or harm to something that is valued.[5] A related term is the fire safety level, which the Australian Fire Safety Verification Method handbook (2020) calls the reciprocal of fire risk: when the risk to occupants falls, the safety level rises.[6]

Frequency and probability

A frequency states how often an event occurs in a period, such as the number of fires per year. On its own it is not a probability, because the number of possible occurrences is also needed.[7] In a hypothetical example, 20 fires a year in toasters that are switched on 20 million times a year give a probability of one in a million per start.[7] Fire incident data therefore have to be combined with usage or exposure data, such as the number of appliances in use or the floor area of a type of building.[4]

There are two views of probability. In the frequency view, probability is the proportion of the time that an event occurs in the long run. In the subjective view, it measures how strongly a person believes that an event will occur.[1] Fires are relatively rare, and buildings and their contents change over time, so past losses are a limited guide to future ones. This is a strong argument for using subjective probabilities, based on current knowledge and judgement, in building fire risk analysis.[7]

The amount of available data differs widely. For US homes there are very many recorded fires with limited detail, while for US nuclear power plants there are far fewer fires but much more detail on each. For a single existing building there are very few fires at all. In fire safety engineering, risk analysis is therefore mostly used for an application or a class of facility with a considerable fire loss history.[1]

Typical values

The frequency of fire depends strongly on the use of a building. In British Standards Institution data from 2001, quoted in the International Fire Engineering Guidelines (2005), a dwelling had about 0.003 fire starts per year and an office about 0.006. Schools and industrial buildings had about 0.04, entertainment venues about 0.12 and hospitals about 0.3 fire starts per building per year. The guidelines warn that such values may have changed with new technologies and materials.[8] Finnish data show that the number of fires per square metre falls as buildings get larger, while the number per building generally rises with floor area.[9]

Risk studies often sort frequencies into broad classes. One example in the SFPE Handbook calls events anticipated if they occur more often than once in 100 years. Events are unlikely between once in 100 and once in 10,000 years, and extremely unlikely between once in 10,000 and once in a million years. Rarer events are beyond extremely unlikely. Frequencies should be counted for a given loss rather than for a single scenario: 30 scenarios that each occur once in 10 million years together occur three times in a million years.[10]

Reliability values are typical inputs as well. In reported US home fires, roughly one-third of smoke alarms were not working, but a general study of home installations found only one-fifth not working. Data from unreported fires suggest that the main reason is that working alarms keep many fires so small that the fire service is never called. Reported US fires suggest that sprinklers do not operate in one-sixth to one-fifth of the fires large enough to activate them, yet their real reliability could be well over 90 %.[11]

Individual and societal risk

Risk to people is often expressed in two complementary ways. Individual risk is the probability of injury or death to a person at a specified location relative to a fire or explosion source. It can be drawn as contour lines that connect points of equal risk, regardless of whether anyone is actually present there.[12] In the Australian Fire Safety Verification Method handbook (2020), individual risk is the frequency at which a person may be expected to suffer a given level of harm from a fire in the building.[13]

Societal risk takes into account the likelihood of fires or explosions that cause multiple casualties. It is often shown as an F-N curve, which plots the frequency of events that exceed a given number of fatalities, N, against that number.[12] Such a curve requires the population at risk, the likelihood that people are present and the reliability of measures such as evacuation to be defined.[14] Barry (2002) describes these measures for the chemical process industries, where most calculations of risk to people are based on fatalities.[14]

Location-based individual contours contrast with cumulative frequency for multiple casualties.
Individual and societal risk answer different questions. Based on Barry (2002), pp. 5-210–5-211.

The two measures answer different questions. Individual risk shows how the risk to one person varies from place to place, while societal risk shows how often losses of many lives can occur.[12] Single-value risk indices, such as an annual predicted fatality rate, are easy to understand and useful for comparing design options. A ranking of the events that contribute most to the total helps to focus risk reduction.[14] In Australia, the Fire Safety Verification Method Standard 2022 accepts the deemed-to-satisfy provisions of the National Construction Code as reflecting societal expectations, including on individual and societal risk.[15]

Acceptable risk

Acceptable risk is a value judgement applied to a chosen scale for measuring risk. It needs two prior decisions: how risk is measured, and whose views on acceptability count. For a practising engineer, acceptable risk is usually the risk acceptable to the client, while for an authority it is meant to be acceptable to society or to a particular community. A universally acceptable level of fire risk does not exist, because it depends on the problem and on the person judging it.[3]

People judge the same risk in different ways. Experts mainly weigh the calculated reduction in fire risk, while ordinary people also weigh costs and other needs. Enforcers act on behalf of society, and managers such as builders are most directly affected by the costs.[2] The reduced fire risk of a home sprinkler system, for example, appears to be valued less by the average citizen than the benefit of a new car.[2] Risks that are objectively equal are also perceived differently: people prefer certain over uncertain, familiar over unfamiliar, voluntary over involuntary and ordinary over dramatic risks.[1] Dying in a fire is perceived as worse than dying in a car accident, and most people who die in fires die at home.[16]

Reducing fire risk may even increase other risks, as with the potential damage to the ozone layer from halon extinguishing agents. The goal that comes closest to zero risk is risk as low as is technically possible. In fire protection engineering, this may mean accepting the residual risk after all identified risk reduction measures have been adopted. A complication is that this residual risk may then be perceived as zero, although a non-zero risk remains.[3] In Australia, workplace health and safety legislation also requires safe design, which a code of practice defines as eliminating risks to health and safety or, if this is not reasonably practicable, minimising them.[17]

Building regulations rarely state an acceptable risk in numbers. The Australian Fire Safety Verification Method Standard 2022 notes that the National Construction Code contains no specific safety targets. A design assessed with this method must therefore be at least equivalent to the deemed-to-satisfy provisions.[15] It adds that a full quantitative probabilistic risk assessment would ideally be used, but the tools and data for it are not included. The method instead permits a simple deterministic comparison of available and required escape times, with additional checks.[18]

In the Netherlands, where no risk-based limit values exist, the residual risk can be expressed as an acceptable probability of failure. One way to set it is by comparison with a reference situation that follows the rules.[19][20] In performance-based design, deciding which consequences matter is often described as setting fire safety goals, fire safety objectives and criteria.[21]

Fire statistics as evidence

Fire incident data show how often fires start and how severe they are. In the United States, the national fire incident reporting system collects roughly a million fires a year, but only about half of the fires reported to fire departments. A separate survey of fire departments is therefore used to scale the data up to national estimates. Fires with an unknown cause must be allocated over the known causes. If they are ignored while the share of unknowns falls, every known cause can appear to grow although the total number of fires stays the same.[22]

Not every fire appears in these statistics. Fires handled by the occupants or by private fire brigades are not reported, and fires in buildings with sprinklers or good detection are more likely to be controlled on site. Anecdotes show the range of fires that can happen but cannot be used to estimate rates or probabilities. Detailed databases that are not statistically representative can also mislead, so analysts should not give up statistical validity for detail.[23]

Data on the reliability of fire protection systems are scarce.[23] Expert estimates tend to rate reliable systems even higher and unreliable systems even lower than they really are. Inspection and testing records usually come from well-maintained properties, so they show better reliability than typical buildings achieve. They can also miss short-lived failures, such as a door blocked open.[24]

Assessing and reducing fire risk

Fire risk analysis is a structured approach to decision making under uncertainty. A general procedure identifies the fire hazards, estimates their consequences and probabilities, identifies options to control them, estimates how each option changes the risk, and selects the protection.[3] Methods of fire risk assessment range from checklists and written recommendations through risk indexing to probabilistic methods.[3] Checklists and written recommendations do not quantify risk: a design passes if it follows them, and the residual risk is never evaluated.[25]

A risk matrix sorts hazards by classes of consequence and likelihood, and each cell can record whether such risks are acceptable or how they should be reduced. Probabilistic methods are the most informative, because their results can be traced back through explicit assumptions, data and relationships. Common tools are event trees, which follow the possible outcomes after an initiating event in time order, and fault trees, which show the combinations of system states that lead to an outcome.[25]

Risk can be reduced at several points in the chain from cause to consequence. The SFPE Handbook describes a causal sequence from an initiating event through its outcome and the exposure of people or property to the final consequences. The sequence can be interrupted at each of these points, by blocking the event, the outcome, the exposure or the consequence.[26] In the chemical process industries, some measures reduce how often incidents occur, such as preventive maintenance, control of ignition sources and operator training. Others reduce how severe they are, such as gas and fire detection, fireproofing of steel and water sprays.[14]

Ignition, fire development, exposure and consequences offer different intervention points.
Risk reduction can act at several points in the fire scenario. Based on Meacham (2002), pp. 5-157–5-159 and Barry (2002), p. 5-211.

Measures only reduce risk if they work when they are needed. Typical reliability questions are whether the battery in a smoke alarm works, whether a sprinkler valve is open and whether a fire door is blocked open.[27] A US Nuclear Regulatory Commission guide lists causes of sprinkler failure. Examples are a closed water supply valve, an empty tank and a fire pump that fails to start, for instance after a power failure.[28] Failures can also share a common cause, as when a failure of the fire detection system stops a smoke control system from working as intended.[29]

Uncertainty and variability

Fire risk estimates are always uncertain. Unwanted combustion is perhaps the least predictable common physical phenomenon, and uncertainty analysis should underpin the choice of safety factors and safety margins. This concerns the uncertainty of the engineer about how large a risk is, not the uncertainty of a potential victim about whether a fire loss will occur.[27] A totally objective way to measure fire risk does not exist, because defining the problem, collecting data and combining information all involve subjective judgements.[1]

Uncertainty and variability are different things. It may not be known how many people will be exposed, which is uncertainty, while the people who are exposed differ from each other, which is variability.[7] Scientific uncertainties come from theories and models, from data and inputs, from limits of the calculation, from the level of detail and from how well a model represents reality. Further uncertainty lies in human behaviour, in perceptions of risk and values, and in decision making itself.[30]

Calculations can hide much of this uncertainty. Fire models give single values, such as a detector activation time of 121 s, although the real time may be longer or shorter. One widely used egress model assumes that all occupants are readily mobile and start leaving as soon as they hear an alarm, which experience shows is often not the case. In a full uncertainty analysis, only the inputs that could change the decision on whether a design is acceptable, a change called switchover, need detailed quantitative treatment.[31]

Design practice also handles variability and uncertainty in simpler ways. The Dutch national annex to Eurocode 1 (NEN-EN 1991-1-2/NB), for example, gives both average fire loads and 80 % fractiles for a more conservative approach. An 80 % fractile is a value that the actual fire load does not exceed in 80 % of cases.[32] An escape time analysis keeps a safety margin between the available and the required escape time, because many of the inputs are uncertain. The more reliable the inputs are, the smaller the margin needs to be.[33]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Watts and Hall (2002), p. 5-3.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Watts and Hall (2002), pp. 5-1–5-2.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Watts and Hall (2002), p. 5-4.
  4. ↑ 4.0 4.1 Hall and Ahrens (2002), p. 5-65.
  5. ↑ 5.0 5.1 Meacham (2002), pp. 5-153–5-154.
  6. ↑ Australian Building Codes Board (2020b), p. 140.
  7. ↑ 7.0 7.1 7.2 7.3 Meacham (2002), p. 5-159.
  8. ↑ National Research Council of Canada et al. (2005), p. 3.2-2.
  9. ↑ National Research Council of Canada et al. (2005), p. 3.2-3.
  10. ↑ Meacham (2002), pp. 5-166–5-167.
  11. ↑ Hall and Ahrens (2002), p. 5-72.
  12. ↑ 12.0 12.1 12.2 Barry (2002), p. 5-210.
  13. ↑ Australian Building Codes Board (2020b), p. 22.
  14. ↑ 14.0 14.1 14.2 14.3 Barry (2002), p. 5-211.
  15. ↑ 15.0 15.1 Australian Building Codes Board (2022), p. 7.
  16. ↑ Van Rossum (2027), §7.
  17. ↑ Australian Building Codes Board (2020b), p. 25.
  18. ↑ Australian Building Codes Board (2022), p. 18.
  19. ↑ Van Rossum (2027), §1.2.
  20. ↑ Van Rossum (2027), §1.4.
  21. ↑ Meacham (2002), p. 5-155.
  22. ↑ Hall and Ahrens (2002), pp. 5-67–5-68.
  23. ↑ 23.0 23.1 Hall and Ahrens (2002), pp. 5-69–5-70.
  24. ↑ Hall and Ahrens (2002), p. 5-71.
  25. ↑ 25.0 25.1 Watts and Hall (2002), p. 5-5.
  26. ↑ Meacham (2002), p. 5-157.
  27. ↑ 27.0 27.1 Watts and Hall (2002), p. 5-6.
  28. ↑ Iqbal and Salley (2004), p. 10-2.
  29. ↑ Australian Building Codes Board (2020a), Data Sheet C4, p. 131.
  30. ↑ Meacham (2002), p. 5-160.
  31. ↑ Notarianni (2002), pp. 5-43–5-44.
  32. ↑ Van Rossum (2027), §8.5.
  33. ↑ Van Rossum (2027), §7.1.

References

  • Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
  • Australian Building Codes Board. (2020b). Handbook: Fire Safety Verification Method (Print version 1.1).
  • Australian Building Codes Board. (2022). Fire Safety Verification Method Standard 2022.
  • Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-176–5-213). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Meacham, B. J. (2002). Building fire risk analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-153–5-175). National Fire Protection Association; Society of Fire Protection Engineers.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Notarianni, K. A. (2002). Uncertainty. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-40–5-64). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Watts, J. M., Jr., & Hall, J. R., Jr. (2002). Introduction to fire risk analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-1–5-7). National Fire Protection Association; Society of Fire Protection Engineers.