<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Limiting_oxidant_concentration</id>
	<title>Limiting oxidant concentration - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Limiting_oxidant_concentration"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Limiting_oxidant_concentration&amp;action=history"/>
	<updated>2026-11-21T22:38:01Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Limiting_oxidant_concentration&amp;diff=5390&amp;oldid=prev</id>
		<title>Emma: Add SVG figures fse-limiting-oxidant-concentration-v1.svg, fse-limiting-oxidant-concentration-v2.svg, fse-limiting-oxidant-concentration-v3.svg, fse-limiting-oxidant-concentration-v4.svg (list-2 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Limiting_oxidant_concentration&amp;diff=5390&amp;oldid=prev"/>
		<updated>2026-11-09T07:47:45Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-limiting-oxidant-concentration-v1.svg, fse-limiting-oxidant-concentration-v2.svg, fse-limiting-oxidant-concentration-v3.svg, fse-limiting-oxidant-concentration-v4.svg (list-2 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:47, 9 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l7&quot;&gt;Line 7:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 7:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The concept is easiest to see on a flammability diagram. This is a triangular graph with fuel, oxidant and inert gas at the three corners, on which every possible mixture is a single point.&amp;lt;ref name=&amp;quot;UG-17-143&amp;quot; /&amp;gt; The flammable mixtures form a closed region on this graph. Beyler (2002b) describes the &amp;quot;limit line&amp;quot; as the line of fixed oxygen-to-nitrogen ratio that just touches the flammable region. Any oxygen-nitrogen mixture with a lower oxygen-to-nitrogen ratio cannot support flame propagation when it is mixed with any amount of methane, and this condition is the limiting oxygen concentration.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; A US Nuclear Regulatory Commission guide describes the same point on a flammability diagram taken from NFPA 69 (1997 edition): any mixture containing less oxygen than the LOC cannot be ignited.&amp;lt;ref name=&amp;quot;IS-16-5&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The concept is easiest to see on a flammability diagram. This is a triangular graph with fuel, oxidant and inert gas at the three corners, on which every possible mixture is a single point.&amp;lt;ref name=&amp;quot;UG-17-143&amp;quot; /&amp;gt; The flammable mixtures form a closed region on this graph. Beyler (2002b) describes the &amp;quot;limit line&amp;quot; as the line of fixed oxygen-to-nitrogen ratio that just touches the flammable region. Any oxygen-nitrogen mixture with a lower oxygen-to-nitrogen ratio cannot support flame propagation when it is mixed with any amount of methane, and this condition is the limiting oxygen concentration.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; A US Nuclear Regulatory Commission guide describes the same point on a flammability diagram taken from NFPA 69 (1997 edition): any mixture containing less oxygen than the LOC cannot be ignited.&amp;lt;ref name=&amp;quot;IS-16-5&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-limiting-oxidant-concentration-v1.svg|thumb|upright=1.5|alt=Two-axis flammability diagram for methane, oxygen and nitrogen with flammable region, air line and limit line marking the minimum oxygen|Flammability diagram for methane, oxygen and nitrogen at atmospheric pressure. Mixtures whose oxygen-to-nitrogen ratio lies below the limit line cannot burn at any methane concentration; the tangent point marks the limiting oxygen concentration.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Zalosh (2002) gives the definition used in explosion protection. The maximum safe oxygen concentration for explosion prevention by inerting is called the limiting oxidant concentration in NFPA 69 (1997 edition).&amp;lt;ref name=&amp;quot;Zalosh2002-3-402&amp;quot; /&amp;gt; The same guide quotes the NFPA 69 wording: the LOC is the concentration of oxidant below which a deflagration cannot occur in a specified mixture.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot;&amp;gt;Iqbal and Salley (2004), p. B-27.&amp;lt;/ref&amp;gt; The word &amp;quot;oxidant&amp;quot; is used because materials other than oxygen can act as oxidants.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Zalosh (2002) gives the definition used in explosion protection. The maximum safe oxygen concentration for explosion prevention by inerting is called the limiting oxidant concentration in NFPA 69 (1997 edition).&amp;lt;ref name=&amp;quot;Zalosh2002-3-402&amp;quot; /&amp;gt; The same guide quotes the NFPA 69 wording: the LOC is the concentration of oxidant below which a deflagration cannot occur in a specified mixture.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot;&amp;gt;Iqbal and Salley (2004), p. B-27.&amp;lt;/ref&amp;gt; The word &amp;quot;oxidant&amp;quot; is used because materials other than oxygen can act as oxidants.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l49&quot;&gt;Line 49:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 50:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Ural and Garzia (2008) compare tube data with measurements in a 120 L sphere of 60 cm diameter, made with nitrogen as the diluent at 1 atm and 20 to 30 °C. The sphere values are lower for every fuel listed. Hydrogen gives 4.6 instead of 5.0 vol% and methane 11.0 instead of 12.0 vol%, while ethylene gives 8.5 instead of 10.0 vol% and propane 10.6 instead of 11.5 vol%. The sphere data were unpublished and not peer-reviewed at the time of writing.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt; Some values measured to ASTM E2079 are about 1 vol% oxygen lower than the old tube values, and a few are up to 2 vol% lower. The lower values from larger chambers are considered more appropriate for hazard assessment.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Ural and Garzia (2008) compare tube data with measurements in a 120 L sphere of 60 cm diameter, made with nitrogen as the diluent at 1 atm and 20 to 30 °C. The sphere values are lower for every fuel listed. Hydrogen gives 4.6 instead of 5.0 vol% and methane 11.0 instead of 12.0 vol%, while ethylene gives 8.5 instead of 10.0 vol% and propane 10.6 instead of 11.5 vol%. The sphere data were unpublished and not peer-reviewed at the time of writing.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt; Some values measured to ASTM E2079 are about 1 vol% oxygen lower than the old tube values, and a few are up to 2 vol% lower. The lower values from larger chambers are considered more appropriate for hazard assessment.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-limiting-oxidant-concentration-v2.svg|thumb|upright=1.5|alt=Grouped bar chart comparing LOC values of five fuels measured in a 5 cm tube and in a 120 L sphere, sphere values lower|Limiting oxygen concentration with nitrogen as diluent, measured in a 5 cm flammability tube and in a 120 L sphere (ASTM E2079, 1 atm, 20 to 30 °C). The larger vessel gives lower, more appropriate values.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For dusts, the 2008 handbook refers to an ASTM draft standard, WK1680. A sufficiently strong chemical igniter should be used so that the result is not limited by the weakness of the ignition source. Older dust LOC values obtained with spark ignition may therefore be suspect.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; The older apparatus described by Schwab (2008c) was a vertical tube with tungsten electrodes, flushed with the inert gas-air mixture, into which the dust was blown downward; flame leaving the open bottom showed ignition.&amp;lt;ref name=&amp;quot;Schwab-6-150&amp;quot;&amp;gt;Schwab (2008c), p. 6-150.&amp;lt;/ref&amp;gt; Because the LOC of a dust depends on its particle size distribution, tabulated values should be used with care.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For dusts, the 2008 handbook refers to an ASTM draft standard, WK1680. A sufficiently strong chemical igniter should be used so that the result is not limited by the weakness of the ignition source. Older dust LOC values obtained with spark ignition may therefore be suspect.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; The older apparatus described by Schwab (2008c) was a vertical tube with tungsten electrodes, flushed with the inert gas-air mixture, into which the dust was blown downward; flame leaving the open bottom showed ignition.&amp;lt;ref name=&amp;quot;Schwab-6-150&amp;quot;&amp;gt;Schwab (2008c), p. 6-150.&amp;lt;/ref&amp;gt; Because the LOC of a dust depends on its particle size distribution, tabulated values should be used with care.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l74&quot;&gt;Line 74:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 76:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the United States, NFPA 69 (1997 edition), as summarised by Zalosh (2002), sets the maximum allowable oxygen concentration at least 2 vol% below the LOC where the oxygen is monitored continuously. A greater margin is needed without continuous monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; The NUREG-1805 guide of the US Nuclear Regulatory Commission also summarises the NFPA 69 safety margins, without naming an edition. It gives an oxygen level of 60 percent of the LOC where the LOC is above 5 percent, and a stricter margin where it is below 5 percent.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the United States, NFPA 69 (1997 edition), as summarised by Zalosh (2002), sets the maximum allowable oxygen concentration at least 2 vol% below the LOC where the oxygen is monitored continuously. A greater margin is needed without continuous monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; The NUREG-1805 guide of the US Nuclear Regulatory Commission also summarises the NFPA 69 safety margins, without naming an edition. It gives an oxygen level of 60 percent of the LOC where the LOC is above 5 percent, and a stricter margin where it is below 5 percent.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-limiting-oxidant-concentration-v3.svg|thumb|upright=1.5|alt=Vertical oxygen scale from 21 to 0 percent marking air, methane LOC of 12 percent, and design levels of 10 and 7.2 percent|Oxygen levels for nitrogen inerting of methane: normal air, the LOC and two design levels below it.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l81&quot;&gt;Line 81:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 84:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The vessel can be brought to these levels by vacuum purging. In this batch method the pressure is lowered from &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; to &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; and inert gas is admitted to restore &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;. For a well-mixed vessel, the fraction of the original gas left after one cycle is &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;, and after &amp;#039;&amp;#039;n&amp;#039;&amp;#039; cycles it is &amp;#039;&amp;#039;X&amp;#039;&amp;#039;&amp;lt;sup&amp;gt;&amp;#039;&amp;#039;n&amp;#039;&amp;#039;&amp;lt;/sup&amp;gt;.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt; With &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; = 100 kPa and &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; = 60 kPa, &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = 0.6. Starting from air with 20.9 vol% oxygen and purging with pure nitrogen, the oxygen falls to 12.6, 7.6 and 4.6 vol% after one, two and three cycles (rounded up). Two cycles therefore meet the 10 vol% design value, and three cycles meet the 7.2 vol% value.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The vessel can be brought to these levels by vacuum purging. In this batch method the pressure is lowered from &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; to &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; and inert gas is admitted to restore &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;. For a well-mixed vessel, the fraction of the original gas left after one cycle is &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;, and after &amp;#039;&amp;#039;n&amp;#039;&amp;#039; cycles it is &amp;#039;&amp;#039;X&amp;#039;&amp;#039;&amp;lt;sup&amp;gt;&amp;#039;&amp;#039;n&amp;#039;&amp;#039;&amp;lt;/sup&amp;gt;.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt; With &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; = 100 kPa and &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; = 60 kPa, &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = 0.6. Starting from air with 20.9 vol% oxygen and purging with pure nitrogen, the oxygen falls to 12.6, 7.6 and 4.6 vol% after one, two and three cycles (rounded up). Two cycles therefore meet the 10 vol% design value, and three cycles meet the 7.2 vol% value.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-limiting-oxidant-concentration-v4.svg|thumb|upright=1.5|alt=Step chart of oxygen concentration after zero to four vacuum purge cycles, falling from 20.9 to 2.7 percent, with lines at 10 and 7.2 percent|Residual oxygen after vacuum purging with pure nitrogen between 100 kPa and 60 kPa (X = 0.6 per cycle), assuming perfect mixing.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The example assumes a perfectly mixed vessel and pure nitrogen. Real vessels can contain stratified or poorly mixed zones, which is why Zalosh (2002) links the safety margin to the quality of oxygen monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The example assumes a perfectly mixed vessel and pure nitrogen. Real vessels can contain stratified or poorly mixed zones, which is why Zalosh (2002) links the safety margin to the quality of oxygen monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-2942:rev-5390:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Emma</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Limiting_oxidant_concentration&amp;diff=2942&amp;oldid=prev</id>
		<title>Jan: New FSE wiki article: Limiting oxidant concentration (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Limiting_oxidant_concentration&amp;diff=2942&amp;oldid=prev"/>
		<updated>2026-11-07T21:01:52Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Limiting oxidant concentration (written by Claude Opus 5.5)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;The &amp;#039;&amp;#039;&amp;#039;limiting oxidant concentration&amp;#039;&amp;#039;&amp;#039; (&amp;#039;&amp;#039;&amp;#039;LOC&amp;#039;&amp;#039;&amp;#039;) is the oxygen (or other oxidant) concentration below which a mixture of fuel, air and added inert gas cannot sustain a deflagration. Below the LOC, no amount of gas, vapour, mist or dust makes the mixture flammable.&amp;lt;ref name=&amp;quot;Zalosh2002-3-402&amp;quot;&amp;gt;Zalosh (2002), pp. 3-402–3-403.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot;&amp;gt;Beyler (2002b), p. 2-179.&amp;lt;/ref&amp;gt; When the oxidant is the oxygen in air, the same quantity is called the &amp;#039;&amp;#039;&amp;#039;limiting oxygen concentration&amp;#039;&amp;#039;&amp;#039;.&amp;lt;ref name=&amp;quot;UG-17-144&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-144.&amp;lt;/ref&amp;gt; It is the basis of [[inerting]], the explosion prevention method in which nitrogen, carbon dioxide, steam or another inert gas replaces part of the air in a vessel.&lt;br /&gt;
&lt;br /&gt;
For most hydrocarbon gases and vapours diluted with nitrogen, the LOC lies around 10 to 12 percent oxygen by volume.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; Normal air contains 21 percent.&amp;lt;ref name=&amp;quot;IS-16-5&amp;quot;&amp;gt;Iqbal and Salley (2004), p. 16-5.&amp;lt;/ref&amp;gt; The LOC is not a fixed material constant. It depends on the fuel, the inert gas, the temperature, the pressure and, for dusts, the particle size distribution, and it also depends on the test apparatus used to measure it.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-147.&amp;lt;/ref&amp;gt; In the United States, the 2008 edition of [[NFPA 69]], &amp;#039;&amp;#039;Standard on Explosion Prevention Systems&amp;#039;&amp;#039;, gives LOC values. Its inerting guidelines (1997 edition) set safety margins between the LOC and the oxygen level at which an inerted process may operate.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-149.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot;&amp;gt;Zalosh (2002), p. 3-403.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Definition and physical basis ==&lt;br /&gt;
Ural and Garzia (2008) note that the classic fire triangle of fuel, oxidant and ignition source oversimplifies what a deflagration needs. A fuel-air mixture burns only within a range of fuel concentrations, and only if enough oxygen is present.&amp;lt;ref name=&amp;quot;UG-17-143&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-143.&amp;lt;/ref&amp;gt; The lower and upper [[flammability limits]] describe the fuel range in ordinary air. The LOC adds the third dimension: how far the oxygen can fall before no fuel concentration at all will propagate a flame.&lt;br /&gt;
&lt;br /&gt;
The concept is easiest to see on a flammability diagram. This is a triangular graph with fuel, oxidant and inert gas at the three corners, on which every possible mixture is a single point.&amp;lt;ref name=&amp;quot;UG-17-143&amp;quot; /&amp;gt; The flammable mixtures form a closed region on this graph. Beyler (2002b) describes the &amp;quot;limit line&amp;quot; as the line of fixed oxygen-to-nitrogen ratio that just touches the flammable region. Any oxygen-nitrogen mixture with a lower oxygen-to-nitrogen ratio cannot support flame propagation when it is mixed with any amount of methane, and this condition is the limiting oxygen concentration.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; A US Nuclear Regulatory Commission guide describes the same point on a flammability diagram taken from NFPA 69 (1997 edition): any mixture containing less oxygen than the LOC cannot be ignited.&amp;lt;ref name=&amp;quot;IS-16-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Zalosh (2002) gives the definition used in explosion protection. The maximum safe oxygen concentration for explosion prevention by inerting is called the limiting oxidant concentration in NFPA 69 (1997 edition).&amp;lt;ref name=&amp;quot;Zalosh2002-3-402&amp;quot; /&amp;gt; The same guide quotes the NFPA 69 wording: the LOC is the concentration of oxidant below which a deflagration cannot occur in a specified mixture.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot;&amp;gt;Iqbal and Salley (2004), p. B-27.&amp;lt;/ref&amp;gt; The word &amp;quot;oxidant&amp;quot; is used because materials other than oxygen can act as oxidants.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The physical reason for the limit is thermal. Beyler (2002b) explains the LOC with the same adiabatic flame temperature concept that explains the flammability limits.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; Ural and Garzia (2008) state that a mixture of fuel, oxygen and inert gas becomes nonflammable when its heat capacity rises above about 250 J/(mol·K) per mole of oxygen in the mixture. The heat capacity of the inert gas is therefore its most important inerting property: the higher it is, the less gas is needed.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; At 25 °C the molar heat capacity is 20.9 J/(mol·K) for argon, 28.4 J/(mol·K) for nitrogen and 37.5 J/(mol·K) for carbon dioxide.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-148.&amp;lt;/ref&amp;gt; This explains why LOC values measured with carbon dioxide are generally 2 to 3 percentage points higher than those measured with nitrogen.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Typical values ==&lt;br /&gt;
For gases and vapours diluted with nitrogen, the LOC is generally in the range 10 to 12 percent oxygen by volume. Carbon monoxide and hydrogen have lower values, and chlorinated fuels have higher values.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; Zalosh (2002) gives the ranges for the fuels in his table as 9.5 to 12 vol% oxygen for nitrogen inerting and 11.5 to 14.5 vol% for carbon dioxide inerting, hydrogen excepted.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; The table below gives selected values at normal temperature and pressure. They were measured decades ago in explosion tubes with spark or pilot-flame ignition, and they are adapted from Table C-1 of NFPA 69.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
|+ Selected limiting oxygen concentrations of gases and vapours (vol% O&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; above which deflagration can take place)&lt;br /&gt;
! Fuel !! With nitrogen as diluent !! With carbon dioxide as diluent&lt;br /&gt;
|-&lt;br /&gt;
| Hydrogen || 5 || 5.2&lt;br /&gt;
|-&lt;br /&gt;
| Carbon monoxide || 5.5 || 5.5&lt;br /&gt;
|-&lt;br /&gt;
| Methanol || 10 || 12&lt;br /&gt;
|-&lt;br /&gt;
| Ethylene || 10 || 11.5&lt;br /&gt;
|-&lt;br /&gt;
| Propane || 11.5 || 14.5&lt;br /&gt;
|-&lt;br /&gt;
| Acetone || 11.5 || 14&lt;br /&gt;
|-&lt;br /&gt;
| &amp;#039;&amp;#039;n&amp;#039;&amp;#039;-Hexane || 12 || 14.5&lt;br /&gt;
|-&lt;br /&gt;
| Natural gas (Pittsburgh) || 12 || 14.5&lt;br /&gt;
|-&lt;br /&gt;
| Methylene chloride || 19 (at 30 °C) || not given&lt;br /&gt;
|}&lt;br /&gt;
Source: Beyler (2002b), Table 2-7.2.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Combustible dusts show a wider spread. Zalosh (2002) reports carbon dioxide LOC values of 11 to 15 vol% for organic dusts, but much lower values for some metals. His table lists, for nitrogen and carbon dioxide inerting respectively, 14 and 17 vol% for bituminous coal, 9 vol% (nitrogen) for corn starch, 5 and 2 vol% for aluminium, and 0 for zirconium.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; The zero value for zirconium reflects its pyrophoric behaviour as a powder.&amp;lt;ref name=&amp;quot;Zalosh2002-3-404&amp;quot;&amp;gt;Zalosh (2002), p. 3-404.&amp;lt;/ref&amp;gt; Pyrophoric materials ignite spontaneously on contact with air.&amp;lt;ref name=&amp;quot;DP-9-126&amp;quot;&amp;gt;DeGiorgio and Peterkin (2008), p. 9-126.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039;, Schwab (2008c) gives limiting oxygen percentages for spark ignition in a table of explosion characteristics of dusts. Lycopodium is listed as C13, wheat starch and sulfur as C12 and polycarbonate as C15; &amp;quot;C13&amp;quot; means dilution to 13 percent oxygen with carbon dioxide as the diluent.&amp;lt;ref name=&amp;quot;Schwab-6-143&amp;quot;&amp;gt;Schwab (2008c), p. 6-143.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The values change with conditions. For a given dust, the LOC decreases linearly with increasing temperature, following correlations by Siwek.&amp;lt;ref name=&amp;quot;Zalosh2002-3-404&amp;quot; /&amp;gt; The methylene chloride entry illustrates the effect for vapours: its LOC with nitrogen falls from 19 vol% at 30 °C to 17 vol% at 100 °C.&amp;lt;ref name=&amp;quot;Beyler-2-179&amp;quot; /&amp;gt; Ural and Garzia (2008) therefore advise determining the LOC at the worst-case conditions of the process.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Measurement ==&lt;br /&gt;
For gases and vapours, the test method of choice described in the 2008 handbook is ASTM E2079, &amp;#039;&amp;#039;Standard Test Methods for Limiting Oxygen (Oxidant) Concentration in Gases and Vapors&amp;#039;&amp;#039;.&amp;lt;ref name=&amp;quot;UG-17-146&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-146.&amp;lt;/ref&amp;gt; Most published data, however, were obtained decades earlier in flammability tubes. The old US Bureau of Mines data come mostly from a tube of 5 cm diameter, which may be too narrow to avoid quenching of the flame by the tube wall. ASTM E2079 specifies a minimum vessel volume of 4 L, which corresponds to a diameter of at least 20 cm.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; Preliminary round-robin results showed that the LOC data in most reference publications are nonconservative, that is, too high.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Ural and Garzia (2008) compare tube data with measurements in a 120 L sphere of 60 cm diameter, made with nitrogen as the diluent at 1 atm and 20 to 30 °C. The sphere values are lower for every fuel listed. Hydrogen gives 4.6 instead of 5.0 vol% and methane 11.0 instead of 12.0 vol%, while ethylene gives 8.5 instead of 10.0 vol% and propane 10.6 instead of 11.5 vol%. The sphere data were unpublished and not peer-reviewed at the time of writing.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt; Some values measured to ASTM E2079 are about 1 vol% oxygen lower than the old tube values, and a few are up to 2 vol% lower. The lower values from larger chambers are considered more appropriate for hazard assessment.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For dusts, the 2008 handbook refers to an ASTM draft standard, WK1680. A sufficiently strong chemical igniter should be used so that the result is not limited by the weakness of the ignition source. Older dust LOC values obtained with spark ignition may therefore be suspect.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; The older apparatus described by Schwab (2008c) was a vertical tube with tungsten electrodes, flushed with the inert gas-air mixture, into which the dust was blown downward; flame leaving the open bottom showed ignition.&amp;lt;ref name=&amp;quot;Schwab-6-150&amp;quot;&amp;gt;Schwab (2008c), p. 6-150.&amp;lt;/ref&amp;gt; Because the LOC of a dust depends on its particle size distribution, tabulated values should be used with care.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Inert gas requirement and design margins ==&lt;br /&gt;
Once the LOC is known, the amount of inert gas needed can be estimated. Air contains 21 percent oxygen by volume.&amp;lt;ref name=&amp;quot;IS-16-5&amp;quot; /&amp;gt; Adding inert gas dilutes the air, and with it the oxygen, until the oxygen fraction of the whole mixture falls to the LOC. Zalosh (2002) gives the volume percentage of inert gas needed for this as:&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;\%\,\mathrm{Inert} = 100 - 4.76\,\mathrm{LOC}\left[1 + \left(\frac{F}{A}\right)\right]&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\%\,\mathrm{Inert}&amp;lt;/math&amp;gt; || Added inert gas as a percentage of the total mixture volume || vol%&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\mathrm{LOC}&amp;lt;/math&amp;gt; || Limiting oxidant (oxygen) concentration for the fuel and inert gas || vol% O&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt;&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;F/A&amp;lt;/math&amp;gt; || Fuel-to-air volume ratio of the mixture that is hardest to inert || –&lt;br /&gt;
|-&lt;br /&gt;
| 4.76 || Ratio of air to oxygen in air (1/0.21) || –&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The ratio &amp;#039;&amp;#039;F&amp;#039;&amp;#039;/&amp;#039;&amp;#039;A&amp;#039;&amp;#039; is read from the full fuel-air-inert flammability diagram, at the &amp;quot;nose&amp;quot; of the flammable region. For methane this is the stoichiometric ratio of 0.105, and for &amp;#039;&amp;#039;n&amp;#039;&amp;#039;-hexane it is about 0.03.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; Where the diagram is not available, Zalosh (2002) recommends setting &amp;#039;&amp;#039;F&amp;#039;&amp;#039;/&amp;#039;&amp;#039;A&amp;#039;&amp;#039; = 0 as a reasonably conservative approximation, because it gives the largest inert gas fraction.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The LOC itself is not a safe operating point. If inerting is the primary means of explosion protection, several safety margins are applied to the LOC to obtain the design inerting concentration. They cover uneven mixing, temperature and pressure fluctuations, the accuracy and response time of oxygen measurement and alarms, and the consequences of false alarms.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States, NFPA 69 (1997 edition), as summarised by Zalosh (2002), sets the maximum allowable oxygen concentration at least 2 vol% below the LOC where the oxygen is monitored continuously. A greater margin is needed without continuous monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; The NUREG-1805 guide of the US Nuclear Regulatory Commission also summarises the NFPA 69 safety margins, without naming an edition. It gives an oxygen level of 60 percent of the LOC where the LOC is above 5 percent, and a stricter margin where it is below 5 percent.&amp;lt;ref name=&amp;quot;IS-B-27&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
=== Worked example ===&lt;br /&gt;
A process vessel may contain methane in air and is to be inerted with nitrogen. Zalosh (2002) lists a methane LOC of 12 vol% for nitrogen inerting.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; With the conservative choice &amp;#039;&amp;#039;F&amp;#039;&amp;#039;/&amp;#039;&amp;#039;A&amp;#039;&amp;#039; = 0, the nitrogen fraction that just reaches the LOC is 100 − 4.76 × 12 = 42.9 vol%. With the stoichiometric ratio &amp;#039;&amp;#039;F&amp;#039;&amp;#039;/&amp;#039;&amp;#039;A&amp;#039;&amp;#039; = 0.105, it would be 36.9 vol%, so the conservative choice adds about 6 percentage points.&lt;br /&gt;
&lt;br /&gt;
The vessel is monitored continuously, so the design oxygen concentration under the 2 vol% margin described by Zalosh (2002) is 10 vol%. The nitrogen fraction then becomes 100 − 4.76 × 10 = 52.4 vol%. Under the 60 percent rule summarised in NUREG-1805, the design oxygen concentration is 0.6 × 12 = 7.2 vol%, and the nitrogen fraction is 65.8 vol% (rounded up). The 120 L sphere gives a methane LOC of 11.0 vol% instead of the tube value. With that value, the design oxygen concentration under the 2 vol% margin falls to 9.0 vol% and the nitrogen fraction rises to 57.2 vol%.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The vessel can be brought to these levels by vacuum purging. In this batch method the pressure is lowered from &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; to &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; and inert gas is admitted to restore &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;. For a well-mixed vessel, the fraction of the original gas left after one cycle is &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt;/&amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt;, and after &amp;#039;&amp;#039;n&amp;#039;&amp;#039; cycles it is &amp;#039;&amp;#039;X&amp;#039;&amp;#039;&amp;lt;sup&amp;gt;&amp;#039;&amp;#039;n&amp;#039;&amp;#039;&amp;lt;/sup&amp;gt;.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt; With &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;1&amp;lt;/sub&amp;gt; = 100 kPa and &amp;#039;&amp;#039;P&amp;#039;&amp;#039;&amp;lt;sub&amp;gt;2&amp;lt;/sub&amp;gt; = 60 kPa, &amp;#039;&amp;#039;X&amp;#039;&amp;#039; = 0.6. Starting from air with 20.9 vol% oxygen and purging with pure nitrogen, the oxygen falls to 12.6, 7.6 and 4.6 vol% after one, two and three cycles (rounded up). Two cycles therefore meet the 10 vol% design value, and three cycles meet the 7.2 vol% value.&lt;br /&gt;
&lt;br /&gt;
The example assumes a perfectly mixed vessel and pure nitrogen. Real vessels can contain stratified or poorly mixed zones, which is why Zalosh (2002) links the safety margin to the quality of oxygen monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Use in explosion prevention ==&lt;br /&gt;
The LOC is one of the material properties used in an explosion hazard analysis. Ural and Garzia (2008) list a generic chain of events that leads to an explosion. In it, &amp;quot;oxygen control&amp;quot; based on the LOC is one of the engineering interventions at the stage where a flammable mixture forms.&amp;lt;ref name=&amp;quot;UG-17-142&amp;quot;&amp;gt;Ural and Garzia (2008), p. 17-142.&amp;lt;/ref&amp;gt; In their flowchart for [[dust explosion]] protection, the LOC test leads directly to process or powder inerting.&amp;lt;ref name=&amp;quot;UG-17-144&amp;quot; /&amp;gt; Other options at the same stage are keeping the fuel concentration below the lower flammable limit and removing ignition sources. If an explosion cannot be prevented, protection by venting, suppression, containment or isolation limits the consequences.&amp;lt;ref name=&amp;quot;UG-17-142&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Nitrogen is commonly used as an inerting gas. It can be obtained from cryogenic liquid storage or produced by catalytic combustion of ammonia in air. Carbon dioxide is somewhat more effective because of its higher heat capacity. Flue gas, a mixture of carbon dioxide and nitrogen with little oxygen, is commonly used to inert storage tanks when oil is offloaded from ships.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt; Carbon dioxide should not be used for certain refractory metals such as magnesium, silicon and zirconium. A noble gas such as argon may then be needed.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Several applications in the handbook show the margins used in practice. Low-oxygen ovens evaporate solvents in an atmosphere with too little oxygen for combustion. Ostrowski (2008a) gives an operating value of about 8 percent oxygen for some solvents, including a safety factor of about 3 percent, and notes that oxygen analysis is needed to verify it.&amp;lt;ref name=&amp;quot;Ostrowski-8-80&amp;quot;&amp;gt;Ostrowski (2008a), p. 8-80.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
On tank vessels, the inert gas system keeps the oxygen content of the cargo tank spaces below 8 percent by volume at a positive pressure. When such tanks are gas-freed for work inside, the atmosphere passes through the flammable range, which is a particularly dangerous phase.&amp;lt;ref name=&amp;quot;Eberly-21-171&amp;quot;&amp;gt;Eberly (2008), p. 21-171.&amp;lt;/ref&amp;gt; Inerting is not always practical. Maness and Sargent (2008) note that it has limited application in grain handling because of the size of the equipment, although machines such as hammer mills are more likely candidates.&amp;lt;ref name=&amp;quot;MS-9-98&amp;quot;&amp;gt;Maness and Sargent (2008), p. 9-98.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Where full inerting is not possible for technical or financial reasons, partial inerting may be combined with other prevention and protection methods. Even above the LOC, a reduced oxygen concentration generally narrows the flammable range, lowers the [[deflagration index]] &amp;#039;&amp;#039;K&amp;#039;&amp;#039; and raises the minimum ignition energy.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt; Inerted equipment is itself a hazard to people, because the atmosphere cannot sustain life. In the United States, the 2008 handbook refers to OSHA rules for entry into protected equipment, and warns that leakage of inert gas into unventilated areas is a hidden risk.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt; Ural and Garzia (2008) also note that examples of LOC values for gases, metals and carbonaceous dusts can be found in the 2008 edition of NFPA 69.&amp;lt;ref name=&amp;quot;UG-17-149&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Limits and uncertainty ==&lt;br /&gt;
A tabulated LOC applies to the conditions of its test. It changes with temperature, pressure, fuel concentration and the type of diluent, so it should be determined at the worst-case conditions of the process.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; Many tabulated values for gases come from small flammability tubes, and tests to ASTM E2079 gave some values about 1 vol% oxygen lower and a few up to 2 vol% lower.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt; For dusts, the particle size distribution and the strength of the igniter both affect the result.&amp;lt;ref name=&amp;quot;UG-17-147&amp;quot; /&amp;gt; Real vessels are rarely uniform: Zalosh (2002) stresses that practical evaluations must account for nonuniform or stratified mixtures and for the accuracy, response time and reliability of oxygen monitoring.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt; These uncertainties are the reason for the safety margins between the LOC and the design oxygen concentration.&lt;br /&gt;
&lt;br /&gt;
== Related concepts and misconceptions ==&lt;br /&gt;
The LOC is often confused with the [[oxygen index]]. The oxygen index, or limiting oxygen index (LOI), is measured with ASTM D2863. It is the minimum oxygen concentration in a flowing oxygen-nitrogen mixture that supports candlelike downward burning of a small plastic specimen.&amp;lt;ref name=&amp;quot;Hirschler-6-42&amp;quot;&amp;gt;Hirschler (2008a), p. 6-42.&amp;lt;/ref&amp;gt; It describes a diffusion flame on a solid, not a premixed fuel-air cloud, and Hirschler (2008a) notes that it serves mainly as a measure of how easily a burning material is extinguished.&amp;lt;ref name=&amp;quot;Hirschler-6-42&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The numbers can nevertheless be close. Beyler (2002b) finds a very close correspondence between the LOC with nitrogen and the LOI, and cites experiments in which flames on pool burners were extinguished at oxygen concentrations of 12.4 to 14.3 percent.&amp;lt;ref name=&amp;quot;Beyler-2-184&amp;quot;&amp;gt;Beyler (2002b), p. 2-184.&amp;lt;/ref&amp;gt; The Fire Dynamics Simulator uses a similar concept in its flame extinction model, with a default limiting oxygen volume fraction of 0.135 at 20 °C.&amp;lt;ref name=&amp;quot;McGrattan-63&amp;quot;&amp;gt;McGrattan et al. (2026), p. 63.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A second misconception is that the oxygen level that extinguishes a fire is the same as the level that prevents an explosion. Inert gas fire suppression works in the same thermal way, by lowering the oxygen concentration and raising the heat capacity of the atmosphere.&amp;lt;ref name=&amp;quot;DiNenno-17-96&amp;quot;&amp;gt;DiNenno and Taylor (2008), p. 17-96.&amp;lt;/ref&amp;gt; DiNenno and Taylor (2008) state that nitrogen added until the oxygen falls below 12 percent will extinguish flaming fires, and give nitrogen extinguishing concentrations of about 30 percent, corresponding to 14.6 percent oxygen.&amp;lt;ref name=&amp;quot;DiNenno-17-96&amp;quot; /&amp;gt; These values refer to extinguishing established flames. The LOC for preventing a deflagration can be much lower: 5 vol% for hydrogen and 0 for zirconium dust.&amp;lt;ref name=&amp;quot;Zalosh2002-3-403&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A third source of confusion is the abbreviation MOC. In the glossary of NUREG-1805, MOC stands for &amp;quot;maximum allowable oxygen concentration&amp;quot;, which is the design limit set below the LOC, not the LOC itself.&amp;lt;ref name=&amp;quot;IS-G-7&amp;quot;&amp;gt;Iqbal and Salley (2004), p. G-7.&amp;lt;/ref&amp;gt; The two values differ by the safety margin described above, so treating them as equal removes the margin.&lt;br /&gt;
&lt;br /&gt;
A fourth misconception is that any reduction of oxygen makes a process safe. Maness and Sargent (2008) point out that the oxygen needed for a grain dust explosion is simply that of the normal atmosphere.&amp;lt;ref name=&amp;quot;MS-9-98&amp;quot; /&amp;gt; Reduced oxygen above the LOC makes a deflagration less likely and less severe, but it does not prevent one; only a concentration below the LOC, with a margin, does that.&amp;lt;ref name=&amp;quot;UG-17-148&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Deflagration]]&lt;br /&gt;
* [[Minimum ignition energy]]&lt;br /&gt;
* [[Explosion venting]]&lt;br /&gt;
* [[Explosion suppression system]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* DeGiorgio, V., &amp;amp; Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 9-119–9-129). National Fire Protection Association.&lt;br /&gt;
* DiNenno, P. J., &amp;amp; Taylor, G. M. (2008). Halon and halon replacement agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 17-93–17-121). National Fire Protection Association.&lt;br /&gt;
* Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 21-151–21-185). National Fire Protection Association.&lt;br /&gt;
* Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-35–6-60). National Fire Protection Association.&lt;br /&gt;
* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.&lt;br /&gt;
* Maness, J. E., &amp;amp; Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 9-85–9-103). National Fire Protection Association.&lt;br /&gt;
* McGrattan, K., Hostikka, S., Floyd, J., McDermott, R., Vanella, M., Mueller, E., &amp;amp; Paul, C. (2026). &amp;#039;&amp;#039;Fire Dynamics Simulator technical reference guide: Vol. 1. Mathematical model&amp;#039;&amp;#039; (6th ed., NIST Special Publication 1018-1). National Institute of Standards and Technology. https://doi.org/10.6028/NIST.SP.1018&lt;br /&gt;
* Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 8-71–8-92). National Fire Protection Association.&lt;br /&gt;
* Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-141–6-152). National Fire Protection Association.&lt;br /&gt;
* Ural, E. A., &amp;amp; Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 17-141–17-165). National Fire Protection Association.&lt;br /&gt;
* Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
&lt;br /&gt;
[[Category:Explosions &amp;amp; Industrial Fires]]&lt;/div&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
</feed>