<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Salvage</id>
	<title>Salvage - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Salvage"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Salvage&amp;action=history"/>
	<updated>2026-11-21T21:46:43Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=8961&amp;oldid=prev</id>
		<title>Linda: Add SVG figures fse-salvage-v1.svg, fse-salvage-v2.svg, fse-salvage-v3.svg, fse-salvage-v4.svg (list-8 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=8961&amp;oldid=prev"/>
		<updated>2026-11-14T17:27:15Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-salvage-v1.svg, fse-salvage-v2.svg, fse-salvage-v3.svg, fse-salvage-v4.svg (list-8 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 18:27, 14 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l18&quot;&gt;Line 18:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 18:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Insurance interests then took up the task. By about 1850, the major US cities had paid fire departments with steam engines, and insurers in nineteen of these cities formed salvage corps whose job was to reduce water damage at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot;&amp;gt;Denlinger (2008), p. 12-54.&amp;lt;/ref&amp;gt; Rising operating costs and improved fire-fighting procedures later made the corps obsolete, and they were disbanded. By 2008, public fire departments carried out salvage operations at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Insurance interests then took up the task. By about 1850, the major US cities had paid fire departments with steam engines, and insurers in nineteen of these cities formed salvage corps whose job was to reduce water damage at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot;&amp;gt;Denlinger (2008), p. 12-54.&amp;lt;/ref&amp;gt; Rising operating costs and improved fire-fighting procedures later made the corps obsolete, and they were disbanded. By 2008, public fire departments carried out salvage operations at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-salvage-v4.svg|thumb|upright=1.5|alt=Timeline of salvage in the United States from Boston mutual fire societies in 1718 to public fire departments|Who carried out salvage at US fires: mutual fire societies, insurance salvage corps and public fire departments.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Sources of damage ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Sources of damage ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l25&quot;&gt;Line 25:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 26:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As an illustration of that comparison, take the largest number of sprinklers in that statement, four, each at the upper flow of 25 gpm. Their total discharge is &amp;lt;math&amp;gt;Q_\mathrm{s} = n\,q_\mathrm{s} = 4 \times 25 = 100&amp;lt;/math&amp;gt; gpm (about 380 L/min). A single hose stream at its lowest flow of 150 gpm delivers 1.5 times as much. In addition, hose streams are used later in a fire, must be aimed at the general area until the smoke clears, and need more water for extinguishment.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; They can also sweep materials from shelves into a disorganised mass on a flooded floor. Wet materials left in place under the gentler action of a [[Sprinkler system]] have much better prospects of salvage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As an illustration of that comparison, take the largest number of sprinklers in that statement, four, each at the upper flow of 25 gpm. Their total discharge is &amp;lt;math&amp;gt;Q_\mathrm{s} = n\,q_\mathrm{s} = 4 \times 25 = 100&amp;lt;/math&amp;gt; gpm (about 380 L/min). A single hose stream at its lowest flow of 150 gpm delivers 1.5 times as much. In addition, hose streams are used later in a fire, must be aimed at the general area until the smoke clears, and need more water for extinguishment.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; They can also sweep materials from shelves into a disorganised mass on a flooded floor. Wet materials left in place under the gentler action of a [[Sprinkler system]] have much better prospects of salvage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-salvage-v1.svg|thumb|upright=1.5|alt=Bar chart comparing water flow of one sprinkler, four sprinklers and one fire department hose stream|Water discharge of sprinklers and of one hose stream (US data, 2008). Most sprinklered fires are controlled by fewer than five sprinklers.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Statistics point the same way. In 1994 to 1998 US structure fires in libraries and museums reported to local fire departments, sprinklers reduced the average dollar loss per fire by 72 percent, and in places of worship by 32 percent. This is roughly consistent with the general finding that sprinklers reduce the average loss by one-half to two-thirds.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; For many years, however, managers of cultural collections opposed sprinklers because they feared water damage even more than fire damage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Statistics point the same way. In 1994 to 1998 US structure fires in libraries and museums reported to local fire departments, sprinklers reduced the average dollar loss per fire by 72 percent, and in places of worship by 32 percent. This is roughly consistent with the general finding that sprinklers reduce the average loss by one-half to two-thirds.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; For many years, however, managers of cultural collections opposed sprinklers because they feared water damage even more than fire damage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l40&quot;&gt;Line 40:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 42:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;During the fire, endangered collections are removed if staff are not put at risk, and tarpaulins or plastic sheeting protect nearby materials from water. After the fire, damaged articles are wrapped and frozen, and restoration follows specialist advice.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot; /&amp;gt; Freeze/vacuum drying removes water and smoke odours very effectively, but it cannot undo physical damage from hose streams, trampling or mishandling.&amp;lt;ref name=&amp;quot;McDaniel-20-194-195&amp;quot;&amp;gt;McDaniel (2008), pp. 20-194–20-195.&amp;lt;/ref&amp;gt; Museums and places of worship, with fewer but more valuable items, concentrate on moving endangered collections to a safe place quickly and carefully.&amp;lt;ref name=&amp;quot;McDaniel-20-194&amp;quot;&amp;gt;McDaniel (2008), p. 20-194.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;During the fire, endangered collections are removed if staff are not put at risk, and tarpaulins or plastic sheeting protect nearby materials from water. After the fire, damaged articles are wrapped and frozen, and restoration follows specialist advice.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot; /&amp;gt; Freeze/vacuum drying removes water and smoke odours very effectively, but it cannot undo physical damage from hose streams, trampling or mishandling.&amp;lt;ref name=&amp;quot;McDaniel-20-194-195&amp;quot;&amp;gt;McDaniel (2008), pp. 20-194–20-195.&amp;lt;/ref&amp;gt; Museums and places of worship, with fewer but more valuable items, concentrate on moving endangered collections to a safe place quickly and carefully.&amp;lt;ref name=&amp;quot;McDaniel-20-194&amp;quot;&amp;gt;McDaniel (2008), p. 20-194.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-salvage-v2.svg|thumb|upright=1.5|alt=Three-column diagram of damage limitation actions before, during and after a fire in a library or museum|Damage limitation for library and museum collections before, during and after a fire.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Smoke and corrosion damage to equipment ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Smoke and corrosion damage to equipment ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l80&quot;&gt;Line 80:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 83:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As a worked example with these values, a tenfold rise in the concentration of corrosive products raises the corrosion rate by a factor of &amp;lt;math&amp;gt;10^{1/2} \approx 3.2&amp;lt;/math&amp;gt;. Tewarson (2002) draws the same conclusion: the rate does not increase rapidly with concentration.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; Where a protective layer forms, the depth grows with the square root of time. As a separate illustration of this relation, exposure four times as long doubles the depth; the corrosion rate falls as time passes.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; The fitted values apply to that steel probe and those acid solutions.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As a worked example with these values, a tenfold rise in the concentration of corrosive products raises the corrosion rate by a factor of &amp;lt;math&amp;gt;10^{1/2} \approx 3.2&amp;lt;/math&amp;gt;. Tewarson (2002) draws the same conclusion: the rate does not increase rapidly with concentration.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; Where a protective layer forms, the depth grows with the square root of time. As a separate illustration of this relation, exposure four times as long doubles the depth; the corrosion rate falls as time passes.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; The fitted values apply to that steel probe and those acid solutions.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-salvage-v3.svg|thumb|upright=1.5|alt=Line chart of relative corrosion depth against relative time for exponents one and one half|Relative corrosion depth versus relative exposure time from the relation D = μ c^m t^n, without (n = 1) and with (n = 1/2) a protective film.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage, business continuity and loss ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage, business continuity and loss ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-5654:rev-8961:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Linda</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=5654&amp;oldid=prev</id>
		<title>Peter: Correct errors identified in the editorial review of 9 November 2026</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=5654&amp;oldid=prev"/>
		<updated>2026-11-09T15:08:16Z</updated>

		<summary type="html">&lt;p&gt;Correct errors identified in the editorial review of 9 November 2026&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 16:08, 9 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l35&quot;&gt;Line 35:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 35:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other media are more vulnerable. The emulsion of photographic records is particularly susceptible to steam, and even cold extinguishing water tends to soften it. Photographic records therefore get priority in salvage, because the emulsion tends to stick to adjacent material if salvage is not started immediately.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Magnetic tape can be considered safe only up to about 125 °F (52 °C) and a relative humidity of 85 percent.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Cellulose nitrate material that has been heated, such as material salvaged from a fire, may have changed so much that it can ignite spontaneously.&amp;lt;ref name=&amp;quot;BC-6-223&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-223.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other media are more vulnerable. The emulsion of photographic records is particularly susceptible to steam, and even cold extinguishing water tends to soften it. Photographic records therefore get priority in salvage, because the emulsion tends to stick to adjacent material if salvage is not started immediately.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Magnetic tape can be considered safe only up to about 125 °F (52 °C) and a relative humidity of 85 percent.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Cellulose nitrate material that has been heated, such as material salvaged from a fire, may have changed so much that it can ignite spontaneously.&amp;lt;ref name=&amp;quot;BC-6-223&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-223.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fire at the US National Archives&#039; Washington &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Regional &lt;/del&gt;Records Center on 29 February 2000 shows salvage by facility staff working alongside the fire department. While the fire was still under way, employees spread salvage covers, directed firefighters to ventilation equipment, moved out smouldering boxes and began records salvage. Once the fire was out, salvage and cleanup started, fire watches were set and drying equipment was ordered.&amp;lt;ref name=&quot;Beals-9-116&quot;&amp;gt;Beals (2008), p. 9-116.&amp;lt;/ref&amp;gt; About 100 m³ of records were wetted, but only about 50 boxes were lost.&amp;lt;ref name=&quot;Beals-9-116&quot; /&amp;gt; Because no method protects or salvages records with full certainty, Beals (2008) recommends storing duplicates at another site.&amp;lt;ref name=&quot;Beals-9-117&quot;&amp;gt;Beals (2008), p. 9-117.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fire at the US National Archives&#039; Washington &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;National &lt;/ins&gt;Records Center on 29 February 2000 shows salvage by facility staff working alongside the fire department. While the fire was still under way, employees spread salvage covers, directed firefighters to ventilation equipment, moved out smouldering boxes and began records salvage. Once the fire was out, salvage and cleanup started, fire watches were set and drying equipment was ordered.&amp;lt;ref name=&quot;Beals-9-116&quot;&amp;gt;Beals (2008), p. 9-116.&amp;lt;/ref&amp;gt; About 100 m³ of records were wetted, but only about 50 boxes were lost.&amp;lt;ref name=&quot;Beals-9-116&quot; /&amp;gt; Because no method protects or salvages records with full certainty, Beals (2008) recommends storing duplicates at another site.&amp;lt;ref name=&quot;Beals-9-117&quot;&amp;gt;Beals (2008), p. 9-117.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For [[Library and museum fire protection]], McDaniel (2008) calls this work damage limitation and divides it into three stages. Before a fire, the institution sets priorities for what to save first and identifies preservation specialists and sources of equipment. It also trains employees and briefs the fire service on where valuable collections are stored.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot;&amp;gt;McDaniel (2008), p. 20-195.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For [[Library and museum fire protection]], McDaniel (2008) calls this work damage limitation and divides it into three stages. Before a fire, the institution sets priorities for what to save first and identifies preservation specialists and sources of equipment. It also trains employees and briefs the fire service on where valuable collections are stored.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot;&amp;gt;McDaniel (2008), p. 20-195.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4207:rev-5654:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=4207&amp;oldid=prev</id>
		<title>Lisa: FSE wiki: fact-check corrections (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=4207&amp;oldid=prev"/>
		<updated>2026-11-07T23:40:09Z</updated>

		<summary type="html">&lt;p&gt;FSE wiki: fact-check corrections (written by Claude Opus 5.5)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 00:40, 8 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Salvage&amp;#039;&amp;#039;&amp;#039; is the part of [[Firefighting]] that protects a building&amp;#039;s contents and structure from avoidable damage by smoke, heat and water during and after a fire, for example by covering or removing contents.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-10.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-196&amp;quot;&amp;gt;Snyder (2008), p. 12-196.&amp;lt;/ref&amp;gt; In US fireground practice, as described in the 2008 &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039;, salvage belongs to property conservation, the third operational priority after life safety and extinguishment.&amp;lt;ref name=&amp;quot;KS-13-5&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-5.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt; Being last does not make it unimportant. Fire departments are expected to save both lives and property, and crews should be assigned to cover or remove exposed furniture as soon as staffing allows.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Salvage&amp;#039;&amp;#039;&amp;#039; is the part of [[Firefighting]] that protects a building&amp;#039;s contents and structure from avoidable damage by smoke, heat and water during and after a fire, for example by covering or removing contents.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-10.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-196&amp;quot;&amp;gt;Snyder (2008), p. 12-196.&amp;lt;/ref&amp;gt; In US fireground practice, as described in the 2008 &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039;, salvage belongs to property conservation, the third operational priority after life safety and extinguishment.&amp;lt;ref name=&amp;quot;KS-13-5&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-5.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt; Being last does not make it unimportant. Fire departments are expected to save both lives and property, and crews should be assigned to cover or remove exposed furniture as soon as staffing allows.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage began in the United States with mutual fire societies and insurance-funded salvage corps, and the task later passed to public fire departments.&amp;lt;ref name=&quot;Denlinger-12-53-54&quot;&amp;gt;Denlinger (2008), pp. 12-53–12-54.&amp;lt;/ref&amp;gt; Much of the damage it addresses is not caused by flames. Smoke can damage goods far from the fire, corrosive gases attack electronic equipment, and hose streams can &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;soak whole buildings&lt;/del&gt;.&amp;lt;ref name=&quot;Watts-1-162&quot;&amp;gt;Watts (2008b), p. 1-162.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;BC-6-225&quot;&amp;gt;Benedetti and Colonna (2008), p. 6-225.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;McDaniel-20-190&quot;&amp;gt;McDaniel (2008), p. 20-190.&amp;lt;/ref&amp;gt; Salvage is closely linked to [[Overhaul]], to the protection of records and collections, and to the recovery of a business after a fire.&amp;lt;ref name=&quot;Snyder-12-194&quot;&amp;gt;Snyder (2008), p. 12-194.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Schmidt-1-146&quot;&amp;gt;Schmidt (2008), p. 1-146.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage began in the United States with mutual fire societies and insurance-funded salvage corps, and the task later passed to public fire departments.&amp;lt;ref name=&quot;Denlinger-12-53-54&quot;&amp;gt;Denlinger (2008), pp. 12-53–12-54.&amp;lt;/ref&amp;gt; Much of the damage it addresses is not caused by flames. Smoke can damage goods far from the fire, corrosive gases attack electronic equipment, and hose streams can &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;wet materials on floors far below the fire&lt;/ins&gt;.&amp;lt;ref name=&quot;Watts-1-162&quot;&amp;gt;Watts (2008b), p. 1-162.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;BC-6-225&quot;&amp;gt;Benedetti and Colonna (2008), p. 6-225.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;McDaniel-20-190&quot;&amp;gt;McDaniel (2008), p. 20-190.&amp;lt;/ref&amp;gt; Salvage is closely linked to [[Overhaul]], to the protection of records and collections, and to the recovery of a business after a fire.&amp;lt;ref name=&quot;Snyder-12-194&quot;&amp;gt;Snyder (2008), p. 12-194.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Schmidt-1-146&quot;&amp;gt;Schmidt (2008), p. 1-146.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Definition and place in fireground operations ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Definition and place in fireground operations ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l10&quot;&gt;Line 10:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 10:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage is part of the size-up. The property conservation part of the US checklist asks where the salvageable property is and how susceptible it is to water and smoke damage. It also asks what damage entry and ventilation will cause, which pathways water will take, and which salvage and water removal methods are available.&amp;lt;ref name=&amp;quot;KS-13-6&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-6.&amp;lt;/ref&amp;gt; Risk to firefighters is weighed as well. NFPA 1500, as quoted by Klaene and Sanders (2008), treats activities routinely used to protect property as inherent risks that must be reduced or avoided, and accepts no risk where nothing can be saved.&amp;lt;ref name=&amp;quot;KS-13-6-7&amp;quot;&amp;gt;Klaene and Sanders (2008), pp. 13-6–13-7.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage is part of the size-up. The property conservation part of the US checklist asks where the salvageable property is and how susceptible it is to water and smoke damage. It also asks what damage entry and ventilation will cause, which pathways water will take, and which salvage and water removal methods are available.&amp;lt;ref name=&amp;quot;KS-13-6&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-6.&amp;lt;/ref&amp;gt; Risk to firefighters is weighed as well. NFPA 1500, as quoted by Klaene and Sanders (2008), treats activities routinely used to protect property as inherent risks that must be reduced or avoided, and accepts no risk where nothing can be saved.&amp;lt;ref name=&amp;quot;KS-13-6-7&amp;quot;&amp;gt;Klaene and Sanders (2008), pp. 13-6–13-7.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In US fire departments, salvage is one of the fireground duties of ladder companies, together with search and rescue, forcible entry, ventilation and overhaul.&amp;lt;ref name=&quot;Denlinger-12-63-64&quot;&amp;gt;Denlinger (2008), pp. 12-63–12-64.&amp;lt;/ref&amp;gt; An example organisational chart of a large department in the same chapter includes a separate salvage company.&amp;lt;ref name=&quot;Denlinger-12-64&quot;&amp;gt;Denlinger (2008), p. 12-64.&amp;lt;/ref&amp;gt; In rural departments, ladder truck equipment for salvage is sometimes carried on pumpers.&amp;lt;ref name=&quot;Granito-12-9&quot;&amp;gt;Granito (2008), p. 12-9.&amp;lt;/ref&amp;gt; &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Fire apparatus carry &lt;/del&gt;salvage covers &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;to protect &lt;/del&gt;unburned contents&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, and the &lt;/del&gt;Insurance Services Office (ISO) grading of US fire departments described by Granito (2008) checks salvage covers among &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;the &lt;/del&gt;service equipment.&amp;lt;ref name=&quot;Tutterow-12-280&quot;&amp;gt;Tutterow (2008), p. 12-280.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Granito-12-15&quot;&amp;gt;Granito (2008), p. 12-15.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Granito-12-17&quot;&amp;gt;Granito (2008), p. 12-17.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In US fire departments, salvage is one of the fireground duties of ladder companies, together with search and rescue, forcible entry, ventilation and overhaul.&amp;lt;ref name=&quot;Denlinger-12-63-64&quot;&amp;gt;Denlinger (2008), pp. 12-63–12-64.&amp;lt;/ref&amp;gt; An example organisational chart of a large department in the same chapter includes a separate salvage company.&amp;lt;ref name=&quot;Denlinger-12-64&quot;&amp;gt;Denlinger (2008), p. 12-64.&amp;lt;/ref&amp;gt; In rural departments, ladder truck equipment for salvage is sometimes carried on pumpers.&amp;lt;ref name=&quot;Granito-12-9&quot;&amp;gt;Granito (2008), p. 12-9.&amp;lt;/ref&amp;gt; &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Tutterow (2008) lists &lt;/ins&gt;salvage covers &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;among apparatus equipment for protecting &lt;/ins&gt;unburned contents&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. The &lt;/ins&gt;Insurance Services Office (ISO) grading of US fire departments described by Granito (2008) checks salvage covers among service equipment.&amp;lt;ref name=&quot;Tutterow-12-280&quot;&amp;gt;Tutterow (2008), p. 12-280.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Granito-12-15&quot;&amp;gt;Granito (2008), p. 12-15.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;Granito-12-17&quot;&amp;gt;Granito (2008), p. 12-17.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Industrial fire brigades do the same work. &lt;/del&gt;Snyder (2008) &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;notes that, concurrently &lt;/del&gt;with fire fighting, brigades should reduce the damage caused by the fire and by &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;the &lt;/del&gt;fire-fighting through &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;salvage and overhaul&lt;/del&gt;. Salvage equipment should include ventilation fans, flexible ducts for smoke removal, floor squeegees, water vacuums and tarps. In many manufacturing facilities the fans need explosion-proof motors.&amp;lt;ref name=&quot;Snyder-12-194&quot; /&amp;gt;&amp;lt;ref name=&quot;Snyder-12-196&quot; /&amp;gt; The word is also used in a different sense. In the Dutch guidance on car park fires by the Netherlands Institute for Public Safety (NIPV), a &quot;salvage company&quot; is the firm that removes a burnt electric vehicle together with the fire service.&amp;lt;ref name=&quot;VdG-42&quot;&amp;gt;Van der Graaf et al. (2021/2023), p. 42.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Snyder (2008) &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;assigns salvage and overhaul to industrial fire brigades as well. Concurrently &lt;/ins&gt;with fire fighting, brigades should reduce the damage caused by the fire and by fire-fighting &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;efforts &lt;/ins&gt;through &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;these tasks&lt;/ins&gt;. Salvage equipment should include ventilation fans, flexible ducts for smoke removal, floor squeegees, water vacuums and tarps. In many manufacturing facilities the fans need explosion-proof motors.&amp;lt;ref name=&quot;Snyder-12-194&quot; /&amp;gt;&amp;lt;ref name=&quot;Snyder-12-196&quot; /&amp;gt; The word is also used in a different sense. In the Dutch guidance on car park fires by the Netherlands Institute for Public Safety (NIPV), a &quot;salvage company&quot; is the firm that removes a burnt electric vehicle together with the fire service.&amp;lt;ref name=&quot;VdG-42&quot;&amp;gt;Van der Graaf et al. (2021/2023), p. 42.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== History ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== History ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l31&quot;&gt;Line 31:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 31:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage of records and collections ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage of records and collections ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Different materials survive fire very differently, which shapes salvage priorities in [[Records protection]]. Beals (2008) notes that ordinary paper records survive most fire effects, except direct exposure to flame, and that burned paper is almost always a total loss. A high recovery rate is practical for paper exposed only to water, high humidity, smoke and moderately high temperatures of about 350 °F (177 °C). Packed files burn slowly at the edges, so near-total recovery of wet paper with charred edges is possible.&amp;lt;ref name=&quot;Beals-9-108&quot;&amp;gt;Beals (2008), p. 9-108.&amp;lt;/ref&amp;gt; Virtually any wet paper record can be recovered, provided prompt and proper action is taken.&amp;lt;ref name=&quot;Beals-9-108&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Different materials survive fire very differently, which shapes salvage priorities in [[Records protection]]. Beals (2008) notes that ordinary paper records survive most fire effects &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;reasonably well&lt;/ins&gt;, except direct exposure to flame, and that burned paper is almost always a total loss. A high recovery rate is practical for paper exposed only to water, high humidity, smoke and moderately high temperatures of about 350 °F (177 °C). Packed files burn slowly at the edges, so near-total recovery of wet paper with charred edges is possible.&amp;lt;ref name=&quot;Beals-9-108&quot;&amp;gt;Beals (2008), p. 9-108.&amp;lt;/ref&amp;gt; Virtually any wet paper record can be recovered, provided prompt and proper action is taken.&amp;lt;ref name=&quot;Beals-9-108&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other media are more vulnerable. The emulsion of photographic records is particularly susceptible to steam, and even cold extinguishing water tends to soften it. Photographic records therefore get priority in salvage, because the emulsion tends to stick to adjacent material if salvage is not started immediately.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Magnetic tape can be considered safe only up to about 125 °F (52 °C) and a relative humidity of 85 percent.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Cellulose nitrate material that has been heated, such as material salvaged from a fire, may have changed so much that it can ignite spontaneously.&amp;lt;ref name=&amp;quot;BC-6-223&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-223.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other media are more vulnerable. The emulsion of photographic records is particularly susceptible to steam, and even cold extinguishing water tends to soften it. Photographic records therefore get priority in salvage, because the emulsion tends to stick to adjacent material if salvage is not started immediately.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Magnetic tape can be considered safe only up to about 125 °F (52 °C) and a relative humidity of 85 percent.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Cellulose nitrate material that has been heated, such as material salvaged from a fire, may have changed so much that it can ignite spontaneously.&amp;lt;ref name=&amp;quot;BC-6-223&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-223.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l59&quot;&gt;Line 59:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 59:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The growth of corrosion with time and concentration follows an empirical relation given by Tewarson (2002). The depth of corrosion increases with the concentration of the corrosive product and with exposure time, each raised to an empirical power. Tewarson (2002) applies it to metal surfaces exposed to corrosive fire products, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;such as aqueous &lt;/del&gt;solutions &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;of hydrogen chloride&lt;/del&gt;.&amp;lt;ref name=&quot;Tewarson-3-138&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The growth of corrosion with time and concentration follows an empirical relation given by Tewarson (2002). The depth of corrosion increases with the concentration of the corrosive product and with exposure time, each raised to an empirical power. Tewarson (2002) applies it to metal surfaces exposed to corrosive fire products, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;including acid &lt;/ins&gt;solutions &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;tested on a steel probe&lt;/ins&gt;.&amp;lt;ref name=&quot;Tewarson-3-138&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;-139&lt;/ins&gt;&quot;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;&amp;gt;Tewarson (2002), pp. 3-138–3-139.&amp;lt;&lt;/ins&gt;/&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;ref&lt;/ins&gt;&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;D_\mathrm{corr} = \mu\, c^{m}\, t^{n}&amp;lt;/math&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;D_\mathrm{corr} = \mu\, c^{m}\, t^{n}&amp;lt;/math&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l79&quot;&gt;Line 79:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 79:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The exponent &amp;lt;math&amp;gt;n&amp;lt;/math&amp;gt; depends on the surface film. Where a protective film of corrosion products forms, further corrosion is limited by diffusion and &amp;lt;math&amp;gt;n = 1/2&amp;lt;/math&amp;gt;. Where the film offers no protection, &amp;lt;math&amp;gt;n = 1&amp;lt;/math&amp;gt; and the corrosion rate does not change with time.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt; For a mild steel probe in aqueous solutions of hydrochloric and nitric acid over 24 hours, regression gave &amp;lt;math&amp;gt;\mu = 2.08&amp;lt;/math&amp;gt; (Å/min)(g/m³)&amp;lt;sup&amp;gt;−1/2&amp;lt;/sup&amp;gt; and &amp;lt;math&amp;gt;m = 1/2&amp;lt;/math&amp;gt;, with no protective layer.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot;&amp;gt;Tewarson (2002), p. 3-139.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The exponent &amp;lt;math&amp;gt;n&amp;lt;/math&amp;gt; depends on the surface film. Where a protective film of corrosion products forms, further corrosion is limited by diffusion and &amp;lt;math&amp;gt;n = 1/2&amp;lt;/math&amp;gt;. Where the film offers no protection, &amp;lt;math&amp;gt;n = 1&amp;lt;/math&amp;gt; and the corrosion rate does not change with time.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt; For a mild steel probe in aqueous solutions of hydrochloric and nitric acid over 24 hours, regression gave &amp;lt;math&amp;gt;\mu = 2.08&amp;lt;/math&amp;gt; (Å/min)(g/m³)&amp;lt;sup&amp;gt;−1/2&amp;lt;/sup&amp;gt; and &amp;lt;math&amp;gt;m = 1/2&amp;lt;/math&amp;gt;, with no protective layer.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot;&amp;gt;Tewarson (2002), p. 3-139.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As a worked example with these values, a tenfold rise in the concentration of corrosive products raises the corrosion rate by a factor of &amp;lt;math&amp;gt;10^{1/2} \approx 3.2&amp;lt;/math&amp;gt;. Tewarson (2002) draws the same conclusion: the rate does not increase rapidly with concentration.&amp;lt;ref name=&quot;Tewarson-3-139&quot; /&amp;gt; Where a protective layer forms, the depth grows &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;only &lt;/del&gt;with the square root of time, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;so &lt;/del&gt;exposure four times as long doubles the depth&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, and &lt;/del&gt;the corrosion rate falls as time passes.&amp;lt;ref name=&quot;Tewarson-3-138&quot; /&amp;gt;&amp;lt;ref name=&quot;Tewarson-3-139&quot; /&amp;gt; The fitted values apply to that steel probe and those acid solutions.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As a worked example with these values, a tenfold rise in the concentration of corrosive products raises the corrosion rate by a factor of &amp;lt;math&amp;gt;10^{1/2} \approx 3.2&amp;lt;/math&amp;gt;. Tewarson (2002) draws the same conclusion: the rate does not increase rapidly with concentration.&amp;lt;ref name=&quot;Tewarson-3-139&quot; /&amp;gt; Where a protective layer forms, the depth grows with the square root of time&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. As a separate illustration of this relation&lt;/ins&gt;, exposure four times as long doubles the depth&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;; &lt;/ins&gt;the corrosion rate falls as time passes.&amp;lt;ref name=&quot;Tewarson-3-138&quot; /&amp;gt;&amp;lt;ref name=&quot;Tewarson-3-139&quot; /&amp;gt; The fitted values apply to that steel probe and those acid solutions.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage, business continuity and loss ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Salvage, business continuity and loss ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage also forms part of an organisation&amp;#039;s recovery after a fire. Schmidt (2008) lists salvage and cleanup among the minimum functions of a facility&amp;#039;s emergency organisation.&amp;lt;ref name=&amp;quot;Schmidt-1-145&amp;quot;&amp;gt;Schmidt (2008), p. 1-145.&amp;lt;/ref&amp;gt; As soon as it is safe, that organisation should assess damage together with the [[Business continuity]] team and start mitigation and recovery, including debris removal, cleanup, repairs and the restoration of utilities.&amp;lt;ref name=&amp;quot;Schmidt-1-146&amp;quot; /&amp;gt; Snyder (2008) names plans for business continuity, including salvage, cleanup and alternative locations for conducting business, among the key elements of an industrial emergency plan. Industrial fire brigades assist in salvage operations after fires.&amp;lt;ref name=&amp;quot;Snyder-12-190&amp;quot;&amp;gt;Snyder (2008), p. 12-190.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-180&amp;quot;&amp;gt;Snyder (2008), p. 12-180.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Salvage also forms part of an organisation&amp;#039;s recovery after a fire. Schmidt (2008) lists salvage and cleanup among the minimum functions of a facility&amp;#039;s emergency organisation.&amp;lt;ref name=&amp;quot;Schmidt-1-145&amp;quot;&amp;gt;Schmidt (2008), p. 1-145.&amp;lt;/ref&amp;gt; As soon as it is safe, that organisation should assess damage together with the [[Business continuity]] team and start mitigation and recovery, including debris removal, cleanup, repairs and the restoration of utilities.&amp;lt;ref name=&amp;quot;Schmidt-1-146&amp;quot; /&amp;gt; Snyder (2008) names plans for business continuity, including salvage, cleanup and alternative locations for conducting business, among the key elements of an industrial emergency plan. Industrial fire brigades assist in salvage operations after fires.&amp;lt;ref name=&amp;quot;Snyder-12-190&amp;quot;&amp;gt;Snyder (2008), p. 12-190.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-180&amp;quot;&amp;gt;Snyder (2008), p. 12-180.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The economic stakes go beyond direct damage. In the SFPE Handbook, Ramachandran (2002b) separates direct damage from indirect loss, which includes business interruption, also called consequential loss.&amp;lt;ref name=&quot;Ramachandran-5-79&quot;&amp;gt;Ramachandran (2002b), p. 5-79.&amp;lt;/ref&amp;gt; A study by NFPA of 109 US fires from 1989 found that indirect losses, mainly business interruption costs, add a fraction &amp;lt;math&amp;gt;f&amp;lt;/math&amp;gt; to the direct loss that depends on the property class.&amp;lt;ref name=&quot;Ramachandran-5-80&quot;&amp;gt;Ramachandran (2002b), p. 5-80.&amp;lt;/ref&amp;gt; &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;The &lt;/del&gt;total [[Fire loss]] &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;then follows from the &lt;/del&gt;direct loss.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The economic stakes go beyond direct damage. In the SFPE Handbook, Ramachandran (2002b) separates direct damage from indirect loss, which includes business interruption, also called consequential loss.&amp;lt;ref name=&quot;Ramachandran-5-79&quot;&amp;gt;Ramachandran (2002b), p. 5-79.&amp;lt;/ref&amp;gt; A study by NFPA of 109 US fires from 1989 found that indirect losses, mainly business interruption costs, add a fraction &amp;lt;math&amp;gt;f&amp;lt;/math&amp;gt; to the direct loss that depends on the property class.&amp;lt;ref name=&quot;Ramachandran-5-80&quot;&amp;gt;Ramachandran (2002b), p. 5-80.&amp;lt;/ref&amp;gt; &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;As an algebraic summary of those estimates, the &lt;/ins&gt;total [[Fire loss]] &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;is &lt;/ins&gt;direct &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;loss plus estimated indirect &lt;/ins&gt;loss.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;L_\mathrm{total} = L_\mathrm{direct}\,(1 + f)&amp;lt;/math&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;L_\mathrm{total} = L_\mathrm{direct}\,(1 + f)&amp;lt;/math&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l98&quot;&gt;Line 98:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 98:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As an illustration, a direct loss of 1.0 million dollars in a manufacturing plant would correspond, with &amp;lt;math&amp;gt;f = 0.65&amp;lt;/math&amp;gt;, to a total loss of about 1.65 million dollars. &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;The &lt;/del&gt;fractions are &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;averages. &lt;/del&gt;Ramachandran (2002b) &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;notes that a &lt;/del&gt;few well-publicised fires with very large indirect losses are more than offset by the far more numerous fires with small or no indirect loss.&amp;lt;ref name=&quot;Ramachandran-5-80&quot; /&amp;gt; In the World Fire Statistics Centre reports discussed in the same chapter, indirect losses tended to be below 25 percent of direct damage in every reporting country except Switzerland, at 40 percent.&amp;lt;ref name=&quot;Ramachandran-5-80&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;As an illustration, a direct loss of 1.0 million dollars in a manufacturing plant would correspond, with &amp;lt;math&amp;gt;f = 0.65&amp;lt;/math&amp;gt;, to a total loss of about 1.65 million dollars. &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;These &lt;/ins&gt;fractions are &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;NFPA estimates from the 1989 sample, as reported by &lt;/ins&gt;Ramachandran (2002b)&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. A &lt;/ins&gt;few well-publicised fires with very large indirect losses are more than offset by the far more numerous fires with small or no indirect loss.&amp;lt;ref name=&quot;Ramachandran-5-80&quot; /&amp;gt; In the World Fire Statistics Centre reports discussed in the same chapter, indirect losses tended to be below 25 percent of direct damage in every reporting country except Switzerland, at 40 percent.&amp;lt;ref name=&quot;Ramachandran-5-80&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire safety engineering guidance also addresses property protection. The IFEG (2005) list protection of property from damage due to fire and its products, and minimising business interruption, among the activities for which fire services commonly have a responsibility.&amp;lt;ref name=&amp;quot;IFEG-2.9-3&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-3.&amp;lt;/ref&amp;gt; The Fire Brigade Intervention Model includes a chart for the time to protect uninvolved contents, called salvage operations.&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-5.&amp;lt;/ref&amp;gt; That chart lies outside the primary path used where a building code has no requirement to protect the building or its contents.&amp;lt;ref name=&amp;quot;IFEG-2.9-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-4.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire safety engineering guidance also addresses property protection. The IFEG (2005) list protection of property from damage due to fire and its products, and minimising business interruption, among the activities for which fire services commonly have a responsibility.&amp;lt;ref name=&amp;quot;IFEG-2.9-3&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-3.&amp;lt;/ref&amp;gt; The Fire Brigade Intervention Model includes a chart for the time to protect uninvolved contents, called salvage operations.&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-5.&amp;lt;/ref&amp;gt; That chart lies outside the primary path used where a building code has no requirement to protect the building or its contents.&amp;lt;ref name=&amp;quot;IFEG-2.9-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-4.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3517:rev-4207:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Lisa</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=3517&amp;oldid=prev</id>
		<title>Lisa: New FSE wiki article: Salvage (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Salvage&amp;diff=3517&amp;oldid=prev"/>
		<updated>2026-11-07T21:29:21Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Salvage (written by Claude Opus 5.5)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Salvage&amp;#039;&amp;#039;&amp;#039; is the part of [[Firefighting]] that protects a building&amp;#039;s contents and structure from avoidable damage by smoke, heat and water during and after a fire, for example by covering or removing contents.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-10.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-196&amp;quot;&amp;gt;Snyder (2008), p. 12-196.&amp;lt;/ref&amp;gt; In US fireground practice, as described in the 2008 &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039;, salvage belongs to property conservation, the third operational priority after life safety and extinguishment.&amp;lt;ref name=&amp;quot;KS-13-5&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-5.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt; Being last does not make it unimportant. Fire departments are expected to save both lives and property, and crews should be assigned to cover or remove exposed furniture as soon as staffing allows.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Salvage began in the United States with mutual fire societies and insurance-funded salvage corps, and the task later passed to public fire departments.&amp;lt;ref name=&amp;quot;Denlinger-12-53-54&amp;quot;&amp;gt;Denlinger (2008), pp. 12-53–12-54.&amp;lt;/ref&amp;gt; Much of the damage it addresses is not caused by flames. Smoke can damage goods far from the fire, corrosive gases attack electronic equipment, and hose streams can soak whole buildings.&amp;lt;ref name=&amp;quot;Watts-1-162&amp;quot;&amp;gt;Watts (2008b), p. 1-162.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;BC-6-225&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-225.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot;&amp;gt;McDaniel (2008), p. 20-190.&amp;lt;/ref&amp;gt; Salvage is closely linked to [[Overhaul]], to the protection of records and collections, and to the recovery of a business after a fire.&amp;lt;ref name=&amp;quot;Snyder-12-194&amp;quot;&amp;gt;Snyder (2008), p. 12-194.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Schmidt-1-146&amp;quot;&amp;gt;Schmidt (2008), p. 1-146.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Definition and place in fireground operations ==&lt;br /&gt;
Klaene and Sanders (2008) state that property conservation tactics can substantially reduce property loss. Life safety and extinguishment are assigned first, and property conservation may be delayed until enough staff are on scene. Even so, personnel should be given specific property conservation duties, such as covering or removing exposed furniture, as soon as possible.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt; Once staffing permits during an offensive attack, the incident commander should attend to all three priorities at the same time.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Well-executed firefighting also limits damage. An attack on the seat of the fire with a hose line that flows at or above the required rate extinguishes the fire quickly and causes less water damage.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt; Proper ventilation directs smoke and heat away from the parts of the structure and contents that are not yet exposed. According to Klaene and Sanders (2008), the products of combustion are often the primary cause of damage, and improper ventilation spreads them through the building.&amp;lt;ref name=&amp;quot;KS-13-10&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Salvage is part of the size-up. The property conservation part of the US checklist asks where the salvageable property is and how susceptible it is to water and smoke damage. It also asks what damage entry and ventilation will cause, which pathways water will take, and which salvage and water removal methods are available.&amp;lt;ref name=&amp;quot;KS-13-6&amp;quot;&amp;gt;Klaene and Sanders (2008), p. 13-6.&amp;lt;/ref&amp;gt; Risk to firefighters is weighed as well. NFPA 1500, as quoted by Klaene and Sanders (2008), treats activities routinely used to protect property as inherent risks that must be reduced or avoided, and accepts no risk where nothing can be saved.&amp;lt;ref name=&amp;quot;KS-13-6-7&amp;quot;&amp;gt;Klaene and Sanders (2008), pp. 13-6–13-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In US fire departments, salvage is one of the fireground duties of ladder companies, together with search and rescue, forcible entry, ventilation and overhaul.&amp;lt;ref name=&amp;quot;Denlinger-12-63-64&amp;quot;&amp;gt;Denlinger (2008), pp. 12-63–12-64.&amp;lt;/ref&amp;gt; An example organisational chart of a large department in the same chapter includes a separate salvage company.&amp;lt;ref name=&amp;quot;Denlinger-12-64&amp;quot;&amp;gt;Denlinger (2008), p. 12-64.&amp;lt;/ref&amp;gt; In rural departments, ladder truck equipment for salvage is sometimes carried on pumpers.&amp;lt;ref name=&amp;quot;Granito-12-9&amp;quot;&amp;gt;Granito (2008), p. 12-9.&amp;lt;/ref&amp;gt; Fire apparatus carry salvage covers to protect unburned contents, and the Insurance Services Office (ISO) grading of US fire departments described by Granito (2008) checks salvage covers among the service equipment.&amp;lt;ref name=&amp;quot;Tutterow-12-280&amp;quot;&amp;gt;Tutterow (2008), p. 12-280.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Granito-12-15&amp;quot;&amp;gt;Granito (2008), p. 12-15.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Granito-12-17&amp;quot;&amp;gt;Granito (2008), p. 12-17.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Industrial fire brigades do the same work. Snyder (2008) notes that, concurrently with fire fighting, brigades should reduce the damage caused by the fire and by the fire-fighting through salvage and overhaul. Salvage equipment should include ventilation fans, flexible ducts for smoke removal, floor squeegees, water vacuums and tarps. In many manufacturing facilities the fans need explosion-proof motors.&amp;lt;ref name=&amp;quot;Snyder-12-194&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-196&amp;quot; /&amp;gt; The word is also used in a different sense. In the Dutch guidance on car park fires by the Netherlands Institute for Public Safety (NIPV), a &amp;quot;salvage company&amp;quot; is the firm that removes a burnt electric vehicle together with the fire service.&amp;lt;ref name=&amp;quot;VdG-42&amp;quot;&amp;gt;Van der Graaf et al. (2021/2023), p. 42.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== History ==&lt;br /&gt;
Denlinger (2008) traces salvage in the United States to the mutual fire societies of Boston. In 1718, a group of affluent Bostonians organised to help each other save goods from homes and businesses hit by fire. Each member carried a bag for valuables, a screwdriver and a bed key for taking apart beds, which were valuable possessions at the time. These societies were active for about a century, until [[Fire insurance]] became generally affordable.&amp;lt;ref name=&amp;quot;Denlinger-12-53-54&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Insurance interests then took up the task. By about 1850, the major US cities had paid fire departments with steam engines, and insurers in nineteen of these cities formed salvage corps whose job was to reduce water damage at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot;&amp;gt;Denlinger (2008), p. 12-54.&amp;lt;/ref&amp;gt; Rising operating costs and improved fire-fighting procedures later made the corps obsolete, and they were disbanded. By 2008, public fire departments carried out salvage operations at fires.&amp;lt;ref name=&amp;quot;Denlinger-12-54&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Sources of damage ==&lt;br /&gt;
Fire damages property in several ways. Watts (2008b) notes that property is affected by the thermal and non-thermal products of combustion and by extinguishing agents, and that smoke may damage goods far from the heat and flames. Fires that are not extinguished quickly often cause considerable water damage, unless special measures prevent it. Yet the water damage caused in extinguishing a fire rarely exceeds the damage of a fire that is not suppressed.&amp;lt;ref name=&amp;quot;Watts-1-162&amp;quot; /&amp;gt; In industrial and commercial occupancies, the largest part of a loss is often due to smoke damage outside the immediate fire area. Serapiglia (2008) adds that the pre-incident plan should detail salvage needs.&amp;lt;ref name=&amp;quot;Serapiglia-12-295&amp;quot;&amp;gt;Serapiglia (2008), p. 12-295.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water is the obvious extinguishing agent for burning solids, but it can irreversibly damage some items. In many cases, however, water-damaged items can be salvaged.&amp;lt;ref name=&amp;quot;YN-2-82&amp;quot;&amp;gt;Yu and Newman (2008), p. 2-82.&amp;lt;/ref&amp;gt; How the water is applied matters. McDaniel (2008) explains that a single sprinkler releases 20 to 25 gpm (76 to 95 L/min) in a spray, while each firefighter&amp;#039;s hose stream delivers 150 to 250 gpm (568 to 946 L/min). Most fires in sprinklered buildings are controlled by fewer than five sprinklers, which together release less water per minute than one hose stream.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
As an illustration of that comparison, take the largest number of sprinklers in that statement, four, each at the upper flow of 25 gpm. Their total discharge is &amp;lt;math&amp;gt;Q_\mathrm{s} = n\,q_\mathrm{s} = 4 \times 25 = 100&amp;lt;/math&amp;gt; gpm (about 380 L/min). A single hose stream at its lowest flow of 150 gpm delivers 1.5 times as much. In addition, hose streams are used later in a fire, must be aimed at the general area until the smoke clears, and need more water for extinguishment.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; They can also sweep materials from shelves into a disorganised mass on a flooded floor. Wet materials left in place under the gentler action of a [[Sprinkler system]] have much better prospects of salvage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Statistics point the same way. In 1994 to 1998 US structure fires in libraries and museums reported to local fire departments, sprinklers reduced the average dollar loss per fire by 72 percent, and in places of worship by 32 percent. This is roughly consistent with the general finding that sprinklers reduce the average loss by one-half to two-thirds.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt; For many years, however, managers of cultural collections opposed sprinklers because they feared water damage even more than fire damage.&amp;lt;ref name=&amp;quot;McDaniel-20-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Beals (2008) states that sprinklers in records storage limit both fire and water damage, because water is discharged only near the fire. Salvage techniques have been perfected to the point where recovery of wetted items is no longer unusual.&amp;lt;ref name=&amp;quot;Beals-9-113&amp;quot;&amp;gt;Beals (2008), p. 9-113.&amp;lt;/ref&amp;gt; In sprinklered warehouses, J. Moore (2008) advises that water damage should not be a concern until the fire is out, and that pressure from owners to shut off sprinklers must be ignored.&amp;lt;ref name=&amp;quot;Moore-20-174&amp;quot;&amp;gt;J. Moore (2008), p. 20-174.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Salvage of records and collections ==&lt;br /&gt;
Different materials survive fire very differently, which shapes salvage priorities in [[Records protection]]. Beals (2008) notes that ordinary paper records survive most fire effects, except direct exposure to flame, and that burned paper is almost always a total loss. A high recovery rate is practical for paper exposed only to water, high humidity, smoke and moderately high temperatures of about 350 °F (177 °C). Packed files burn slowly at the edges, so near-total recovery of wet paper with charred edges is possible.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot;&amp;gt;Beals (2008), p. 9-108.&amp;lt;/ref&amp;gt; Virtually any wet paper record can be recovered, provided prompt and proper action is taken.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Other media are more vulnerable. The emulsion of photographic records is particularly susceptible to steam, and even cold extinguishing water tends to soften it. Photographic records therefore get priority in salvage, because the emulsion tends to stick to adjacent material if salvage is not started immediately.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Magnetic tape can be considered safe only up to about 125 °F (52 °C) and a relative humidity of 85 percent.&amp;lt;ref name=&amp;quot;Beals-9-108&amp;quot; /&amp;gt; Cellulose nitrate material that has been heated, such as material salvaged from a fire, may have changed so much that it can ignite spontaneously.&amp;lt;ref name=&amp;quot;BC-6-223&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-223.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A fire at the US National Archives&amp;#039; Washington Regional Records Center on 29 February 2000 shows salvage by facility staff working alongside the fire department. While the fire was still under way, employees spread salvage covers, directed firefighters to ventilation equipment, moved out smouldering boxes and began records salvage. Once the fire was out, salvage and cleanup started, fire watches were set and drying equipment was ordered.&amp;lt;ref name=&amp;quot;Beals-9-116&amp;quot;&amp;gt;Beals (2008), p. 9-116.&amp;lt;/ref&amp;gt; About 100 m³ of records were wetted, but only about 50 boxes were lost.&amp;lt;ref name=&amp;quot;Beals-9-116&amp;quot; /&amp;gt; Because no method protects or salvages records with full certainty, Beals (2008) recommends storing duplicates at another site.&amp;lt;ref name=&amp;quot;Beals-9-117&amp;quot;&amp;gt;Beals (2008), p. 9-117.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For [[Library and museum fire protection]], McDaniel (2008) calls this work damage limitation and divides it into three stages. Before a fire, the institution sets priorities for what to save first and identifies preservation specialists and sources of equipment. It also trains employees and briefs the fire service on where valuable collections are stored.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot;&amp;gt;McDaniel (2008), p. 20-195.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
During the fire, endangered collections are removed if staff are not put at risk, and tarpaulins or plastic sheeting protect nearby materials from water. After the fire, damaged articles are wrapped and frozen, and restoration follows specialist advice.&amp;lt;ref name=&amp;quot;McDaniel-20-195&amp;quot; /&amp;gt; Freeze/vacuum drying removes water and smoke odours very effectively, but it cannot undo physical damage from hose streams, trampling or mishandling.&amp;lt;ref name=&amp;quot;McDaniel-20-194-195&amp;quot;&amp;gt;McDaniel (2008), pp. 20-194–20-195.&amp;lt;/ref&amp;gt; Museums and places of worship, with fewer but more valuable items, concentrate on moving endangered collections to a safe place quickly and carefully.&amp;lt;ref name=&amp;quot;McDaniel-20-194&amp;quot;&amp;gt;McDaniel (2008), p. 20-194.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Smoke and corrosion damage to equipment ==&lt;br /&gt;
Some damage appears only after the fire. Benedetti and Colonna (2008) warn that severe corrosion damage to sensitive electronic equipment and metal surfaces can follow fires involving plastics such as polyvinyl chloride (PVC).&amp;lt;ref name=&amp;quot;BC-6-225&amp;quot; /&amp;gt; Such fires release hydrogen chloride, which is corrosive to metals and electrical equipment. The equipment should be ventilated, rinsed or treated with dilute ammonia, and rinsed as soon as possible after exposure.&amp;lt;ref name=&amp;quot;BC-6-230&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-230.&amp;lt;/ref&amp;gt; The IFEG (2005) note that where property protection is a concern, fire safety engineers often consider corrosive species such as hydrogen chloride and smoke particles.&amp;lt;ref name=&amp;quot;IFEG-1.5-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 1.5-4.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Tewarson (2002) bases his discussion on the experience of telephone central offices, where galvanised or zinc-chromated finishes make up much of the equipment and ductwork. On exposure to hydrogen chloride gas, zinc forms zinc chloride, which absorbs moisture from air with a relative humidity as low as 10 percent. The resulting conductive solution runs onto equipment and causes serious short circuits.&amp;lt;ref name=&amp;quot;Tewarson-3-136-137&amp;quot;&amp;gt;Tewarson (2002), pp. 3-136–3-137.&amp;lt;/ref&amp;gt; In two major losses it strongly affected both the rate of restoration and the ability to salvage equipment. In such fires involving PVC cables, contamination of about 5 to 900 micrograms of chloride per square centimetre has been observed, against less than 2 µg/cm² on clean equipment.&amp;lt;ref name=&amp;quot;Tewarson-3-137&amp;quot;&amp;gt;Tewarson (2002), p. 3-137.&amp;lt;/ref&amp;gt; The levels used to judge restoration are given in the table.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot;&amp;gt;Tewarson (2002), p. 3-138.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
|+ Chloride contamination levels for electronic equipment after a fire, from Tewarson (2002), Table 3-4.22&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt;&lt;br /&gt;
! Level !! Chloride on surface (µg/cm²) !! Damage, cleaning and restoration&lt;br /&gt;
|-&lt;br /&gt;
| One || 2 || No damage expected; no cleaning or restoration required&lt;br /&gt;
|-&lt;br /&gt;
| Two || less than 30 || Easily restored to service by cleaning, with little impact on long-term reliability&lt;br /&gt;
|-&lt;br /&gt;
| Three || 30 to 90 || Can be restored by cleaning if no unusual corrosion arises and the environment is strictly controlled soon after the fire&lt;br /&gt;
|-&lt;br /&gt;
| Four || more than 90 || Cleaning becomes less effective and its cost approaches replacement; severe environmental control may be needed even after cleaning&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The growth of corrosion with time and concentration follows an empirical relation given by Tewarson (2002). The depth of corrosion increases with the concentration of the corrosive product and with exposure time, each raised to an empirical power. Tewarson (2002) applies it to metal surfaces exposed to corrosive fire products, such as aqueous solutions of hydrogen chloride.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;D_\mathrm{corr} = \mu\, c^{m}\, t^{n}&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;D_\mathrm{corr}&amp;lt;/math&amp;gt; || Metal corrosion (penetration depth or metal loss) || µm, Å or mils&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;c&amp;lt;/math&amp;gt; || Concentration of the corrosive product || g/m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;t&amp;lt;/math&amp;gt; || Exposure time || min or day&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\mu&amp;lt;/math&amp;gt; || Empirical corrosion parameter of the corrosive product || depends on &amp;lt;math&amp;gt;m&amp;lt;/math&amp;gt; and &amp;lt;math&amp;gt;n&amp;lt;/math&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;m&amp;lt;/math&amp;gt;, &amp;lt;math&amp;gt;n&amp;lt;/math&amp;gt; || Empirical exponents || –&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The exponent &amp;lt;math&amp;gt;n&amp;lt;/math&amp;gt; depends on the surface film. Where a protective film of corrosion products forms, further corrosion is limited by diffusion and &amp;lt;math&amp;gt;n = 1/2&amp;lt;/math&amp;gt;. Where the film offers no protection, &amp;lt;math&amp;gt;n = 1&amp;lt;/math&amp;gt; and the corrosion rate does not change with time.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt; For a mild steel probe in aqueous solutions of hydrochloric and nitric acid over 24 hours, regression gave &amp;lt;math&amp;gt;\mu = 2.08&amp;lt;/math&amp;gt; (Å/min)(g/m³)&amp;lt;sup&amp;gt;−1/2&amp;lt;/sup&amp;gt; and &amp;lt;math&amp;gt;m = 1/2&amp;lt;/math&amp;gt;, with no protective layer.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot;&amp;gt;Tewarson (2002), p. 3-139.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
As a worked example with these values, a tenfold rise in the concentration of corrosive products raises the corrosion rate by a factor of &amp;lt;math&amp;gt;10^{1/2} \approx 3.2&amp;lt;/math&amp;gt;. Tewarson (2002) draws the same conclusion: the rate does not increase rapidly with concentration.&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; Where a protective layer forms, the depth grows only with the square root of time, so exposure four times as long doubles the depth, and the corrosion rate falls as time passes.&amp;lt;ref name=&amp;quot;Tewarson-3-138&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Tewarson-3-139&amp;quot; /&amp;gt; The fitted values apply to that steel probe and those acid solutions.&lt;br /&gt;
&lt;br /&gt;
== Salvage, business continuity and loss ==&lt;br /&gt;
Salvage also forms part of an organisation&amp;#039;s recovery after a fire. Schmidt (2008) lists salvage and cleanup among the minimum functions of a facility&amp;#039;s emergency organisation.&amp;lt;ref name=&amp;quot;Schmidt-1-145&amp;quot;&amp;gt;Schmidt (2008), p. 1-145.&amp;lt;/ref&amp;gt; As soon as it is safe, that organisation should assess damage together with the [[Business continuity]] team and start mitigation and recovery, including debris removal, cleanup, repairs and the restoration of utilities.&amp;lt;ref name=&amp;quot;Schmidt-1-146&amp;quot; /&amp;gt; Snyder (2008) names plans for business continuity, including salvage, cleanup and alternative locations for conducting business, among the key elements of an industrial emergency plan. Industrial fire brigades assist in salvage operations after fires.&amp;lt;ref name=&amp;quot;Snyder-12-190&amp;quot;&amp;gt;Snyder (2008), p. 12-190.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Snyder-12-180&amp;quot;&amp;gt;Snyder (2008), p. 12-180.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The economic stakes go beyond direct damage. In the SFPE Handbook, Ramachandran (2002b) separates direct damage from indirect loss, which includes business interruption, also called consequential loss.&amp;lt;ref name=&amp;quot;Ramachandran-5-79&amp;quot;&amp;gt;Ramachandran (2002b), p. 5-79.&amp;lt;/ref&amp;gt; A study by NFPA of 109 US fires from 1989 found that indirect losses, mainly business interruption costs, add a fraction &amp;lt;math&amp;gt;f&amp;lt;/math&amp;gt; to the direct loss that depends on the property class.&amp;lt;ref name=&amp;quot;Ramachandran-5-80&amp;quot;&amp;gt;Ramachandran (2002b), p. 5-80.&amp;lt;/ref&amp;gt; The total [[Fire loss]] then follows from the direct loss.&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;L_\mathrm{total} = L_\mathrm{direct}\,(1 + f)&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;L_\mathrm{total}&amp;lt;/math&amp;gt; || Total loss (direct plus indirect) || currency&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;L_\mathrm{direct}&amp;lt;/math&amp;gt; || Direct fire damage || currency&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;f&amp;lt;/math&amp;gt; || Indirect loss as a fraction of direct loss: 0.65 manufacturing and industrial; 0.25 public assembly, educational, institutional, retail and office; 0.10 residential, storage and special structures; 0 vehicles and outdoor fires (US, 1989 data) || –&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
As an illustration, a direct loss of 1.0 million dollars in a manufacturing plant would correspond, with &amp;lt;math&amp;gt;f = 0.65&amp;lt;/math&amp;gt;, to a total loss of about 1.65 million dollars. The fractions are averages. Ramachandran (2002b) notes that a few well-publicised fires with very large indirect losses are more than offset by the far more numerous fires with small or no indirect loss.&amp;lt;ref name=&amp;quot;Ramachandran-5-80&amp;quot; /&amp;gt; In the World Fire Statistics Centre reports discussed in the same chapter, indirect losses tended to be below 25 percent of direct damage in every reporting country except Switzerland, at 40 percent.&amp;lt;ref name=&amp;quot;Ramachandran-5-80&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fire safety engineering guidance also addresses property protection. The IFEG (2005) list protection of property from damage due to fire and its products, and minimising business interruption, among the activities for which fire services commonly have a responsibility.&amp;lt;ref name=&amp;quot;IFEG-2.9-3&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-3.&amp;lt;/ref&amp;gt; The Fire Brigade Intervention Model includes a chart for the time to protect uninvolved contents, called salvage operations.&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-5.&amp;lt;/ref&amp;gt; That chart lies outside the primary path used where a building code has no requirement to protect the building or its contents.&amp;lt;ref name=&amp;quot;IFEG-2.9-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 2.9-4.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-2.9-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The New Zealand version of the guidelines notes that an analysis can go beyond minimum life safety requirements and identify property, business interruption and consequential loss protection for the owner.&amp;lt;ref name=&amp;quot;IFEG-0.3-4&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), Part 0 (New Zealand), p. 0.3-4.&amp;lt;/ref&amp;gt; Van Rossum (2027) lists preserving the building, preserving its contents and business continuity among the possible goals of fire safety, which mix public and private interests.&amp;lt;ref name=&amp;quot;VR-1&amp;quot;&amp;gt;Van Rossum (2027), §1.&amp;lt;/ref&amp;gt; The Dutch building regulations in the &amp;#039;&amp;#039;Besluit bouwwerken leefomgeving&amp;#039;&amp;#039; (Bbl), however, explicitly exclude preserving the building from their aims.&amp;lt;ref name=&amp;quot;VR-1.2&amp;quot;&amp;gt;Van Rossum (2027), §1.2.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Pre-incident planning]]&lt;br /&gt;
* [[Industrial fire brigade]]&lt;br /&gt;
* [[Public Protection Classification]]&lt;br /&gt;
* [[Fire apparatus]]&lt;br /&gt;
* [[Size-up]]&lt;br /&gt;
* [[Fire watch]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 9-105–9-117). National Fire Protection Association.&lt;br /&gt;
* Benedetti, R. P., &amp;amp; Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-209–6-231). National Fire Protection Association.&lt;br /&gt;
* Denlinger, R. F. (2008). Managing fire-rescue departments. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 12-51–12-78). National Fire Protection Association.&lt;br /&gt;
* Granito, J. A. (2008). Planning for public fire-rescue protection. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 12-3–12-22). National Fire Protection Association.&lt;br /&gt;
* Klaene, B. J., &amp;amp; Sanders, R. (2008). Fireground operations. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 13-3–13-11). National Fire Protection Association.&lt;br /&gt;
* McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 20-179–20-202). National Fire Protection Association.&lt;br /&gt;
* Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 20-157–20-178). National Fire Protection Association.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
* Ramachandran, G. (2002b). Measuring fire consequences in economic terms (J. R. Hall Jr., Rev.). In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 5-79–5-92). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Schmidt, D. L. (2008). Emergency management and business continuity. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 1-137–1-156). National Fire Protection Association.&lt;br /&gt;
* Serapiglia, M. J. (2008). Pre-Incident planning for industrial and municipal emergency response. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 12-289–12-298). National Fire Protection Association.&lt;br /&gt;
* Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 12-177–12-198). National Fire Protection Association.&lt;br /&gt;
* Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Tutterow, R. (2008). Fire department apparatus and equipment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 12-267–12-287). National Fire Protection Association.&lt;br /&gt;
* Van der Graaf, J., Hessels, T., &amp;amp; Rosmuller, N. (2023). &amp;#039;&amp;#039;Fire safety of indoor car parks accommodating electrically powered vehicles&amp;#039;&amp;#039;. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)&lt;br /&gt;
* Van Rossum, E. (2027). &amp;#039;&amp;#039;Introduction to Fire Safety Engineering&amp;#039;&amp;#039;. Fire Safety Academy.&lt;br /&gt;
* Watts, J. M., Jr. (2008b). Systems approach to fire-safe building design. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 1-157–1-170). National Fire Protection Association.&lt;br /&gt;
* Yu, H.-Z., &amp;amp; Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 2-79–2-92). National Fire Protection Association.&lt;br /&gt;
&lt;br /&gt;
[[Category:Firefighting &amp;amp; Fire Service]]&lt;/div&gt;</summary>
		<author><name>Lisa</name></author>
	</entry>
</feed>