<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Woodworking_facility</id>
	<title>Woodworking facility - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Woodworking_facility"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;action=history"/>
	<updated>2026-11-21T22:24:08Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=5551&amp;oldid=prev</id>
		<title>Emma: Correct alt text/caption of SVG figure to match the drawing</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=5551&amp;oldid=prev"/>
		<updated>2026-11-09T08:09:40Z</updated>

		<summary type="html">&lt;p&gt;Correct alt text/caption of SVG figure to match the drawing&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 09:09, 9 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l25&quot;&gt;Line 25:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 25:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Four conditions must exist together. The dust must be fine enough, generally below an equivalent diameter of 420 μm, and it must be suspended in air. Its concentration must reach the minimum explosible concentration (MEC), and a competent igniter must deliver enough power per unit volume.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot;&amp;gt;Cholin (2008d), p. 9-13.&amp;lt;/ref&amp;gt; Coarser particles still burn, but too slowly to build dangerous pressure. Finer dust gives a higher maximum pressure &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; and dust constant &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; and ignites more easily, although below about 20 μm the hazard generally stops increasing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt; Elongated, fibrous wood particles behave as if they were smaller than a sieve analysis suggests, which can lead to a dangerous underestimation of the hazard.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Four conditions must exist together. The dust must be fine enough, generally below an equivalent diameter of 420 μm, and it must be suspended in air. Its concentration must reach the minimum explosible concentration (MEC), and a competent igniter must deliver enough power per unit volume.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot;&amp;gt;Cholin (2008d), p. 9-13.&amp;lt;/ref&amp;gt; Coarser particles still burn, but too slowly to build dangerous pressure. Finer dust gives a higher maximum pressure &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; and dust constant &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; and ignites more easily, although below about 20 μm the hazard generally stops increasing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt; Elongated, fibrous wood particles behave as if they were smaller than a sieve analysis suggests, which can lead to a dangerous underestimation of the hazard.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-woodworking-facility-v1.svg|thumb|upright=1.5|alt=&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Four nested &lt;/del&gt;regions&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;: &lt;/del&gt;combustible wood particulate&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, deflagrable &lt;/del&gt;fraction below 420 micrometres, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;suspension &lt;/del&gt;above the MEC, and a competent &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;ignition source&lt;/del&gt;|Four conditions must coincide for a wood dust deflagration.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-woodworking-facility-v1.svg|thumb|upright=1.5|alt=&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Nested &lt;/ins&gt;regions &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;inside &lt;/ins&gt;combustible wood particulate&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;: fine &lt;/ins&gt;fraction below 420 micrometres, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;suspended in air, at or &lt;/ins&gt;above the MEC, and a competent &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;igniter in the innermost region where all four overlap&lt;/ins&gt;|Four conditions must coincide for a wood dust deflagration.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For most wood particulates the MEC is approximately 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot;&amp;gt;Cholin (2008d), p. 9-21.&amp;lt;/ref&amp;gt; Zalosh (2002) adds that the worst-case concentration of many dusts is about 500 g/m³, five to ten times the MEC.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot;&amp;gt;Zalosh (2002), p. 3-407.&amp;lt;/ref&amp;gt; Handbook test data for wood and related dusts are summarised below.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot;&amp;gt;Schwab (2008c), p. 6-145.&amp;lt;/ref&amp;gt; Measured values depend on particle size and on test conditions such as igniter energy and turbulence.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For most wood particulates the MEC is approximately 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot;&amp;gt;Cholin (2008d), p. 9-21.&amp;lt;/ref&amp;gt; Zalosh (2002) adds that the worst-case concentration of many dusts is about 500 g/m³, five to ten times the MEC.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot;&amp;gt;Zalosh (2002), p. 3-407.&amp;lt;/ref&amp;gt; Handbook test data for wood and related dusts are summarised below.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot;&amp;gt;Schwab (2008c), p. 6-145.&amp;lt;/ref&amp;gt; Measured values depend on particle size and on test conditions such as igniter energy and turbulence.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-5376:rev-5551:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Emma</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=5376&amp;oldid=prev</id>
		<title>Emma: Add SVG figures fse-woodworking-facility-v1.svg, fse-woodworking-facility-v2.svg, fse-woodworking-facility-v3.svg, fse-woodworking-facility-v4.svg (list-2 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=5376&amp;oldid=prev"/>
		<updated>2026-11-09T07:46:20Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-woodworking-facility-v1.svg, fse-woodworking-facility-v2.svg, fse-woodworking-facility-v3.svg, fse-woodworking-facility-v4.svg (list-2 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:46, 9 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l25&quot;&gt;Line 25:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 25:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Four conditions must exist together. The dust must be fine enough, generally below an equivalent diameter of 420 μm, and it must be suspended in air. Its concentration must reach the minimum explosible concentration (MEC), and a competent igniter must deliver enough power per unit volume.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot;&amp;gt;Cholin (2008d), p. 9-13.&amp;lt;/ref&amp;gt; Coarser particles still burn, but too slowly to build dangerous pressure. Finer dust gives a higher maximum pressure &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; and dust constant &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; and ignites more easily, although below about 20 μm the hazard generally stops increasing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt; Elongated, fibrous wood particles behave as if they were smaller than a sieve analysis suggests, which can lead to a dangerous underestimation of the hazard.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Four conditions must exist together. The dust must be fine enough, generally below an equivalent diameter of 420 μm, and it must be suspended in air. Its concentration must reach the minimum explosible concentration (MEC), and a competent igniter must deliver enough power per unit volume.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot;&amp;gt;Cholin (2008d), p. 9-13.&amp;lt;/ref&amp;gt; Coarser particles still burn, but too slowly to build dangerous pressure. Finer dust gives a higher maximum pressure &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; and dust constant &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; and ignites more easily, although below about 20 μm the hazard generally stops increasing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt; Elongated, fibrous wood particles behave as if they were smaller than a sieve analysis suggests, which can lead to a dangerous underestimation of the hazard.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-woodworking-facility-v1.svg|thumb|upright=1.5|alt=Four nested regions: combustible wood particulate, deflagrable fraction below 420 micrometres, suspension above the MEC, and a competent ignition source|Four conditions must coincide for a wood dust deflagration.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For most wood particulates the MEC is approximately 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot;&amp;gt;Cholin (2008d), p. 9-21.&amp;lt;/ref&amp;gt; Zalosh (2002) adds that the worst-case concentration of many dusts is about 500 g/m³, five to ten times the MEC.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot;&amp;gt;Zalosh (2002), p. 3-407.&amp;lt;/ref&amp;gt; Handbook test data for wood and related dusts are summarised below.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot;&amp;gt;Schwab (2008c), p. 6-145.&amp;lt;/ref&amp;gt; Measured values depend on particle size and on test conditions such as igniter energy and turbulence.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For most wood particulates the MEC is approximately 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot;&amp;gt;Cholin (2008d), p. 9-21.&amp;lt;/ref&amp;gt; Zalosh (2002) adds that the worst-case concentration of many dusts is about 500 g/m³, five to ten times the MEC.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot;&amp;gt;Zalosh (2002), p. 3-407.&amp;lt;/ref&amp;gt; Handbook test data for wood and related dusts are summarised below.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot;&amp;gt;Schwab (2008c), p. 6-145.&amp;lt;/ref&amp;gt; Measured values depend on particle size and on test conditions such as igniter energy and turbulence.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l42&quot;&gt;Line 42:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 43:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Most explosions in woodworking plants are a chain of deflagrations rather than a single event. A primary deflagration starts inside a mill, hog, sander, dust collector, bin or chip silo.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot;&amp;gt;Cholin (2008d), p. 9-19.&amp;lt;/ref&amp;gt; Its pressure wave travels through steel and concrete at about 4560 m/s, against about 330 m/s in air, so floors, walls and roof flex and throw settled dust into the air.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt; Flame escaping from the failed equipment ignites these clouds. The secondary deflagration often bursts the wall-to-roof joint first and leaves residual fires with a damaged sprinkler system.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-20&amp;quot;&amp;gt;Cholin (2008d), p. 9-20.&amp;lt;/ref&amp;gt; Zalosh (2002) notes that a secondary explosion in an occupied building can cause many casualties.&amp;lt;ref name=&amp;quot;Zalosh-3-409&amp;quot;&amp;gt;Zalosh (2002), pp. 3-409–3-410.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Most explosions in woodworking plants are a chain of deflagrations rather than a single event. A primary deflagration starts inside a mill, hog, sander, dust collector, bin or chip silo.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot;&amp;gt;Cholin (2008d), p. 9-19.&amp;lt;/ref&amp;gt; Its pressure wave travels through steel and concrete at about 4560 m/s, against about 330 m/s in air, so floors, walls and roof flex and throw settled dust into the air.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt; Flame escaping from the failed equipment ignites these clouds. The secondary deflagration often bursts the wall-to-roof joint first and leaves residual fires with a damaged sprinkler system.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-20&amp;quot;&amp;gt;Cholin (2008d), p. 9-20.&amp;lt;/ref&amp;gt; Zalosh (2002) notes that a secondary explosion in an occupied building can cause many casualties.&amp;lt;ref name=&amp;quot;Zalosh-3-409&amp;quot;&amp;gt;Zalosh (2002), pp. 3-409–3-410.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-woodworking-facility-v2.svg|thumb|upright=1.5|alt=Four panels of a building cross-section showing primary deflagration in equipment, dust lifted by vibration, secondary deflagration and roof-wall failure|Escalation from a primary deflagration in process equipment to a secondary deflagration in the building.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Estimating a secondary deflagration ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Estimating a secondary deflagration ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l75&quot;&gt;Line 75:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 77:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;At the worst-case concentration the reference mass is 500 × 4 = 2000 g/m², so &amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;b&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; = 180/2000 = 0.09. The pressure rise is 9.3 × 0.09 ≈ 0.84 bar, or about 84 kPa, and a 0.5 mm layer still gives about 0.42 bar. In an example of a butane release, Zalosh (2002) describes 0.456 bar g as greater than the strength of rooms in industrial facilities.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot; /&amp;gt; A layer of about 1 mm can therefore produce a pressure well above that level.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;At the worst-case concentration the reference mass is 500 × 4 = 2000 g/m², so &amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;b&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; = 180/2000 = 0.09. The pressure rise is 9.3 × 0.09 ≈ 0.84 bar, or about 84 kPa, and a 0.5 mm layer still gives about 0.42 bar. In an example of a butane release, Zalosh (2002) describes 0.456 bar g as greater than the strength of rooms in industrial facilities.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot; /&amp;gt; A layer of about 1 mm can therefore produce a pressure well above that level.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-woodworking-facility-v4.svg|thumb|upright=1.5|alt=Line chart of estimated pressure rise against wood dust layer thickness from 0 to 2 mm, rising linearly to about 1.7 bar, with a reference line at 0.456 bar|Estimated pressure rise from a dispersed sawdust layer in a 4 m high room.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Dust collection systems ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Dust collection systems ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l84&quot;&gt;Line 84:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 87:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An ember can be as small as a BB pellet, about 4.5 mm (0.177 in.) across, and dozens of sparks per hour have been detected in some plants. Perhaps one in a million survives the journey to the collector.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt; The usual answer is a [[Spark detection and extinguishing system]]: detectors on the duct, a water spray unit downstream and a control panel. Sparks often travel at up to 30 m/s (6000 ft/min), so the distance between detector and spray unit must be calculated from the air velocity and response times.&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot;&amp;gt;Cholin (2008d), p. 9-23.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An ember can be as small as a BB pellet, about 4.5 mm (0.177 in.) across, and dozens of sparks per hour have been detected in some plants. Perhaps one in a million survives the journey to the collector.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt; The usual answer is a [[Spark detection and extinguishing system]]: detectors on the duct, a water spray unit downstream and a control panel. Sparks often travel at up to 30 m/s (6000 ft/min), so the distance between detector and spray unit must be calculated from the air velocity and response times.&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot;&amp;gt;Cholin (2008d), p. 9-23.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-woodworking-facility-v3.svg|thumb|upright=1.5|alt=Schematic of a woodworking dust collection system with spark detectors, water spray unit, baghouse with deflagration vent, fan and abort gate on the return duct|Typical spark detection and extinguishing arrangement for a woodworking dust collector.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Each discharge lasts 3 to 15 seconds and uses less than about 25 L (6.6 gal) of water, while the system keeps running.&amp;lt;ref name=&amp;quot;CholinD-9-24&amp;quot;&amp;gt;Cholin (2008d), p. 9-24.&amp;lt;/ref&amp;gt; The handbook describes spark detection at the collector, which trips a return-air abort gate, as the minimum code-compliant arrangement and not the accepted best practice. In most plants, additional spark detection and extinguishing equipment is installed to limit downtime and preserve the investment in the dust collection system.&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Each discharge lasts 3 to 15 seconds and uses less than about 25 L (6.6 gal) of water, while the system keeps running.&amp;lt;ref name=&amp;quot;CholinD-9-24&amp;quot;&amp;gt;Cholin (2008d), p. 9-24.&amp;lt;/ref&amp;gt; The handbook describes spark detection at the collector, which trips a return-air abort gate, as the minimum code-compliant arrangement and not the accepted best practice. In most plants, additional spark detection and extinguishing equipment is installed to limit downtime and preserve the investment in the dust collection system.&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4894:rev-5376:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Emma</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4894&amp;oldid=prev</id>
		<title>Linda: Remove bibliographic source lines from image captions and descriptions</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4894&amp;oldid=prev"/>
		<updated>2026-11-08T07:27:47Z</updated>

		<summary type="html">&lt;p&gt;Remove bibliographic source lines from image captions and descriptions&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:27, 8 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l94&quot;&gt;Line 94:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 94:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Housekeeping]] controls the fuel for secondary deflagrations. No collection system is 100 percent effective, and the handbook calls routine vacuum cleaning of the entire facility of paramount importance.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Blowing dust down with high-pressure air while equipment is energised only lifts the finest dust to the highest and least accessible surfaces. The handbook therefore permits it only during shutdowns with all equipment de-energised.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In the United States, the handbook advises that hot work follow NFPA 51B, with the area cleaned of all wood waste and a fire watch kept for at least 2 hours afterwards.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Housekeeping]] controls the fuel for secondary deflagrations. No collection system is 100 percent effective, and the handbook calls routine vacuum cleaning of the entire facility of paramount importance.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Blowing dust down with high-pressure air while equipment is energised only lifts the finest dust to the highest and least accessible surfaces. The handbook therefore permits it only during shutdowns with all equipment de-energised.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In the United States, the handbook advises that hot work follow NFPA 51B, with the area cleaned of all wood waste and a fire watch kept for at least 2 hours afterwards.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-woodworking-facility-v5.jpg|thumb|upright=1.5|alt=Fine wood dust lying on top of ducts and beams near the ceiling of a woodworking shop|Fine wood dust settled on upward-facing surfaces near the ceiling is the fuel for secondary deflagrations and must be removed by routine vacuum cleaning&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cholin (2008d), pp. 9-14 and 9-17&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-woodworking-facility-v5.jpg|thumb|upright=1.5|alt=Fine wood dust lying on top of ducts and beams near the ceiling of a woodworking shop|Fine wood dust settled on upward-facing surfaces near the ceiling is the fuel for secondary deflagrations and must be removed by routine vacuum cleaning.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers are considered the most appropriate general area protection, although full coverage can be difficult in some older buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In 1994 to 1998, 54 percent of reported US structure fires in wood, paper and related product plants occurred in sprinklered buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; The handbook states that in the United States NFPA 13, in the edition it describes, requires Ordinary Hazard Group 3 design for woodworking machinery spaces, with higher densities for finishing and upholstery rooms. It recommends yard mains and hydrants supplying at least 3.78 m³/min (1000 gpm), enough for four 64 mm (2½ in.) hose streams.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Heat transfer fluid, or thermal oil, heats many panel presses at temperatures above its flashpoint, and a leak can form a spray or a spreading pool fire.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt; According to the handbook, sprinklers are required where such fluid serves hot presses.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers are considered the most appropriate general area protection, although full coverage can be difficult in some older buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In 1994 to 1998, 54 percent of reported US structure fires in wood, paper and related product plants occurred in sprinklered buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; The handbook states that in the United States NFPA 13, in the edition it describes, requires Ordinary Hazard Group 3 design for woodworking machinery spaces, with higher densities for finishing and upholstery rooms. It recommends yard mains and hydrants supplying at least 3.78 m³/min (1000 gpm), enough for four 64 mm (2½ in.) hose streams.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Heat transfer fluid, or thermal oil, heats many panel presses at temperatures above its flashpoint, and a leak can form a spray or a spreading pool fire.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt; According to the handbook, sprinklers are required where such fluid serves hot presses.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4761:rev-4894:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Linda</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4761&amp;oldid=prev</id>
		<title>Linda: Add watermarked Fire Safety Academy illustration at the location specified in the visual plan</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4761&amp;oldid=prev"/>
		<updated>2026-11-08T07:18:53Z</updated>

		<summary type="html">&lt;p&gt;Add watermarked Fire Safety Academy illustration at the location specified in the visual plan&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:18, 8 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l93&quot;&gt;Line 93:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 93:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Housekeeping]] controls the fuel for secondary deflagrations. No collection system is 100 percent effective, and the handbook calls routine vacuum cleaning of the entire facility of paramount importance.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Blowing dust down with high-pressure air while equipment is energised only lifts the finest dust to the highest and least accessible surfaces. The handbook therefore permits it only during shutdowns with all equipment de-energised.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In the United States, the handbook advises that hot work follow NFPA 51B, with the area cleaned of all wood waste and a fire watch kept for at least 2 hours afterwards.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Housekeeping]] controls the fuel for secondary deflagrations. No collection system is 100 percent effective, and the handbook calls routine vacuum cleaning of the entire facility of paramount importance.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Blowing dust down with high-pressure air while equipment is energised only lifts the finest dust to the highest and least accessible surfaces. The handbook therefore permits it only during shutdowns with all equipment de-energised.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In the United States, the handbook advises that hot work follow NFPA 51B, with the area cleaned of all wood waste and a fire watch kept for at least 2 hours afterwards.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-woodworking-facility-v5.jpg|thumb|upright=1.5|alt=Fine wood dust lying on top of ducts and beams near the ceiling of a woodworking shop|Fine wood dust settled on upward-facing surfaces near the ceiling is the fuel for secondary deflagrations and must be removed by routine vacuum cleaning. Based on Cholin (2008d), pp. 9-14 and 9-17.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers are considered the most appropriate general area protection, although full coverage can be difficult in some older buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In 1994 to 1998, 54 percent of reported US structure fires in wood, paper and related product plants occurred in sprinklered buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; The handbook states that in the United States NFPA 13, in the edition it describes, requires Ordinary Hazard Group 3 design for woodworking machinery spaces, with higher densities for finishing and upholstery rooms. It recommends yard mains and hydrants supplying at least 3.78 m³/min (1000 gpm), enough for four 64 mm (2½ in.) hose streams.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Heat transfer fluid, or thermal oil, heats many panel presses at temperatures above its flashpoint, and a leak can form a spray or a spreading pool fire.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt; According to the handbook, sprinklers are required where such fluid serves hot presses.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers are considered the most appropriate general area protection, although full coverage can be difficult in some older buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In 1994 to 1998, 54 percent of reported US structure fires in wood, paper and related product plants occurred in sprinklered buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; The handbook states that in the United States NFPA 13, in the edition it describes, requires Ordinary Hazard Group 3 design for woodworking machinery spaces, with higher densities for finishing and upholstery rooms. It recommends yard mains and hydrants supplying at least 3.78 m³/min (1000 gpm), enough for four 64 mm (2½ in.) hose streams.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Heat transfer fluid, or thermal oil, heats many panel presses at temperatures above its flashpoint, and a leak can form a spray or a spreading pool fire.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt; According to the handbook, sprinklers are required where such fluid serves hot presses.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4003:rev-4761:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Linda</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4003&amp;oldid=prev</id>
		<title>Jan: NFPA wiki: fact-check corrections (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=4003&amp;oldid=prev"/>
		<updated>2026-11-07T22:04:12Z</updated>

		<summary type="html">&lt;p&gt;NFPA wiki: fact-check corrections (written by Claude Opus 5.5)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;amp;diff=4003&amp;amp;oldid=2994&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=2994&amp;oldid=prev</id>
		<title>Jan: New FSE wiki article: Woodworking facility (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Woodworking_facility&amp;diff=2994&amp;oldid=prev"/>
		<updated>2026-11-07T21:05:01Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Woodworking facility (written by Claude Opus 5.5)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;woodworking facility&amp;#039;&amp;#039;&amp;#039; is a plant that manufactures wooden products by sawing, drying, milling, sanding, gluing and finishing wood, from dimension lumber and panels to furniture, millwork and musical instruments.&amp;lt;ref name=&amp;quot;CholinD-9-3&amp;quot;&amp;gt;Cholin (2008d), p. 9-3.&amp;lt;/ref&amp;gt; These plants range from one-person shops to sites with as many as 2000 employees, and in the United States NFPA 664 addresses their fire and explosion hazards.&amp;lt;ref name=&amp;quot;CholinD-9-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot;&amp;gt;Cholin (2008d), p. 9-5.&amp;lt;/ref&amp;gt; Almost every woodworking process reduces wood in size mechanically, so heat, sparks and fine particles arise together. Settled particles can smoulder for days, and suspended particles can burn as a deflagration.&amp;lt;ref name=&amp;quot;CholinD-9-4&amp;quot;&amp;gt;Cholin (2008d), p. 9-4.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt; The &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039; (2008) treats fire and explosion as separate hazards, each with its own protection, such as an outdoor dust collector, spark detection in ducts, collector venting or suppression, housekeeping and sprinklers.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot;&amp;gt;Cholin (2008d), p. 9-15.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot;&amp;gt;Cholin (2008d), p. 9-17.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot;&amp;gt;Cholin (2008d), p. 9-18.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot;&amp;gt;Cholin (2008d), p. 9-22.&amp;lt;/ref&amp;gt; Fine dust that settles high in the building fuels the secondary deflagrations that cause most injuries and fatalities.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Facilities and processes ==&lt;br /&gt;
The handbook divides the forest products industry into four groups. Primary products, such as structural timbers, dimensioned lumber, shingles and veneers, need only cutting and drying. Secondary products, such as plywood, particle board, oriented strand board (OSB), fibreboard and millwork, need further processing but are not yet sold at retail. Tertiary products, such as houses and furniture, are sold to consumers, while pulp and paper is a largely wet process outside the scope of the chapter.&amp;lt;ref name=&amp;quot;CholinD-9-4&amp;quot; /&amp;gt; Engineered panels are covered in [[Wood-based panel products]].&lt;br /&gt;
&lt;br /&gt;
Dimension cutting takes place in a sawmill, where logs are debarked, cut to length, squared and sawn into green stock.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot;&amp;gt;Cholin (2008d), p. 9-6.&amp;lt;/ref&amp;gt; Green wood usually holds 30 to 50 percent water by weight, and lumber for dimension stock is kiln-dried to 5 to 7 percent.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt; Lumber is dried in hacks, layered stacks of boards about 4.3 m long, 1.8 to 2.4 m wide and 1.2 to 1.8 m high, stacked up to 4.9 m. Once a fire in such a honeycomb stack is under way it is almost impossible to extinguish.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt; Kilns often run at up to 149 °C (300 °F) at 100 percent humidity, and the handbook notes a financial incentive to run them as hot as possible.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-7&amp;quot;&amp;gt;Cholin (2008d), p. 9-7.&amp;lt;/ref&amp;gt; Particles for particle board, medium-density fibreboard (MDF) and OSB are dried in rotary drum driers, most of them direct-fired with flue gas that enters close to or above the ignition temperature of wood.&amp;lt;ref name=&amp;quot;CholinD-9-7&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-8&amp;quot;&amp;gt;Cholin (2008d), p. 9-8.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Later stages shape the dried stock. Milling passes boards through edgers, jointers and planers with hardened cutters at high speed, and cutting produces sawdust, block scraps and resaw kerfs.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot;&amp;gt;Cholin (2008d), p. 9-9.&amp;lt;/ref&amp;gt; Turning on a lathe often combines roughing, shaping and sanding at one machine, which sends a very wide range of particle sizes into the waste system.&amp;lt;ref name=&amp;quot;CholinD-9-10&amp;quot;&amp;gt;Cholin (2008d), p. 9-10.&amp;lt;/ref&amp;gt; Sanding gives every product its final surface, and wide-belt abrasive planers can remove more than 3.2 mm (1/8 in.) in a single pass.&amp;lt;ref name=&amp;quot;CholinD-9-10&amp;quot; /&amp;gt; Finishing lines in large plants may use about 20 spray booths on 1900 to 3700 m² of floor, with curing ovens at about 121 °C (250 °F).&amp;lt;ref name=&amp;quot;CholinD-9-11&amp;quot;&amp;gt;Cholin (2008d), p. 9-11.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Waste is a major part of the process. Almost 25 percent of a tree becomes waste when dimensioned lumber is produced, and a further 25 percent when that stock becomes a finished product.&amp;lt;ref name=&amp;quot;CholinD-9-8&amp;quot; /&amp;gt; Large pieces are reduced in a hog, a high-power mill that turns them into chips, splinters or flakes, and much of the waste is burned as fuel for driers and boilers.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-8&amp;quot; /&amp;gt; Dungan (2008b) classes sawdust and shavings as Class A combustible material with a possible explosion hazard from dust buildup.&amp;lt;ref name=&amp;quot;Dungan-7-8&amp;quot;&amp;gt;Dungan (2008b), p. 7-8.&amp;lt;/ref&amp;gt; Storage of logs, chips and lumber is treated in [[Outdoor storage of forest products]].&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Ignition sources ==&lt;br /&gt;
Mechanical work on wood liberates heat. If that heat accumulates in a small mass of wood, its temperature rises until exothermic pyrolysis begins, usually at approximately 280 °C (536 °F); from that point the wood heats itself and chars.&amp;lt;ref name=&amp;quot;CholinD-9-4&amp;quot; /&amp;gt; Powered cutting and shaping tools reach such temperatures easily. In one case described by Cholin (2008d), a routing operation turned a milling cutter blue, which indicates more than 316 °C (600 °F), and ignited a fire in the dust collection system.&amp;lt;ref name=&amp;quot;CholinD-9-4&amp;quot; /&amp;gt; In milling and cutting, sparks and embers are described as the rule rather than the exception.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The likelihood of sparks depends on both the wood and the process. Species with wide variations in density produce more sparks, because the feed rate of a saw is set for the average density and a hard spot generates excess heat.&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt; Maple, hickory, cherry and white oak are regarded as high-probability species in milling and cutting.&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt; Softwoods produce fewer sparks in sawing, but in sanding their resins load the abrasive grit, and resinous softwoods then generate sparks several orders of magnitude more often than hardwoods.&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Foreign objects add further ignition sources. Logs may contain arrowheads, bullets, nails, sugar-taps and stones, and a saw that strikes one ejects sparks, embers or broken teeth into the sawdust around it.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt; That sawdust dries in air to about 10 percent moisture, at which wood is readily ignitable, while the green stock itself, above 25 percent moisture, is unlikely to ignite.&amp;lt;ref name=&amp;quot;CholinD-9-6&amp;quot; /&amp;gt; Tramp metal that enters ducts can heat up against the steel walls and ignite dust where it comes to rest in a hopper.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Process equipment is not the only cause. In US fire data for 1994 to 1998, only about one quarter of reported fires in woodworking facilities involved processing equipment in ignition, and one third involved no equipment at all.&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt; Cutting and welding, heating equipment and electrical distribution equipment caused a significant share.&amp;lt;ref name=&amp;quot;CholinD-9-5&amp;quot; /&amp;gt; Glue pots, bending irons, portable space heaters, worn switches and frayed cords are all named as sources to control.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-16&amp;quot;&amp;gt;Cholin (2008d), p. 9-16.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Wood waste can also ignite without an outside source. Gray (2002) notes in the &amp;#039;&amp;#039;SFPE Handbook of Fire Protection Engineering&amp;#039;&amp;#039; that solid wood is not subject to spontaneous ignition at normal ambient temperatures, but woodchips and sawdust are.&amp;lt;ref name=&amp;quot;Gray-2-224&amp;quot;&amp;gt;Gray (2002), p. 2-224.&amp;lt;/ref&amp;gt; Experiments reported by Ohlemiller (2002) found that the minimum layer depth for sustained smouldering in still air was typically about 0.01 m for small particles of beech or pine sawdust.&amp;lt;ref name=&amp;quot;Ohlemiller-2-205&amp;quot;&amp;gt;Ohlemiller (2002), p. 2-205.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Dust explosion hazard ==&lt;br /&gt;
Wood dust suspended in air can deflagrate, so woodworking is one of the industries described by Schwab (2008c) as plagued by [[Dust explosion|dust explosions]].&amp;lt;ref name=&amp;quot;Schwab-6-141&amp;quot;&amp;gt;Schwab (2008c), p. 6-141.&amp;lt;/ref&amp;gt; In US usage, a deflagration is a flame front moving through a fuel–air mixture fast enough to raise the pressure but slower than sound. An explosion is the rupture of an enclosure by that pressure, so the deflagration is the process and the explosion the result. European standards use the two terms differently.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot;&amp;gt;Cholin (2008d), p. 9-12.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Four conditions must exist together. The dust must be fine enough, generally below an equivalent diameter of 420 μm, and it must be suspended in air. Its concentration must reach the minimum explosible concentration (MEC), and a competent igniter must deliver enough power per unit volume.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot;&amp;gt;Cholin (2008d), p. 9-13.&amp;lt;/ref&amp;gt; Coarser particles still burn, but too slowly to build dangerous pressure. Finer dust gives a higher maximum pressure &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; and dust constant &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; and ignites more easily, although below about 20 μm the hazard generally stops increasing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt; Elongated, fibrous wood particles behave as if they were smaller than a sieve analysis suggests, which can lead to a dangerous underestimation of the hazard.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For most wood particulates the MEC is approximately 30 to 60 g/m³ (0.03 to 0.06 oz/ft³).&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot;&amp;gt;Cholin (2008d), p. 9-21.&amp;lt;/ref&amp;gt; Zalosh (2002) adds that the worst-case concentration of many dusts is about 500 g/m³, five to ten times the MEC.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot;&amp;gt;Zalosh (2002), p. 3-407.&amp;lt;/ref&amp;gt; Handbook test data for wood and related dusts are summarised below.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot;&amp;gt;Schwab (2008c), p. 6-145.&amp;lt;/ref&amp;gt; Measured values depend on particle size and on test conditions such as igniter energy and turbulence.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
|+ Explosion and ignition data for wood-related dusts&lt;br /&gt;
! Dust !! Particle size (μm) !! MEC (g/m³) !! &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; (bar) !! &amp;#039;&amp;#039;K&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;St&amp;lt;/sub&amp;gt; (bar·m/s) !! Cloud ignition (°C) !! MIE (mJ) !! Layer (glow) ignition (°C) !! Source&lt;br /&gt;
|-&lt;br /&gt;
| Wood dust || 33 || – || – || – || 500 || 100 || 320 || &amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Cellulose || 51 || 60 || 9.3 || 66 || 500 || 250 || 380 || &amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Lignin dust || 18 || 15 || 8.7 || 208 || 470 || – || &amp;gt;450 || &amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Wood flour || – || – || – || – || colspan=&amp;quot;3&amp;quot; | 260 (minimum cloud or layer ignition temperature) || &amp;lt;ref name=&amp;quot;Milatovich-8-166&amp;quot;&amp;gt;Milatovich (2008), p. 8-166.&amp;lt;/ref&amp;gt;&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
Most explosions in woodworking plants are a chain of deflagrations rather than a single event. A primary deflagration starts inside a mill, hog, sander, dust collector, bin or chip silo.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot;&amp;gt;Cholin (2008d), p. 9-19.&amp;lt;/ref&amp;gt; Its pressure wave travels through steel and concrete at about 4560 m/s, against about 330 m/s in air, so floors, walls and roof flex and throw settled dust into the air.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt; Flame escaping from the failed equipment ignites these clouds. The secondary deflagration often bursts the wall-to-roof joint first and leaves residual fires with a damaged sprinkler system.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-20&amp;quot;&amp;gt;Cholin (2008d), p. 9-20.&amp;lt;/ref&amp;gt; Zalosh (2002) notes that a secondary explosion in an occupied building can cause many casualties.&amp;lt;ref name=&amp;quot;Zalosh-3-409&amp;quot;&amp;gt;Zalosh (2002), pp. 3-409–3-410.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Estimating a secondary deflagration ==&lt;br /&gt;
A simple estimate shows why thin dust layers matter. Zalosh (2002) assumes that the fractional pressure rise in an unvented enclosure equals the fraction of the total mass that has burned. The relation also applies when only part of the enclosure is filled with a combustible mixture.&amp;lt;ref name=&amp;quot;Zalosh-3-408&amp;quot;&amp;gt;Zalosh (2002), p. 3-408.&amp;lt;/ref&amp;gt; For a dust layer it is applied per unit floor area: the mass of the layer is compared with the mass that would fill the lower part of the room at the worst-case concentration.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot;&amp;gt;Zalosh (2002), p. 3-410.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;\frac{P - P_0}{P_\mathrm{m} - P_0} = \frac{m_\mathrm{b}}{m_0}, \qquad \frac{m_\mathrm{b}}{A} = \rho_\mathrm{b}\, t, \qquad \frac{m_0}{A} = c_\mathrm{w}\, H&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;P&amp;#039;&amp;#039; − &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; || pressure rise in the enclosure || bar&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;m&amp;lt;/sub&amp;gt; − &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; || closed-vessel deflagration pressure of the dust (gauge) || bar&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;b&amp;lt;/sub&amp;gt; || mass of dust that burns (the dispersed layer) || g&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; || total fuel mass at the worst-case concentration in the enclosure || g&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;A&amp;#039;&amp;#039; || floor area || m²&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;ρ&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;b&amp;lt;/sub&amp;gt; || bulk density of the dust layer || kg/m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;t&amp;#039;&amp;#039; || layer thickness || m&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;c&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;w&amp;lt;/sub&amp;gt; || worst-case dust concentration || g/m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;H&amp;#039;&amp;#039; || height of the room (ceiling height) || m&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The model assumes a closed, unvented enclosure in which the pressure is spatially uniform at any moment.&amp;lt;ref name=&amp;quot;Zalosh-3-407&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh-3-408&amp;quot; /&amp;gt; Zalosh (2002) applies it in this way to a layer of coal dust in a power plant.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot; /&amp;gt; The handbook table lists no &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;max&amp;lt;/sub&amp;gt; for wood dust, so the example uses the 9.3 bar listed for cellulose dust; lignin dust, at 8.7 bar, gives almost the same result.&amp;lt;ref name=&amp;quot;Schwab-6-145&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Worked example.&amp;#039;&amp;#039;&amp;#039; A machine room is 4 m high, the ceiling height used by Zalosh (2002), and carries a 1 mm layer of fine sawdust.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot; /&amp;gt; Its bulk density is taken as 180 kg/m³, the value Ohlemiller (2002) gives for the sawdusts in smouldering experiments.&amp;lt;ref name=&amp;quot;Ohlemiller-2-205&amp;quot; /&amp;gt; The layer then holds 180 g/m². Spread evenly through the 4 m height, it would give 45 g/m³, inside the MEC range of 30 to 60 g/m³ for wood; about 0.7 mm already reaches the lower end.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
At the worst-case concentration the reference mass is 500 × 4 = 2000 g/m², so &amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;b&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;m&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;0&amp;lt;/sub&amp;gt; = 180/2000 = 0.09. The pressure rise is 9.3 × 0.09 ≈ 0.84 bar, or about 84 kPa, and a 0.5 mm layer still gives about 0.42 bar. Zalosh (2002) describes 0.456 bar g as greater than the strength of rooms in industrial facilities.&amp;lt;ref name=&amp;quot;Zalosh-3-410&amp;quot; /&amp;gt; A layer of about 1 mm can therefore produce a pressure well above that level.&lt;br /&gt;
&lt;br /&gt;
== Dust collection systems ==&lt;br /&gt;
A [[Dust collector|dust collection system]] consists of ducts from each machine, a large fan and a collector that separates chips and dust from the conveying air.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt; Single-stage systems use a cyclone or a combined cyclone and bag filter, and two-stage systems place a cyclone before a baghouse. In many installations about 80 percent of the air is returned to the plant to save heating, which raises serious fire concerns.&amp;lt;ref name=&amp;quot;CholinD-9-12&amp;quot; /&amp;gt; Cyclones and baghouses work through a concentration gradient, so part of their interior can always support a deflagration, and bag cleaning raises a dense dust cloud at every cycle.&amp;lt;ref name=&amp;quot;CholinD-9-14&amp;quot;&amp;gt;Cholin (2008d), p. 9-14.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Collection does not remove the hazard. The finest particles pass the filters and settle on upward-facing surfaces in the shop, and the better the collector, the finer and more combustible the returned dust.&amp;lt;ref name=&amp;quot;CholinD-9-14&amp;quot; /&amp;gt; Without any collection, dust simply spreads through the workplace, so the choice is between a hazard concentrated at one point and one distributed throughout the plant.&amp;lt;ref name=&amp;quot;CholinD-9-14&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States, NFPA 664, as described in the 2008 handbook, requires dust collectors of noncombustible construction located outside the structure. If cleaned air is returned to the building, a listed spark detection system must operate an abort gate that diverts flame and burning material outside.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot; /&amp;gt; Only green material, with at least 25 percent moisture, may pass through a fan without fire detection and extinguishing downstream.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot; /&amp;gt; Ducts serving sanders should stay well below the MEC even at the maximum depth of cut and feed rate, which avoids the need for explosion prevention on the ducts.&amp;lt;ref name=&amp;quot;CholinD-9-11&amp;quot; /&amp;gt; Separate ducts for fine sander dust and coarse chips, and longer ducts, lower the chance that a burning particle survives to the collector.&amp;lt;ref name=&amp;quot;CholinD-9-16&amp;quot; /&amp;gt; Dungan (2008b) adds magnetic separators, fans downstream of collectors, and chokes such as rotary air locks.&amp;lt;ref name=&amp;quot;Dungan-7-10&amp;quot;&amp;gt;Dungan (2008b), p. 7-10.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An ember can be as small as a BB pellet, about 4.5 mm (0.177 in.) across, and dozens of sparks per hour have been detected in some plants. Perhaps one in a million survives the journey to the collector.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt; The usual answer is a [[Spark detection and extinguishing system]]: detectors on the duct, a water spray unit downstream and a control panel. Sparks often travel at up to 30 m/s (6000 ft/min), so the distance between detector and spray unit must be calculated from the air velocity and response times.&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot;&amp;gt;Cholin (2008d), p. 9-23.&amp;lt;/ref&amp;gt; Each discharge lasts 3 to 15 seconds and uses less than about 25 L (6.6 gal) of water, while the system keeps running.&amp;lt;ref name=&amp;quot;CholinD-9-24&amp;quot;&amp;gt;Cholin (2008d), p. 9-24.&amp;lt;/ref&amp;gt; The handbook calls this the minimum code-compliant protection, not best practice.&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The collector itself needs deflagration protection, because a spark can start a fire on the filter media that turns into a deflagration at the next cleaning cycle.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt; Cholin (2008d) names three practical means: venting to NFPA 68, a listed dust retention and flame-quenching vent to NFPA 69, and suppression to NFPA 69.&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot; /&amp;gt; Fire protection by sprinklers or deluge is needed as well, because these measures address only the deflagration.&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot; /&amp;gt; Flame fronts move at least ten times faster than conveying air, so the air flow does not stop a deflagration from travelling back into the plant through the ducts.&amp;lt;ref name=&amp;quot;CholinD-9-22&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Fire prevention and protection ==&lt;br /&gt;
Layout is the first measure. Ignition-prone processes should be moved away from heavy fuel loads, and shaping, finishing, assembly and storage areas separated by fire-resistive construction with listed fire doors.&amp;lt;ref name=&amp;quot;CholinD-9-15&amp;quot; /&amp;gt; Furnaces should take combustion air from outside the building, so that dust in the shop air cannot ignite in the burner.&amp;lt;ref name=&amp;quot;CholinD-9-16&amp;quot; /&amp;gt; Sharp cutters and clean abrasive belts produce less heat and less dust, and the handbook recommends a measurable criterion, such as motor current demand, for when to sharpen or replace them.&amp;lt;ref name=&amp;quot;CholinD-9-16&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[Housekeeping]] controls the fuel for secondary deflagrations. No collection system is 100 percent effective, and the handbook calls routine vacuum cleaning of the entire facility of paramount importance.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Blowing dust down with high-pressure air while equipment is energised only lifts the finest dust to the highest and least accessible surfaces. The handbook therefore permits it only during shutdowns with all equipment de-energised.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; Hot work should follow NFPA 51B, with the area cleaned of all wood waste and a fire watch kept for at least 2 hours afterwards.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Automatic sprinklers are considered the most appropriate general area protection, although full coverage can be difficult in some older buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt; In 1994 to 1998, 54 percent of reported US structure fires in wood, paper and related product plants occurred in sprinklered buildings.&amp;lt;ref name=&amp;quot;CholinD-9-17&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; The handbook states that NFPA 13 requires Ordinary Hazard Group 3 design for woodworking machinery spaces, with higher densities for finishing and upholstery rooms. It recommends yard mains and hydrants supplying at least 3.78 m³/min (1000 gpm), enough for four 64 mm (2½ in.) hose streams.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Heat transfer fluid, or thermal oil, heats many panel presses at temperatures above its flashpoint, and a leak can form a spray or a spreading pool fire.&amp;lt;ref name=&amp;quot;CholinD-9-9&amp;quot; /&amp;gt; According to the handbook, sprinklers are required where such fluid serves hot presses.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Portable extinguishers must suit mixed fuels. Water or aqueous film-forming foam units suit wood storage and production areas, and dry chemical units suit finishing areas and electrical equipment.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Gaseous units, including clean agent and carbon dioxide, should not be used, because their discharge stirs up dust that can deflagrate on contact with the flame.&amp;lt;ref name=&amp;quot;CholinD-9-18&amp;quot; /&amp;gt; Spray booths for finishing follow NFPA 33, and curing ovens are continuous Class A ovens under NFPA 86.&amp;lt;ref name=&amp;quot;CholinD-9-19&amp;quot; /&amp;gt; In the US classification summarised by Bouchard (2008), sawing, shaping and sanding areas in woodworking plants are an example of Class III, Division 1 locations, where easily ignitable fibres or flyings are handled. Only certain electric and diesel truck types are recommended there, and petrol and LP-gas trucks are not.&amp;lt;ref name=&amp;quot;Bouchard-8-33&amp;quot;&amp;gt;Bouchard (2008), p. 8-33.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Fire loads and limits of the guidance ==&lt;br /&gt;
The fire load of woodworking occupancies varies widely. The &amp;#039;&amp;#039;International Fire Engineering Guidelines&amp;#039;&amp;#039; (2005) reproduce Swiss survey values from 1967 to 1969, summarised below; storage values are multiplied by the storage height in metres. For industrial occupancies the guidelines suggest a coefficient of variation of 50 to 80 percent, and they note that such data vary between countries and survey methods.&amp;lt;ref name=&amp;quot;IFEG-3.4-2&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 3.4-2.&amp;lt;/ref&amp;gt; The values describe only the fuel for a fire, not the explosion potential of dust. The burning of wood itself is described in [[Timber in fire]].&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
|+ Average variable fire load densities, Swiss surveys 1967–1969&lt;br /&gt;
! Occupancy !! Fabrication (MJ/m²) !! Storage (MJ/m² per m height) !! Source&lt;br /&gt;
|-&lt;br /&gt;
| Sawmill (without wood yard) || 400 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-6&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 3.4-6.&amp;lt;/ref&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Joiners (machine room) || 500 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-5&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 3.4-5.&amp;lt;/ref&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Furniture manufacturing (wood) || 600 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-5&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Joinery || 700 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-5&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Chipboard pressing || 100 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 3.4-4.&amp;lt;/ref&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Chipboard finishing || 800 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-4&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Plywood manufacturing || 800 || 2900 || &amp;lt;ref name=&amp;quot;IFEG-3.4-6&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Veneer manufacturing || 800 || 4200 || &amp;lt;ref name=&amp;quot;IFEG-3.4-7&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 3.4-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Wood drying plant || 800 || – || &amp;lt;ref name=&amp;quot;IFEG-3.4-7&amp;quot; /&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| Parquetry manufacturing || 2000 || 1200 || &amp;lt;ref name=&amp;quot;IFEG-3.4-6&amp;quot; /&amp;gt;&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
A spark detection and extinguishing system is a fire control device that reduces the chance of burning material entering the collector, not explosion protection.&amp;lt;ref name=&amp;quot;CholinD-9-25&amp;quot;&amp;gt;Cholin (2008d), p. 9-25.&amp;lt;/ref&amp;gt; It cannot be used where a duct runs at or above the MEC. A deflagration flame would outrun the spray and can accelerate to a detonation, so such ducts need venting or suppression.&amp;lt;ref name=&amp;quot;CholinD-9-24&amp;quot; /&amp;gt; Decades of operation without a fire do not justify leaving a collector unprotected, since the laws of probability predict a fire in every collector handling wood particulates sooner or later.&amp;lt;ref name=&amp;quot;CholinD-9-21&amp;quot; /&amp;gt; An abort gate protects the building and its occupants but not the collector. Shutting down the air flow can then let a fire in the collector turn into a deflagration.&amp;lt;ref name=&amp;quot;CholinD-9-23&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;CholinD-9-25&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The guidance describes US standards, statistics and practice as summarised in the 2008 handbook, mostly NFPA 664 and related NFPA codes, without naming their editions. Several values, such as the MEC range and the water quantity per spark discharge, are approximate values for typical wood dusts and equipment. The handbook also states that the quenching effect of coarse particles can at present only be quantified by testing.&amp;lt;ref name=&amp;quot;CholinD-9-13&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Industrial dryer]]&lt;br /&gt;
* [[Explosion venting]]&lt;br /&gt;
* [[Explosion suppression system]]&lt;br /&gt;
* [[Heat transfer fluid system]]&lt;br /&gt;
* [[Spray booth]]&lt;br /&gt;
* [[Hazardous area classification]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Bouchard, J. K. (2008). Materials-Handling equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 8-31–8-41). National Fire Protection Association.&lt;br /&gt;
* Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 9-3–9-25). National Fire Protection Association.&lt;br /&gt;
* Dungan, K. W. (2008b). Storage and handling of solid fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 7-3–7-13). National Fire Protection Association.&lt;br /&gt;
* Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 8-127–8-173). National Fire Protection Association.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
* Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-141–6-152). National Fire Protection Association.&lt;br /&gt;
* Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
&lt;br /&gt;
[[Category:Explosions &amp;amp; Industrial Fires]]&lt;/div&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
</feed>