A '''Smoke detector''' is a device that responds to smoke particles or aerosol produced by combustion and thermal decomposition. It can provide an earlier indication than a heat detector because smoke can be produced before the fire's heat output becomes large. Its response depends on particle properties, transport, entry into the detector and the detection algorithm.<ref name="NUREG-1805-11-3">U.S. Nuclear Regulatory Commission (2005), pp. 11-3–11-4.</ref><ref name="Schifiliti-4-23">Schifiliti, Meacham, and Custer (2002), p. 4-23.</ref>
A '''smoke detector''' is a device that responds to particles produced by combustion and supplies a signal when its alarm criterion is reached. Common sensing principles use changes in ion current, scattered light or transmitted light. The response depends on the particles reaching the sensing region and interacting with the particular sensor.<ref name="Mu_2-266_2-267">Mulholland (2002), pp. 2-266–2-267.</ref><ref name="SMC_4-21_4-24">Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-24.</ref>


Smoke detectors use several principles, including ionisation, light scattering, optical obscuration, projected beams, air sampling and multi-sensor detection. No principle responds identically to every smoke type. Large smouldering droplets and small flaming-combustion particles can produce very different responses.<ref name="Mulholland-2-267">Mulholland (2002), pp. 2-267–2-268.</ref><ref name="Ohlemiller-2-203">Ohlemiller (2002), p. 2-203.</ref>
Smoke varies with the fuel, burning mode and conditions during transport. Two smokes with the same measured optical density can produce different responses in a scattering or ionisation detector. A calibration threshold therefore needs to be interpreted with the smoke and test conditions used to establish it.<ref name="SMC_4-21_4-24" />


The device does not measure fire size or safety directly. It indicates that smoke with particular properties has reached and entered the detector in sufficient quantity or form to meet a response condition. That condition must be evaluated within the fire scenario and the detector's actual installation.<ref name="Schifiliti-4-23" /><ref name="NUREG-1805-11-6">U.S. Nuclear Regulatory Commission (2005), p. 11-6.</ref>
Detection time also includes transport and, for enclosed sensing chambers, smoke-entry delay. Air sampling and projected-beam arrangements introduce different measurement paths. Engineering assessment combines those physical processes with the detector's response criterion and any later alarm processing, while recognising the limits of available input data.<ref name="SMC_4-22_4-24">Schifiliti, Meacham, and Custer (2002), pp. 4-22–4-24.</ref><ref name="CVM_27_28">Ministry of Business, Innovation and Employment (2025), pp. 27–28.</ref>


== Detection principles ==
== How smoke becomes a detection signal ==


Ionisation detectors respond when smoke particles intercept gaseous ions and reduce the detector's ion current. They tend to be sensitive to high concentrations of small particles, such as those from flaming paper and wood fires. Their response is less sensitive to low concentrations of large smouldering droplets in the cited comparison.<ref name="Mulholland-2-267" />
Smoke contains particles whose properties depend on the fuel and the way it burns. Detectors can respond through changes in electrical current or changes in light reaching a receiver. The SFPE Handbook distinguishes the response of the sensor from the transport of smoke to it. Both processes affect the time at which an alarm signal becomes available.<ref name="Mu_2-266_2-267" /><ref name="SMC_4-21_4-24" />


Photoelectric or light-scattering detectors respond to light scattered by smoke. Their sensitivity depends on particle size distribution, refractive index, wavelength, scattering angle and scattering volume. They can be more sensitive to large smouldering droplets and less sensitive to low-smoking flaming fires in the cited comparison.<ref name="Mulholland-2-267" /><ref name="Schifiliti-4-24">Schifiliti, Meacham, and Custer (2002), p. 4-24.</ref>
An ionisation detector uses an ion current within its sensing chamber. Smoke particles intercept ions and reduce the current until the alarm criterion is reached, while a light-scattering detector instead measures light redirected by particles within the chamber. The two mechanisms respond differently to particle size, concentration and other smoke characteristics.<ref name="Mu_2-266_2-267" />


Projected-beam detectors measure attenuation along a light path. Total optical density is determined across that path, so beam length and smoke distribution matter. This approach can cover a large volume without requiring smoke to enter a small sensing chamber, although the beam and its wavelength must match the assessment.<ref name="Schifiliti-4-23" /><ref name="Schifiliti-4-24" />
A [[Beam smoke detector]] measures attenuation of a light beam across a space. Attenuation is the reduction of transmitted light caused by the smoke along its path. [[Aspirating smoke detection]] uses a sampling arrangement that draws air towards a sensing chamber. These arrangements introduce different measurement geometries and, for sampling systems, additional transport through the sampling network.<ref name="SMC_4-22_4-23">Schifiliti, Meacham, and Custer (2002), pp. 4-22–4-23.</ref><ref name="N_F-52">Iqbal and Salley (2004), p. F-52.</ref><ref name="CVM_27_28" />


Aspirating or air-sampling detectors draw air through a sampling system for analysis. This can support very high sensitivity and different placement strategies, but sampling time, filter condition and system design affect response. Their suitability should be established using product-specific testing rather than assuming faster activation in every scenario.<ref name="CVM2-26">Ministry of Business, Innovation and Employment (2025), p. 26.</ref><ref name="NUREG-6850-S1-13-5">U.S. Nuclear Regulatory Commission (2010), p. 13-5.</ref>
A detector supplies an input to the [[Fire alarm system]], which processes the signal and produces its configured outputs. Detection and occupant notification are separate functions. The presence of smoke at the sensing location does not establish that the complete warning sequence is already finished. Processing and the intended human response remain part of the system assessment.<ref name="SMC_4-2_4-3">Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3.</ref>


[[Multi-sensor detector]] designs use more than one sensing principle or input to improve fire-signature recognition. They can help distinguish fire from nuisance conditions, but their logic and thresholds are manufacturer-specific. Combining technologies does not eliminate unwanted alarms or the need for correct placement and testing.<ref name="Schifiliti-4-23" /><ref name="Proulx-3-351">Proulx (2002), p. 3-351.</ref>
[[File:fse-smoke-detector-v1.svg|thumb|upright=1.5|alt=Ionisation chamber, scattering chamber, projected beam and aspirating sampler.|Smoke-detection principles measure different particle responses. Based on Mulholland (2002), pp. 2-266–2-267 and Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-24 and Iqbal and Salley (2004), p. F-52.]]


== Optical density and light response ==
== Particle size, fuel and burning mode ==


[[Optical density]] expresses light attenuation per unit distance and is related to particle concentration and extinction properties. A projected-beam detector evaluates it along the beam, with the total response depending on path length. Smoke that is not uniformly distributed requires segment-by-segment evaluation rather than one room-average value.<ref name="Schifiliti-4-23" /><ref name="VR-6.4">Van Rossum (2027), §6.4.</ref>
Smoke is not a uniform substance with one universal detector response. Schifiliti and colleagues identify particle size distribution, concentration, composition, colour and refractive index as relevant characteristics. Refractive index describes how the material interacts with light. Fuel composition, flaming or smouldering combustion and the supply of combustion air affect the particles produced.<ref name="SMC_4-21">Schifiliti, Meacham, and Custer (2002), p. 4-21.</ref>


Wavelength is essential when comparing optical measurements with a detector. Data measured at another wavelength can introduce errors because scattering and absorption depend on it. The light source used in the test or model must match the detector being evaluated.<ref name="Schifiliti-4-23" /><ref name="Schifiliti-4-24" />
Mulholland compares ionisation and scattering responses for particular detectors. In that comparison, ionisation response is stronger for particles smaller than about 0.3 µm. Light-scattering response is stronger for particles larger than about 0.3 µm. This is an approximate comparison from the reported detector response functions, not a sharp dividing line for every device.<ref name="Mu_2-266_2-267" />


A scattering-type detector can respond at different optical densities for different smoke types. Schifiliti and colleagues give an example of a detector responding at 0.029 per metre to grey cotton-wick smoke but at 0.15 per metre for kerosene smoke. At those thresholds, both smoke types scatter the same amount of light to the receiver but differ in colour and reflection.<ref name="Schifiliti-4-24" />
The chapter associates relatively small particles with examples of flaming paper and wood fires. Larger droplets from smouldering combustion can favour the response of scattering detectors. These relationships explain why the same nominal optical obscuration does not imply the same electrical signal in every sensor. The burning mode and the detector principle must be considered together.<ref name="Mu_2-266_2-267" />


UL acceptance testing described by Mulholland uses optical density per metre of 0.06 for grey cellulosic smoke and 0.14 for black kerosene smoke. These source values are test criteria, not universal alarm thresholds for every detector or fire. Detector-specific calibration and smoke signature remain necessary.<ref name="Mulholland-2-267" />
Particle properties also change during transport. Particles can settle or combine, changing the number and size distribution that reaches the detector. The SFPE detection chapter therefore distinguishes smoke characteristics at the fire from those at the sensing location. Using generation data alone can omit changes relevant to the eventual response.<ref name="SMC_4-21__4-24">Schifiliti, Meacham, and Custer (2002), pp. 4-21, 4-24.</ref>


== Particle size and fire mode ==
[[File:fse-smoke-detector-v2.svg|thumb|upright=1.5|alt=Ionisation sensitivity stronger below 0.3 µm and light-scattering sensitivity stronger above it.|Detector sensitivity varies with particle size. Based on Mulholland (2002), pp. 2-266–2-267.]]


Particle size distribution influences detector response. Ionisation detectors in the cited comparison are more sensitive to particles smaller than about 0.3 micrometres, while light-scattering detectors are more sensitive to larger particles. These tendencies help explain why detector choice should reflect the expected fire mode.<ref name="Mulholland-2-267" />
== Getting smoke into the sensing region ==


Smouldering cellulosic insulation produced a mass mean particle size of 2 to 3 micrometres in Ohlemiller's study, much larger than cigarette smoke and the sooty particles from flaming combustion. This contributed to poor ionisation-detector sensitivity and to filtration of aerosol by the fuel bed. A detector suitable for one fire mode can therefore be slow or insensitive to another.<ref name="Ohlemiller-2-203" />
A rising plume can carry smoke towards the ceiling, where a [[Ceiling jet]] distributes it away from the fire. Ceiling height, geometry and intervening barriers influence this route. Natural and mechanical air currents also affect the movement of smoke, particularly during early, low-energy fires. The transport time cannot be assumed identical for different detector locations.<ref name="SMC_4-21_4-22">Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-22.</ref>


Flaming fires can produce small carbonaceous particles and strong light emission, while pyrolysis and smouldering often produce larger droplets and light-coloured smoke. Those physical differences affect both scattering and ionisation. A detector threshold cannot be inferred from fuel name alone without knowing the combustion mode.<ref name="Mulholland-2-258">Mulholland (2002), p. 2-258.</ref><ref name="Mulholland-2-267" />
Smoke reaching the outside of a spot detector must still enter its sensing chamber. Screens, chamber geometry and the flow around the housing can resist entry. The SFPE Handbook calls this entry resistance. During an increasing external smoke concentration, the concentration within the chamber can lag behind the surrounding smoke.<ref name="SMC_4-24">Schifiliti, Meacham, and Custer (2002), p. 4-24.</ref>


Smoke properties also change with transport. Particles can coagulate, evaporate, deposit or form through condensation, altering concentration and size distribution. A detector response measured near the source cannot simply be applied to an older or remote smoke cloud.<ref name="Mulholland-2-259">Mulholland (2002), p. 2-259.</ref><ref name="Schifiliti-4-24" />
This lag is conceptually separate from the detector's response threshold. A device may be sensitive to a particular smoke once it is inside the chamber but still receive that smoke slowly. The local gas velocity and the device's aerodynamic characteristics therefore matter. Treating external smoke concentration as instantaneously identical to chamber concentration can understate the response time.<ref name="SMC_4-22__4-24">Schifiliti, Meacham, and Custer (2002), pp. 4-22, 4-24.</ref>


== Transport and ceiling jet ==
A weak fire beneath a high ceiling may also produce smoke that loses buoyancy before entering the assumed ceiling flow. The handbook discusses this possibility when examining low-energy fires and stratification. Stratification means that smoke can collect at a level determined by the surrounding temperature conditions. A detector near the ceiling may therefore receive a different exposure from the one assumed in a simple spreading-layer calculation.<ref name="SMC_4-28">Schifiliti, Meacham, and Custer (2002), p. 4-28.</ref>


A [[Ceiling jet]] carries hot gases and smoke away from the plume and across the ceiling. Detector response depends on when that flow reaches the device and how much smoke it contains. Location, spacing, fire size and ceiling geometry therefore affect activation time.<ref name="IFEG-2.5-2">Australian Building Codes Board et al. (2005), p. 2.5-2.</ref><ref name="NUREG-1805-11-6" />
Air sampling introduces a different transport arrangement. C/VM2 identifies airflow, sampling-tube length and alarm threshold as factors in the response of very high sensitivity sampling systems. The method treats these systems as requiring specialised design. A sensitive measuring chamber alone does not determine the time needed for a sample to arrive and initiate the intended output.<ref name="CVM_27">Ministry of Business, Innovation and Employment (2025), p. 27.</ref>


Smoke entry resistance adds another delay. Bug screens, chamber design and aerodynamic characteristics can make optical density inside the chamber lower than outside for a period. Schifiliti and colleagues describe this with a detector time constant, analogous to a response lag.<ref name="Schifiliti-4-24" />
== Calibration does not define every fire response ==


Weak smouldering plumes can fail to reach a ceiling detector at all. Ohlemiller notes that very weak smouldering sources may not produce a plume reaching the ceiling, while the fuel bed can filter the aerosol. Ceiling placement alone therefore does not guarantee early detection of every smouldering fire.<ref name="Ohlemiller-2-203" />
[[Optical density]] describes how smoke attenuates a light beam over a specified distance, and it is useful for measuring smoke and for modelling projected-beam detectors. A scattering detector, however, measures redirected light rather than the same beam attenuation quantity. Its alarm threshold expressed as optical density therefore depends on the calibration smoke and the detector characteristics.<ref name="SMC_4-22_4-24" />


Transport lag is not the only delay. Smoke must then enter and produce a sufficient signal, after which the alarm algorithm and notification sequence begin. These stages should be separated when evaluating the time to occupant response.<ref name="Schifiliti-4-23" /><ref name="CVM2-30">Ministry of Business, Innovation and Employment (2025), p. 30.</ref>
The SFPE Handbook gives an example of a scattering detector responding at 0.029 m<sup>−1</sup> to smoke from a smouldering grey cotton lamp wick. The same example describes a response at 0.15 m<sup>−1</sup> for kerosene-fire smoke. At those response points, the receiver detects the same scattered-light signal. The darker kerosene smoke scatters light differently from the lighter wick smoke.<ref name="SMC_4-23">Schifiliti, Meacham, and Custer (2002), p. 4-23.</ref>


== Response and activation time ==
These values are examples for the particular comparison, not universal detector sensitivities, and they show why a calibration value cannot be transferred indiscriminately between smoke types. Wavelength and scattering angle also affect the response. Appropriate input data need to represent both the smoke and the sensing mechanism being modelled.<ref name="SMC_4-23_4-24">Schifiliti, Meacham, and Custer (2002), pp. 4-23–4-24.</ref>


[[Detector activation time]] includes smoke production, transport, entry and signal processing. It varies with fire growth, detector location, particle properties and the response algorithm. A single generic activation time cannot be assigned to a detector model across different fires.<ref name="Schifiliti-4-23" /><ref name="NUREG-1805-11-6" />
[[File:fse-smoke-detector-v3.svg|thumb|upright=1.5|alt=Grey cotton-wick smoke 0.029 and kerosene smoke 0.15 per metre as response examples.|Optical-density response depends on smoke type. Based on Schifiliti, Meacham, and Custer (2002), p. 4-23.]]


Smoke-detector models are less certain than heat-detector models. Early smoke production and transport are highly variable, and manufacturers often do not publish their response algorithms. Estimation methods should therefore be used mainly to compare changes in spacing or location while other variables are held constant.<ref name="Schifiliti-4-23" />
The handbook also discusses limits imposed by manufacturer algorithms: a product may process sensor readings over time rather than operate at one simple instantaneous threshold. Those algorithms can affect nuisance rejection and genuine-fire response. Without suitable product information, a concentration calculation may describe the exposure but not the complete activation decision.<ref name="SMC_4-22_4-24" />


Product tests can provide useful response ranges. Standards may require activation at particular levels or times under specified fuels and buildup rates, but those conditions may not match the intended fire. Test limits should be used as evidence of that product's tested performance rather than as universal values.<ref name="Schifiliti-4-24" /><ref name="NUREG-1805-11-6" />
== A beam calculation with a worked example ==


C/VM2 provides different response modelling constants for smoke, projected-beam and air-sampling detectors in its design scenarios. Those parameters belong to that 2025 New Zealand method and should not be reused as universal detector constants. Actual system design still requires scenario and product evidence.<ref name="CVM2-26" />
For uniform smoke along a beam, optical density per unit length is calculated from the fraction of light transmitted. The calculation uses the base-ten logarithm of the intensity ratio and divides by beam length. Greater attenuation gives a larger optical density. C/VM2 provides this relationship when describing projected-beam detector response.<ref name="CVM_28">Ministry of Business, Innovation and Employment (2025), p. 28.</ref>


== Unwanted fire alarms ==
<math display="block">D_u=-\frac{1}{L}\log_{10}\left(\frac{I}{I_0}\right),\qquad \frac{I}{I_0}=\frac{100-O}{100}</math>


[[Unwanted fire alarms]] can result from non-fire signatures, test activations, pranks or unsuitable placement. Complex algorithms are intended to reduce nuisance alarms and improve signature matching, but they are often proprietary. Exact prediction of false-alarm frequency is therefore difficult without product evidence.<ref name="Schifiliti-4-23" /><ref name="Proulx-3-351" />
{| class="wikitable"
! Symbol !! Description !! Unit
|-
| <math>D_u</math> || Optical density per unit beam length || m<sup>−1</sup>
|-
| <math>L</math> || Beam path length || m
|-
| <math>I</math> || Intensity at the receiver with smoke present || Same intensity unit as <math>I_0</math>
|-
| <math>I_0</math> || Intensity at the receiver without smoke || Same intensity unit as <math>I</math>
|-
| <math>O</math> || Total obscuration expressed as a percentage || %
|}


Frequent false alarms can make occupants less responsive. Proulx describes reduced credibility of the alarm signal, with occupants delaying or failing to look for further information. Correct detector selection and management should address nuisance causes without making genuine detection less effective.<ref name="Proulx-3-351" />
The worked example in New Zealand's C/VM2 (2025) uses a 10 m beam and an alarm setting of 50% total obscuration. Half of the original light intensity remains at the receiver. Substituting the source values gives approximately 0.030 m<sup>−1</sup>. This is the uniform optical density corresponding to the stated path and setting.<ref name="CVM_28" />


Smoke-detector testing and sensitivity settings require particular care. NRC guidance for incipient systems says reduced sensitivity should be evaluated to ensure that early detection is not compromised. Testing, commissioning and maintenance should preserve that function rather than treating fewer alarms as automatically better.<ref name="NUREG-6850-S1-13-5" />
<math display="block">D_u=-\frac{1}{10}\log_{10}\left(\frac{100-50}{100}\right)=0.0301\ \mathrm{m}^{-1}\approx0.030\ \mathrm{m}^{-1}</math>


Unwanted activation is not always a device fault. Smoke-like conditions, contamination and inappropriate siting can create valid signals under the wrong interpretation. The assessment should distinguish those conditions from a genuine fire and from a detector malfunction.<ref name="Schifiliti-4-23" /><ref name="Proulx-3-351" />
The calculation does not predict when the smoke will reach that value; a fire and smoke-transport analysis is still needed to estimate activation time. Nor is the result a universal point-detector threshold. It describes attenuation along the specified beam, using the detector's total-obscuration setting.<ref name="CVM_27_28" /><ref name="SMC_4-22_4-23" />


== Placement and system design ==
Smoke may occupy only part of the path, as when a plume crosses the beam. C/VM2 describes dividing a non-uniform path into segments and summing each segment's optical-density contribution. Schifiliti and colleagues describe the same distinction between uniform and segmented representations. Assuming a uniform layer when the actual exposure is local can misrepresent the beam measurement.<ref name="CVM_28" /><ref name="SMC_4-23" />


A [[Fire alarm system]] integrates detectors with control, alarm and notification. Detector choice should follow the required response time and the fire scenario, and the complete chain must be tested. An early detector signal alone does not guarantee an effective evacuation response.<ref name="Schifiliti-4-1">Schifiliti, Meacham, and Custer (2002), pp. 4-1–4-2.</ref><ref name="IFEG-1.8-7">Australian Building Codes Board et al. (2005), p. 1.8-7.</ref>
== Prescribed inputs in the New Zealand method ==


Spot detectors require smoke to reach and enter the sensing chamber, while projected beams can observe a path through a larger volume. Aspirating systems can use high sensitivity where appropriate, but all types have transport and maintenance requirements. Selection should be based on evidence for the intended environment.<ref name="Schifiliti-4-23" /><ref name="CVM2-26" />
C/VM2, second edition (2025), specifies detector inputs for its verification calculations, and its smoke-detector representation includes ionisation, photoelectric spot and air sampling arrangements. The specified optical density at alarm is 0.097 m<sup>−1</sup>. The table also gives a radial distance of 7.0 m and a position at least 25 mm below the ceiling.<ref name="CVM_27" />


Ceiling construction and height affect spacing. Smooth ceilings favour distribution of heated air and smoke, while obstructions and high ceilings change transport and may require different placement or detector types. The fire's location relative to the detector also matters.<ref name="NUREG-1805-12-3">U.S. Nuclear Regulatory Commission (2005), p. 12-3.</ref><ref name="Schifiliti-4-23" />
The document requires these analysis values regardless of the actual detector make or model, so they represent the method's prescribed simulation, rather than measured properties of every installed device. Projected-beam detectors are treated separately using beam length and total obscuration. The distinction prevents the spot-detector input from being applied as though it described every sensing arrangement.<ref name="CVM_27_28" />


Multi-sensor detection and redundancy can improve resilience, but they can also share dependencies. Control, power and communication failures can affect several devices at once. Reliability analysis should include those common paths and the system's failure indication.<ref name="IFEG-1.2-24">Australian Building Codes Board et al. (2005), p. 1.2-24.</ref>
C/VM2 permits the activation exposure to be obtained using a model with a ceiling-jet correlation or computational fluid dynamics. The latter approach calculates the gas flow and smoke or soot concentration directly. In either case, the response criterion and its application remain part of the method. A more detailed flow calculation does not by itself establish a different permitted detector threshold.<ref name="CVM_27" />


[[Aspirating smoke detection]] draws air through a sampling system for analysis and can support very high sensitivity. Sampling transport, filter condition and system design affect the response, so product-specific testing is required. [[Beam smoke detector]] arrangements instead measure attenuation across a light path, with total optical density depending on path length and smoke distribution. These are different measurement problems from spot-chamber detection.<ref name="CVM2-26" /><ref name="Schifiliti-4-23" />
Prescribed regulatory inputs and experimental detector data answer different questions. The former provide consistency within a particular assessment route, while the latter describe response under the tested smoke and exposure conditions. A calculation identifies which type of evidence it uses so that its result can be interpreted within the correct scope.<ref name="CVM_27_28" /><ref name="SMC_4-22_4-24" />


For maintenance, the complete alarm chain should be checked. A sensing element can operate while a panel, sounder or communication path fails, and a blocked sampling or optical path can alter the response without an obvious electronic fault. Inspection should include those paths as well as the detector itself.<ref name="Schifiliti-4-24" /><ref name="CVM2-13">Ministry of Business, Innovation and Employment (2025), p. 13.</ref>
== Signal processing and unwanted alarms ==


Documentation should identify the detector model, principle, threshold, location and test evidence. Response algorithms and thresholds should not be invented when manufacturers do not publish them. Where exact activation is critical, product-specific tests and scenario analysis are needed.<ref name="Schifiliti-4-23" /><ref name="NUREG-1805-11-6">U.S. Nuclear Regulatory Commission (2005), p. 11-6.</ref>
[[Unwanted fire alarms]] influence how a detector's signal is processed. The SFPE Handbook describes algorithms intended to distinguish fire signatures while reducing false and nuisance alarms; their details vary between products. These processing functions can change response relative to a calculation based solely on one smoke concentration.<ref name="SMC_4-22">Schifiliti, Meacham, and Custer (2002), p. 4-22.</ref>


For final acceptance, the detector should be evaluated by the response it enables. Early indication is useful only if it produces intelligible notification and enough time for action. That makes the detector one part of the alarm and evacuation system rather than a guarantee of protection.<ref name="Schifiliti-4-1" /><ref name="Proulx-3-350" />
A [[Multi-sensor detector]] combines sensing information, so the response of the combined device needs its own evidence. Knowing the calibration of one sensing element does not describe the complete processing decision, and the same principle applies when an alarm system requires confirmation from another detector. IFEG describes coincident systems that wait for two similar or dissimilar detectors before recognising an alarm.<ref name="SMC_4-22_4-24" /><ref name="IFEG_2.7-2">Australian Building Codes Board et al. (2005), p. 2.7-2.</ref>


Testing should preserve sensitivity and correct operation. Product-specific acceptance tests, sensitivity checks and maintenance should follow the manufacturer and applicable standard. Changes to sensitivity should be evaluated for their effect on early detection rather than accepted solely as a way to reduce nuisance alarms.<ref name="NUREG-6850-S1-13-5" />
A specialised nuclear-industry example illustrates the consequence of changing sensitivity. The 2010 supplement to NUREG/CR-6850 requires reduced sensitivity in very early warning systems to be assessed for loss of early detection benefit. It distinguishes early alerts from later fire alarms and controls their settings. Those provisions concern the defined United States nuclear application, not a universal classification of building alarms.<ref name="N10_13-6">U.S. Nuclear Regulatory Commission and Electric Power Research Institute (2010), p. 13-6.</ref>


Smoke-entry paths and sensing chambers require maintenance. Contamination, blocked screens and altered airflow can change the response, and an optical path can be obstructed without an obvious device fault. Inspection should include those physical paths as well as electronics.<ref name="Schifiliti-4-24" /><ref name="CVM2-13">Ministry of Business, Innovation and Employment (2025), p. 13.</ref>
The nuclear report also limits the cabinet applications in which sampling can provide the credited warning. Smoke needs a path from the developing fault to the sampling location, but a tightly sealed cabinet can prevent the transport on which the arrangement depends. This application-specific limitation reinforces the distinction between a sensitive instrument and an effective detection path through the protected equipment.<ref name="N10_13-5">U.S. Nuclear Regulatory Commission and Electric Power Research Institute (2010), p. 13-5.</ref>


Documentation should identify the detector model, principle, threshold, location and test evidence. Response algorithms and thresholds should not be invented when manufacturers do not publish them. Where exact activation is critical, product-specific tests and scenario analysis are needed.<ref name="Schifiliti-4-23" /><ref name="NUREG-1805-11-6" />
The full response sequence includes the sensor, processing and the intended protective action. A lower number of nuisance signals alone does not demonstrate that the required fire is detected soon enough. Equally, a sensitive sensor can provide limited benefit if transport or subsequent action is delayed. The performance objective remains the basis for assessing the complete arrangement.<ref name="SMC_4-2_4-3__4-22">Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3, 4-22.</ref><ref name="N10_13-6" />


Maintenance should preserve the complete alarm chain. A detector can be operational while the panel, sounder or communication path fails, so testing should not stop at the sensing element. The system must produce intelligible notification and an appropriate response.<ref name="Schifiliti-4-1" /><ref name="Proulx-3-350">Proulx (2002), pp. 3-350–3-351.</ref>
== Evidence needed for a response prediction ==


== Limits and common misunderstandings ==
Schifiliti and colleagues identify a gap between common smoke measurements and the information needed to predict individual detector response. Optical density is widely available, but it does not fully characterise ionisation or scattering behaviour. Manufacturer response algorithms and fuel-specific thresholds may also be unavailable. These limitations need to remain visible in the interpretation of a calculated activation time.<ref name="SMC_4-22_4-24" />


A smoke detector does not detect every fire early. Weak smouldering sources may not deliver smoke to the detector, and some particles produce a weak response. Detector principle and placement must match the expected fire mode.<ref name="Ohlemiller-2-203" /><ref name="Schifiliti-4-23" />
The handbook discusses experiments with detectors present as another source of response evidence. Product performance tests can provide limiting conditions even when detailed response traces are unpublished. The test fuel, smoke production, airflow and geometry still define the scope of that evidence. A result from one controlled exposure does not establish performance for every fire scenario.<ref name="SMC_4-23_4-24" />


Higher sensitivity is not automatically better. It can increase unwanted alarms and undermine credibility, while reducing sensitivity can delay genuine detection. Settings should be justified using product tests and the required response time.<ref name="NUREG-6850-S1-13-5" /><ref name="Proulx-3-351" />
Mulholland gives an illustrative calculation linking smoke production, detector response and deteriorating visibility. He explicitly notes that the example omits travel time to the detector and entry delay. He also identifies missing information on particle distributions and detector response to smoke agglomerates. The example therefore demonstrates a method and its data needs rather than establishing a complete real-fire warning time.<ref name="Mu_2-267_2-268">Mulholland (2002), pp. 2-267–2-268.</ref>


Optical density is not a universal alarm threshold. It varies with wavelength, particle properties and smoke colour, and detector response algorithms differ. Manufacturer-specific data and test conditions are required for meaningful use.<ref name="Schifiliti-4-24" /><ref name="Mulholland-2-267" />
A sound comparison holds the fire and other relevant conditions consistent while examining changes in detector location or spacing. Schifiliti and colleagues caution against comparing uncertain smoke-response estimates directly with other predicted safety times without understanding their accuracy. The model, its inputs and its intended use must be compatible. Reported precision in seconds cannot remove uncertainty in the underlying smoke and sensor behaviour.<ref name="SMC_4-23" />
 
Finally, a detector signal is not an evacuation instruction. The alarm system must provide intelligible notification, and occupants must understand what to do. Detection is only the first stage of that response.<ref name="Proulx-3-350" /><ref name="Schifiliti-4-1" />
 
For final acceptance, detector choice should be tied to the expected fire mode and measurement problem. Spot chambers, beams and aspirating systems each have different transport and response characteristics, and each needs compatible evidence. Selecting by sensitivity alone would ignore those differences and could produce unreliable activation timing.<ref name="Schifiliti-4-23" /><ref name="CVM2-26" />


== See also ==
== See also ==


* [[Aspirating smoke detection]]
* [[Smouldering]]
* [[Detector activation time]]
* [[Heat detector]]
* [[Optical density]]
* [[Smoke stratification]]
* [[Smouldering-to-flaming transition]]


== Notes ==
== Notes ==
Line 117: Line 126:
== References ==
== References ==


* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines'' (2005 ed.). Australian Building Codes Board.
* Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). ''International fire engineering guidelines''. Australian Building Codes Board.
* Ministry of Business, Innovation and Employment. (2025). ''C protection from fire: Verification method C/VM2'' (2nd ed.). New Zealand Government.
* Iqbal, N., & Salley, M. H. (2004). ''Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program'' (NUREG-1805). U.S. Nuclear Regulatory Commission.
* Mulholland, G. W. (2002). Smoke production and properties. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Ministry of Business, Innovation and Employment. (2025). ''C protection from fire: Verification method C/VM2'' (2nd ed.).
* Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Mulholland, G. W. (2002). Smoke production and properties. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 2-258–2-268). National Fire Protection Association.
* Proulx, G. (2002). Movement of people: The evacuation timing. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed., pp. 4-1–4-43). National Fire Protection Association.
* Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), ''SFPE handbook of fire protection engineering'' (3rd ed.). National Fire Protection Association.
* U.S. Nuclear Regulatory Commission, & Electric Power Research Institute. (2010). ''Fire probabilistic risk assessment methods enhancements'' (NUREG/CR-6850, Supplement 1).
* U.S. Nuclear Regulatory Commission. (2005). ''Fire dynamics tools: Quantitative fire hazard analysis methods for the U.S. nuclear regulatory commission fire protection inspection program'' (NUREG-1805). Author.
* U.S. Nuclear Regulatory Commission. (2010). ''Fire PRA methods enhancements'' (NUREG/CR-6850, Supplement 1). Author.
* Van Rossum, E. (2027). ''Introduction to Fire Safety Engineering''. Fire Safety Academy.


[[Category:Detection & Alarm]]
[[Category:Detection & Alarm]]

Latest revision as of 19:42, 2 November 2026

A smoke detector is a device that responds to particles produced by combustion and supplies a signal when its alarm criterion is reached. Common sensing principles use changes in ion current, scattered light or transmitted light. The response depends on the particles reaching the sensing region and interacting with the particular sensor.[1][2]

Smoke varies with the fuel, burning mode and conditions during transport. Two smokes with the same measured optical density can produce different responses in a scattering or ionisation detector. A calibration threshold therefore needs to be interpreted with the smoke and test conditions used to establish it.[2]

Detection time also includes transport and, for enclosed sensing chambers, smoke-entry delay. Air sampling and projected-beam arrangements introduce different measurement paths. Engineering assessment combines those physical processes with the detector's response criterion and any later alarm processing, while recognising the limits of available input data.[3][4]

How smoke becomes a detection signal

Smoke contains particles whose properties depend on the fuel and the way it burns. Detectors can respond through changes in electrical current or changes in light reaching a receiver. The SFPE Handbook distinguishes the response of the sensor from the transport of smoke to it. Both processes affect the time at which an alarm signal becomes available.[1][2]

An ionisation detector uses an ion current within its sensing chamber. Smoke particles intercept ions and reduce the current until the alarm criterion is reached, while a light-scattering detector instead measures light redirected by particles within the chamber. The two mechanisms respond differently to particle size, concentration and other smoke characteristics.[1]

A Beam smoke detector measures attenuation of a light beam across a space. Attenuation is the reduction of transmitted light caused by the smoke along its path. Aspirating smoke detection uses a sampling arrangement that draws air towards a sensing chamber. These arrangements introduce different measurement geometries and, for sampling systems, additional transport through the sampling network.[5][6][4]

A detector supplies an input to the Fire alarm system, which processes the signal and produces its configured outputs. Detection and occupant notification are separate functions. The presence of smoke at the sensing location does not establish that the complete warning sequence is already finished. Processing and the intended human response remain part of the system assessment.[7]

Ionisation chamber, scattering chamber, projected beam and aspirating sampler.
Smoke-detection principles measure different particle responses. Based on Mulholland (2002), pp. 2-266–2-267 and Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-24 and Iqbal and Salley (2004), p. F-52.

Particle size, fuel and burning mode

Smoke is not a uniform substance with one universal detector response. Schifiliti and colleagues identify particle size distribution, concentration, composition, colour and refractive index as relevant characteristics. Refractive index describes how the material interacts with light. Fuel composition, flaming or smouldering combustion and the supply of combustion air affect the particles produced.[8]

Mulholland compares ionisation and scattering responses for particular detectors. In that comparison, ionisation response is stronger for particles smaller than about 0.3 µm. Light-scattering response is stronger for particles larger than about 0.3 µm. This is an approximate comparison from the reported detector response functions, not a sharp dividing line for every device.[1]

The chapter associates relatively small particles with examples of flaming paper and wood fires. Larger droplets from smouldering combustion can favour the response of scattering detectors. These relationships explain why the same nominal optical obscuration does not imply the same electrical signal in every sensor. The burning mode and the detector principle must be considered together.[1]

Particle properties also change during transport. Particles can settle or combine, changing the number and size distribution that reaches the detector. The SFPE detection chapter therefore distinguishes smoke characteristics at the fire from those at the sensing location. Using generation data alone can omit changes relevant to the eventual response.[9]

Ionisation sensitivity stronger below 0.3 µm and light-scattering sensitivity stronger above it.
Detector sensitivity varies with particle size. Based on Mulholland (2002), pp. 2-266–2-267.

Getting smoke into the sensing region

A rising plume can carry smoke towards the ceiling, where a Ceiling jet distributes it away from the fire. Ceiling height, geometry and intervening barriers influence this route. Natural and mechanical air currents also affect the movement of smoke, particularly during early, low-energy fires. The transport time cannot be assumed identical for different detector locations.[10]

Smoke reaching the outside of a spot detector must still enter its sensing chamber. Screens, chamber geometry and the flow around the housing can resist entry. The SFPE Handbook calls this entry resistance. During an increasing external smoke concentration, the concentration within the chamber can lag behind the surrounding smoke.[11]

This lag is conceptually separate from the detector's response threshold. A device may be sensitive to a particular smoke once it is inside the chamber but still receive that smoke slowly. The local gas velocity and the device's aerodynamic characteristics therefore matter. Treating external smoke concentration as instantaneously identical to chamber concentration can understate the response time.[12]

A weak fire beneath a high ceiling may also produce smoke that loses buoyancy before entering the assumed ceiling flow. The handbook discusses this possibility when examining low-energy fires and stratification. Stratification means that smoke can collect at a level determined by the surrounding temperature conditions. A detector near the ceiling may therefore receive a different exposure from the one assumed in a simple spreading-layer calculation.[13]

Air sampling introduces a different transport arrangement. C/VM2 identifies airflow, sampling-tube length and alarm threshold as factors in the response of very high sensitivity sampling systems. The method treats these systems as requiring specialised design. A sensitive measuring chamber alone does not determine the time needed for a sample to arrive and initiate the intended output.[14]

Calibration does not define every fire response

Optical density describes how smoke attenuates a light beam over a specified distance, and it is useful for measuring smoke and for modelling projected-beam detectors. A scattering detector, however, measures redirected light rather than the same beam attenuation quantity. Its alarm threshold expressed as optical density therefore depends on the calibration smoke and the detector characteristics.[3]

The SFPE Handbook gives an example of a scattering detector responding at 0.029 m−1 to smoke from a smouldering grey cotton lamp wick. The same example describes a response at 0.15 m−1 for kerosene-fire smoke. At those response points, the receiver detects the same scattered-light signal. The darker kerosene smoke scatters light differently from the lighter wick smoke.[15]

These values are examples for the particular comparison, not universal detector sensitivities, and they show why a calibration value cannot be transferred indiscriminately between smoke types. Wavelength and scattering angle also affect the response. Appropriate input data need to represent both the smoke and the sensing mechanism being modelled.[16]

Grey cotton-wick smoke 0.029 and kerosene smoke 0.15 per metre as response examples.
Optical-density response depends on smoke type. Based on Schifiliti, Meacham, and Custer (2002), p. 4-23.

The handbook also discusses limits imposed by manufacturer algorithms: a product may process sensor readings over time rather than operate at one simple instantaneous threshold. Those algorithms can affect nuisance rejection and genuine-fire response. Without suitable product information, a concentration calculation may describe the exposure but not the complete activation decision.[3]

A beam calculation with a worked example

For uniform smoke along a beam, optical density per unit length is calculated from the fraction of light transmitted. The calculation uses the base-ten logarithm of the intensity ratio and divides by beam length. Greater attenuation gives a larger optical density. C/VM2 provides this relationship when describing projected-beam detector response.[17]

Du=−1Llog10(II0),II0=100−O100

Symbol Description Unit
Du Optical density per unit beam length m−1
L Beam path length m
I Intensity at the receiver with smoke present Same intensity unit as I0
I0 Intensity at the receiver without smoke Same intensity unit as I
O Total obscuration expressed as a percentage %

The worked example in New Zealand's C/VM2 (2025) uses a 10 m beam and an alarm setting of 50% total obscuration. Half of the original light intensity remains at the receiver. Substituting the source values gives approximately 0.030 m−1. This is the uniform optical density corresponding to the stated path and setting.[17]

Du=−110log10(100−50100)=0.0301 m−1≈0.030 m−1

The calculation does not predict when the smoke will reach that value; a fire and smoke-transport analysis is still needed to estimate activation time. Nor is the result a universal point-detector threshold. It describes attenuation along the specified beam, using the detector's total-obscuration setting.[4][5]

Smoke may occupy only part of the path, as when a plume crosses the beam. C/VM2 describes dividing a non-uniform path into segments and summing each segment's optical-density contribution. Schifiliti and colleagues describe the same distinction between uniform and segmented representations. Assuming a uniform layer when the actual exposure is local can misrepresent the beam measurement.[17][15]

Prescribed inputs in the New Zealand method

C/VM2, second edition (2025), specifies detector inputs for its verification calculations, and its smoke-detector representation includes ionisation, photoelectric spot and air sampling arrangements. The specified optical density at alarm is 0.097 m−1. The table also gives a radial distance of 7.0 m and a position at least 25 mm below the ceiling.[14]

The document requires these analysis values regardless of the actual detector make or model, so they represent the method's prescribed simulation, rather than measured properties of every installed device. Projected-beam detectors are treated separately using beam length and total obscuration. The distinction prevents the spot-detector input from being applied as though it described every sensing arrangement.[4]

C/VM2 permits the activation exposure to be obtained using a model with a ceiling-jet correlation or computational fluid dynamics. The latter approach calculates the gas flow and smoke or soot concentration directly. In either case, the response criterion and its application remain part of the method. A more detailed flow calculation does not by itself establish a different permitted detector threshold.[14]

Prescribed regulatory inputs and experimental detector data answer different questions. The former provide consistency within a particular assessment route, while the latter describe response under the tested smoke and exposure conditions. A calculation identifies which type of evidence it uses so that its result can be interpreted within the correct scope.[4][3]

Signal processing and unwanted alarms

Unwanted fire alarms influence how a detector's signal is processed. The SFPE Handbook describes algorithms intended to distinguish fire signatures while reducing false and nuisance alarms; their details vary between products. These processing functions can change response relative to a calculation based solely on one smoke concentration.[18]

A Multi-sensor detector combines sensing information, so the response of the combined device needs its own evidence. Knowing the calibration of one sensing element does not describe the complete processing decision, and the same principle applies when an alarm system requires confirmation from another detector. IFEG describes coincident systems that wait for two similar or dissimilar detectors before recognising an alarm.[3][19]

A specialised nuclear-industry example illustrates the consequence of changing sensitivity. The 2010 supplement to NUREG/CR-6850 requires reduced sensitivity in very early warning systems to be assessed for loss of early detection benefit. It distinguishes early alerts from later fire alarms and controls their settings. Those provisions concern the defined United States nuclear application, not a universal classification of building alarms.[20]

The nuclear report also limits the cabinet applications in which sampling can provide the credited warning. Smoke needs a path from the developing fault to the sampling location, but a tightly sealed cabinet can prevent the transport on which the arrangement depends. This application-specific limitation reinforces the distinction between a sensitive instrument and an effective detection path through the protected equipment.[21]

The full response sequence includes the sensor, processing and the intended protective action. A lower number of nuisance signals alone does not demonstrate that the required fire is detected soon enough. Equally, a sensitive sensor can provide limited benefit if transport or subsequent action is delayed. The performance objective remains the basis for assessing the complete arrangement.[22][20]

Evidence needed for a response prediction

Schifiliti and colleagues identify a gap between common smoke measurements and the information needed to predict individual detector response. Optical density is widely available, but it does not fully characterise ionisation or scattering behaviour. Manufacturer response algorithms and fuel-specific thresholds may also be unavailable. These limitations need to remain visible in the interpretation of a calculated activation time.[3]

The handbook discusses experiments with detectors present as another source of response evidence. Product performance tests can provide limiting conditions even when detailed response traces are unpublished. The test fuel, smoke production, airflow and geometry still define the scope of that evidence. A result from one controlled exposure does not establish performance for every fire scenario.[16]

Mulholland gives an illustrative calculation linking smoke production, detector response and deteriorating visibility. He explicitly notes that the example omits travel time to the detector and entry delay. He also identifies missing information on particle distributions and detector response to smoke agglomerates. The example therefore demonstrates a method and its data needs rather than establishing a complete real-fire warning time.[23]

A sound comparison holds the fire and other relevant conditions consistent while examining changes in detector location or spacing. Schifiliti and colleagues caution against comparing uncertain smoke-response estimates directly with other predicted safety times without understanding their accuracy. The model, its inputs and its intended use must be compatible. Reported precision in seconds cannot remove uncertainty in the underlying smoke and sensor behaviour.[15]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Mulholland (2002), pp. 2-266–2-267.
  2. ↑ 2.0 2.1 2.2 Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-24.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Schifiliti, Meacham, and Custer (2002), pp. 4-22–4-24.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 Ministry of Business, Innovation and Employment (2025), pp. 27–28.
  5. ↑ 5.0 5.1 Schifiliti, Meacham, and Custer (2002), pp. 4-22–4-23.
  6. ↑ Iqbal and Salley (2004), p. F-52.
  7. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3.
  8. ↑ Schifiliti, Meacham, and Custer (2002), p. 4-21.
  9. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-21, 4-24.
  10. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-21–4-22.
  11. ↑ Schifiliti, Meacham, and Custer (2002), p. 4-24.
  12. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-22, 4-24.
  13. ↑ Schifiliti, Meacham, and Custer (2002), p. 4-28.
  14. ↑ 14.0 14.1 14.2 Ministry of Business, Innovation and Employment (2025), p. 27.
  15. ↑ 15.0 15.1 15.2 Schifiliti, Meacham, and Custer (2002), p. 4-23.
  16. ↑ 16.0 16.1 Schifiliti, Meacham, and Custer (2002), pp. 4-23–4-24.
  17. ↑ 17.0 17.1 17.2 Ministry of Business, Innovation and Employment (2025), p. 28.
  18. ↑ Schifiliti, Meacham, and Custer (2002), p. 4-22.
  19. ↑ Australian Building Codes Board et al. (2005), p. 2.7-2.
  20. ↑ 20.0 20.1 U.S. Nuclear Regulatory Commission and Electric Power Research Institute (2010), p. 13-6.
  21. ↑ U.S. Nuclear Regulatory Commission and Electric Power Research Institute (2010), p. 13-5.
  22. ↑ Schifiliti, Meacham, and Custer (2002), pp. 4-2–4-3, 4-22.
  23. ↑ Mulholland (2002), pp. 2-267–2-268.

References

  • Australian Building Codes Board, National Research Council of Canada, International Code Council, & Department of Building and Housing New Zealand. (2005). International fire engineering guidelines. Australian Building Codes Board.
  • Iqbal, N., & Salley, M. H. (2004). Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program (NUREG-1805). U.S. Nuclear Regulatory Commission.
  • Ministry of Business, Innovation and Employment. (2025). C protection from fire: Verification method C/VM2 (2nd ed.).
  • Mulholland, G. W. (2002). Smoke production and properties. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-258–2-268). National Fire Protection Association.
  • Schifiliti, R. P., Meacham, B. J., & Custer, R. L. P. (2002). Design of detection systems. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-1–4-43). National Fire Protection Association.
  • U.S. Nuclear Regulatory Commission, & Electric Power Research Institute. (2010). Fire probabilistic risk assessment methods enhancements (NUREG/CR-6850, Supplement 1).