<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Sprinkler_head</id>
	<title>Sprinkler head - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Sprinkler_head"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;action=history"/>
	<updated>2026-11-04T11:30:46Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2904&amp;oldid=prev</id>
		<title>Jan: Remove links to pages that do not exist; retain displayed text (wiki-wide link audit).</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2904&amp;oldid=prev"/>
		<updated>2026-11-02T21:35:22Z</updated>

		<summary type="html">&lt;p&gt;Remove links to pages that do not exist; retain displayed text (wiki-wide link audit).&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 22:35, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l89&quot;&gt;Line 89:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 89:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fast-response products reduce thermal lag, while other designs alter droplet size, distribution or protected area. These features address different parts of performance. Faster activation alone does not establish adequate spray penetration or sufficient water at the burning surface.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fast-response products reduce thermal lag, while other designs alter droplet size, distribution or protected area. These features address different parts of performance. Faster activation alone does not establish adequate spray penetration or sufficient water at the burning surface.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[&lt;/del&gt;ESFR sprinkler&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;]] &lt;/del&gt;is an early-suppression, fast-response sprinkler intended for high-challenge fires. NUREG-1805 describes its combination of rapid response, large droplets and velocity. It is designed for suppression rather than only control, subject to strict design and installation conditions.&amp;lt;ref name=&quot;NUREG-10-3&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An ESFR sprinkler is an early-suppression, fast-response sprinkler intended for high-challenge fires. NUREG-1805 describes its combination of rapid response, large droplets and velocity. It is designed for suppression rather than only control, subject to strict design and installation conditions.&amp;lt;ref name=&quot;NUREG-10-3&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Extended-coverage products can protect a larger listed area than conventional arrangements. This can reduce branch piping, but the wider coverage must remain within the product&amp;#039;s tested conditions. Extended coverage is not permission to increase spacing independently of pressure and obstruction requirements.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Extended-coverage products can protect a larger listed area than conventional arrangements. This can reduce branch piping, but the wider coverage must remain within the product&amp;#039;s tested conditions. Extended coverage is not permission to increase spacing independently of pressure and obstruction requirements.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-2793:rev-2904:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2793&amp;oldid=prev</id>
		<title>Jan: Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2793&amp;oldid=prev"/>
		<updated>2026-11-02T18:22:46Z</updated>

		<summary type="html">&lt;p&gt;Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 19:22, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l160&quot;&gt;Line 160:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 160:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Cooper, L. Y. (2002). Smoke and heat venting. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Cooper, L. Y. (2002). Smoke and heat venting. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, pp. 3-219–3-242&lt;/ins&gt;). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, pp. 4-72–4-87&lt;/ins&gt;). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Ministry of Business, Innovation and Employment. (2025). &amp;#039;&amp;#039;C protection from fire: Verification method C/VM2&amp;#039;&amp;#039; (2nd ed.). New Zealand Government.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Ministry of Business, Innovation and Employment. (2025). &amp;#039;&amp;#039;C protection from fire: Verification method C/VM2&amp;#039;&amp;#039; (2nd ed.). New Zealand Government.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Category:Fire Suppression]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Category:Fire Suppression]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-2660:rev-2793:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2660&amp;oldid=prev</id>
		<title>Jan: Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=2660&amp;oldid=prev"/>
		<updated>2026-11-02T17:40:02Z</updated>

		<summary type="html">&lt;p&gt;Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;amp;diff=2660&amp;amp;oldid=1117&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=1117&amp;oldid=prev</id>
		<title>Sanne: Add diagrams fse-sprinkler-head-v1.svg, fse-sprinkler-head-v2.svg, fse-sprinkler-head-v3.svg (level-1 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=1117&amp;oldid=prev"/>
		<updated>2026-11-02T07:20:31Z</updated>

		<summary type="html">&lt;p&gt;Add diagrams fse-sprinkler-head-v1.svg, fse-sprinkler-head-v2.svg, fse-sprinkler-head-v3.svg (level-1 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:20, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l12&quot;&gt;Line 12:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 12:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A glass-bulb sprinkler uses liquid that expands as it warms. At the predetermined condition the bulb shatters and releases the seal. The liquid type and quantity establish the operating temperature, while the glass arrangement provides resistance to atmospheric corrosion in the cited description.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-4.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A glass-bulb sprinkler uses liquid that expands as it warms. At the predetermined condition the bulb shatters and releases the seal. The liquid type and quantity establish the operating temperature, while the glass arrangement provides resistance to atmospheric corrosion in the cited description.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-4.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-sprinkler-head-v1.svg|thumb|upright=1.5|alt=A glass bulb releases a seal and water passes through the orifice to a deflector.|A sprinkler head combines heat detection and water distribution. Based on U.S. Nuclear Regulatory Commission (2005), pp. 10-3–10-4.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other heat-sensitive forms include bimetallic discs, fusible-alloy pellets and chemical pellets. These arrangements perform the same basic function of retaining and then releasing a closure. Their specific response cannot be inferred without product evidence.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other heat-sensitive forms include bimetallic discs, fusible-alloy pellets and chemical pellets. These arrangements perform the same basic function of retaining and then releasing a closure. Their specific response cannot be inferred without product evidence.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l26&quot;&gt;Line 26:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 27:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The [[Response time index (RTI)]] characterises sprinkler thermal response in the calculation methods described by NUREG-1805. A lower response index represents a faster-responding element under comparable conditions. It does not remove the effects of ceiling-jet velocity, activation temperature, starting temperature or distance from the fire.&amp;lt;ref name=&amp;quot;NUREG-10-9&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-9–10-10.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The [[Response time index (RTI)]] characterises sprinkler thermal response in the calculation methods described by NUREG-1805. A lower response index represents a faster-responding element under comparable conditions. It does not remove the effects of ceiling-jet velocity, activation temperature, starting temperature or distance from the fire.&amp;lt;ref name=&amp;quot;NUREG-10-9&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-9–10-10.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-sprinkler-head-v2.svg|thumb|upright=1.5|alt=A ceiling jet heats a sprinkler while frame conduction removes heat and the element warms gradually.|Sprinkler activation is a heat-transfer process with a time lag. Based on U.S. Nuclear Regulatory Commission (2005), pp. 10-9–10-12.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;New Zealand&amp;#039;s C/VM2, second edition, 2025, lists calculation inputs for extended-coverage, standard-response and quick-response categories. The table uses an activation temperature of 68 °C and different response parameters. Those values belong to that verification method and do not replace product-specific installation data.&amp;lt;ref name=&amp;quot;CVM2-27&amp;quot;&amp;gt;Ministry of Business, Innovation and Employment (2025), p. 27.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;New Zealand&amp;#039;s C/VM2, second edition, 2025, lists calculation inputs for extended-coverage, standard-response and quick-response categories. The table uses an activation temperature of 68 °C and different response parameters. Those values belong to that verification method and do not replace product-specific installation data.&amp;lt;ref name=&amp;quot;CVM2-27&amp;quot;&amp;gt;Ministry of Business, Innovation and Employment (2025), p. 27.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l54&quot;&gt;Line 54:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 56:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Sprinkler skipping]] is delayed activation of a downstream head after water from an earlier head cools its sensing element. Droplets carried by the ceiling jet can reduce heating of the later link or bulb. This can change the sequence and number of heads that operate.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot;&amp;gt;Cooper (2002), p. 3-239.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Sprinkler skipping]] is delayed activation of a downstream head after water from an earlier head cools its sensing element. Droplets carried by the ceiling jet can reduce heating of the later link or bulb. This can change the sequence and number of heads that operate.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot;&amp;gt;Cooper (2002), p. 3-239.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-sprinkler-head-v3.svg|thumb|upright=1.5|alt=Large droplets penetrate a plume while an earlier spray cools a downstream element.|Sprays interact with the plume and nearby sprinkler elements. Based on U.S. Nuclear Regulatory Commission (2005), p. 10-11 and Cooper (2002), p. 3-239.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Skipping is not simply a defective head. It results from interaction among spray, hot-gas flow and the thermal element. Its timing can be uncertain because fire location, plume motion and droplet trajectories vary, even between nominally similar installations.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Skipping is not simply a defective head. It results from interaction among spray, hot-gas flow and the thermal element. Its timing can be uncertain because fire location, plume motion and droplet trajectories vary, even between nominally similar installations.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;/table&gt;</summary>
		<author><name>Sanne</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=700&amp;oldid=prev</id>
		<title>Jan: New FSE wiki article: Sprinkler head (written by Kimi Code CLI)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Sprinkler_head&amp;diff=700&amp;oldid=prev"/>
		<updated>2026-11-02T01:42:49Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Sprinkler head (written by Kimi Code CLI)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;Sprinkler head&amp;#039;&amp;#039;&amp;#039; is the outlet of an automatic sprinkler that normally closes a water-filled or pressurised pipe and opens in response to heat. It combines a heat-sensitive element, a seal and a water-distribution arrangement. In a conventional automatic system, the head acts as both a heat detector and a nozzle.&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot;&amp;gt;Fleming (2002), p. 4-85.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-3–10-4.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Heating releases the element and opens the waterway. Water then strikes a deflector and forms a spray over the protected area. Activation time depends on the hot-gas flow, element temperature, response characteristics and installation, while suppression also depends on droplet motion and the fuel arrangement.&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-11.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Different heads are made for different orientations, response speeds, coverage patterns and fire challenges. A head cannot be selected by temperature rating alone. Its listed application, position relative to the ceiling, obstructions, water pressure and compatibility with the system all influence performance.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-2–10-3.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Components and heat operation ==&lt;br /&gt;
&lt;br /&gt;
The frame connects the head to the piping and supports the operating assembly. A cap or seal retains water until the heat-sensitive arrangement releases it. The deflector then shapes the discharged water into the spray pattern intended for that product.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A fusible-link sprinkler uses a metallic alloy with a predetermined melting condition. Levers and struts can reduce the force carried by the solder, allowing a relatively small heat-sensitive mass. When the link releases, the assembly no longer holds the seal closed.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A glass-bulb sprinkler uses liquid that expands as it warms. At the predetermined condition the bulb shatters and releases the seal. The liquid type and quantity establish the operating temperature, while the glass arrangement provides resistance to atmospheric corrosion in the cited description.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-4.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Other heat-sensitive forms include bimetallic discs, fusible-alloy pellets and chemical pellets. These arrangements perform the same basic function of retaining and then releasing a closure. Their specific response cannot be inferred without product evidence.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Open sprinklers and nozzles used on deluge systems do not contain this individual heat-operated closure. A separate detection arrangement opens a valve and permits discharge through the open outlets. This distinction separates head activation from system-valve activation.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot;&amp;gt;Fleming (2002), p. 4-73.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Heating and activation ==&lt;br /&gt;
&lt;br /&gt;
The element exchanges heat with hot combustion products. NUREG-1805 identifies convection from heated gas, radiation from the fire and conduction through surrounding parts. Heat also conducts from the element into the sprinkler frame, so the response includes losses as well as gains.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A [[Ceiling jet]] forms when the rising fire plume turns and spreads beneath a ceiling. It transports hot gas to heads located away from the plume centreline. Both its temperature and velocity influence convective heating, making location relative to the fire important.&amp;lt;ref name=&amp;quot;NUREG-10-10&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-10.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The sensing element does not instantly adopt the surrounding gas temperature. Its thermal mass and heat-transfer conditions produce a lag. NUREG-1805 treats activation as the time needed for the difference between heat inflow and outflow to raise the element to its operating condition.&amp;lt;ref name=&amp;quot;NUREG-10-4&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The [[Response time index (RTI)]] characterises sprinkler thermal response in the calculation methods described by NUREG-1805. A lower response index represents a faster-responding element under comparable conditions. It does not remove the effects of ceiling-jet velocity, activation temperature, starting temperature or distance from the fire.&amp;lt;ref name=&amp;quot;NUREG-10-9&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-9–10-10.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
New Zealand&amp;#039;s C/VM2, second edition, 2025, lists calculation inputs for extended-coverage, standard-response and quick-response categories. The table uses an activation temperature of 68 °C and different response parameters. Those values belong to that verification method and do not replace product-specific installation data.&amp;lt;ref name=&amp;quot;CVM2-27&amp;quot;&amp;gt;Ministry of Business, Innovation and Employment (2025), p. 27.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Position and spray distribution ==&lt;br /&gt;
&lt;br /&gt;
Upright, pendant and sidewall are three basic installation configurations. Their names describe orientation and arrangement rather than different extinguishing chemicals. Each requires a compatible deflector and listing so that water reaches the intended area.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Distance below the ceiling affects both heating and spray development. NUREG-1805 cautions against placing a head too far below the ceiling on a heat collector, because hot gas can pass above it. A suitable position supports activation and allows the intended spray pattern to develop.&amp;lt;ref name=&amp;quot;NUREG-10-12&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. 10-12.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Conduction into the frame and airflow deflection around the installation can alter response. Fleming notes that some models omit these effects, along with orientation and radiation. Calculated activation is therefore most useful for comparison when its assumptions match the installation.&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The [[Sprinkler design density]] describes water applied over an area in a design method. It is not simply the flow leaving one head divided by an arbitrary room area. Pressure, spacing, spray distribution and the design area determine how the system delivers water to the fuel.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water must reach burning surfaces despite the rising plume. Droplets that are too small can evaporate or be carried upward before reaching the fuel. Larger droplets and sufficient velocity can improve penetration, particularly for rapidly growing, high-energy fires.&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Response categories and special heads ==&lt;br /&gt;
&lt;br /&gt;
Fast-response products reduce thermal lag, while other designs alter droplet size, distribution or protected area. These features address different parts of performance. Faster activation alone does not establish adequate spray penetration or sufficient water at the burning surface.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An [[ESFR sprinkler]] is an early-suppression, fast-response sprinkler intended for high-challenge fires. NUREG-1805 describes its combination of rapid response, large droplets and velocity. It is designed for suppression rather than only control, subject to strict design and installation conditions.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Extended-coverage products can protect a larger listed area than conventional arrangements. This can reduce branch piping, but the wider coverage must remain within the product&amp;#039;s tested conditions. Extended coverage is not permission to increase spacing independently of pressure and obstruction requirements.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In-rack, dry, corrosion-resistant, concealed and recessed heads address particular installation needs. Their physical arrangement responds to storage, temperature, environment or appearance requirements. Each remains part of a specific tested assembly rather than a cosmetic variation of a standard head.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Interactions and delayed operation ==&lt;br /&gt;
&lt;br /&gt;
[[Sprinkler skipping]] is delayed activation of a downstream head after water from an earlier head cools its sensing element. Droplets carried by the ceiling jet can reduce heating of the later link or bulb. This can change the sequence and number of heads that operate.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot;&amp;gt;Cooper (2002), p. 3-239.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Skipping is not simply a defective head. It results from interaction among spray, hot-gas flow and the thermal element. Its timing can be uncertain because fire location, plume motion and droplet trajectories vary, even between nominally similar installations.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Traditional sprinkler criteria account for such effects through empirical development and the number of installed heads. This does not make activation sequence irrelevant in special interactions with smoke vents. Cooper distinguishes the extensive sprinkler array from a smaller number of vents when discussing combined operation.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water discharge can also cool nearby smoke and alter the upper layer. Fleming&amp;#039;s review describes convective heat transfer to droplets and, for small droplets, evaporation. These effects can assist fire control while also changing conditions for other heat-operated devices.&amp;lt;ref name=&amp;quot;Fleming-4-86&amp;quot;&amp;gt;Fleming (2002), p. 4-86.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Installation and reliability ==&lt;br /&gt;
&lt;br /&gt;
A head must remain physically and thermally connected to the conditions assumed in its design. Storage, ceiling services and other obstructions can intercept the spray or change hot-gas movement. Commodity height and arrangement can also change the fire challenge after installation.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Paint, corrosion and mechanical damage can prevent normal operation or alter spray distribution. A painted bulb or link should not be treated as merely an appearance issue. NUREG-1805 includes corroded or painted heads among possible causes of sprinkler failure.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An operational head still requires a functioning [[Sprinkler system]]. Closed valves, inadequate supplies, obstructed piping and pump failures can prevent useful discharge after the seal opens. Component reliability therefore cannot be separated from the supporting network.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Different system arrangements create different discharge delays. A wet system has water at the head, whereas a dry system must exhaust gas and fill the piping. Preaction and deluge arrangements also depend on separate detection and valve functions.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Calculation and application limits ==&lt;br /&gt;
&lt;br /&gt;
Activation correlations in NUREG-1805 assume an unobstructed, smooth, flat, horizontal and unconfined ceiling. The fire is away from walls and corners, and the cited steady-fire method does not include a developing smoke layer below the ceiling jet. Actual rooms can depart from all these conditions.&amp;lt;ref name=&amp;quot;NUREG-10-12&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The simplified calculation considers convective heating and treats the element as having a uniform internal temperature. It does not explicitly include direct flame radiation. Results should not be presented as exact activation predictions where those omitted processes matter.&amp;lt;ref name=&amp;quot;NUREG-10-12&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Suppression models have additional fuel limitations. Fleming describes a wood-crib-based method that does not represent every fuel&amp;#039;s resistance to suppression or individual sprinkler distributions. A heat-response calculation consequently cannot be used as a complete extinction calculation.&amp;lt;ref name=&amp;quot;Fleming-4-87&amp;quot;&amp;gt;Fleming (2002), pp. 4-86–4-87.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Product listings and full-scale test evidence provide the application context for special heads. Pressure, spacing, ceiling, storage and obstruction details belong to that evidence. Substituting a head with the same nominal temperature but different spray or response characteristics can change the design.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Temperature rating and response speed answer different questions. The rating concerns the condition at which the operating element releases, while response concerns how quickly heat transfer brings it to that condition. Two heads with the same nominal temperature can therefore activate at different times in the same hot-gas flow.&amp;lt;ref name=&amp;quot;NUREG-10-9&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
C/VM2&amp;#039;s 2025 table illustrates this distinction with standard-response and quick-response model inputs. It assigns different response indices and conduction factors to those categories while retaining the same nominal activation temperature. These parameters must be used with the method&amp;#039;s prescribed geometry and radial distances.&amp;lt;ref name=&amp;quot;CVM2-27&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fleming gives a calculation example with response indices of 221 and 55 in SI units for standard- and quick-response sprinklers. Under the stated fire and installation assumptions, calculated activation was 200 and 172 seconds respectively. These are results of a specific comparison, not typical values for every installation.&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A head&amp;#039;s spray cannot be inferred solely from its orifice. Fleming relates droplet size to orifice and pressure in geometrically similar sprinklers, but droplet trajectories also depend on gas motion. The spray reaching fuel reflects the interaction of water momentum and the rising plume.&amp;lt;ref name=&amp;quot;Fleming-4-86&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Droplet surface area affects heat absorption from hot gases. Smaller droplets offer more total surface for a given water flow, while larger droplets can better resist plume deflection. Head design consequently balances gas cooling and delivery to the fuel rather than maximising one isolated property.&amp;lt;ref name=&amp;quot;Fleming-4-86&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-11&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The protected area also influences the activation sequence. A remote head experiences different ceiling-jet conditions from one above the fire, and earlier sprays can cool it. This makes the number and location of operating heads a coupled fire-and-water problem.&amp;lt;ref name=&amp;quot;Cooper-3-239&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Heat collectors installed far below a ceiling illustrate an installation error rather than a faster-response accessory. NUREG-1805 warns that rising heat can pass above such arrangements. Placement must maintain contact with the hot ceiling flow without sacrificing the intended spray development.&amp;lt;ref name=&amp;quot;NUREG-10-12&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Sidewall and other directional patterns require attention to the room surfaces that shape distribution. A deflector designed for one orientation cannot simply be turned to another orientation while retaining its tested pattern. Product orientation and room geometry therefore remain linked.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Dry and concealed constructions introduce additional physical parts around the basic release mechanism. Their response and spray must be assessed as the complete listed assembly. The visible cover or barrel should not be treated as independent of activation and water distribution.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For inspection, the relevant question is whether the complete installed head remains in its tested condition. Damage, coatings, loading, obstruction or a changed orientation can affect the release element or deflector. Supply pressure and system condition then determine whether a correctly opened head delivers useful water.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A sprinkler head differs from a standalone heat detector because it also controls water distribution. Detection criteria alone cannot describe droplet size, velocity or protected area. Conversely, an adequate spray pattern does not demonstrate timely heat response in the intended ceiling jet.&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The activation model and the suppression model should consequently be evaluated as separate stages. The first estimates when the closure releases under stated thermal conditions. The second addresses what the resulting water spray does to a particular fuel and enclosure.&amp;lt;ref name=&amp;quot;NUREG-10-12&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-87&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Records should preserve both stages through the product identity, temperature and response category, orientation, hydraulic conditions and installation geometry. This provides a traceable link between the tested assembly and the head installed above the protected fuel. Any substitution should preserve the relevant thermal and hydraulic characteristics rather than only the head&amp;#039;s external appearance.&amp;lt;ref name=&amp;quot;NUREG-10-3&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The distinction between detection and water delivery also guides fault finding. A head that fails to open presents a different problem from one that opens without sufficient pressure or with an obstructed deflector. Inspection and testing should identify which stage has departed from its intended condition, because the remedies and effects on protection differ.&amp;lt;ref name=&amp;quot;NUREG-10-2&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
&lt;br /&gt;
* [[Dry pipe sprinkler system]]&lt;br /&gt;
* [[Response time index (RTI)]]&lt;br /&gt;
* [[Wet pipe sprinkler system]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
&lt;br /&gt;
* Cooper, L. Y. (2002). Smoke and heat venting. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Ministry of Business, Innovation and Employment. (2025). &amp;#039;&amp;#039;C protection from fire: Verification method C/VM2&amp;#039;&amp;#039; (2nd ed.). New Zealand Government.&lt;br /&gt;
* U.S. Nuclear Regulatory Commission. (2005). &amp;#039;&amp;#039;Fire dynamics tools: Quantitative fire hazard analysis methods for the U.S. nuclear regulatory commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). Author.&lt;br /&gt;
&lt;br /&gt;
[[Category:Fire Suppression]]&lt;/div&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
</feed>